Search
MENU
  • Expressions / Script language
  • Users and Permissions
  • Backup, restore, reset to factory settings
  • Equithermic regulation

    Equithermic regulation is a simple method of calculating the temperature of heating or cooling medium in primary circuit depending on the outdoor temperature. In most cases, this function is managed internally by boiler or heat pump.

    If the shape of the curve is set correctly, it should be possible to achieve desired temperature in zones with coolest possible medium (in heating mode) or warmest possible medium (in cooling mode).

    Disadvantage of this method is, that it does not have automatic correction mechanism built-in. So if the equithermic curve is not set correctly, it may result in insufficient or excessive heating / cooling in zones.


    Heating mode

    Cooling mode

    Inputs

    • Outdoor temperature
    • Temperatures from zones

    • Outdoor temperature
    • Temperatures from zones
    • Humidity from zones

    Output

    • Set point of virtual thermostat for primary circuit

    • Set point of virtual thermostat for primary circuit

    Limits

    • Minimum / Maximum set point

    • Minimum / Maximum set point
    • Dew point limit (Early warning)
      Calculates minimal set point temperature based on highest relative humidity from all linked zone thermostats

    PID correction

    (X)

    (X)


    For more information about cooling / heating modes, see this page.

    How final set point is calculated

    Equitherm curve returns temperature of flow water based on outdoor temperature. Angle of the curve, parallel shift, temperature limits and adjustments based on data from thermostats are affecting the final results.

    Angle

    For floor heating systems, values between 0.2 and 0.8 are commonly used. Lower values are more suitable for high quality insulation.

    Table below shows resulting set point temperature based on outdoor temperature and angle of the curve:

    Outdoor temperature

    Angle:

    -20ºC-15ºC-10ºC-5ºC0ºC5ºC10ºC15ºC20ºC
    0.2333232302927242220
    0.4424038363330272420
    0.6504845413733292520
    0.8595652474237312620
    1.0656157534740342720
    1.2746964585244372820
    1.5827670645850403020
    1.75908477716354433220
    2.0909084777060473420
    2.25909088827565523620
    2.5909090878070563820
    2.75909090908473573820
    3.0909090908677614120

    E.g. if outdoor temperature is 0ºC and angle of equithermic curve is 0.6, resulting set point temperature is 37ºC.

    Parallel shift

    Increases or decreases the curve by defined value.

    E.g. if set point temperature based on angle of curve is 37ºC, and parallel shift is set to 4ºC, resulting set point is 41ºC.

    Adjustments based on data from thermostats

    All zone termostats that are linked to equithermic Smart Rule are affecting the final result.


    Heating mode

    Cooling mode

    Set point from zones

    Equithermic curve will be shifted up if highest set point of zone thermostats is more than 22ºC

    Equithermic curve will be shifted down if lowest set point of zone thermostats is less than 22ºC

    Result

    Resulting set point = Set point based on angle and parallel shift + Ratio * (highest zone setpoint - 22)

    Resulting set point = Set point based on angle and parallel shift + Ratio * (lowest zone setpoint - 22)

    Dew point limit

    --

    Resulting set point can not be less than dew point temperature calculated from highest relative humidity in zones

    Example scenario for zone hydronic heating with equitherm regulation

    Example scenario for zone hydronic cooling with equitherm regulation