Search
MENU
- • Requirements for the controlled devices
- • Dashboards, Zones, Categories
- • Simple thermostat with hysteresis
- • Simple Heating management using Weekly schedule and Presence switch
- • Power limiting
- • Notification on high temperature (DEPRECATED)
- • Configuring hysteresis control via Equation Smart Rule
- • PID Temperature regulation
- • PID Cascade
- • Regulation of Boiler Cascade
- • Equithermic regulation
- • Heating control in high electricity tariff via load management tariff indicator input
- • Heating and Cooling modes
- • Editing multiple devices at once
- • Setting the response speed of push buttons
- • Integrate multiple control units Core
- • Safe values
- • How to combine two daily schedules in one day
- • Linking devices together
- • Device log
- • Using statistic values in Smart Rules
- • Hot water circulation pump control
- • Exporting data from TapHome into Google Spreadsheet using Integromat
- • Exporting device descriptions
- • 2024
- • 2023
- • 2022.2
- • 2022.1
- • 2021.3
- • 2021.2
- • 2021.1
- • 2020.1
- • 2019.1
- • 2018.1
- • 2017.1 - Blinds automation - angle control update
- • 2017.1 - Blinds automation - Depth of sun rays
- • 2017.1 - Charts updated
- • 2017.1 - Core update from the app
- • 2017.1 - Double click and triple click
- • 2017.1 - Expose devices
- • 2017.1 - Multi-value switch
- • 2017.1 - Permissions
- • 2017.1 - Replace module action
- • 2017.1 - Set to Automatic mode - "Push buttons event" Smart Rule
- • 2017.1 – Daily schedule Smart Rule
- • Firmware changelog
- Documentation
- Configuration
- Heating / Cooling
- Configuring hysteresis control via Equation Smart Rule
Configuring hysteresis control via Equation Smart Rule
The example below shows how to configure filling of retention tank based on measurement of minimum and maximum water level.
Inputs:
- Reed contact for min level (Variable name: St)
- Reed contact for max level (Variable name: St1)
Output:
- Digital output for control of valve or pump (Name: Valve)
Configuring Equation Smart Rule
Equation Smart Rule has internal variable called LastState. This variable returns TRUE or FALSE based on last result of evaluation of this Smart Rule.
Equation
(LastState AND !St1) OR (!LastState AND !St)
Action
If result is TRUE: Valve ... Turn On
If result is FALSE: Valve ... Turn Off
Duration
Minimum duration ... 0:05:00 minutes