title: "Schrack i-CHARGE CION"
description: "Wallbox Schrack Technik i-CHARGE CION (11 kW a 22 kW) integrovaný cez Modbus RTU po RS-485."
url: "https://taphome.com/sk/compatibility/schrack-i-charge-cion/"
language: sk
lastmod: 2026-03-28
generator: hugo
ai:
  topics: ["modbus-rtu","wallbox","rs485","ev-charger","dip-switch","mode-3"]
  questions: ["Ako integrovať Schrack i-CHARGE CION s TapHome?","Čo ovláda TapHome šablóna pre Schrack i-CHARGE CION?","Ako pripojiť Schrack i-CHARGE CION cez RS-485 k TapHome?","Ako aktivovať Modbus RTU režim na Schrack i-CHARGE CION?","Aké nastavenie DIP prepínačov je potrebné pre Modbus na i-CHARGE CION?","Ako ovládať nabíjací prúd EV cez TapHome?"]
---

# Schrack i-CHARGE CION

Komunikácia: Modbus RTU

- [Oficiálna stránka Schrack Technik](https://www.schrack.com)

## Návod na integráciu

Schrack Technik i-CHARGE CION je nabíjacia stanica Mode 3 pre elektromobily, dostupná vo variantoch 11 kW a 22 kW. S TapHome komunikuje cez Modbus RTU po RS-485. Keďže TapHome Core používa Modbus TCP, medzi TapHome a nabíjačkou je potrebná brána Modbus-TCP-to-RS-485 (napr. prevodník Waveshare RS485-to-Ethernet).

TapHome šablóna poskytuje riadenie nabíjania (autorizácia/odmietnutie, nastavenie prúdu, minimálny prúd), monitoring stavu CP signálu, detekciu kábla, ovládanie zámku konektora, meranie napätia a teploty a diagnostické varovania pre bežné poruchové stavy.

## Hardvérové pripojenie

### Zapojenie RS-485 Modbus RTU

![Schrack i-CHARGE CION schéma riadiacej jednotky — pripojenie RS-485 Modbus RTU](https://taphome.com/images/compatibility/schrack-i-charge-cion/wiring-rs485-modbus_hu_db6f283de3df0e90.jpg)

RS-485 zbernica sa pripája na svorky **A** a **B** v spodnej časti dosky riadiacej jednotky. Tieto svorky pripojte k bráne Modbus-TCP:

- **A** → A+/D+ na RS-485 bráne
- **B** → B-/D- na RS-485 bráne

Použite štandardný CAT kábel (CAT5 alebo lepší). Uzemnenie tienenia podľa výrobcu **nie je potrebné** pre prenos dát.

> [!NOTE]
> DIP prepínače 1 a 2 musia byť oba nastavené na **OFF** pred tým, ako sa svorky RS-485 aktivujú. V režime Modbus RTU sú externé vstupy E1 a E3 ignorované.

### Prehľad riadiacej dosky

![Schrack i-CHARGE CION riadiaca doska — rozloženie svoriek s RS-485, E1, E3 a RFID pripojením](https://taphome.com/images/compatibility/schrack-i-charge-cion/wiring-controller-schematic_hu_eb444934f60a2009.jpg)

Riadiaca doska má nasledujúce svorky (horný rad, zľava doprava): A4, A3, A2, A1, E1, E3, Pb, Pa. RS-485 linky A/B sa pripájajú v spodnej časti dosky. RFID čítačka sa pripája cez RJ11.

## Konfigurácia

### Aktivácia Modbus komunikácie

![Schrack i-CHARGE CION konfigurácia DIP prepínačov — pozície 1-4](https://taphome.com/images/compatibility/schrack-i-charge-cion/dip-switch-configuration_hu_3c2be14791878f3.jpg)

4-polohový DIP prepínač na riadiacej jednotke nastavuje prevádzkový režim a maximálny nabíjací prúd.

**DIP prepínače 1-2 — Prevádzkový režim:**

| DIP 1 | DIP 2 | Režim |
|-------|-------|-------|
| **OFF** | **OFF** | **RS-485 Modbus RTU** (vyžadovaný pre TapHome) |
| OFF | ON | Normálna prevádzka, rozhranie 0-10V režim 1 |
| ON | OFF | Normálna prevádzka, rozhranie 0-10V režim 2 |
| ON | ON | Vymazanie/tréning RFID kariet |

**DIP prepínače 3-4 — Maximálny nabíjací prúd:**

| DIP 3 | DIP 4 | Prúd |
|-------|-------|------|
| ON | ON | 32 A (iba modely 22 kW) |
| OFF | ON | 20 A (iba modely 22 kW) |
| ON | OFF | 16 A |
| OFF | OFF | 13 A (predvolené) |

> [!WARNING]
> Po zmene pozícií DIP prepínačov je nutné nabíjaciu stanicu reštartovať, aby sa nové nastavenia prejavili.

### Komunikačné parametre

| Parameter | Predvolená hodnota |
|-----------|---------------------|
| Prenosová rýchlosť | 57600 |
| Dátové bity | 8 |
| Stop bity | 1 |
| Parita | Žiadna |
| Slave ID | 1 |

Slave ID je možné zmeniť cez Modbus register H:500. Prenosovú rýchlosť je možné zmeniť cez register H:509 (0=9600, 1=14400, 2=19200, 3=28800, 4=38400, 5=57600; ostatné hodnoty sa nastavia na 115200).

## Schopnosti zariadenia

### Riadenie nabíjania

- **Autorizácia nabíjania** (H:100) — povoľuje alebo zakazuje nabíjanie. V režime Modbus nahrádza externý vstup E1. Zariadenie tiež zobrazuje **Dobu nabíjania** ako servisný atribút s uplynutým časom nabíjania vo formáte HH:MM:SS.
- **Nastavenie nabíjacieho prúdu** (H:101) — nastavuje aktívny nabíjací prúd v ampéroch, obmedzený na rozsah 6-32 A.
- **Minimálny nabíjací prúd** (H:507) — nastavuje minimálny prah nabíjacieho prúdu v ampéroch (predvolené 13 A, rozsah 6-32 A). Primárne sa používa ako spodná hranica pre rozhranie 0-10V PV.

### Monitoring stavu

- **Stav CP** (H:139) — zobrazuje stav riadiaceho pilotného signálu Mode 3: A (Pohotovosť), B (Vozidlo detegované), C (Pripravené/Nabíjanie), D (S ventiláciou), E (Bez napájania), F (Chyba) alebo U (Neznámy).
- **Nabíjací kábel pripojený** (H:121, bit 0) — binárny senzor indikujúci, či je nabíjací kábel pripojený. Zariadenie tiež zobrazuje **Dobu pripojenia** ako servisný atribút.
- **Aktuálny nabíjací prúd** (H:126) — senzor zobrazujúci aktuálny nabíjací prúd v ampéroch (iba na čítanie).

### Napätie a teplota

- **Napätie fázy 1** (H:167) — sieťové napätie na fáze 1, surová hodnota delená 100 pre zobrazenie vo voltoch.
- **Teplota** (H:303) — vstavaný teplotný senzor v riadiacej jednotke, v °C.

### Zámok konektora

- **Zámok konektora** (H:118) — ovláda zámok nabíjacej zásuvky s tromi režimami: Automatický (predvolený), Zamknutý alebo Odomknutý.

### Diagnostika

Modul na úrovni ReadScript priebežne monitoruje poruchové stavy a hlási varovania v TapHome:

| Podmienka | Varovanie |
|-----------|-----------|
| H:306 != 0 | Chyba riadiacej jednotky |
| H:146 != 0 | Chyba vierohodnosti signálov PP/CP |
| H:121 bit 6 | Súhrnná chyba |
| H:121 bit 7 | Výpadok napájania RCCB/MCB |
| H:121 bit 8 | Chybný nabíjací kábel |
| H:121 bit 9 | Nabíjací kábel odmietnutý |
| H:121 bit 10 | Chyba nabíjacieho stýkača |
| H:121 bit 12 | Zlyhanie samotestu RCMU |
| H:121 bit 13 | Detegovaný reziduálny prúd |

### Ďalšie schopnosti

i-CHARGE CION tiež poskytuje registre pre ovládanie LED (manuálna aktivácia LED Pripravené/Nabíjanie a RGB signalizácia), spätnú väzbu maximálneho nabíjacieho prúdu, prúdovú kapacitu kábla, stav CP generátora, identifikáciu PP kábla, chybové slovo s individuálnymi poruchovými bitmi, monitoring napájacieho napätia, meranie vstupného napätia (E1, E3), detekciu konfiguračných chýb, časové režimy zámku konektora, analógový teplotný senzor, PV škálovací faktor a prepínanie fáz cez výstup A4 (pre ovládanie externého stýkača). Tieto funkcie je možné pridať v budúcej aktualizácii šablóny.

## Riešenie problémov

### Žiadna Modbus komunikácia

1. Overte, že DIP prepínače 1 a 2 sú oba nastavené na **OFF**
2. Skontrolujte zapojenie RS-485 — A na A+, B na B-
3. Potvrďte, že brána Modbus-TCP je nakonfigurovaná na 57600 baud, 8N1
4. Overte, že slave ID sa zhoduje (predvolené: 1, konfigurovateľné cez H:500)
5. Reštartujte nabíjaciu stanicu po akejkoľvek zmene DIP prepínačov

### Autorizácia nabíjania nemá účinok

Príznak „Autorizácia nabíjania ignorovaná" (H:120) sa nastaví, keď autorizáciu nabíjania nie je možné aplikovať — napríklad keď nie je pripojené vozidlo, existuje chyba kábla alebo je nabíjačka v chybovom stave. Najprv vyriešte základnú príčinu.

### Hodnota napätia sa javí nesprávna

Napätie fázy 1 (H:167) používa násobiteľ 1/100 — surová hodnota 23000 zodpovedá 230,00 V. Ak sa zobrazená hodnota zdá 100× väčšia, overte, že zariadenie v TapHome je nakonfigurované so správnou konverziou.

## Dostupné zariadenia 9

Tieto zariadenia sa po importe zobrazia v TapHome.

Schrack i-CHARGE CION Modul

Servisné atribúty

|                    |                                                                                                            |
|--------------------|------------------------------------------------------------------------------------------------------------|
| Názov výrobcu      |                                                                                                            |
| Názov zariadenia   |                                                                                                            |
| Verzia firmvéru    |                                                                                                            |
| Prenosová rýchlosť | Aktuálna prenosová rýchlosť Modbus — dekódovaný enum: 9600, 14400, 19200, 28800, 38400, 57600 alebo 115200 |
| RFID Tag           | Identifikátor posledného naskenovaného RFID tagu                                                           |

Servisné akcie

|                            |                                            |
|----------------------------|--------------------------------------------|
| Reštart riadiacej jednotky | Spustí úplný reset EVCC riadiacej jednotky |

Čítanie (modul)

```taphome
if(modbusr(H, 306, Uint16), ADDWARNING("Storung"));
if(modbusr(H, 146, Uint16), ADDWARNING("Plausibitatzfehler bei PPbzw. CP"));
var r121 := modbusr(H, 121, Uint16);
if(getbit(r121, 6), ADDWARNING("Sammelstorung"));
if(getbit(r121, 7), ADDWARNING("Storung: Netzausfall FI/LS"));
if(getbit(r121, 8), ADDWARNING("Storung: Ladekabel"));
if(getbit(r121, 9), ADDWARNING("Storung: Ladekabel abgewiesen"));
if(getbit(r121, 10), ADDWARNING("Storung: charging contactor"));
if(getbit(r121, 12), ADDWARNING("Storung: RCMU Selbttest fehler"));
if(getbit(r121, 13), ADDWARNING("Storung: Fehlerstrom"));
```

Servisné atribúty

Herstellerbezeichnung

```taphome
modbusr(H, 800, String, 15)
```

Geratebezeichnung

```taphome
modbusr(H, 816, String, 15)
```

Firmwareversion

```taphome
modbusr(H, 832, String, 16)
```

Baudrate

```taphome
switch(modbusr(H, 509, Uint16),
0, 9600,
1, 14400,
2, 19200,
3, 28800,
4, 38400,
5, 57600,
115200)
```

RFID Tag

```taphome
modbusr(H, 129, String, 4)
```

Servisné akcie

Controller Neustart

```taphome
modbusw(H, 1000, Uint16, 1234)
```

Aktuálny nabíjací prúd Premenná Len na čítanie

Aktuálny nabíjací prúd Mode 3 v ampéroch

Register: H:126 UInt16 Jednotka: A numeric

Čítanie

```taphome
MODBUSR(H, 126, Uint16)
```

Autorizácia nabíjania Prepínač Čítanie aj zápis

Povoľuje alebo zakazuje nabíjanie EV — v režime Modbus nahrádza externý vstup E1

Register: H:100 UInt16

Hodnoty / Stavy: ${general\_enabled} · ${general\_disabled}

Čítanie stavu prepínača

```taphome
MODBUSR(H, 100, Uint16)
```

Zápis stavu prepínača

```taphome
MODBUSW(H, 100, Uint16, St)
```

Servisné atribúty

Ladedauer

```taphome
var total := MODBUSR(H, 151, LittleEndianUint32);
var sec := mod(total, 60);
var min := mod(floor(total/60), 60);
var hod := floor(total/3600);

hod + ":" + tostring(min, "X2") + ":" + tostring(sec, "X2")
```

Stav CP Viacstavový prepínač Len na čítanie

Stav riadiaceho pilotného signálu Mode 3 — A (Pohotovosť), B (Vozidlo detegované), C (Pripravené/Nabíjanie), D (S ventiláciou), E (Bez napájania), F (Chyba), U (Neznámy)

Register: H:139 Char numeric

Hodnoty / Stavy: A - Standby · B - Vehicle detected · C - Ready (charging) · D - With ventilation · E - No power (shut off) · F - Error · U - Unknown

Čítanie stavu prepínača

```taphome
switch(MODBUSR(H, 139, Uint16),
65, 0,
66, 1,
67, 2,
68, 3,
69, 4,
70, 5,
6)
```

Nabíjací kábel pripojený Jazýčkový kontakt Len na čítanie

Register: H:121 UInt16 bitmask

Servisné atribúty

|                 |                                          |
|-----------------|------------------------------------------|
| Doba pripojenia | Čas pripojenia kábla vo formáte HH:MM:SS |

Čítanie

```taphome
GETBIT(MODBUSR(H, 121, Uint16), 0)
```

Servisné atribúty

Angesteckt-Dauer

```taphome
var total := MODBUSR(H, 153, LittleEndianUint32);
var sec := mod(total, 60);
var min := mod(floor(total/60), 60);
var hod := floor(total/3600);

hod + ":" + tostring(min, "X2") + ":" + tostring(sec, "X2")
```

Nastavenie nabíjacieho prúdu Premenná Čítanie aj zápis

Aktívne nastavenie nabíjacieho prúdu v ampéroch, nastaviteľné od 6 do 32 A

Register: H:101 UInt16 Jednotka: A numeric

Čítanie

```taphome
MODBUSR(H, 101, Uint16)
```

Zápis

```taphome
MODBUSW(H, 101, Uint16, LINEAR(Va, 6, 6, 32, 32, BOUNDS))
```

Minimálny nabíjací prúd Premenná Čítanie aj zápis

Minimálny prah nabíjacieho prúdu v ampéroch (predvolené 13 A) — spodná hranica pre rozhranie 0-10V PV

Register: H:507 UInt16 Jednotka: A numeric

Čítanie

```taphome
MODBUSR(H, 507, Uint16)
```

Zápis

```taphome
MODBUSW(H, 507, Uint16, LINEAR(Va, 6, 6, 32, 32, BOUNDS))
```

Napätie fázy 1 Premenná Len na čítanie

Register: H:167 UInt16 Jednotka: V numeric

Čítanie

```taphome
MODBUSR(H, 167, Uint16)
```

Teplota Teplotný senzor Len na čítanie

Register: H:303 UInt16 Jednotka: °C numeric

Čítanie teploty

```taphome
MODBUSR(H, 303, Uint16)
```

Zámok konektora Viacstavový prepínač Čítanie aj zápis

Ovládanie zámku nabíjacej zásuvky — Automatický, Zamknutý alebo Odomknutý

Register: H:118 UInt16 numeric

Hodnoty / Stavy: Automatic · Verriegeln · Entriegeln

Čítanie stavu prepínača

```taphome
switch(MODBUSR(H, 118, Uint16),
1, 1,
2, 2,
0)
```

Zápis stavu prepínača

```taphome
MODBUSW(H, 118, Uint16, Mu)
```

**Pripojenie:** Modbus RTU • 57600 baud• 8N1 • Slave ID: $\[SlaveId]

Možné vylepšenia (25)

- H:102 Automatic LED Activation — 0=manual LED control via registers 103-117, 1=automatic. Low priority — cosmetic
- H:103-117 LED Control Registers — Manual control of Ready/Charging LEDs and RGB signalling. 15 registers for timing, duty, color. Low priority — cosmetic
- H:120 Charging Authorisation Ignored — Read-only flag indicating charging authorisation was ignored (e.g. no car connected, error). Useful for diagnostics
- H:121 bits 1-5 Additional Status Bits — Contactor 1/2 active, ventilation requested, connector locking activation/response. Template only uses bit 0 (cable plugged) and bits 6-13 (errors in readscript)
- H:127 Maximum Charging Current — Maximum Mode 3 charging current value in A. Read-only. Useful to show hardware limit
- H:128 Cable Current Carrying Capacity — Current carrying capacity of charging cable in A: 0, 13, 20, 32, 63. Read-only
- H:140 CP Generator State — 0=high resistance, 1=DC positive, 2=DC negative, 3=PWM. Low-level diagnostics
- H:141 PP Status — Proximity pilot cable identification: 0, 13, 20, 32, 63 A, or SC. Read-only. Partially covered by operating manual reference
- H:147 Configuration Error — 0=no error, 1=plausibility error in configuration. Read-only diagnostic
- H:148 Voltage E1 — Voltage at input E1 in mV (multiplier 1/1000). DC input for external activation
- H:149 Voltage E3 — Voltage at input E3 in mV (multiplier 1/1000). DC input for 0-10V PV interface
- H:150 Error Word — 16-bit error word with 9 individual error bits. Partially covered by readscript warnings on H:121 bits 6-13
- H:300 Operating Mode — 0=slave. Read-only. Low value — always 0 in Modbus RTU mode
- H:301 Supply Voltage — Supply voltage of charging controller in mV (multiplier 1/1000). Internal diagnostics
- H:302 Mains Voltage — Mains voltage measured at RCCB/MCB in V (multiplier 1/100). Alternative to H:167
- H:305 Locked Time Mode — Connector lock timing mode: 1=plugged-to-unplugged, 2=charging-start-to-end, 3=charging-start-to-unplugged. R/W
- H:307 Analogue Temperature Sensor — Temperature measured value in mV. Raw analogue reading, lower priority than H:303
- H:308 A4 Control via Modbus — Control signal output A4 for external contactor. Used for phase switching (L2/L3) with safety constraints. R/W
- H:500 Bus Address Override — Modbus slave address override. Default 1. R/W
- H:501 Default Charging Current Override — Default charging current in A, only effective with specific DIP switch position. R/W
- H:503 Locking Delay — Connector locking delay in ms. Default 250ms. R/W
- H:505 Motor Activation Time — Lock motor activation time in ms. Default 500ms. R/W
- H:506 Cable Mode — 0=charging socket, 1=permanently connected cable. R/W
- H:508 PV Scaling — x ampere per volt for PV control via 0-10V interface. Default 6 A/V. R/W
- H:700 DIP Switch Configuration — Read DIP switch state via Modbus. Not in official register table — undocumented register found in nymea plugin

## Parametre importu

Tieto hodnoty zadáte pri importe XML.

| Pýta sa v aplikácii | Predvolené    |
|---------------------|---------------|
| Slave Id            | `1`           |
| IP address          | `192.168.1.0` |

## Zdroje

- Modbus Register Table CION Home and Semipublic (EN)
  
  [image.schrack.com](https://image.schrack.com/dokumentationen/cion_doku/emcion11cr/modbusregistertabelle/a_emcion_homecontroller_modbus_lookup_table_en.pdf) 2026-03-28
  
  [PDF](https://taphome.com/compatibility/devices/schrack-i-charge-cion/manufacturer/modbus-register-table-en.pdf)
- Operating Manual i-CHARGE CION V2.2 (EN)
  
  [image.schrackcdn.com](https://image.schrackcdn.com/bedienungsanleitungen/a_emcionxxxx_evcchome_v2.2_en.pdf) 2026-03-28
  
  [PDF](https://taphome.com/compatibility/devices/schrack-i-charge-cion/manufacturer/operating-manual-en.pdf)
- Nymea Modbus Plugin — CION Register Definitions
  
  [github.com](https://github.com/nymea/nymea-plugins-modbus/blob/master/schrack/cion-registers.json) 2026-03-28
- evcc Discussion — CION Phase Switching
  
  [github.com](https://github.com/evcc-io/evcc/discussions/11059) 2026-03-28

Dokumenty výrobcov sú © ich príslušných vlastníkov. Poskytujeme ich tak, ako ich zverejnil výrobca, len na informačné účely.

## Súvisiaca dokumentácia

- [Modbus Integration](https://taphome.com/sk/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/sk/docs/integration/modbus/)
- [Jednoduchá konfigurácia pomocou šablón](https://taphome.com/sk/docs/integration/modbus/templates/)
- [Skripty Modbus a prefetch](https://taphome.com/sk/docs/script/modbus-scripts/)
- [Funkcie Modbus](https://taphome.com/sk/docs/script/modbus/)
- [Dátové typy Modbus](https://taphome.com/sk/docs/script/modbus-data-types/)