- • Requirements for the controlled devices
- • Dashboards, Zones, Categories
- • Simple thermostat with hysteresis
- • Simple Heating management using Weekly schedule and Presence switch
- • Power limiting
- • Notification on high temperature (DEPRECATED)
- • Configuring hysteresis control via Equation Smart Rule
- • PID Temperature regulation
- • PID Cascade
- • Regulation of Boiler Cascade
- • Equithermic regulation
- • Heating control in high electricity tariff via load management tariff indicator input
- • Heating and Cooling modes
- • Editing multiple devices
- • Integrate multiple control units Core
- • Safe values
- • How to combine two daily schedules in one day
- • Grouping or linking devices together
- • Using statistic values in Smart Rules
- • Hot water circulation pump control
- • Exporting data from TapHome into Google Spreadsheet using Integromat
- • Exporting device descriptions
- • 2023
- • 2022.2
- • 2022.1
- • 2021.3
- • 2021.2
- • 2021.1
- • 2020.1
- • 2019.1
- • 2018.1
- • 2017.1 - Blinds automation - angle control update
- • 2017.1 - Blinds automation - Depth of sun rays
- • 2017.1 - Charts updated
- • 2017.1 - Core update from the app
- • 2017.1 - Double click and triple click
- • 2017.1 - Expose devices
- • 2017.1 - Multi-value switch
- • 2017.1 - Permissions
- • 2017.1 - Replace module action
- • 2017.1 - Set to Automatic mode - "Push buttons event" Smart Rule
- • 2017.1 – Daily schedule Smart Rule
- • Firmware changelog
- • Transition of MAC address handling
- Documentation
- Compatibility list
- Jablotron alarm
Jablotron alarm
Jablotron 100 alarm system provides RS485 gateway to securely connect to 3rd party systems.
TapHome Core control unit provides 3 terminals for TapHome Bus devices, or other RS485-based devices. Thanks to support of Jablotron protocol, TapHome can read values from/to Jablotron 100 alarm.
Step-by-step guide
Connect JA-121T with TapHome Core.
The JA-121T provides galvanic isolation, so the GNDs of the Jablotron and TapHome power supplies should not be connected.
- Open Settings → Hardware:
a. Disable Terminal 3 in TapHome Bus → Terminals
b. + Add new interface → Jablotron
- Open Settings → Hardware → Jablotron:
a. Enable Terminal 3
b. For example, set the Jablotron password (format 1 * 2345, where 1 is the external user ID and 2345 is the password or other format you are using). This password must be created in the Jablotron system.
- Program PG outputs in Jablotron. In order to achieve immediate response from e.g. motion sensor, it must be programmed as PG output in Jablotron.
Typical use cases:- Armed status of the house, in order to adjust blinds, heating, cooling and ventilation
- Motion sensor to turn on the light in corridor when there is motion at night
- Windows in a zone to provide push notification when leaving the house with windows open
a. Read-only device types for Reed contacts
b. Read/write device types for Switches
IMPORTANT: It is not possible to combine Jablotron Gateway with any other device on the same bus terminal. All terminals are RS485 standard, but this provides only electric compatibility, not data compatibility.