---
title: "BAXI Auriga M/T-A Air-to-Water Heat Pump"
description: "Ovládajte zóny, TÚV, režim a požadované teploty BAXI Auriga M/T-A a čítajte teploty a kódy porúch v TapHome cez Modbus RTU na ovládači H1/H2."
url: "https://taphome.com/sk/compatibility/baxi-auriga-m-t-a/"
language: sk
lastmod: 2026-11-15
generator: hugo
ai:
  topics: ["modbus-rtu","heat-pump","rs485","air-to-water","dhw","hydronic","inverter-compressor","climate-curve"]
  questions: ["Ako integrovať tepelné čerpadlo BAXI Auriga M/T-A s TapHome?","Kde je port Modbus RS-485 na tepelnom čerpadle BAXI Auriga?","Ako nastaviť adresu Modbus na BAXI Auriga prepínačom S3?","Prečo BAXI Auriga neodpovedá na adrese Modbus 1?","Čo ovláda a monitoruje šablóna TapHome pre BAXI Auriga M/T-A?","Ako čítať kódy porúch BAXI Auriga v TapHome?"]
---

# BAXI Auriga M/T-A Air-to-Water Heat Pump

Komunikácia: Modbus RTU

## Návod na integráciu

**BAXI Auriga M/T-A** je invertorové monoblokové tepelné čerpadlo vzduch-voda, ktoré sa predáva ako **AURIGA 4-16 M-A** (jednofázové, 4–16 kW) a **AURIGA 12-16 T-A** (trojfázové, 12–16 kW). Káblový ovládač dodávaný s jednotkou má port RS-485 Modbus, cez ktorý TapHome číta a zapisuje holding registre celej jednotky protokolom Modbus RTU pri rýchlosti 9600 baudov, 8N1.

Šablóna zapína a vypína zónu 1, zónu 2 a ohrev teplej úžitkovej vody (TÚV), volí prevádzkový režim, nastavuje požadované teploty vody, miestnosti a TÚV, prepína režim ECO a tichý režim a volí ekvitermickú krivku. Číta štyri teplotné senzory, zobrazuje kompletné prevádzkové údaje ako servisné atribúty, aktuálny kód poruchy prevádza na chybové hlásenia a hlavné parametre pre inštalatéra ponúka ako servisné akcie.

> [!NOTE]
> Toto je komunitná šablóna. Názvy zariadení, servisné atribúty, servisné akcie a chybové hlásenia sa v TapHome zobrazujú po taliansky, tak ako ich autor vytvoril. Návod uvádza najprv taliansky názov a vedľa neho jeho význam.

## Hardvérové pripojenie

### Kde je port Modbus

Port Modbus je na **káblovom ovládači**, nie na hydraulickom module. Podľa návodu ku káblovému ovládaču sa ovládač pripája k hydraulickému modulu svorkami **A, B, X, Y, E** a samostatné svorky **H1** a **H2** sú komunikačný port Modbus. TapHome sa preto pripája na H1 a H2 káblového ovládača.

![Zapojenie káblového ovládača BAXI Auriga: svorky A, B, X, Y, E k jednotke a port Modbus H2 (A+), H1 (B-) s E pre tienenie](https://taphome.com/images/compatibility/baxi-auriga-m-t-a/wiring-rs485_hu_8d63492c55e96655.jpg)

| Zbernica RS-485 TapHome | Svorka káblového ovládača |
|---|---|
| A+ | **H2** (A+ Modbus) |
| B- | **H1** (B-) |
| Tienenie kábla | **E** |

Svorky A a B káblového ovládača nie sú vedenia RS-485: návod ich uvádza ako vstup **13,5 V AC** pre napájanie ovládača, zapojený vodičmi 0,75 mm².

> [!WARNING]
> Svorkovnica **CN30** v hydraulickom module má tiež svorky označené **H1** a **H2** (piny 9 a 10). Návod na inštaláciu ich priraďuje internej kaskáde medzi jednotkami, nie Modbusu. TapHome pripojte iba na H1 a H2 káblového ovládača.

Káblový ovládač musí zostať pripojený k hydraulickému modulu: podľa návodu sa parametre celej jednotky (registre 100 a vyššie) dajú čítať iba vtedy, keď je káblový ovládač pripojený k hydraulickému modulu.

### Pravidlá kabeláže od výrobcu

Návod ku káblovému ovládaču a návod na inštaláciu uvádzajú pre komunikačnú kabeláž ovládača tieto pravidlá:

- Obvod ovládača je nízkonapäťový. Nikdy ho nepripájajte k obvodu 220 V / 380 V a nikdy ho neveďte v tej istej chráničke; silové a komunikačné káble veďte oddelene.
- Použite tienený kábel a tienenie spoľahlivo uzemnite, inak môže prenos zlyhať.
- Tienený kábel nepredlžujte prerezaním a spojením; na spojenie použite svorkovnicu.
- Kábel medzi jednotkou a káblovým ovládačom je plášťovaný kábel 5 × 0,75 mm² s dĺžkou najviac 50 m.

> [!WARNING]
> Izoláciu signálneho kábla po dokončení zapojenia netestujte prístrojom **Megger** (merač izolačného odporu) — návod to výslovne zakazuje.

## Konfigurácia

### Adresa Modbus (prepínač S3)

Adresa Modbus sa nastavuje otočným kódovým prepínačom **S3 (0–F)** na **hlavnej riadiacej doske hydraulického modulu**. Poloha **0**, výrobné nastavenie, zodpovedá adrese **16**; každá iná poloha sa rovná svojmu číslu (poloha 2 = adresa 2, poloha 5 = adresa 5, poloha F = adresa 15).

![Otočný kódový prepínač S3 (0–F), ktorým sa nastavuje adresa Modbus; poloha 0 znamená adresu 16](https://taphome.com/images/compatibility/baxi-auriga-m-t-a/s3-modbus-address-switch_hu_c23c26b0fa37a25e.jpg)

| Poloha S3 | Adresa Modbus |
|---|---|
| 0 (výrobné nastavenie) | 16 |
| 1 | 1 |
| 2 … 9 | 2 … 9 |
| A … F | 10 … 15 |

Šablóna sa predvolene importuje so **Slave ID 1**, čo zodpovedá **S3 = 1**. Buď otočte S3 do polohy 1, alebo ponechajte výrobnú polohu 0 a pri importe šablóny zadajte ako Slave ID **16**.

> [!NOTE]
> Hydraulický modul aj doska PCB B (hlavná riadiaca doska systému tepelného čerpadla) majú každá otočný prepínač označený S3. Návod ku káblovému ovládaču uvádza ako prepínač adresy Modbus ten na hlavnej doske hydraulického modulu.

### Komunikačné parametre

| Parameter | Hodnota |
|---|---|
| Rozhranie | RS-485 |
| Protokol | Modbus RTU (Modbus ASCII nie je podporovaný) |
| Prenosová rýchlosť | 9600 |
| Dátové bity | 8 |
| Parita | Žiadna |
| Stop bity | 1 |
| Funkčné kódy | 03H (čítanie holding registrov), 06H (zápis jedného registra), 10H (zápis viacerých registrov) |

V TapHome importujte šablónu do rozhrania Modbus RTU nastaveného na 9600 baudov, 8 dátových bitov, bez parity, 1 stop bit a ako Slave ID zadajte adresu z S3.

## Možnosti zariadenia

### Zapnutie a vypnutie zón a TÚV

Tri spínače ovládajú bity registra 0. Každý spínač prečíta register, zmení iba svoj bit a zapíše ho späť, takže ostatné funkcie si zachovajú svoj stav:

- **Pompa di calore — Zona 1 On/Off** (zapnutie a vypnutie zóny 1 tepelného čerpadla) — register 0, bit 1
- **Pompa di calore — Zona 2 On/Off** (zapnutie a vypnutie zóny 2 tepelného čerpadla) — register 0, bit 3
- **ACS — Riscaldamento On/Off** (zapnutie a vypnutie ohrevu TÚV) — register 0, bit 2

### Prevádzkový režim

**Modalità di funzionamento** (prevádzkový režim) je viachodnotový prepínač na registri 1 s tromi hodnotami: **Auto** (1), **Raffreddamento** (chladenie, 2) a **Riscaldamento** (vykurovanie, 3).

### Požadované teploty

Tri premenné na čítanie aj zápis nastavujú cieľové hodnoty priamo v °C:

- **Setpoint temperatura acqua T1s** (požadovaná teplota výstupnej vody T1s) — register 2
- **Setpoint temperatura ambiente Ts** (požadovaná izbová teplota Ts) — register 3; návod uvádza rozsah 17–30 °C, platný iba vtedy, keď je prítomný snímač izbovej teploty Ta
- **Setpoint temperatura ACS T5s** (požadovaná teplota zásobníka TÚV T5s) — register 4; rozsah 40–60 °C

### Režim ECO a tichý režim

Dva spínače menia jednotlivé bity registra 5 (nastavenie funkcií) rovnakým spôsobom čítanie – úprava – zápis:

- **Modalità ECO** (režim ECO) — register 5, bit 10
- **Modalità Silenziosa** (tichý režim) — register 5, bit 6

### Ekvitermická krivka

**Curva climatica — selezione** (výber ekvitermickej krivky) na registri 6 volí jednu z prednastavených kriviek **1–8**, ktoré určujú požadovanú teplotu vody T1s podľa vonkajšej teploty T4. Dva body používateľskej krivky sú dostupné ako servisné atribúty a servisné akcie modulu (registre 261–268, pozri nižšie).

### Teplotné senzory

- **Temperatura ingresso acqua TW_in** (teplota vstupnej vody) — register 104
- **Temperatura uscita acqua TW_out** (teplota výstupnej vody) — register 105
- **Temperatura esterna T4** (vonkajšia teplota) — register 107
- **Temperatura serbatoio ACS T5** (teplota zásobníka TÚV) — register 115

### Prevádzkové údaje (servisné atribúty modulu)

Modul **BAXI Auriga M/T-A** zobrazuje prevádzkové údaje celej jednotky ako servisné atribúty:

- Kompresor: frekvencia v Hz (register 100), skutočný prevádzkový režim — vypnuté, chladenie, vykurovanie (101), prevádzkové hodiny kompresora (122)
- Vonkajšia jednotka: otáčky ventilátora v ot./min (102), otvorenie elektronického expanzného ventilu v krokoch (103), vysoký a nízky tlak chladiva v kPa (116, 117), prúd v A (118), napätie vo V (119)
- Teploty chladiva a vody: kondenzátor T3 (106), výtlak kompresora Tp (108), sanie kompresora (109), celková výstupná voda T1 (110), výstupná voda za záložným ohrievačom T1B (111), kvapalné chladivo T2 (112), plynné chladivo T2B (113), izbová teplota Ta (114)
- Invertor: prúd jednosmernej zbernice (133), napätie jednosmernej zbernice (134), teplota modulu TF (135)
- Hydraulika: prietok vody v m³/h (138) a výkon hydraulického modulu v kW (140); jednotka posiela obe hodnoty vynásobené 100 a šablóna ich delí 100
- Verzie: verzia firmvéru jednotky (130) a verzia firmvéru káblového ovládača (131)
- Parametre pre inštalatéra (iba na čítanie): horná a dolná hranica T1S pre chladenie a vykurovanie (201–204), doba chodu čerpadla TÚV (209), teplota dezinfekcie T5s_DI (220), najdlhšie trvanie dezinfekcie (221), dovolenkové požadované teploty pre vykurovanie a TÚV (245, 246) a body používateľskej krivky T1SetC1/C2, T4C1/C2, T1SetH1/H2, T4H1/H2 (261–268)

### Chybové a stavové hlásenia

Skript modulu číta aktuálny kód poruchy z registra 124 a 30 kódov skupín E, P, H a L (napríklad E0 porucha prietoku vody, E2 chyba komunikácie medzi káblovým ovládačom a hydraulickým modulom, P1 ochrana proti vysokému tlaku, L1 ochrana DC generátora pri nízkom napätí) prevádza na chybové hlásenia v taliančine. Každý nenulový kód zároveň vyvolá varovanie **Codice guasto attivo: n**, kde *n* je surové číslo kódu z registra 124.

Zo stavových slov modul hlási aj:

- register 128: prebieha odmrazovanie, aktívna protimrazová ochrana, prebieha návrat oleja (informačné hlásenia)
- register 129: aktívne odmrazovanie a aktívny externý ohrievač (informačné hlásenia), systémový alarm (chyba)

### Parametre pre inštalatéra (servisné akcie modulu)

Servisné akcie modulu zapisujú hlavné parametre pre inštalatéra. Vstupný rozsah každej akcie určuje šablóna:

| Servisná akcia | Parameter | Register | Rozsah |
|---|---|---|---|
| Imposta limite superiore T1S raffreddamento | Horná hranica T1S, chladenie | 201 | 18–25 °C |
| Imposta limite inferiore T1S raffreddamento | Dolná hranica T1S, chladenie | 202 | 5–25 °C |
| Imposta limite T1S riscaldamento superiore | Horná hranica T1S, vykurovanie | 203 | 25–60 °C |
| Imposta limite T1S riscaldamento inferiore | Dolná hranica T1S, vykurovanie | 204 | 22–55 °C |
| Imposta tempo funzionamento pompa ACS | Doba chodu čerpadla TÚV | 209 | 5–120 min |
| Imposta temperatura disinfezione T5s_DI | Teplota dezinfekcie | 220 | 60–70 °C |
| Imposta temperatura esterna abilitazione IBH | Vonkajšia teplota, pri ktorej sa povolí záložný ohrievač IBH | 233 | -15–10 °C |
| Imposta ritardo avvio IBH | Oneskorenie štartu záložného ohrievača IBH | 235 | 15–120 min |
| Imposta setpoint riscaldamento holiday T1S | Dovolenková požadovaná teplota vykurovania | 245 | 20–25 °C |
| Imposta setpoint ACS holiday T5S | Dovolenková požadovaná teplota TÚV | 246 | 20–25 °C |
| Imposta T1SetC1 / T1SetC2 | Používateľská krivka, chladenie: body teploty vody | 261, 262 | 5–25 °C |
| Imposta T4C1 / T4C2 | Používateľská krivka, chladenie: body vonkajšej teploty | 263, 264 | -5–46 °C |
| Imposta T1SetH1 / T1SetH2 | Používateľská krivka, vykurovanie: body teploty vody | 265, 266 | 25–60 °C |
| Imposta T4H1 / T4H2 | Používateľská krivka, vykurovanie: body vonkajšej teploty | 267, 268 | -25–30 °C |

> [!TIP]
> Keď sa používajú obe vykurovacie zóny, na jednotke musí byť zapnuté nastavenie dvoch zón — návod ho uvádza ako bit 3 registra 211 („dual zone setting is valid“).

## Riešenie problémov

### Tepelné čerpadlo neodpovedá

1. Skontrolujte, či je TapHome zapojený na **H1 a H2 káblového ovládača** — H2 na A+, H1 na B- — a nie na svorky ovládača A a B (napájanie 13,5 V AC) ani na kaskádové svorky H1/H2 na CN30 v hydraulickom module.
2. Skontrolujte polohu prepínača S3 na hlavnej doske hydraulického modulu: poloha 0 je adresa **16**, nie 1. Slave ID zadané pri importe sa musí zhodovať.
3. Skontrolujte, či rozhranie beží na Modbus RTU s rýchlosťou 9600 baudov, 8 dátovými bitmi, bez parity a s 1 stop bitom; Modbus ASCII nie je podporovaný.
4. Skontrolujte, či je tienenie kábla pripojené na E a spoľahlivo uzemnené.
5. Návod na inštaláciu uvádza aj položku servisného menu **MENU > FOR SERVICEMAN > HMI ADDRESS SET** s parametrami **17.2 HMI ADDRESS FOR BMS** (predvolene 1, rozsah 1–16) a **17.3 STOP BIT** (predvolene 1). Ak jednotka na adrese z S3 stále neodpovedá, skontrolujte tieto hodnoty na káblovom ovládači a STOP BIT ponechajte na 1.

### Prevádzkové údaje zostávajú prázdne alebo nulové

Parametre celej jednotky (registre 100 a vyššie) sú dostupné iba vtedy, keď je káblový ovládač pripojený k hydraulickému modulu. Skontrolujte prepojenie A, B, X, Y, E medzi ovládačom a jednotkou. Požadovaná izbová teplota Ts platí iba vtedy, keď je nainštalovaný snímač izbovej teploty Ta.

### Čítanie kódov porúch

Číslo vo varovaní **Codice guasto attivo: n** je surová hodnota registra 124. Vyhľadajte ho v tabuľke chybových kódov v návode ku káblovému ovládaču (časť 7.1.3), ktorá uvádza každý písmenový kód s jeho číslom — napríklad 1 = E0, 9 = E8, 21 = P1, 39 = H0, 43 = H4, 44 = H5, 49 = HA, 50 = Hb, 134 = L0.

> [!NOTE]
> Pri surových hodnotách 44 až 50 sú talianske texty chýb v šablóne posunuté o jeden krok oproti tabuľke v návode (šablóna označuje 44 ako H4, zatiaľ čo návod uvádza 43 = H4 a 44 = H5). Pri týchto kódoch sa riaďte surovým číslom vo varovaní. Kódy, ktoré šablóna nedekóduje (napríklad Pb, Hd, HE, F1, L4–L9), sa zobrazia iba ako varovanie s ich číslom.

## Dostupné zariadenia 14

Tieto zariadenia sa po importe zobrazia v TapHome.

BAXI Auriga M/T-A Modul

Servisné atribúty

|                                                           |
|-----------------------------------------------------------|
| Frequenza compressore \[Hz]                               |
| Modalità operativa corrente                               |
| Velocità ventilatore \[RPM]                               |
| Apertura EEV PMV \[passi]                                 |
| Temperatura condensatore T3 \[°C]                         |
| Temperatura mandata compressore Tp \[°C]                  |
| Temperatura aspirazione compressore \[°C]                 |
| Temperatura uscita acqua totale T1 \[°C]                  |
| Temperatura uscita acqua T1B (a valle riscaldatore) \[°C] |
| Temperatura refrigerante liquido T2 \[°C]                 |
| Temperatura refrigerante gassoso T2B \[°C]                |
| Temperatura ambiente Ta \[°C]                             |
| Alta pressione unità esterna \[kPa]                       |
| Bassa pressione unità esterna \[kPa]                      |
| Corrente unità esterna \[A]                               |
| Tensione unità esterna \[V]                               |
| Ore di funzionamento compressore \[h]                     |
| Tensione bus DC \[V]                                      |
| Corrente bus DC \[A]                                      |
| Temperatura modulo TF \[°C]                               |
| Portata acqua \[m³/h]                                     |
| Potenza modulo idraulico \[kW]                            |
| Versione firmware unità                                   |
| Versione firmware controllore cablato                     |
| Limite superiore T1S raffreddamento \[°C]                 |
| Limite inferiore T1S raffreddamento \[°C]                 |
| Limite superiore T1S riscaldamento \[°C]                  |
| Limite inferiore T1S riscaldamento \[°C]                  |
| Tempo funzionamento pompa ACS \[min]                      |
| Temperatura disinfezione T5s\_DI \[°C]                    |
| Durata massima disinfezione \[min]                        |
| Setpoint riscaldamento holiday T1S \[°C]                  |
| Setpoint ACS holiday T5S \[°C]                            |
| T1SetH1 (curva riscald. punto 1) \[°C]                    |
| T1SetH2 (curva riscald. punto 2) \[°C]                    |
| T4H1 (temp. esterna punto 1 riscald.) \[°C]               |
| T4H2 (temp. esterna punto 2 riscald.) \[°C]               |
| T1SetC1 (curva raffr. punto 1) \[°C]                      |
| T1SetC2 (curva raffr. punto 2) \[°C]                      |
| T4C1 (temp. esterna punto 1 raffr.) \[°C]                 |
| T4C2 (temp. esterna punto 2 raffr.) \[°C]                 |

Servisné akcie

|                                                 |
|-------------------------------------------------|
| Imposta limite T1S riscaldamento superiore      |
| Imposta limite T1S riscaldamento inferiore      |
| Imposta limite superiore T1S raffreddamento     |
| Imposta limite inferiore T1S raffreddamento     |
| Imposta tempo funzionamento pompa ACS           |
| Imposta temperatura disinfezione T5s\_DI        |
| Imposta ritardo avvio IBH                       |
| Imposta temperatura esterna abilitazione IBH    |
| Imposta setpoint riscaldamento holiday T1S      |
| Imposta setpoint ACS holiday T5S                |
| Imposta T1SetH1 (curva riscald. punto 1)        |
| Imposta T1SetH2 (curva riscald. punto 2)        |
| Imposta T4H1 (temp. esterna curva riscald. p.1) |
| Imposta T4H2 (temp. esterna curva riscald. p.2) |
| Imposta T1SetC1 (curva raffr. punto 1)          |
| Imposta T1SetC2 (curva raffr. punto 2)          |
| Imposta T4C1 (temp. esterna curva raffr. p.1)   |
| Imposta T4C2 (temp. esterna curva raffr. p.2)   |

Čítanie (modul)

```taphome
VAR errCode := MODBUSR(H, 124, Int16);
IF(errCode = 1)
  ADDERROR(1, "E0 — Errore flusso acqua (dopo 3 E8)");
END
IF(errCode = 2)
  ADDERROR(2, "E1 — Mancanza fase o inversione fase/neutro");
END
IF(errCode = 3)
  ADDERROR(3, "E2 — Errore comunicazione controllore-modulo idraulico");
END
IF(errCode = 4)
  ADDERROR(4, "E3 — Guasto sonda temperatura uscita acqua T1");
END
IF(errCode = 5)
  ADDERROR(5, "E4 — Guasto sonda temperatura serbatoio ACS T5");
END
IF(errCode = 6)
  ADDERROR(6, "E5 — Guasto sonda temperatura refrigerante condensatore T3");
END
IF(errCode = 7)
  ADDERROR(7, "E6 — Guasto sonda temperatura esterna T4");
END
IF(errCode = 8)
  ADDERROR(8, "E7 — Guasto sonda temperatura buffer superiore Tbt1");
END
IF(errCode = 9)
  ADDERROR(9, "E8 — Errore flusso acqua");
END
IF(errCode = 10)
  ADDERROR(10, "E9 — Guasto sonda temperatura aspirazione Th");
END
IF(errCode = 11)
  ADDERROR(11, "EA — Guasto sonda temperatura mandata compressore Tp");
END
IF(errCode = 14)
  ADDERROR(14, "Ed — Guasto sonda temperatura ingresso acqua Tw_in");
END
IF(errCode = 15)
  ADDERROR(15, "EE — Errore EEprom modulo idraulico");
END
IF(errCode = 20)
  ADDERROR(20, "P0 — Protezione pressostato bassa pressione");
END
IF(errCode = 21)
  ADDERROR(21, "P1 — Protezione pressostato alta pressione");
END
IF(errCode = 23)
  ADDERROR(23, "P3 — Protezione sovracorrente compressore");
END
IF(errCode = 24)
  ADDERROR(24, "P4 — Protezione alta temperatura mandata");
END
IF(errCode = 25)
  ADDERROR(25, "P5 — Protezione differenziale Tw_out-Tw_in elevato");
END
IF(errCode = 26)
  ADDERROR(26, "P6 — Protezione modulo inverter");
END
IF(errCode = 39)
  ADDERROR(39, "H0 — Errore comunicazione PCB-B e scheda principale modulo idraulico");
END
IF(errCode = 40)
  ADDERROR(40, "H1 — Errore comunicazione modulo inverter PCB-A e PCB-B");
END
IF(errCode = 44)
  ADDERROR(44, "H4 — Tre attivazioni protezione P6");
END
IF(errCode = 46)
  ADDERROR(46, "H6 — Errore ventilatore DC");
END
IF(errCode = 47)
  ADDERROR(47, "H7 — Protezione tensione");
END
IF(errCode = 48)
  ADDERROR(48, "H8 — Errore sonda pressione");
END
IF(errCode = 49)
  ADDERROR(49, "H9 — Guasto sonda temperatura uscita acqua zona 2 Tw2");
END
IF(errCode = 50)
  ADDERROR(50, "HA — Guasto sonda temperatura uscita acqua Tw_out");
END
IF(errCode = 134)
  ADDERROR(134, "L0 — Protezione modulo");
END
IF(errCode = 135)
  ADDERROR(135, "L1 — Protezione bassa tensione generatore DC");
END
IF(errCode = 136)
  ADDERROR(136, "L2 — Protezione alta tensione generatore DC");
END
IF(errCode > 0)
  ADDWARNING(0, "Codice guasto attivo: " + TOSTRING(errCode, "F0"));
END
VAR statusBits := MODBUSR(H, 128, UInt16);
IF(GETBIT(statusBits, 1))
  ADDINFO(1, "Sbrinamento in corso");
END
IF(GETBIT(statusBits, 2))
  ADDINFO(2, "Protezione antigelo attiva");
END
IF(GETBIT(statusBits, 3))
  ADDINFO(3, "Ritorno olio in corso");
END
VAR loadBits := MODBUSR(H, 129, UInt16);
IF(GETBIT(loadBits, 15))
  ADDINFO(10, "Sbrinamento attivo");
END
IF(GETBIT(loadBits, 14))
  ADDINFO(11, "Riscaldatore esterno attivo");
END
IF(GETBIT(loadBits, 12))
  ADDERROR(50, "Allarme impianto");
END
```

Servisné atribúty

Frequenza compressore \[Hz]

```taphome
TOSTRING(MODBUSR(H, 100, Int16), "F0") + " Hz"
```

Modalità operativa corrente

```taphome
SWITCH(MODBUSR(H, 101, Int16), 0, "Spento", 2, "Raffreddamento", 3, "Riscaldamento", "Sconosciuto")
```

Velocità ventilatore \[RPM]

```taphome
TOSTRING(MODBUSR(H, 102, Int16), "F0") + " RPM"
```

Apertura EEV PMV \[passi]

```taphome
TOSTRING(MODBUSR(H, 103, Int16), "F0")
```

Temperatura condensatore T3 \[°C]

```taphome
TOSTRING(MODBUSR(H, 106, Int16), "F0") + " °C"
```

Temperatura mandata compressore Tp \[°C]

```taphome
TOSTRING(MODBUSR(H, 108, Int16), "F0") + " °C"
```

Temperatura aspirazione compressore \[°C]

```taphome
TOSTRING(MODBUSR(H, 109, Int16), "F0") + " °C"
```

Temperatura uscita acqua totale T1 \[°C]

```taphome
TOSTRING(MODBUSR(H, 110, Int16), "F0") + " °C"
```

Temperatura uscita acqua T1B (a valle riscaldatore) \[°C]

```taphome
TOSTRING(MODBUSR(H, 111, Int16), "F0") + " °C"
```

Temperatura refrigerante liquido T2 \[°C]

```taphome
TOSTRING(MODBUSR(H, 112, Int16), "F0") + " °C"
```

Temperatura refrigerante gassoso T2B \[°C]

```taphome
TOSTRING(MODBUSR(H, 113, Int16), "F0") + " °C"
```

Temperatura ambiente Ta \[°C]

```taphome
TOSTRING(MODBUSR(H, 114, Int16), "F0") + " °C"
```

Alta pressione unità esterna \[kPa]

```taphome
TOSTRING(MODBUSR(H, 116, Int16), "F0") + " kPa"
```

Bassa pressione unità esterna \[kPa]

```taphome
TOSTRING(MODBUSR(H, 117, Int16), "F0") + " kPa"
```

Corrente unità esterna \[A]

```taphome
TOSTRING(MODBUSR(H, 118, Int16), "F0") + " A"
```

Tensione unità esterna \[V]

```taphome
TOSTRING(MODBUSR(H, 119, Int16), "F0") + " V"
```

Ore di funzionamento compressore \[h]

```taphome
TOSTRING(MODBUSR(H, 122, Int16), "F0") + " h"
```

Tensione bus DC \[V]

```taphome
TOSTRING(MODBUSR(H, 134, Int16) / 10, "F1") + " V"
```

Corrente bus DC \[A]

```taphome
TOSTRING(MODBUSR(H, 133, Int16), "F0") + " A"
```

Temperatura modulo TF \[°C]

```taphome
TOSTRING(MODBUSR(H, 135, Int16), "F0") + " °C"
```

Portata acqua \[m³/h]

```taphome
TOSTRING(MODBUSR(H, 138, Int16) / 100, "F2") + " m³/h"
```

Potenza modulo idraulico \[kW]

```taphome
TOSTRING(MODBUSR(H, 140, Int16) / 100, "F2") + " kW"
```

Versione firmware unità

```taphome
TOSTRING(MODBUSR(H, 130, Int16), "F0")
```

Versione firmware controllore cablato

```taphome
TOSTRING(MODBUSR(H, 131, Int16), "F0")
```

Limite superiore T1S raffreddamento \[°C]

```taphome
TOSTRING(MODBUSR(H, 201, Int16), "F0") + " °C"
```

Limite inferiore T1S raffreddamento \[°C]

```taphome
TOSTRING(MODBUSR(H, 202, Int16), "F0") + " °C"
```

Limite superiore T1S riscaldamento \[°C]

```taphome
TOSTRING(MODBUSR(H, 203, Int16), "F0") + " °C"
```

Limite inferiore T1S riscaldamento \[°C]

```taphome
TOSTRING(MODBUSR(H, 204, Int16), "F0") + " °C"
```

Tempo funzionamento pompa ACS \[min]

```taphome
TOSTRING(MODBUSR(H, 209, Int16), "F0") + " min"
```

Temperatura disinfezione T5s\_DI \[°C]

```taphome
TOSTRING(MODBUSR(H, 220, Int16), "F0") + " °C"
```

Durata massima disinfezione \[min]

```taphome
TOSTRING(MODBUSR(H, 221, Int16), "F0") + " min"
```

Setpoint riscaldamento holiday T1S \[°C]

```taphome
TOSTRING(MODBUSR(H, 245, Int16), "F0") + " °C"
```

Setpoint ACS holiday T5S \[°C]

```taphome
TOSTRING(MODBUSR(H, 246, Int16), "F0") + " °C"
```

T1SetH1 (curva riscald. punto 1) \[°C]

```taphome
TOSTRING(MODBUSR(H, 265, Int16), "F0") + " °C"
```

T1SetH2 (curva riscald. punto 2) \[°C]

```taphome
TOSTRING(MODBUSR(H, 266, Int16), "F0") + " °C"
```

T4H1 (temp. esterna punto 1 riscald.) \[°C]

```taphome
TOSTRING(MODBUSR(H, 267, Int16), "F0") + " °C"
```

T4H2 (temp. esterna punto 2 riscald.) \[°C]

```taphome
TOSTRING(MODBUSR(H, 268, Int16), "F0") + " °C"
```

T1SetC1 (curva raffr. punto 1) \[°C]

```taphome
TOSTRING(MODBUSR(H, 261, Int16), "F0") + " °C"
```

T1SetC2 (curva raffr. punto 2) \[°C]

```taphome
TOSTRING(MODBUSR(H, 262, Int16), "F0") + " °C"
```

T4C1 (temp. esterna punto 1 raffr.) \[°C]

```taphome
TOSTRING(MODBUSR(H, 263, Int16), "F0") + " °C"
```

T4C2 (temp. esterna punto 2 raffr.) \[°C]

```taphome
TOSTRING(MODBUSR(H, 264, Int16), "F0") + " °C"
```

Servisné akcie

Imposta limite T1S riscaldamento superiore

Parametre: Temperatura \[°C] (25–60 val)

```taphome
MODBUSWNE(H, 203, Int16, val);
```

Imposta limite T1S riscaldamento inferiore

Parametre: Temperatura \[°C] (22–55 val)

```taphome
MODBUSWNE(H, 204, Int16, val);
```

Imposta limite superiore T1S raffreddamento

Parametre: Temperatura \[°C] (18–25 val)

```taphome
MODBUSWNE(H, 201, Int16, val);
```

Imposta limite inferiore T1S raffreddamento

Parametre: Temperatura \[°C] (5–25 val)

```taphome
MODBUSWNE(H, 202, Int16, val);
```

Imposta tempo funzionamento pompa ACS

Parametre: Tempo \[min] (5–120 val)

```taphome
MODBUSWNE(H, 209, Int16, val);
```

Imposta temperatura disinfezione T5s\_DI

Parametre: Temperatura \[°C] (60–70 val)

```taphome
MODBUSWNE(H, 220, Int16, val);
```

Imposta ritardo avvio IBH

Parametre: Minuti (15–120 val)

```taphome
MODBUSWNE(H, 235, Int16, val);
```

Imposta temperatura esterna abilitazione IBH

Parametre: Temperatura \[°C] (-15–10 val)

```taphome
MODBUSWNE(H, 233, Int16, val);
```

Imposta setpoint riscaldamento holiday T1S

Parametre: Temperatura \[°C] (20–25 val)

```taphome
MODBUSWNE(H, 245, Int16, val);
```

Imposta setpoint ACS holiday T5S

Parametre: Temperatura \[°C] (20–25 val)

```taphome
MODBUSWNE(H, 246, Int16, val);
```

Imposta T1SetH1 (curva riscald. punto 1)

Parametre: Temperatura \[°C] (25–60 val)

```taphome
MODBUSWNE(H, 265, Int16, val);
```

Imposta T1SetH2 (curva riscald. punto 2)

Parametre: Temperatura \[°C] (25–60 val)

```taphome
MODBUSWNE(H, 266, Int16, val);
```

Imposta T4H1 (temp. esterna curva riscald. p.1)

Parametre: Temperatura \[°C] (-25–30 val)

```taphome
MODBUSWNE(H, 267, Int16, val);
```

Imposta T4H2 (temp. esterna curva riscald. p.2)

Parametre: Temperatura \[°C] (-25–30 val)

```taphome
MODBUSWNE(H, 268, Int16, val);
```

Imposta T1SetC1 (curva raffr. punto 1)

Parametre: Temperatura \[°C] (5–25 val)

```taphome
MODBUSWNE(H, 261, Int16, val);
```

Imposta T1SetC2 (curva raffr. punto 2)

Parametre: Temperatura \[°C] (5–25 val)

```taphome
MODBUSWNE(H, 262, Int16, val);
```

Imposta T4C1 (temp. esterna curva raffr. p.1)

Parametre: Temperatura \[°C] (-5–46 val)

```taphome
MODBUSWNE(H, 263, Int16, val);
```

Imposta T4C2 (temp. esterna curva raffr. p.2)

Parametre: Temperatura \[°C] (-5–46 val)

```taphome
MODBUSWNE(H, 264, Int16, val);
```

Pompa di calore — Zona 1 On/Off Prepínač

Hodnoty / Stavy: ON · OFF

Čítanie stavu prepínača

```taphome
GETBIT(MODBUSR(H, 0, UInt16), 1)
```

Zápis stavu prepínača

```taphome
VAR reg := MODBUSR(H, 0, UInt16);
reg := SETBIT(reg, 1, St);
MODBUSWNE(H, 0, UInt16, reg);
```

Pompa di calore — Zona 2 On/Off Prepínač

Hodnoty / Stavy: ON · OFF

Čítanie stavu prepínača

```taphome
GETBIT(MODBUSR(H, 0, UInt16), 3)
```

Zápis stavu prepínača

```taphome
VAR reg := MODBUSR(H, 0, UInt16);
reg := SETBIT(reg, 3, St);
MODBUSWNE(H, 0, UInt16, reg);
```

ACS — Riscaldamento On/Off Prepínač

Hodnoty / Stavy: ON · OFF

Čítanie stavu prepínača

```taphome
GETBIT(MODBUSR(H, 0, UInt16), 2)
```

Zápis stavu prepínača

```taphome
VAR reg := MODBUSR(H, 0, UInt16);
reg := SETBIT(reg, 2, St);
MODBUSWNE(H, 0, UInt16, reg);
```

Modalità di funzionamento Viacstavový prepínač

Hodnoty / Stavy: Auto · Raffreddamento · Riscaldamento

Čítanie stavu prepínača

```taphome
MODBUSR(H, 1, Int16)
```

Zápis stavu prepínača

```taphome
MODBUSWNE(H, 1, Int16, Mu)
```

Setpoint temperatura acqua T1s Premenná

Čítanie

```taphome
MODBUSR(H, 2, Int16)
```

Zápis

```taphome
MODBUSWNE(H, 2, Int16, Va)
```

Setpoint temperatura ambiente Ts Premenná

Čítanie

```taphome
MODBUSR(H, 3, Int16)
```

Zápis

```taphome
MODBUSWNE(H, 3, Int16, Va)
```

Setpoint temperatura ACS T5s Premenná

Čítanie

```taphome
MODBUSR(H, 4, Int16)
```

Zápis

```taphome
MODBUSWNE(H, 4, Int16, Va)
```

Modalità ECO Prepínač

Hodnoty / Stavy: ECO · OFF

Čítanie stavu prepínača

```taphome
GETBIT(MODBUSR(H, 5, UInt16), 10)
```

Zápis stavu prepínača

```taphome
VAR reg := MODBUSR(H, 5, UInt16);
reg := SETBIT(reg, 10, St);
MODBUSWNE(H, 5, UInt16, reg);
```

Modalità Silenziosa Prepínač

Hodnoty / Stavy: Silenziosa · OFF

Čítanie stavu prepínača

```taphome
GETBIT(MODBUSR(H, 5, UInt16), 6)
```

Zápis stavu prepínača

```taphome
VAR reg := MODBUSR(H, 5, UInt16);
reg := SETBIT(reg, 6, St);
MODBUSWNE(H, 5, UInt16, reg);
```

Curva climatica — selezione Premenná

Čítanie

```taphome
MODBUSR(H, 6, Int16)
```

Zápis

```taphome
MODBUSWNE(H, 6, Int16, Va)
```

Temperatura ingresso acqua TW\_in Teplotný senzor

Čítanie teploty

```taphome
MODBUSR(H, 104, Int16)
```

Temperatura uscita acqua TW\_out Teplotný senzor

Čítanie teploty

```taphome
MODBUSR(H, 105, Int16)
```

Temperatura esterna T4 Teplotný senzor

Čítanie teploty

```taphome
MODBUSR(H, 107, Int16)
```

Temperatura serbatoio ACS T5 Teplotný senzor

Čítanie teploty

```taphome
MODBUSR(H, 115, Int16)
```

**Pripojenie:** Modbus RTU • 9600 baud• 8N1 • Slave ID: $\[SlaveId]

## Parametre importu

Tieto hodnoty zadáte pri importe XML.

| Pýta sa v aplikácii | Predvolené |
|---------------------|------------|
| Modbus Slave ID     | `1`        |

## Súvisiaca dokumentácia

- [Modbus Integration](https://taphome.com/sk/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/sk/docs/integration/modbus/)
- [Jednoduchá konfigurácia pomocou šablón](https://taphome.com/sk/docs/integration/modbus/templates/)
- [Skripty Modbus a prefetch](https://taphome.com/sk/docs/script/modbus-scripts/)
- [Funkcie Modbus](https://taphome.com/sk/docs/script/modbus/)
- [Dátové typy Modbus](https://taphome.com/sk/docs/script/modbus-data-types/)

