    Encoderinstellingen

    De berekening van de positie en de hoek van de zonwering is gebaseerd op het tellen van impulsen van de encoder

    Het gedeelte Encoderinstellingen bestaat uit de volgende kenmerken:

     

    Attribuut

    Standaardwaarde

    Maximale tijd om te wachten op encodersignalen start omhoog

                 
    150 ms
    doc_tap_Max_time_down;    150 ms

    doc_tap_Number;

    2000

    Number of impulses for angle change

    Not applicable for slides.

    103

    doc_tap_Number_impulses;

    doc_tap_not;

    103

    Calibration current
    Limit of current during calibration.

    71%

    doc_tap_Calibration;

    doc_tap_Limit_calibration; 

    71%

    Normal operation current 
    Limit of current during normal operation up.

    83%

    doc_tap_Normal;

    doc_tap_Limit_operation;

    83%

    Normal operation current down
    Limit of current during normal operation down.

    38%

    doc_tap_Normal_down;

    doc_tap_Limit_down;

    38%

    Maximal current down change
    Prevent reloading blind up in case when it is moving down. Stops blind moving down in case the current down is higher than average current down in defined percent.

    250%

    doc_tap_Maximal;

    doc_tap_Prevent;

    250%

    Impulses per second to regulate speed. 
    Holds constant speed by using the number of impulses per second. If this is not possible to reach it holds higher possible or lower possible speed. To disable speed control set to 0.

    0

    doc_tap_Impulses;

    doc_tap_Holds;

    0

    Minimal PWM value. 
    Set minimal PWM value to regulate blind speed or to use soft start and soft end.

    50

    doc_tap_Minimal;

    doc_tap_set;

    50