  questions: ["Ako integrovať striedač Sofar Solar HYD KTL-3PH s TapHome?","Čo monitoruje TapHome šablóna pre Sofar Solar HYD KTL-3PH?","Ako pripojiť Sofar Solar HYD KTL-3PH cez RS-485 k TapHome?","Ako zapojiť viacero striedačov Sofar Solar na jednu zbernicu RS-485?","Aké parametre batérie číta TapHome šablóna pre Sofar Solar?","Ako monitorovať FV výrobu a energiu zo siete cez TapHome?"]
---

# Sofar Solar HYD KTL-3PH

Komunikácia: Modbus RTU

- [Oficiálna stránka Sofar Solar](https://www.sofarsolar.com)

## Návod na integráciu

Sofar Solar HYD 5/6/8/10/15/20KTL-3PH je séria trojfázových hybridných striedačov kombinujúcich solárnu FV výrobu s batériovým úložiskom energie. TapHome sa pripája cez Modbus RTU po RS-485 pomocou 16-pinového konektora COM na striedači a číta holding registre pre FV výkon v reálnom čase, stav batérií, výkon siete, napätia jednotlivých fáz a počítadlá energie.

Striedač podporuje až 31 zariadení na jednej zbernici RS-485 v zapojení daisy-chain. Každý striedač vyžaduje unikátne Modbus Slave ID (konfigurovateľné, predvolené 1). Komunikačné parametre sú fixné: 9600 baudov, 8N1.

## Hardvérové pripojenie

### Komunikačné rozhrania

![Umiestnenie komunikačných rozhraní Sofar Solar HYD KTL-3PH](https://taphome.com/images/compatibility/sofarsolar-inverter-3p/communication-interfaces_hu_5a569478a95349ec.jpg)

RS-485 pripojenie pre monitorovanie cez TapHome využíva **port COM** — 16-pinový multifunkčný konektor na spodnej strane striedača.

### Pinout konektora COM

![Pinout 16-pinového konektora COM na Sofar Solar HYD KTL-3PH](https://taphome.com/images/compatibility/sofarsolar-inverter-3p/com-port-pinout_hu_1534b25dbbb0b858.jpg)

**Relevantné piny pre pripojenie TapHome:**

| Pin | Funkcia | Poznámka |
|-----|---------|----------|
| **1** | RS485A1-1 (+) | Monitorovací/riadiaci RS-485 signál A |
| **2** | RS485A1-2 (+) | Druhý konektor pre daisy-chain |
| **3** | RS485B1-1 (-) | RS-485 signál B |
| **4** | RS485B1-2 (-) | Druhý konektor pre daisy-chain |
| 5 | RS485A2 (+) | Smart meter — samostatná zbernica |
| 6 | RS485B2 (-) | Smart meter — samostatná zbernica |
| 7 | CAN0_H | Komunikácia s BMS (CAN) |
| 8 | CAN0_L | Komunikácia s BMS (CAN) |

Pripojte TapHome k **pinom 1+3** (alebo 2+4):
- **Pin 1 (RS485A1)** → A+/D+ na RS-485 TapHome
- **Pin 3 (RS485B1)** → B-/D- na RS-485 TapHome

> [!WARNING]
> **Nepoužívajte piny 5+6** — tie sú vyhradené pre smart meter na samostatnej zbernici RS-485. TapHome sa musí pripojiť k pinom 1+3 (alebo 2+4) pre Modbus monitorovanie.

### Zapojenie RS-485 daisy-chain

![Zapojenie RS-485 daisy-chain pre viacero striedačov Sofar Solar](https://taphome.com/images/compatibility/sofarsolar-inverter-3p/wiring-rs485-daisy-chain_hu_1365fa6dd95340c6.jpg)

Pri pripojení viacerých striedačov ich zapojte do daisy-chain na zbernici RS-485. Na prvé a posledné zariadenie na zbernici umiestnite **120 Ohm terminačný rezistor** medzi Pin 1 a Pin 4.

**Špecifikácia kábla:**
- Typ: Tienený krútený pár, prierez medi > 0,5 mm²
- Maximálna dĺžka: **1200 m**
- Kábel veďte mimo silových káblov a elektrických polí

## Konfigurácia

### Parametre Modbus komunikácie

Komunikačné parametre RS-485 sú fixné a nevyžadujú konfiguráciu na strane striedača:

| Parameter | Hodnota |
|-----------|---------|
| Prenosová rýchlosť | 9600 bps |
| Dátové bity | 8 |
| Parita | Žiadna |
| Stop bity | 1 |
| Slave ID | 1 (predvolené, konfigurovateľné 1–31) |

Pri viacerých striedačoch na rovnakej zbernici musí mať každý unikátne Slave ID. Slave ID sa konfiguruje cez LCD menu striedača alebo aplikáciu SolarMAN.

## Funkcie zariadenia

### Monitorovanie batérií

Šablóna poskytuje monitorovanie stavu nabitia (SOC) pre až dva batériové pakety. SOC batérie 1 je dostupný na všetkých modeloch HYD KTL-3PH, SOC batérie 2 na modeloch HYD 10–20KTL-3PH s dvojitým batériovým vstupom.

Každé zariadenie SOC batérie obsahuje päť servisných atribútov pre detailnú diagnostiku: teplota, napätie, nabíjací/vybíjací prúd, nabíjací/vybíjací výkon a stav zdravia (SOH).

Dve zariadenia počítadiel energie sledujú denné nabíjanie a vybíjanie batérie v kWh, každé so servisným atribútom pre celoživotný súčet.

### Monitorovanie FV výroby

Šablóna číta výkon z až troch individuálnych FV stringov (PV1, PV2, PV3), každý so servisnými atribútmi pre napätie a prúd stringu. Kombinované zariadenie PV Power Total zobrazuje agregovaný výkon zo všetkých stringov.

Dve zariadenia počítadiel energie sledujú FV výrobu — denné a celoživotné súčty v kWh.

### Energia zo siete a spotreba

Tri zariadenia počítadiel energie poskytujú denné hodnoty pre interakciu so sieťou a spotrebu:
- **Energy Purchase Today** — energia odobratá zo siete (kWh)
- **Energy Selling Today** — energia dodaná do siete (kWh)
- **Load Consumption Today** — celková spotreba (kWh)

Každé denné počítadlo obsahuje servisný atribút s celoživotným súčtom.

### Monitorovanie AC výstupu

Šablóna poskytuje tri zariadenia napätia pre jednotlivé fázy (R/S/T-fáza, zodpovedajúce L1/L2/L3), každé so servisným atribútom pre fázový prúd. Frekvencia siete je udávaná v Hz.

Dve zariadenia výkonu monitorujú výstup striedača v rôznych meracích bodoch:
- **Total Active Power Output** — výstupný výkon striedača v kW, so servisnými atribútmi pre jalový výkon (kVAR) a zdanlivý výkon (kVA)
- **Total Active Power PCC** — výkon v bode spoločného pripojenia (bod pripojenia k sieti) v kW, so servisnými atribútmi pre jalový a zdanlivý výkon. Toto meranie sa používa pre obmedzenie dodávky do siete a funkcie regulátora elektrárne.

### Servisné atribúty modulu

Modul poskytuje tri servisné atribúty pre diagnostiku striedača:
- **Product Code** — identifikácia produktu striedača
- **System State** — aktuálny prevádzkový stav: Čakanie, Detekcia, Pripojený k sieti, Núdzové napájanie, Opraviteľná porucha, Trvalá porucha, Aktualizácia alebo Samodobíjanie
- **Ambient Temperature** — vnútorná teplota striedača v °C

Modul ReadScript tiež monitoruje tri registre chybových bitmások (H:0x0405–H:0x0407), ktoré hlásia poruchy ochrany siete, chyby vzorkovania a hardvérové poruchy ako chyby v TapHome.

### Ďalšie možnosti

Striedače HYD KTL-3PH tiež poskytujú registre pre vzdialené zapnutie/vypnutie, výber režimu úložiska energie (Vlastná spotreba, Časové pásma, Časovanie, Pasívny, Strihanie špičiek, Ostrovný režim) a pasívne riadenie nabíjania/vybíjania batérie pre externé systémy energetického manažmentu. K dispozícii sú aj činný výkon a účinník pre jednotlivé fázy, monitorovanie ostrovného/EPS výstupu, ďalšie FV vstupy (PV4+), počty cyklov batérie, teplota chladiča a parametre pre batérie 3–6. Tieto je možné pridať v budúcej aktualizácii šablóny.

> [!TIP]
> Registre pasívneho režimu (H:0x1110 a H:0x1187) umožňujú externé Modbus riadenie výkonu nabíjania/vybíjania batérie. To je obzvlášť užitočné pre smart rules v TapHome na implementáciu stratégií energetického manažmentu, ako je nabíjanie batérií počas období nízkeho tarifu.

## Riešenie problémov

### Žiadna Modbus komunikácia

1. Overte, že kábel RS-485 je pripojený k **pinom 1+3** (alebo 2+4) na konektore COM — nie k pinom 5+6 (zbernica smart metra)
2. Skontrolujte polaritu kábla: Pin 1 (A+) na TapHome A+, Pin 3 (B-) na TapHome B-
3. Potvrďte, že TapHome je nakonfigurovaný na 9600 baudov, bez parity, 1 stop bit
4. Overte, že Slave ID súhlasí medzi striedačom a TapHome
5. Skontrolujte 120 Ohm terminačný rezistor na prvom a poslednom zariadení na zbernici

### Prerušovaná komunikácia

1. Uistite sa, že kábel RS-485 je tienený krútený pár s prierezom medi > 0,5 mm²
2. Veďte kábel RS-485 mimo silových káblov a DC vedení
3. Skontrolujte, že celková dĺžka zbernice nepresahuje 1200 m
4. Overte, že na zbernici nie sú duplicitné Slave ID

### System State hlási poruchu

1. Skontrolujte servisný atribút System State pre konkrétny kód stavu (4 = Opraviteľná porucha, 5 = Trvalá porucha)
2. Prezrite detaily chybových registrov v servisnej diagnostike TapHome — šablóna číta tri registre chybových bitmások pokrývajúce ochranu siete, chyby vzorkovania a hardvérové poruchy
3. Pozrite LCD displej striedača alebo aplikáciu SolarMAN pre podrobné chybové kódy

## Dostupné zariadenia 19

Tieto zariadenia sa po importe zobrazia v TapHome.

Sofar Solar HYD KTL-3PH Modul

Servisné atribúty

|                |                                                                                                                                                        |
|----------------|--------------------------------------------------------------------------------------------------------------------------------------------------------|
| Kód produktu   |                                                                                                                                                        |
| Stav systému   | Prevádzkový stav striedača — Čakanie, Detekcia, Pripojený k sieti, Núdzové napájanie, Opraviteľná porucha, Trvalá porucha, Aktualizácia, Samodobíjanie |
| Teplota okolia | Vnútorná teplota striedača v °C                                                                                                                        |

Čítanie (modul)

```taphome
#fault 1
var fault :=MODBUSR(H, 0x0405, Uint16);
IF fault !=0 
IF(GETBIT(fault, 0) != 0, ADDERROR("Grid over-voltage"));
IF(GETBIT(fault, 1) != 0, ADDERROR("Grid undervoltage"));
IF(GETBIT(fault, 2) != 0, ADDERROR("Grid overfrequency"));
IF(GETBIT(fault, 3) != 0, ADDERROR("Grid underfrequency"));
IF(GETBIT(fault, 4) != 0, ADDERROR("Leakage current fault"));
IF(GETBIT(fault, 5) != 0, ADDERROR("High penetration error"));
IF(GETBIT(fault, 6) != 0, ADDERROR("Low penetration error"));
IF(GETBIT(fault, 7) != 0, ADDERROR("Islanding error"));
IF(GETBIT(fault, 8) != 0, ADDERROR("Grid voltage transient value overvoltage 1"));
IF(GETBIT(fault, 9) != 0, ADDERROR("Grid voltage transient value overvoltage 2"));
IF(GETBIT(fault, 10) != 0, ADDERROR("Grid line voltage error"));
IF(GETBIT(fault, 11) != 0, ADDERROR("Inverter voltage error"));
IF(GETBIT(fault, 12) != 0, ADDERROR("Anti-backflow overload"));
END

#fault 2
fault :=MODBUSR(H, 0x0406, Uint16);
IF fault !=0 
IF(GETBIT(fault, 0) != 0, ADDERROR("Grid current sampling error"));
IF(GETBIT(fault, 1) != 0, ADDERROR("Grid current DC component sampling error (AC side)"));
IF(GETBIT(fault, 2) != 0, ADDERROR("Grid voltage sampling error (DC side)"));
IF(GETBIT(fault, 3) != 0, ADDERROR("Grid voltage sampling error (AC side)"));
IF(GETBIT(fault, 4) != 0, ADDERROR("Leakage current sampling error (DC side)"));
IF(GETBIT(fault, 5) != 0, ADDERROR("Leakage current sampling error (AC side)"));
IF(GETBIT(fault, 6) != 0, ADDERROR("Load voltage DC component sampling error"));
IF(GETBIT(fault, 7) != 0, ADDERROR("DC input current sampling error"));
IF(GETBIT(fault, 8) != 0, ADDERROR("DC component sampling error of grid current (DC side)"));
IF(GETBIT(fault, 9) != 0, ADDERROR("DC input branch current sampling error"));
IF(GETBIT(fault, 12) != 0, ADDERROR("Leakage current consistency error"));
IF(GETBIT(fault, 13) != 0, ADDERROR("Grid voltage consistency error"));
IF(GETBIT(fault, 14) != 0, ADDERROR("DCI consistency error"));
END

#fault 3
fault :=MODBUSR(H, 0x0407, Uint16);
IF fault !=0 
IF(GETBIT(fault, 0) != 0, ADDERROR("SPI communication error (DC side)"));
IF(GETBIT(fault, 1) != 0, ADDERROR("SPI communication error (AC side)"));
IF(GETBIT(fault, 2) != 0, ADDERROR("Chip error (DC side)"));
IF(GETBIT(fault, 3) != 0, ADDERROR("Chip error (AC side)"));
IF(GETBIT(fault, 4) != 0, ADDERROR("Auxiliary power error"));
IF(GETBIT(fault, 5) != 0, ADDERROR("Inverter soft start failure"));
IF(GETBIT(fault, 8) != 0, ADDERROR("Relay detection failure"));
IF(GETBIT(fault, 9) != 0, ADDERROR("Low insulation impedance"));
IF(GETBIT(fault, 10) != 0, ADDERROR("Grounding error"));
IF(GETBIT(fault, 11) != 0, ADDERROR("Input mode setting error"));
IF(GETBIT(fault, 12) != 0, ADDERROR("CT error"));
IF(GETBIT(fault, 13) != 0, ADDERROR("Input reversal error"));
IF(GETBIT(fault, 14) != 0, ADDERROR("Parallel error"));
IF(GETBIT(fault, 15) != 0, ADDERROR("Serial number error"));
END
```

Servisné atribúty

Product Code

```taphome
MODBUSR(H, 0x2000, Uint16);
```

System State

```taphome
SWITCH(MODBUSR(H, 0x0404, Uint16),
0, "Waiting",
1, "Detection",
2, "Grid-connected",
3, "Emergency power supply",
4, "Recoverable fault",
5, "Permanent fault",
6, "Upgrade",
7, "Self-charging",
"Fault")
```

Ambient Temperature

```taphome
MODBUSR(H, 0x0418, Int16) + "°C";
```

Batéria 1 SOC Analógový vstup Len na čítanie

Stav nabitia batérie 1 v percentách — obsahuje servisné atribúty pre teplotu, napätie, prúd, výkon a SOH

Register: H:0x0608 Uint16 Jednotka: % numeric

Servisné atribúty

|         |
|---------|
| Teplota |
| Napätie |
| Prúd    |
| Výkon   |
| SOH     |

Čítanie vstupnej úrovne

```taphome
MODBUSR(H, 0x0608, Uint16)
```

Servisné atribúty

Temperature

```taphome
MODBUSR(H, 0x0607, Int16) + "°C";
```

Voltage

```taphome
MODBUSR(H, 0x0604, Uint16) + " V";
```

Current

```taphome
MODBUSR(H, 0x0605, Int16)/100 + " A";
```

Power

```taphome
MODBUSR(H, 0x0606, Int16)/100 + " kW";
```

SOH

```taphome
MODBUSR(H, 0x0609, Uint16) + " %";
```

Batéria 2 SOC Analógový vstup Len na čítanie

Stav nabitia batérie 2 v percentách — dostupné na modeloch HYD 10–20KTL-3PH s dvojitým batériovým vstupom

Register: H:0x060F Uint16 Jednotka: % numeric

Servisné atribúty

|         |
|---------|
| Teplota |
| Napätie |
| Prúd    |
| Výkon   |
| SOH     |

Čítanie vstupnej úrovne

```taphome
MODBUSR(H, 0x060F, uint16)
```

Servisné atribúty

Temperature

```taphome
MODBUSR(H, 0x060E, Int16) + " °C";
```

Voltage

```taphome
MODBUSR(H, 0x060B, Uint16) + " V";
```

Current

```taphome
MODBUSR(H, 0x060C, Int16) + " A";
```

Power

```taphome
MODBUSR(H, 0x060D, Int16) + " kW";
```

SOH

```taphome
MODBUSR(H, 0x0610, Uint16) + " %";
```

Vybíjanie batérie dnes Premenná Len na čítanie

Denná energia vybíjania batérie v kWh — obsahuje celoživotný súčet

Register: H:0x0698 Uint32 Jednotka: kWh numeric

Servisné atribúty

|                           |
|---------------------------|
| Celkové vybíjanie batérie |

Čítanie

```taphome
MODBUSR(H, 0x0698, Uint32)/100
```

Servisné atribúty

Battery Discharge Total

```taphome
MODBUSR(H, 0x069A, Uint32)/10
```

Nabíjanie batérie dnes Premenná Len na čítanie

Denná energia nabíjania batérie v kWh — obsahuje celoživotný súčet

Register: H:0x0694 Uint32 Jednotka: kWh numeric

Servisné atribúty

|                           |
|---------------------------|
| Celkové nabíjanie batérie |

Čítanie

```taphome
MODBUSR(H, 0x0694, Uint32)/100
```

Servisné atribúty

Battery Charge Total

```taphome
MODBUSR(H, 0x0696, Uint32)/10
```

Odber energie dnes Premenná Len na čítanie

Denná energia odobratá zo siete v kWh — obsahuje celoživotný súčet

Register: H:0x068C Uint32 Jednotka: kWh numeric

Servisné atribúty

|                       |
|-----------------------|
| Celkový odber energie |

Čítanie

```taphome
MODBUSR(H, 0x068C, Uint32)/100
```

Servisné atribúty

Energy Purchase Total

```taphome
MODBUSR(H, 0x068E, Uint32)/10 + " kWh"
```

Dodávka energie dnes Premenná Len na čítanie

Denná energia dodaná do siete v kWh — obsahuje celoživotný súčet

Register: H:0x0690 Uint32 Jednotka: kWh numeric

Servisné atribúty

|                         |
|-------------------------|
| Celková dodávka energie |

Čítanie

```taphome
MODBUSR(H, 0x0690, Uint32)/100
```

Servisné atribúty

Energy Selling Total

```taphome
MODBUSR(H, 0x0692, Uint32)/10
```

Frekvencia siete Premenná Len na čítanie

Register: H:0x0484 UInt16 Jednotka: Hz numeric

Čítanie

```taphome
MODBUSR(H, 0x484, UInt16)/100
```

Spotreba dnes Premenná Len na čítanie

Denná spotreba v kWh — obsahuje celoživotný súčet

Register: H:0x0688 Int32 Jednotka: kWh numeric

Servisné atribúty

|                  |
|------------------|
| Celková spotreba |

Čítanie

```taphome
MODBUSR(H, 0x0688, Int32)/100
```

Servisné atribúty

Load Consumption Total

```taphome
MODBUSR(H, 0x068A, Int32)/100 + "kWh"
```

Celkový FV výkon Premenná Len na čítanie

Kombinovaný výkon zo všetkých FV stringov v kW

Register: H:0x05C4 Uint16 Jednotka: kW numeric

Čítanie

```taphome
MODBUSR(H, 0x05C4, Uint16)/10
```

PV1 výkon Premenná Len na čítanie

Register: H:0x0586 Uint16 Jednotka: kW numeric

Servisné atribúty

|         |
|---------|
| Napätie |
| Prúd    |

Čítanie

```taphome
MODBUSR(H, 0x0586, Uint16)/100
```

Servisné atribúty

Voltage

```taphome
MODBUSR(H, 0x0584, Uint16)/10 + " V";
```

Current

```taphome
MODBUSR(H, 0x0585, Uint16)/100 + " A";
```

PV2 výkon Premenná Len na čítanie

Register: H:0x0589 Uint16 Jednotka: kW numeric

Servisné atribúty

|         |
|---------|
| Napätie |
| Prúd    |

Čítanie

```taphome
MODBUSR(H, 0x0589, Uint16)/100
```

Servisné atribúty

Voltage

```taphome
MODBUSR(H, 0x0587, Uint16)/10 + " V";
```

Current

```taphome
MODBUSR(H, 0x0588, Uint16)/100 + " A";
```

PV3 výkon Premenná Len na čítanie

Register: H:0x058A Uint16 Jednotka: kW numeric

Servisné atribúty

|         |
|---------|
| Napätie |
| Prúd    |

Čítanie

```taphome
MODBUSR(H, 0x058A, Uint16)/100
```

Servisné atribúty

Voltage

```taphome
MODBUSR(H, 0x058A, Uint16)/10 + " V";
```

Current

```taphome
MODBUSR(H, 0x058B, Uint16)/100 + " A"
```

FV výroba dnes Premenná Len na čítanie

Denná FV výroba v kWh

Register: H:0x0684 Int32 Jednotka: kWh numeric

Čítanie

```taphome
MODBUSR(H, 0x0684, Int32)/100
```

Celková FV výroba Premenná Len na čítanie

Celoživotná FV výroba v kWh

Register: H:0x0686 Int32 Jednotka: kWh numeric

Čítanie

```taphome
MODBUSR(H, 0x0686, Int32)/100
```

Napätie fázy R Premenná Len na čítanie

Napätie siete L1/R-fázy v V — obsahuje servisný atribút fázového prúdu

Register: H:0x048D Uint16 Jednotka: V numeric

Servisné atribúty

|        |
|--------|
| Prúd R |

Čítanie

```taphome
MODBUSR(H, 0x048D, Uint16)/10
```

Servisné atribúty

Current R

```taphome
MODBUSR(H, 0x048E, Uint16)/100 + " A";
```

Napätie fázy S Premenná Len na čítanie

Napätie siete L2/S-fázy v V — obsahuje servisný atribút fázového prúdu

Register: H:0x0498 Uint16 Jednotka: V numeric

Servisné atribúty

|        |
|--------|
| Prúd S |

Čítanie

```taphome
MODBUSR(H, 0x0498, Uint16)/10
```

Servisné atribúty

Current S

```taphome
MODBUSR(H, 0x0499, Uint16)/100 + " A"
```

Napätie fázy T Premenná Len na čítanie

Napätie siete L3/T-fázy v V — obsahuje servisný atribút fázového prúdu

Register: H:0x04A3 Uint16 Jednotka: V numeric

Servisné atribúty

|        |
|--------|
| Prúd T |

Čítanie

```taphome
MODBUSR(H, 0x04A3, Uint16)/10
```

Servisné atribúty

Current T

```taphome
MODBUSR(H, 0x04A4, Uint16)/100 + " A"
```

Celkový činný výkon Premenná Len na čítanie

Celkový činný výkon striedača v kW — obsahuje jalový a zdanlivý výkon

Register: H:0x0485 Int16 Jednotka: kW numeric

Servisné atribúty

|                |
|----------------|
| Jalový výkon   |
| Zdanlivý výkon |

Čítanie

```taphome
MODBUSR(H, 0x0485, Int16)/100
```

Servisné atribúty

Reactive Power Output

```taphome
MODBUSR(H, 0x0486, Int16)/100 + " kW" ;
```

Apparent Power Output

```taphome
MODBUSR(H, 0x0487, Int16)/100 + " kW" ;
```

Celkový činný výkon PPC Premenná Len na čítanie

Činný výkon v bode spoločného pripojenia (bod pripojenia k sieti) v kW — používa sa pre obmedzenie dodávky

Register: H:0x0488 Int16 Jednotka: kW numeric

Servisné atribúty

|                    |
|--------------------|
| Jalový výkon PPC   |
| Zdanlivý výkon PPC |

Čítanie

```taphome
MODBUSR(H, 0x0488, Int16)/100
```

Servisné atribúty

Reactive Power PPC

```taphome
MODBUSR(H, 0x0489, Int16)/100 + " kW" ;
```

Apparent Power PPC

```taphome
MODBUSR(H, 0x048A, Int16)/100 + " kW" ;
```

**Pripojenie:** Modbus RTU • 9600 baud• 8N1 • Slave ID: $\[SlaveId]

Možné vylepšenia (12)

- H:0x1104 Remote Switch On/Off — Remote inverter on/off control — useful for TapHome automation
- H:0x1110 Energy Storage Mode — Operating mode selection: Self-use, Time-of-Use, Timing, Passive, Peak Shaving, Off-grid
- H:0x1187 Passive Battery Charge/Discharge — S32, external Modbus control of battery charge/discharge power — enables TapHome smart rule energy management
- H:0x0200 Running State — 0=Wait, 1=CheckState, 2=Normal, 3=CheckDischarge, 4=Discharge, 5=EPS, 6=Fault, 7=Permanent — older register range, covered by H:0x0404 System State in module
- H:0x0504 Off-Grid Active Power — EPS/backup output power (S16, 0.01 kW) — relevant for off-grid/backup scenarios
- H:0x050A-0x0522 Off-Grid Per-Phase Voltage/Current/Power — L1/L2/L3 off-grid output monitoring — 9 registers for 3-phase EPS output
- H:0x0507 Off-Grid Frequency — EPS output frequency (U16, 0.01 Hz)
- H:0x048F-0x04A7 Per-Phase Active/Reactive Power and Power Factor — L1/L2/L3 individual active power, reactive power, and power factor — template only reads voltage+current per phase
- H:0x058D-0x058F PV4 Voltage/Current/Power — PV string 4 input — template supports up to PV3. HA integration supports up to PV10
- H:0x0612-0x0627 Battery 3–6 Parameters — Additional battery packs (voltage, current, power, temperature, SOC, SOH, cycles) — template supports battery 1–2 only
- H:0x022C Battery Cycle Count — Battery cycle times (Uint16, 0–65536) — available at 0x060A per battery in HA integration
- H:0x0419 Heatsink Temperature — Inverter heatsink temperature (S16, °C) — template reads inner temperature (0x0418) only

## Parametre importu

Tieto hodnoty zadáte pri importe XML.

| Pýta sa v aplikácii | Predvolené    |
|---------------------|---------------|
| Slave ID            | `1`           |
| IP adresa           | `192.168.1.0` |

## Zdroje

- SOFARSOLAR ModBus-RTU Communication Protocol
  
  [community.openenergymonitor.org](https://community.openenergymonitor.org/uploads/short-url/dF8j79PsvtCS0xQ5aPxHXO4HZDE.pdf) 2026-03-28
  
  [PDF](https://taphome.com/compatibility/devices/sofarsolar-inverter-3p/manufacturer/sofarsolar-modbus-rtu-protocol.pdf)
- HYD 5/6/8/10/15/20KTL-3PH User Manual
  
  [www.sofarsolar.com](https://www.sofarsolar.com/upload/file/20240321/1710982866939025487.pdf) 2026-03-28
  
  [PDF](https://taphome.com/compatibility/devices/sofarsolar-inverter-3p/manufacturer/hyd-5-20ktl-3ph-user-manual.pdf)
- Home Assistant SolaX/Sofar Modbus Integration
  
  [github.com](https://github.com/wills106/homeassistant-solax-modbus) 2026-03-28

Dokumenty výrobcov sú © ich príslušných vlastníkov. Poskytujeme ich tak, ako ich zverejnil výrobca, len na informačné účely.

## Súvisiaca dokumentácia

- [Modbus Integration](https://taphome.com/sk/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/sk/docs/integration/modbus/)
- [Jednoduchá konfigurácia pomocou šablón](https://taphome.com/sk/docs/integration/modbus/templates/)
- [Skripty Modbus a prefetch](https://taphome.com/sk/docs/script/modbus-scripts/)
- [Funkcie Modbus](https://taphome.com/sk/docs/script/modbus/)
- [Dátové typy Modbus](https://taphome.com/sk/docs/script/modbus-data-types/)