title: "Orno OR-WE-515"
description: "Orno OR-WE-515 jednofázový multitarifný elektromer s Modbus RTU (RS-485). TapHome číta celkovú energiu, 4 tarifné počítadlá a aktuálne elektrické hodnoty."
url: "https://taphome.com/sk/compatibility/orno-or-we-515/"
language: sk
lastmod: 2026-03-27
generator: hugo
ai:
  topics: ["modbus-rtu","electric-meter","rs485","single-phase","energy-metering","din-rail","multitariff"]
  questions: ["Ako integrovať Orno OR-WE-515 s TapHome?","Čo meria šablóna Orno OR-WE-515 v TapHome?","Ako pripojiť Orno OR-WE-515 cez RS-485 k TapHome?","Ako nastaviť časové tarify na OR-WE-515 cez TapHome?","Aký je rozdiel medzi OR-WE-514 a OR-WE-515?","Ako zmeniť Modbus slave adresu a prenosovú rýchlosť na OR-WE-515?"]
---

# Orno OR-WE-515

Komunikácia: Modbus RTU

- [Oficiálna stránka Orno](https://www.orno.pl)

## Návod na integráciu

Orno OR-WE-515 je jednofázový multitarifný elektromer na DIN lištu, ktorý komunikuje cez Modbus RTU po RS-485. So šírkou iba 18 mm (1 DIN modul) meria činnú energiu, jalovú energiu, napätie, prúd, výkon, účinník a frekvenciu. Hlavný rozdiel oproti jednoduchšiemu OR-WE-514 je podpora 4 nezávislých tarifov (špička, vysoký, nízky, plochý) s konfigurovateľným plánovaním časových pásiem a vstavanou lítiovou batériou pre hodiny reálneho času.

TapHome šablóna poskytuje 6 zariadení: celkový elektromer s okamžitým príkonom, 4 samostatné tarifné počítadlá (T1--T4) a snímač elektrického prúdu. Servisné akcie na úrovni modulu umožňujú konfigurovať tarifné plány, nastaviť hodiny RTC, zmeniť Modbus slave adresu, upraviť prenosovú rýchlosť a ovládať čas cyklovania LCD displeja — všetko vzdialene cez TapHome.

## Hardvérové pripojenie

### Zapojenie RS-485

OR-WE-515 má 3-svorkovú RS-485 rozhranie na pravej strane elektromera. Pripojte pomocou reťazovej (daisy-chain) topológie:

- **Svorka 23 (A)** na A+/D+ na TapHome RS-485
- **Svorka 24 (G)** na GND na TapHome RS-485
- **Svorka 25 (B)** na B-/D- na TapHome RS-485

Ostatné svorky slúžia na pripojenie silovej linky: **Svorka 1** je L-IN (vstup fázy), **Svorka 3** je L-OUT (výstup fázy) a dve svorky **N** sú pre nulový vodič.

> [!NOTE]
> Ak RS-485 prevodník nemá svorku G (zem), pripojenie uzemnenia na svorke 24 je možné vynechať. Pre spoľahlivú komunikáciu na dlhších káblových trasách sa však pripojenie GND odporúča.

> [!WARNING]
> Pred inštaláciou vždy odpojte napájanie. Elektromer zvláda prúd až **100 A** cez svoje svorky. Zabezpečte správny prierez vodičov (skrutkové svorky až do 25 mm2) a po zapojení uzavrite kryt svoriek.

## Konfigurácia

### Komunikačné parametre

Predvolené Modbus nastavenia zodpovedajú TapHome šablóne:

| Parameter | Predvolená hodnota | Možnosti |
|-----------|---------------------|----------|
| Prenosová rýchlosť | 9600 | 1200, 2400, 4800, 9600 |
| Dátové bity | 8 | Fixné |
| Parita | Even | Fixná (8E1) |
| Stop bity | 1 | Fixné |
| Slave ID | 1 | 1--255 |

> [!WARNING]
> Hlavička PDF dokumentácie registrov uvádza „N81" (bez parity), ale inštalačný manuál a komunitné implementácie (Arduino knižnica, AGG Software) konzistentne potvrdzujú **8E1 (párna parita)** ako správne nastavenie. V TapHome použite párnu paritu.

### Slave ID

Pri pripojení viacerých elektromerov na rovnakú zbernicu RS-485 musí mať každý elektromer jedinečné Slave ID. Predvolené Slave ID je 1, konfigurovateľné v rozsahu 1--255. TapHome šablóna obsahuje servisnú akciu **Set Slave ID**, ktorá zapisuje do holding registra H:272 a umožňuje vzdialenú zmenu adresy bez fyzického prístupu k elektromeru.

### Prenosová rýchlosť

Prenosovú rýchlosť je možné zmeniť vzdialene cez servisnú akciu **Set Baud Rate**. Dostupné možnosti sú 1200, 2400, 4800 a 9600 bps. Hodnota je uložená v holding registri H:273 ako kódované celé číslo (1=1200, 2=2400, 3=4800, 4=9600). Po zmene prenosovej rýchlosti aktualizujte nastavenia pripojenia modulu v TapHome.

## Schopnosti zariadenia

Šablóna vytvára 6 zariadení organizovaných do dvoch skupín: meranie energie a meranie prúdu. Všetky registre používajú Modbus funkčný kód 03H (holding registre).

### Meranie energie

Päť zariadení ModbusElectricityMeter sleduje spotrebu energie:

- **Total Energy** — celková činná energia (H:40960, UInt32 / 100 na kWh) a okamžitý činný príkon (H:320, Int32 / 1000 na kW). Toto zariadenie obsahuje 4 servisné atribúty: frekvencia siete (Hz), jalový výkon (kVAr), zdanlivý výkon (kVA) a účinník (0,000--1,000).
- **Tariff T1** — činná energia akumulovaná počas tarifných období 1 (H:40962, UInt32 / 100 na kWh). Obsahuje servisný atribút jalovej energie pre T1 (kVArh).
- **Tariff T2** — činná energia akumulovaná počas tarifných období 2 (H:40964, UInt32 / 100 na kWh). Obsahuje servisný atribút jalovej energie pre T2 (kVArh).
- **Tariff T3** — činná energia akumulovaná počas tarifných období 3 (H:40966, UInt32 / 100 na kWh). Obsahuje servisný atribút jalovej energie pre T3 (kVArh).
- **Tariff T4** — činná energia akumulovaná počas tarifných období 4 (H:40968, UInt32 / 100 na kWh). Obsahuje servisný atribút jalovej energie pre T4 (kVArh).

Štyri tarifné sadzby zodpovedajú časovým pásmam spotreby: 1 = špička (najvyššia sadzba), 2 = vysoký tarif, 3 = nízky tarif (mimo špičku), 4 = plochý tarif. Až 8 časových intervalov denne definuje, kedy sa každý tarif uplatňuje.

### Meranie prúdu

- **Electric Current** — okamžitý prúd v linke (H:313, UInt32 / 1000 na A). Obsahuje servisný atribút napätia (H:305, V).

### Správa tarifov a hodín

Modul ponúka 5 servisných akcií pre vzdialenú konfiguráciu:

- **Set Date/Time** — nastaví vstavané hodiny RTC (rok, mesiac, deň, hodina, minúty, sekundy). OR-WE-515 má lítiovú batériu, ktorá udržuje hodiny počas výpadkov napájania.
- **Set Tariffs** — konfiguruje až 8 pracovných časových intervalov. Každý interval definuje čas začiatku (hodina, minúta) a tarifnú sadzbu (0=vypnutý, 1=špička, 2=vysoký, 3=nízky, 4=plochý). Predvolený plán spúšťa tarif 2 (vysoký) o 07:00 a tarif 3 (nízky) o 22:00.
- **Set Slave ID** — zmení Modbus adresu (1--255).
- **Set Baud Rate** — zmení rýchlosť komunikácie RS-485 (1200/2400/4800/9600 bps).
- **Set LCD Cycle Time** — nastaví interval automatického posúvania displeja (1--120 sekúnd).

Servisné atribúty na úrovni modulu zobrazujú aktuálne Slave ID, prenosovú rýchlosť, dátum/čas a 8 nakonfigurovaných plánov časových období s priradením tarifov.

> [!TIP]
> Tarifný plán nakonfigurovaný cez TapHome sa vzťahuje len na **pracovné dni** (registre 0x8100--0x810F). OR-WE-515 podporuje aj samostatné víkendové (0x8110) a sviatočné (0x8130) plány, ale tie nie sú v aktuálnej šablóne dostupné. Dajú sa nakonfigurovať pomocou softvéru Orno alebo pridať ako vlastné Modbus zariadenia v TapHome.

### Ďalšie schopnosti

OR-WE-515 tiež poskytuje vysokopresný register napätia (UInt32, rozlíšenie 0,001 V) ako alternatívu k registru UInt16 použitému v šablóne. Elektromer podporuje obojsmerné meranie (činný výkon vpred a vzad), exportné počítadlá energie podľa tarifov, kombinované obojsmerné celkové počítadlá, celkovú jalovú energiu naprieč všetkými tarifmi a celkové harmonické skreslenie (THD) pre napätie aj prúd. Tieto je možné pridať v budúcej aktualizácii šablóny.

## Riešenie problémov

### Žiadna komunikácia

1. Skontrolujte zapojenie RS-485: svorka 23 = A, svorka 25 = B — prehoďte A a B, ak komunikácia nefunguje
2. Overte, že nastavenie parity v TapHome je **Even** (8E1), nie None
3. Skontrolujte, či prenosová rýchlosť v TapHome zodpovedá elektromeru (predvolená 9600)
4. Overte, že Slave ID v TapHome zodpovedá elektromeru (predvolené 1)
5. Pri dlhých káblových trasách zabezpečte pripojenie GND (svorka 24)

### Nesprávne namerané hodnoty energie

1. Overte režim merania elektromera — Možnosť 1 (predvolená) meria činnú a jalovú energiu; Možnosť 2 meria energiu vpred a vzad (obojsmerné)
2. Tarifné počítadlá (T1--T4) akumulujú energiu iba počas priradených časových období — ak sú všetky tarifné plány vypnuté (nastavené na 0), tarifné počítadlá zostanú na nule, zatiaľ čo Total Energy pokračuje v počítaní
3. Konštanta elektromera je konfigurovateľná (100, 1000 alebo 2000 imp/kWh) — predvolená 1000 imp/kWh zodpovedá škálovaniu registrov v šablóne

### Poznámka ku škálovaniu jalovej energie

Oficiálna dokumentácia registrov uvádza škálovanie 0,01 kVArh pre registre jalovej energie, zatiaľ čo TapHome šablóna používa deliteľa /1000 pre servisné atribúty jalovej energie podľa tarifov. Tento rozdiel môže spôsobiť 10-násobný posun škálovania hodnôt jalovej energie. Ak sa hodnoty jalovej energie zdajú nesprávne, porovnajte ich s LCD displejom na fyzickom elektromere.

## Dostupné zariadenia 6

Tieto zariadenia sa po importe zobrazia v TapHome.

Orno OR-WE-515 Modul

Servisné atribúty

|                    |                                                                                          |
|--------------------|------------------------------------------------------------------------------------------|
| Slave ID           |                                                                                          |
| Prenosová rýchlosť |                                                                                          |
| Dátum/Čas          | Čítanie vstavaných hodín reálneho času — dátum a čas udržiavané lítiovou batériou        |
| Časové obdobie 1   | Tarifný plán slot 1 — čas začiatku (HH:MM) a sadzba (špička, vysoký, nízky alebo plochý) |
| Časové obdobie 2   | Tarifný plán slot 2 — čas začiatku a priradenie sadzby                                   |
| Časové obdobie 3   | Tarifný plán slot 3 — čas začiatku a priradenie sadzby                                   |
| Časové obdobie 4   | Tarifný plán slot 4 — čas začiatku a priradenie sadzby                                   |
| Časové obdobie 5   | Tarifný plán slot 5 — čas začiatku a priradenie sadzby                                   |
| Časové obdobie 6   | Tarifný plán slot 6 — čas začiatku a priradenie sadzby                                   |
| Časové obdobie 7   | Tarifný plán slot 7 — čas začiatku a priradenie sadzby                                   |
| Časové obdobie 8   | Tarifný plán slot 8 — čas začiatku a priradenie sadzby                                   |
| Frekvencia         |                                                                                          |
| Napätie            |                                                                                          |
| Jalový výkon fázy  |                                                                                          |

Servisné akcie

|                             |                                                                                                                              |
|-----------------------------|------------------------------------------------------------------------------------------------------------------------------|
| Nastaviť dátum/čas          | Nastaví vstavané hodiny reálneho času — rok, mesiac, deň, hodina, minúty, sekundy                                            |
| Nastaviť tarify             | Konfigurácia až 8 pracovných časových intervalov — každý s časom začiatku a tarifnou sadzbou (špička, vysoký, nízky, plochý) |
| Nastaviť Slave ID           |                                                                                                                              |
| Nastaviť čas cyklu LCD      | Nastavenie intervalu automatického posúvania LCD displeja (1--120 sekúnd)                                                    |
| Nastaviť prenosovú rýchlosť |                                                                                                                              |

Servisné atribúty

${device\_SlaveId}

```taphome
modbusr(H, 0x110, Int16)
```

${baud\_rate} \[bps]

```taphome
switch(getbyte(modbusr(H, 0x111, Int16),0),0,0,1,1200,2,2400,3,4800,4,9600,"Invalid")
```

${time}

```taphome
var Y := getbyte( modbusr(H,0x8120,uint16),1);
var M := getbyte( modbusr(H,0x8120,uint16),0);
var D := getbyte( modbusr(H,0x8121,uint16),1);
var H := getbyte( modbusr(H,0x8121,uint16),0);
var min := getbyte( modbusr(H,0x8122,uint16),1);
var sec := getbyte( modbusr(H,0x8122,uint16), 0);

tostring(tostring(H,"D2") + ":" + tostring(min,"D2") + ":" + tostring(sec, "D2") + " " + tostring(D,"D2") + "." + tostring(M,"D2") + ".20" + Y)


```

{1. time period starting time}, {rate}

```taphome
var date := modbusr(H, 0x8100, INT16);
var belong := modbusr(H,0x8101,INT16);
tostring(tostring(getbyte(date,1),"D2") + ":" + tostring(getbyte(date,0),"D2") + ", " + belong + " (" + switch(belong,1,"sharp",2,"peak",3,"Valley",4,"flat","NaN")+")")
```

{2. time period starting time}, {rate}

```taphome
var date := modbusr(H, 0x8100+2, INT16);
var belong := modbusr(H,0x8101+2,INT16);
tostring(tostring(getbyte(date,1),"D2") + ":" + tostring(getbyte(date,0),"D2") + ", " + belong + " (" + switch(belong,1,"sharp",2,"peak",3,"Valley",4,"flat","NaN")+")")
```

{3. time period starting time}, {rate}

```taphome
var date := modbusr(H, 0x8100+4, INT16);
var belong := modbusr(H,0x8101+4,INT16);
tostring(tostring(getbyte(date,1),"D2") + ":" + tostring(getbyte(date,0),"D2") + ", " + belong + " (" + switch(belong,1,"sharp",2,"peak",3,"Valley",4,"flat","NaN")+")")
```

{4. time period starting time}, {rate}

```taphome
var date := modbusr(H, 0x8100+6, INT16);
var belong := modbusr(H,0x8101+6,INT16);
tostring(tostring(getbyte(date,1),"D2") + ":" + tostring(getbyte(date,0),"D2") + ", " + belong + " (" + switch(belong,1,"sharp",2,"peak",3,"Valley",4,"flat","NaN")+")")
```

{5. time period starting time}, {rate}

```taphome
var date := modbusr(H, 0x8100+8, INT16);
var belong := modbusr(H,0x8101+8,INT16);
tostring(tostring(getbyte(date,1),"D2") + ":" + tostring(getbyte(date,0),"D2") + ", " + belong + " (" + switch(belong,1,"sharp",2,"peak",3,"Valley",4,"flat","NaN")+")")
```

{6. time period starting time}, {rate}

```taphome
var date := modbusr(H, 0x8100+10, INT16);
var belong := modbusr(H,0x8101+10,INT16);
tostring(tostring(getbyte(date,1),"D2") + ":" + tostring(getbyte(date,0),"D2") + ", " + belong + " (" + switch(belong,1,"sharp",2,"peak",3,"Valley",4,"flat","NaN")+")")
```

{7. time period starting time}, {rate}

```taphome
var date := modbusr(H, 0x8100+12, INT16);
var belong := modbusr(H,0x8101+12,INT16);
tostring(tostring(getbyte(date,1),"D2") + ":" + tostring(getbyte(date,0),"D2") + ", " + belong + " (" + switch(belong,1,"sharp",2,"peak",3,"Valley",4,"flat","NaN")+")")
```

{8. time period starting time}, {rate}

```taphome
var date := modbusr(H, 0x8100+14, INT16);
var belong := modbusr(H,0x8101+14,INT16);
tostring(tostring(getbyte(date,1),"D2") + ":" + tostring(getbyte(date,0),"D2") + ", " + belong + " (" + switch(belong,1,"sharp",2,"peak",3,"Valley",4,"flat","NaN")+")")
```

Frequency \[Hz]

```taphome
round(modbusr(h,0x130,uint16)*0.01)
```

Voltage \[V]

```taphome
round(modbusr(h,0x131,int16)*0.01)
```

Split phase reactive power \[kwar]

```taphome
round(modbusr(h, 0x148,uint32)*0.001*10)/10
```

Servisné akcie

Date/Time

Parametre: Year (22–99 YY), Month (1–12 MM), Day (1–31 DD), Hour (1–24 HH), Minutes (0–59 MI), Seconds (0–59 SS)

```taphome
var out1 := (YY<<8) + MM;
var out2 := (DD<<8) + HH;
var out3 := (MI<<8) + SS;

modbusw(H, 0x8120, uint16, out1);
modbusw(H, 0x8121, uint16, out2);
modbusw(H, 0x8122, uint16, out3);



#var out1 := (tobcd(MI) << 8) + tobcd(SS);
#var out2 := (tobcd(DW) << 8) + tobcd(HH);
#var out3 := (tobcd(MM) << 8) + tobcd(DD);

#modbusw(H, 0x3c, LittleEndianUint16, out1, out2, out3, YY);
```

${set\_tarriffs}

Parametre: Interval 1 - ${hour} (0–23 HH1), Interval 1 - ${minutes} (0–59 MI1), Interval 1 - ${tariff} (0–4 T1), Interval 2 - Hour (0–23 HH2), Interval 2 - Minutes (0–59 MI2), Interval 2 - ${tariff} (0–4 T2), Interval 3 - Hour (0–23 HH3), Interval 3 - Minutes (0–59 MI3), Interval 3 - ${tariff} (0–4 T3), Interval 4 - Hour (0–23 HH4), Interval 4 - Minutes (0–59 MI4), Interval 4 - ${tariff} (0–4 T4), Interval 5 - Hour (0–23 HH5), Interval 5 - Minutes (0–59 MI5), Interval 5 - ${tariff} (0–4 T5), Interval 6 - Hour (0–23 HH6), Interval 6 - Minutes (0–59 MI6), Interval 6 - ${tariff} (0–4 T6), Interval 7 - Hour (0–23 HH7), Interval 7 - Minutes (0–59 MI7), Interval 7 - ${tariff} (0–4 T7), Interval 8 - Hour (0–23 HH8), Interval 8 - Minutes (0–59 MI8), Interval 8 - ${tariff} (0–4 T8)

```taphome
modbusw(H, 0x8100, uint16, (HH1<<8) + MI1);
modbusw(H, 0x8101, uint16, T1);

modbusw(H, 0x8100+2, uint16, (HH2<<8) + MI2);
modbusw(H, 0x8101+2, uint16, T2);

modbusw(H, 0x8100+4, uint16, (HH3<<8) + MI3);
modbusw(H, 0x8101+4, uint16, T3);

modbusw(H, 0x8100+6, uint16, (HH4<<8) + MI4);
modbusw(H, 0x8101+6, uint16, T4);

modbusw(H, 0x8100+8, uint16, (HH5<<8) + MI5);
modbusw(H, 0x8101+8, uint16, T5);

modbusw(H, 0x8100+10, uint16, (HH6<<8) + MI6);
modbusw(H, 0x8101+10, uint16, T6);

modbusw(H, 0x8100+12, uint16, (HH7<<8) + MI7);
modbusw(H, 0x8101+12, uint16, T7);

modbusw(H, 0x8100+14, uint16, (HH8<<8) + MI8);
modbusw(H, 0x8101+14, uint16, T8);
```

Slave ID

Parametre: Parameter1 (1–255 ID)

```taphome
modbusw(H, 0x110, Uint16, ID)
```

LCD Cycle time

Parametre: Time \[s] (1–120 t)

```taphome
modbusw(H, 0x0d, Uint16, t)
```

Baud rate

Parametre: Baud rate

```taphome
modbusw(H,0x111,int16,Br)
```

Elektrický prúd Premenná Len na čítanie

Okamžitý jednofázový prúd v linke (A) so servisným atribútom napätia

Register: H:313 UInt32 Jednotka: A numeric

Servisné atribúty

|         |
|---------|
| Napätie |

Čítanie

```taphome
MODBUSR(H, 0x139, UInt32)/1000
```

Servisné atribúty

Voltage \[V]

```taphome
round(modbusr(H, 0x131, uint16)*0.01)
```

Celková energia Elektromer Len na čítanie

Celková spotreba činnej energie (kWh) a okamžitý príkon (kW) s frekvenciou siete, jalovým výkonom, zdanlivým výkonom a účinníkom

Register: H:40960 (readtotalconsumption), H:320 (readdemand) UInt32 / Int32 Jednotka: kWh / kW numeric

Servisné atribúty

|                  |
|------------------|
| Frekvencia siete |
| Jalový výkon     |
| Zdanlivý výkon   |
| Účinník          |

Čítanie celkovej spotreby

```taphome
MODBUSR(H, 0xA000, UInt32)/100
```

Čítanie odberu

```taphome
MODBUSR(H, 0x140, Int32)/1000
```

Servisné atribúty

${grid\_frequency} \[Hz]

```taphome
tostring(modbusr(H, 0x130,UInt16)/100, "F2")
```

${reactive\_power} \[kVAr]

```taphome
tostring(modbusr(H, 0x148,Int32)/1000, "F2")
```

${apparent\_power} \[kVA]

```taphome
tostring(modbusr(H, 0x150,Int32)/1000, "F2")
```

${power\_factor}

```taphome
tostring(modbusr(H, 0x158,Int16)/1000, "F2")
```

Tarif T1 Elektromer Len na čítanie

Činná energia akumulovaná počas tarifných období 1 (špička) s počítadlom jalovej energie

Register: H:40962 (readtotalconsumption) UInt32 Jednotka: kWh numeric

Servisné atribúty

|                        |
|------------------------|
| Celková jalová energia |

Čítanie celkovej spotreby

```taphome
MODBUSR(H, 0xA002, UInt32)/100
```

Servisné atribúty

${total\_reactive\_energy} \[kVArh]

```taphome
tostring(modbusr(H, 0xA01E + 2,UInt32)/1000, "F2")
```

Tarif T2 Elektromer Len na čítanie

Činná energia akumulovaná počas tarifných období 2 (vysoký tarif) s počítadlom jalovej energie

Register: H:40964 (readtotalconsumption) UInt32 Jednotka: kWh numeric

Servisné atribúty

|                        |
|------------------------|
| Celková jalová energia |

Čítanie celkovej spotreby

```taphome
MODBUSR(H, 0xA004, UInt32)/100
```

Servisné atribúty

Total Reactive Energy \[kwarh]

```taphome
tostring(modbusr(H, 0xA01E + 4,UInt32)/1000, "F2")
```

Tarif T3 Elektromer Len na čítanie

Činná energia akumulovaná počas tarifných období 3 (nízky tarif / mimo špičku) s počítadlom jalovej energie

Register: H:40966 (readtotalconsumption) UInt32 Jednotka: kWh numeric

Servisné atribúty

|                        |
|------------------------|
| Celková jalová energia |

Čítanie celkovej spotreby

```taphome
MODBUSR(H, 0xA006, UInt32)/100
```

Servisné atribúty

Total Reactive Energy

```taphome
tostring(modbusr(H, 0xA01E + 6,UInt32)/1000, "F2")
```

Tarif T4 Elektromer Len na čítanie

Činná energia akumulovaná počas tarifných období 4 (plochý tarif) s počítadlom jalovej energie

Register: H:40968 (readtotalconsumption) UInt32 Jednotka: kWh numeric

Servisné atribúty

|                        |
|------------------------|
| Celková jalová energia |

Čítanie celkovej spotreby

```taphome
MODBUSR(H, 0xA008, UInt32)/100
```

Servisné atribúty

${total\_reactive\_energy} \[kVArh]

```taphome
tostring(modbusr(H, 0xA01E + 8,UInt32)/1000, "F2")
```

**Pripojenie:** Modbus RTU • 9600 baud• 8E1 • Slave ID: $\[SlaveId]

Možné vylepšenia (8)

- H:312 (0x138) Voltage (high-precision UInt32) — UInt32 voltage register with 0.001V resolution — template uses H:305 (UInt16, 0.01V) instead
- H:320 (0x140) — export Active Power (export/negative) — Template reads H:320 for total power but does not split into import/export — no bidirectional energy separation
- H:0xA00A–0xA00E Tariff T1–T4 Export Active Energy — Per-tariff export (reverse) energy counters — template only reads import direction
- H:0xA010 Total Active Energy (combined import+export) — Combined bidirectional total — template uses H:0xA000 (import only)
- H:0xA01C Total Reactive Energy (all tariffs) — Grand total reactive energy across all tariffs — template only reads per-tariff reactive counters
- H:0xA01E (40990) Total Reactive Energy (import) — Total reactive import energy — base address used by per-tariff SA formulas (0xA01E + offset)
- H:0x160 (352) Current THD — Total harmonic distortion of current, %
- H:0x168 (360) Voltage THD — Total harmonic distortion of voltage, %

## Parametre importu

Tieto hodnoty zadáte pri importe XML.

| Pýta sa v aplikácii | Predvolené    |
|---------------------|---------------|
| Slave ID            | `1`           |
| IP adresa           | `192.168.1.0` |

## Zdroje

- Orno OR-WE-514 & OR-WE-515 Register Description
  
  2026-03-27
  
  [PDF](https://taphome.com/compatibility/devices/orno-or-we-515/manufacturer/register-description.pdf)
- Orno OR-WE-512/514/515 Installation Manual
  
  [www.partner.orno.pl](https://www.partner.orno.pl/manuals/OR-WE-512,514,515_manual_EN.pdf) 2026-03-27
  
  [PDF](https://taphome.com/compatibility/devices/orno-or-we-515/manufacturer/installation-manual.pdf)
- AGG Software — OR-WE-514/515 Modbus Register Map
  
  [www.aggsoft.com](https://www.aggsoft.com/serial-data-logger/tutorials/modbus-data-logging/orno-or-we-514-or-we-515.htm) 2026-03-27
- OR\_WE\_Energy\_Meter Arduino Library — Register Definitions
  
  [github.com](https://github.com/CSchoch/OR_WE_Energy_Meter) 2026-03-27

Dokumenty výrobcov sú © ich príslušných vlastníkov. Poskytujeme ich tak, ako ich zverejnil výrobca, len na informačné účely.

## Súvisiaca dokumentácia

- [Modbus Integration](https://taphome.com/sk/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/sk/docs/integration/modbus/)
- [Jednoduchá konfigurácia pomocou šablón](https://taphome.com/sk/docs/integration/modbus/templates/)
- [Skripty Modbus a prefetch](https://taphome.com/sk/docs/script/modbus-scripts/)
- [Funkcie Modbus](https://taphome.com/sk/docs/script/modbus/)
- [Dátové typy Modbus](https://taphome.com/sk/docs/script/modbus-data-types/)