  questions: ["Cum integrez Komfovent DOMEKT cu TapHome?","Ce controlează șablonul TapHome pentru Komfovent Air Recovery?","Cum conectez controlerul Komfovent C6/C6M la TapHome prin RS-485?","Cum configurez setările Modbus RTU pe controlerul Komfovent C6?","Cum comut modurile de ventilație ale Komfovent prin TapHome?","Cum monitorizez consumul de putere și starea filtrului la Komfovent prin TapHome?"]
---

# Komfovent Air Recovery

Comunicație: Modbus RTU

- [Pagina produsului Komfovent DOMEKT](https://www.komfovent.com/en/c-page/products/air-handling-units/domekt-residential-ventilation-units)
- [Site-ul oficial Komfovent](https://www.komfovent.com)

## Ghid de integrare

Șablonul Komfovent Air Recovery integrează în TapHome unitățile rezidențiale de ventilație DOMEKT echipate cu controlere C6 sau C6M, prin Modbus RTU pe RS-485. Șablonul oferă selectarea modului de ventilație, controlul temperaturii setate, activarea modului ECO, monitorizarea temperaturii (aer extras și exterior), măsurarea consumului de putere și gestionarea întreținerii filtrului.

Modelele compatibile includ DOMEKT R 450 V, DOMEKT R 400 V, DOMEKT R 400 H, DOMEKT CF 400 V și DOMEKT CF 500 F — orice unitate DOMEKT cu controler C6 sau C6M.

## Conectarea hardware

### Conexiunea fizică

Controlerul C6/C6M are borne pentru conexiuni externe în cutia de comandă a unității de tratare a aerului. Interfața RS-485 Modbus RTU folosește bornele **A** (borna 1 la C6, borna 41 la C6M) și **B** (borna 2 la C6, borna 42 la C6M).

![Controlerele Komfovent C6 și C6M cu bornele de conectare](https://taphome.com/images/compatibility/komfovent-air-recovery/controller-terminals_hu_1475247556964512.jpg)

### Schema de conectare C6

![Schema de conectare Komfovent C6 pentru elementele externe, cu RS-485, senzori, intrări și ieșiri](https://taphome.com/images/compatibility/komfovent-air-recovery/wiring-c6-terminals_hu_ee6049e54cbfa979.jpg)

### Schema de conectare C6M

![Schema de conectare Komfovent C6M pentru elementele externe, cu bornele RS-485 41-42](https://taphome.com/images/compatibility/komfovent-air-recovery/wiring-c6m-p005_hu_565fdaf33397514d.jpg)

### Cablarea RS-485

Conectați folosind un **cablu cu pereche torsadată**:

- **Borna A** → A+/D+ pe RS-485 TapHome
- **Borna B** → B-/D- pe RS-485 TapHome

| Parametru | Valoare |
|-----------|-------|
| Tip de cablu | Pereche torsadată (recomandat CAT5) |
| Lungime maximă a cablului | **150 m** |

> [!WARNING]
> **Important — masă comună (GND)**
>
> Dacă distanța dintre interfețele RS-485 depășește **10 m**, punctul de masă al controlerului C6/C6M și punctul de masă TapHome **trebuie** conectate între ele. Fără o masă comună (GND) corectă pot apărea erori de comunicare.

## Configurare

### Setările Modbus RTU

Setările implicite ale interfeței RS-485 sunt:

| Parametru | Valoare implicită |
|-----------|---------------|
| Baud rate | **19200** |
| Lungimea cuvântului | 8 |
| Paritate | **Pară** |
| Biți de stop | 1 |
| Slave ID | **254** |

Aceste setări se pot modifica din interfața web C6/C6M. Conectați-vă într-un browser la adresa IP implicită a controlerului, **192.168.0.60**. Autentificați-vă cu numele de utilizator `user` și parola `user`. Mergeți la **Settings → Connectivity**, unde găsiți și puteți modifica setările RS-485 și ID-ul protocolului Modbus RTU.

![Setările de conectivitate din interfața web Komfovent C6, cu Modbus ID, baud rate RS-485 și paritate](https://taphome.com/images/compatibility/komfovent-air-recovery/web-settings-p003_hu_7e7ec5178aaea75.jpg)

Alternativ, adresa IP și masca de rețea se pot modifica de pe **panoul tactil C6.1**: apăsați butonul **Menu**, apoi apăsați și țineți apăsat butonul **Settings** mai mult de 5 secunde pentru a deschide fereastra **Advanced Settings**. Selectați **Connectivity** pentru a vedea și edita parametrii de rețea.

### Configurarea în TapHome

La importul șablonului în TapHome sunt necesari doi parametri:

- **Slave ID** — trebuie să corespundă cu ID-ul Modbus configurat pe controler (implicit: **254**)
- **IP Address** — folosit pentru conexiunile TCP (implicit: **192.168.0.1**). La conexiunile RTU prin RS-485 acest parametru nu se folosește

> [!TIP]
> Intervalul minim de interogare trebuie să fie de **500 ms sau mai mult**. Când la aceeași rețea Modbus sunt conectate mai multe unități Komfovent, se recomandă un interval de interogare de cel puțin **1 secundă**.

### Monitorizarea alarmelor

ReadScript-ul modulului din șablon monitorizează alarmele active citind registrele H:599–H:609. Când există alarme active, acestea sunt raportate în TapHome ca erori, cu numărul de alarme și codurile alarmelor individuale. Codurile de alarmă urmează codificarea Komfovent: codurile de tip F (1–127) indică alarme de defect, codurile de tip W (129–255) indică alarme de avertizare.

Pentru a reseta alarmele active, scrieți valoarea `0x9C5` în registrul H:600 prin TapHome.

### Scriptul de inițializare

Scriptul de inițializare al șablonului setează unitatea de debit la **m3/h** (registrul H:27 = 0), pentru ca debitul de aer să fie citit în aceeași unitate pe toate dispozitivele.

## Funcțiile dispozitivului

### Prezentarea sistemului

![Prezentarea sistemului Komfovent C6/C6M cu harta registrelor pentru componentele unității de ventilație](https://taphome.com/images/compatibility/komfovent-air-recovery/system-diagram-p006_hu_cf38ec7254e908bb.jpg)

### Controlul alimentării

- **Pornit/Oprit** (H:0) — comutatorul principal de alimentare al unității de ventilație. Scrierea valorii 1 pornește unitatea, 0 o oprește.

### Modul de ventilație

**Mod de ventilație** (H:4) selectează modul de funcționare activ printr-un comutator cu mai multe valori, cu 10 opțiuni:

- **Standby** (0) — unitate în standby
- **Absență** (1) — ventilație redusă pentru perioadele fără ocupanți
- **Normal** (2) — ventilație zilnică standard
- **Intensiv** (3) — ventilație crescută pentru un necesar ridicat
- **Boost** (4) — ventilație maximă
- **Bucătărie** (5), **Șemineu** (6), **Comandă prioritară** (7), **Vacanță** (8) — moduri speciale
- **Calitatea aerului** (9) — ventilație comandată de senzori

La scrierea modurilor 1–4 (Absență, Normal, Intensiv, Boost), șablonul setează automat și procentele corespunzătoare ale debitului de aer introdus și extras (20 %, 50 %, 70 %, respectiv 100 %).

Fiecare mod are parametri configurabili, accesibili prin **acțiuni de service** (Setare Absență, Setare Normal, Setare Intensiv, Setare Boost):
- **Debit aer introdus** (m3/h)
- **Debit aer extras** (m3/h)
- **Temperatură setată** (°C, interval 5–40)
- **Încălzire** (Pornit/Oprit)

**19 atribute de service** afișează setările curente pentru toate cele patru moduri configurabile (debit aer introdus/extras, temperatură setată, încălzire pentru Absență, Normal, Intensiv și Boost), plus modul programat următor, ora de început și ziua săptămânii.

### Modurile AUTO și ECO

- **Mod AUTO** (H:3) — activează ventilația automată, controlată fie de programul orar, fie de senzorii de calitate a aerului. Două atribute de service arată sursa curentă de control a modului AUTO (program orar sau Calitatea aerului) și programul orar activ (Acasă, Săptămână de lucru, Birou, Personalizat). O acțiune de service permite schimbarea programului orar.

- **Mod ECO** (H:2) — activează modul de economisire a energiei, cu limite pentru temperatura aerului introdus și încălzire/răcire opțională cu aer exterior. Șase atribute de service afișează setările ECO curente (temperatura minimă/maximă a aerului introdus, încălzire/răcire cu aer exterior, încălzire interzisă, răcire interzisă, recuperare constantă a căldurii). Acțiunea de service **Configurare mod ECO** configurează toți parametrii deodată.

### Monitorizarea temperaturii

- **Temperatura aerului extras** (H:902) — senzor de temperatură a aerului extras, cu conversie /10 în °C. Trei atribute de service arată debitul actual de aer extras (m3/h), intensitatea ventilatorului de extragere (%) și presiunea aerului extras (Pa).

- **Temperatură exterioară** (H:903) — senzor de temperatură a aerului exterior, cu conversie /10 în °C.

- **Temperatură setată — Normal** — dispozitiv termostat care citește temperatura curentă din H:902 (/10 °C) și citește/scrie temperatura setată dorită pentru modul Normal prin H:109 (/10 °C, interval 5–40 °C). Două atribute de service afișează modul de control al temperaturii (Aer introdus, Aer extras, Echilibru, Cameră) și sursa senzorului de cameră (panoul 1 sau panoul 2). Acțiunile de service permit schimbarea ambelor setări.

### Controlul puterii de recuperare

**Controlul puterii de recuperare** — dispozitiv dimmer pentru controlul nivelului puterii de recuperare a căldurii. Este un dispozitiv provizoriu, care poate necesita configurarea manuală a scripturilor de citire/scriere în TapHome.

### Consumul de energie

**Consum de energie** (H:930) — contor electric care citește consumul total de energie din H:930 (UInt32, Wh → kWh cu conversie /1000) și puterea consumată actuală din H:920 (UInt16, W → kW cu conversie /1000).

### Gestionarea filtrului

**Filtru** — monitorizează starea filtrului, cu acțiunea de service **Resetare filtru**, care scrie valoarea 1 în registrul H:1050 pentru a reseta contorul de colmatare a filtrului. Resetarea funcționează numai dacă gradul de murdărire a filtrului este mai mare de 1 %.

### Atribute de service la nivel de modul

Modulul șablonului pune la dispoziție opt atribute de service:

- **Ora sistemului** — data și ora curentă din controler (H:28–H:31)
- **Ziua săptămânii** — ziua curentă a săptămânii
- **DHCP** — starea DHCP (Pornit/Oprit), cu o acțiune de service pentru comutarea ei
- **Adresă IP**, **Mască de rețea**, **Gateway** — configurația de rețea curentă
- **Repornire după alarma de incendiu** — modul de repornire (manual/automat), cu o acțiune de service pentru schimbarea lui
- **Unități de debit** — unitatea de debit de aer setată (m3/h sau l/s)

### Funcții suplimentare

Controlerul C6/C6M pune la dispoziție și registre pentru temperatura exterioară (H:904), temperatura apei (H:905), temperatura aerului evacuat (H:961), nivelul și eficiența schimbătorului de căldură (H:912, H:924), nivelurile încălzitorului electric/de apă și ale răcitorului (H:913–H:916), procentul de murdărire a filtrului (H:917), temperatura și umiditatea camerei măsurate de panou (H:946–H:951), senzorii de calitate a aerului (H:952–H:953), masca de biți de stare (H:900), consumul de putere instantaneu (H:921), modul de control al debitului (H:12), setările de calitate a aerului (H:205–H:214) și configurarea completă a programului orar (H:300–H:555). Acestea pot fi adăugate într-o actualizare viitoare a șablonului.

> [!TIP]
> Gradul de murdărire a filtrului este disponibil în registrul H:917 (0–100 %), dar dispozitivul Filtru din șablon nu are configurat un script de citire. Pentru a monitoriza colmatarea filtrului, adăugați un dispozitiv Modbus personalizat care citește H:917 ca UInt8.

## Rezolvarea problemelor

### Nu există comunicare Modbus

1. **Verificați cablurile RS-485:**
   - Borna A conectată corect la A+/D+ pe TapHome
   - Borna B conectată corect la B-/D- pe TapHome
   - **Masa conectată** dacă lungimea cablului depășește 10 m
2. Verificați dacă Slave ID corespunde cu ID-ul Modbus din interfața web a controlerului (implicit: 254)
3. Verificați dacă TapHome este setat la: **19200 baud, paritate pară, 1 bit de stop, 8 biți de date**
4. Verificați dacă intervalul minim de interogare este de cel puțin 500 ms (1 s pentru instalațiile cu mai multe unități)

### Interfața web nu este accesibilă

1. Verificați dacă dispozitivul și calculatorul sunt în **aceeași subrețea** (IP-ul implicit al controlerului: 192.168.0.60)
2. La conectare directă, dezactivați DHCP și setați un IP static în aceeași subrețea (de ex. 192.168.0.61)
3. Verificați dacă JavaScript este activat în browser
4. Verificați dacă niciun server proxy sau firewall nu blochează conexiunea

### Citirile temperaturii afișează valori greșite

1. Verificați dacă unitățile de debit sunt setate la m3/h (registrul H:27 = 0) — scriptul de inițializare al șablonului face acest lucru automat
2. Verificați dacă modul de control al temperaturii (H:10) corespunde senzorului de temperatură așteptat
3. Rețineți că registrele de temperatură folosesc codificarea ×10 (de ex. 215 = 21,5 °C)

### Coduri de alarmă

Codurile de alarmă raportate în TapHome folosesc codificarea Komfovent. Alarmele de defect (tip F) au codurile 1–127, alarmele de avertizare (tip W) au codurile 129–255. Codurile frecvente includ:

| Cod | Tip | Mesaj |
|------|------|---------|
| 1 | F1 | Supply Flow Not Reached |
| 2 | F2 | Exhaust Flow Not Reached |
| 3 | F3 | Water Temp B5 Too Low |
| 9 | F9 | Internal Fire |
| 10 | F10 | External Fire |
| 129 | W1 | Change Air Filter |
| 130 | W2 | Service Mode |

Lista completă a codurilor de alarmă se găsește în manualul Modbus Komfovent C6/C6M.

## Dispozitive disponibile 10

Aceste dispozitive apar în TapHome după import.

Komfovent Air Recovery Modul

Atribute de service

|                                   |
|-----------------------------------|
| Ora sistemului                    |
| Ziua săptămânii                   |
| DHCP                              |
| Adresă IP                         |
| Mască de rețea                    |
| Gateway                           |
| Repornire după alarma de incendiu |
| Unități de debit                  |

Acțiuni de service

|                                            |
|--------------------------------------------|
| DHCP                                       |
| Setarea repornirii după alarma de incendiu |

Inițializare

```taphome
MODBUSWNE(H, 27, Uint16, 0);
```

Citire (modul)

```taphome
var alarm:= MODBUSR(H, 599, Uint16);
If(alarm>0, ADDERROR("There are " + alarm + " active alarms"));
If(alarm>0, ADDERROR(MODBUSR(H, 600, Uint16), "Alarm 1 active"));
If(alarm>1, ADDERROR(MODBUSR(H, 601, Uint16), "Alarm 2 active"));
If(alarm>2, ADDERROR(MODBUSR(H, 602, Uint16), "Alarm 3 active"));
If(alarm>3, ADDERROR(MODBUSR(H, 603, Uint16), "Alarm 4 active"));
If(alarm>4, ADDERROR(MODBUSR(H, 604, Uint16), "Alarm 5 active"));
If(alarm>5, ADDERROR(MODBUSR(H, 605, Uint16), "Alarm 6 active"));
If(alarm>6, ADDERROR(MODBUSR(H, 606, Uint16), "Alarm 7 active"));
If(alarm>7, ADDERROR(MODBUSR(H, 607, Uint16), "Alarm 8 active"));
If(alarm>8, ADDERROR(MODBUSR(H, 608, Uint16), "Alarm 9 active"));
If(alarm>9, ADDERROR(MODBUSR(H, 609, Uint16), "Alarm 10 active"));
```

Atribute de service

System Time

```taphome
var time := MODBUSR(H, 28, Uint16);
var date := MODBUSR(H, 30, Uint16);

GETBITS(time, 8,8) + ":" + GETBITS(time, 0, 8) + " " + GETBITS(date, 0,8) + "." + GETBITS(date, 8,8) + "." + MODBUSR(H, 29, Uint16);
```

Weekday

```taphome
SWITCH(MODBUSR(H, 31, Uint16), 
1,"Monday",
2,"Tuesday",
3,"Wednesday",
4,"Thursday",
5,"Friday",
6,"Saturday",
7,"Sunday",
"Error"
)
```

DHCP

```taphome
IF(MODBUSR(H, 34, Bool), "On", "Off"); 
```

IP adress

```taphome
var reg := MODBUSR(H, 22, Uint32);
var first := GETBITS(reg, 0, 8);
var second := GETBITS(reg, 8, 8);
var third := GETBITS(reg, 16, 8);
var last := GETBITS(reg, 24, 8);
RETURN (last + "." + third + "." + second + "." + first)
```

Mask

```taphome
var reg := MODBUSR(H, 24, Uint32);
var first := GETBITS(reg, 0, 8);
var second := GETBITS(reg, 8, 8);
var third := GETBITS(reg, 16, 8);
var last := GETBITS(reg, 24, 8);
RETURN (last + "." + third + "." + second + "." + first)
```

Gateway

```taphome
var reg := MODBUSR(H, 26, Uint32);
var first := GETBITS(reg, 0, 8);
var second := GETBITS(reg, 8, 8);
var third := GETBITS(reg, 16, 8);
var last := GETBITS(reg, 24, 8);
RETURN (last + "." + third + "." + second + "." + first)
```

Fire Alarm Restart

```taphome
SWITCH(MODBUSR(H, 41, Uint16), 
1, "Auto",
0, "Manual",
"Error");
```

Flow units

```taphome
SWITCH(MODBUSR(H, 27, Uint16),
 1, "l/s",
 0, "m3/h",
 "Error");
```

Acțiuni de service

DHCP

Parametri: DHCP (On / Off)

```taphome
MODBUSW(H, 34, Bool, dhcp);
```

Fire Alarm Restart Setting

Parametri: Restart setting (Auto / Manual)

```taphome
MODBUSW(H, 41, Bool, rs);
```

Mod AUTO Comutator Citire și scriere

Mod de ventilație automat — urmează programul orar sau semnalul senzorului de calitate a aerului

Registru: H:3 Bool

Valori / Stări: ON · OFF

Acțiuni de service

|                      |
|----------------------|
| Programul orar activ |

Citirea stării comutatorului

```taphome
MODBUSR(H, 3, Bool)
```

Scrierea stării comutatorului

```taphome
MODBUSW(H, 3, Bool, St)
```

Atribute de service

Auto Mode Control

```taphome
SWITCH(MODBUSR(H, 1, Uint16), 1, "Air Quality", 0, "Scheduling", "Error");
```

Scheduler Operation Mode

```taphome
SWITCH(MODBUSR(H, 5, Uint16),
0, "Stay at home",
1, "Working Week",
2, "Office",
3, "Custom",
"Error"
);
```

Acțiuni de service

Scheduler Operation Mode

Parametri: Scheduler Operation Mode

```taphome
MODBUSW(H, 5, Uint16, som);
```

Mod ECO Comutator Citire și scriere

Mod de economisire a energiei, cu limite pentru temperatura aerului introdus și încălzire/răcire opțională cu aer exterior

Registru: H:2 Bool

Valori / Stări: ON · OFF

Acțiuni de service

|                     |
|---------------------|
| Configurare mod ECO |

Citirea stării comutatorului

```taphome
MODBUSR(H, 2, Bool)
```

Scrierea stării comutatorului

```taphome
MODBUSW(H, 2, Bool, St)
```

Atribute de service

Minimum supply air temperature

```taphome
MODBUSR(H, 199, Uint16)/10 + " °C";
```

Maximum supply air temperature

```taphome
MODBUSR(H, 200, Uint16)/10 + " °C";
```

Free heating/cooling

```taphome
SWITCH(MODBUSR(H, 201, Uint16), 0, "Off", 1,"On", "Error");
```

Heating enable denied

```taphome
SWITCH(MODBUSR(H, 202, Uint16), 0, "Off", 1,"On", "Error");
```

Cooling enable denied

```taphome
SWITCH(MODBUSR(H, 203, Uint16), 0, "Off", 1,"On", "Error");
```

Constant heat recovery

```taphome
SWITCH(MODBUSR(H, 216, Uint16), 0, "Off", 1,"On", "Error");
```

Acțiuni de service

Eco mode setup

Parametri: Minimum supply air temp (5–40 minAirT), Maximum Supply Air Temp (5–40 maxAirT), Free Heating/Cooling (${general\_on} / ${general\_off}), Heating enable denied (${general\_on} / ${general\_off}), Cooling enable denied (${general\_on} / ${general\_off}), Constant Heat Recovery (${general\_on} / ${general\_off})

```taphome
MODBUSWNE(H, 199, Uint16, minAirT*10);
MODBUSWNE(H, 200, Uint16, maxAirT*10);
MODBUSWNE(H, 201, Uint16, freeHT);
MODBUSWNE(H, 202, Uint16, hed);
MODBUSWNE(H, 203, Uint16, ced);
MODBUSWNE(H, 216, Uint16, chr);
```

Temperatura aerului extras Senzor de temperatură Doar citire

Temperatura aerului extras din unitatea de ventilație, cu monitorizarea debitului de aer extras și a intensității ventilatorului

Registru: H:902 Int16 Unitate: °C numeric

Atribute de service

|                                                    |
|----------------------------------------------------|
| Debit actual aer extras                            |
| Intensitatea actuală a ventilatorului de extragere |
| Presiune aer extras                                |

Citirea temperaturii

```taphome
MODBUSR(H, 902, Int16) / 10
```

Atribute de service

Current extract flow

```taphome
MODBUSR(H, 907, Uint32) +  " m3/h"
```

Current extract fan intesivity

```taphome
MODBUSR(H, 910, Uint16)/10 + " %"
```

Extract Pressure

```taphome
MODBUSR(H, 919, Uint16) + " Pa";
```

Mod de ventilație Comutator cu mai multe valori Citire și scriere

Selectorul modului de funcționare — Standby, Absență, Normal, Intensiv, Boost, Bucătărie, Șemineu, Comandă prioritară, Vacanță, Calitatea aerului

Registru: H:4 UInt16 multi\_value

Valori / Stări: Standby · •Away · •Normal · •Intensive · •Boost

Acțiuni de service

|                 |
|-----------------|
| Setare Absență  |
| Setare Normal   |
| Setare Intensiv |
| Setare Boost    |

Citirea stării comutatorului

```taphome
MODBUSR(H, 4, UInt16)
```

Scrierea stării comutatorului

```taphome
SWITCH(Mu,
0, 0,
5,5,
6,6,
7,7,
8,8,
9,9,
10,10,
MODBUSW(H, 4, UInt16, Mu));

IF(Mu = 1, MODBUSW(H, 99, Uint32, 20));
IF(Mu = 1, MODBUSW(H, 101, Uint32, 20));
IF(Mu = 2, MODBUSW(H, 105, Uint32, 50));
IF(Mu = 2, MODBUSW(H, 107, Uint32, 50));
IF(Mu = 3, MODBUSW(H, 111, Uint32, 70));
IF(Mu = 3, MODBUSW(H, 113, Uint32, 70));
IF(Mu = 4, MODBUSW(H, 117, Uint32, 100));
IF(Mu = 4, MODBUSW(H, 119, Uint32, 100));
```

Atribute de service

Next Mode

```taphome
SWITCH(MODBUSR(H, 6, Uint16),
0,"Standby",
1, "Away",
2, "Normal",
3, "Intensive",
4, "Boost",
5, "Kitchen",
6, "Fireplace",
7, "Override",
8, "Holidays",
"Error"
);
```

Next Mode Start Time

```taphome
var time:= MODBUSR(H, 7, Uint16);
var hours:= FLOOR(time/60);
var minutes:= MOD(time, 60);
IF(time = 0, RETURN ("Not set"));
RETURN (hours + ":"+ minutes);
```

Next Mode Weekday

```taphome
SWITCH(MODBUSR(H, 8, Uint16), 
0, "None",
1, "Monday",
2, "Tuesday",
3, "Wednesday",
4, "Thursday",
5, "Friday",
6, "Saturday",
7, "Sunday",
"Error"
);
```

Away Supply flow

```taphome
MODBUSR(H, 99, Uint32) + " %";
```

Away Extract flow

```taphome
MODBUSR(H, 101, Uint32) + " %";
```

Away Setpoint

```taphome
MODBUSR(H, 103, Int16)/10 + " °C";
```

Away Heating

```taphome
SWITCH(MODBUSR(H, 104, Uint16), 1, "On", 0, "Off", "Error");
```

Normal Supply flow

```taphome
MODBUSR(H, 105, Uint32) + " %";
```

Normal Extract flow

```taphome
MODBUSR(H, 107, Uint32) + " %";
```

Normal Setpoint

```taphome
MODBUSR(H, 109, Int16)/10 + " °C";
```

Normal Heating

```taphome
SWITCH(MODBUSR(H, 110, Uint16), 1, "On", 0, "Off", "Error");
```

Intensive Supply flow

```taphome
MODBUSR(H, 111, Uint32) + " %";
```

Intensive Extract flow

```taphome
MODBUSR(H, 113, Uint32) + " %";
```

Intensive Setpoint

```taphome
MODBUSR(H, 115, Int16)/10 + " °C";
```

Intensive Heating

```taphome
SWITCH(MODBUSR(H, 116, Uint16), 1, "On", 0, "Off", "Error");
```

Boost Supply flow

```taphome
MODBUSR(H, 117, Uint32) + " %";
```

Boost Extract flow

```taphome
MODBUSR(H, 119, Uint32) + " %";
```

Boost Setpoint

```taphome
MODBUSR(H, 121, Int16)/10 + " °C";
```

Boost Heating

```taphome
SWITCH(MODBUSR(H, 122, Uint16), 1, "On", 0, "Off", "Error");
```

Acțiuni de service

Set Away

Parametri: Supply flow \[m3/h] (0–200000 sf), Extract flow \[m3/h] (0–200000 ex), Setpoint °C (5–40 sp), Heating (${general\_on} / ${general\_off})

```taphome
MODBUSWNE(H, 99, Uint32, sf);
MODBUSWNE(H, 101, Uint32, ex);
MODBUSWNE(H, 103, Int16, sp*10);
MODBUSWNE(H, 104, Bool, he);
```

Set Normal

Parametri: Supply flow \[m3/h] (0–200000 sf), Extract flow \[m3/h] (0–200000 ex), Setpoint °C (5–40 sp), Heating (${general\_on} / ${general\_off})

```taphome
var q := 6;
MODBUSWNE(H, 99+q, Uint32, sf);
MODBUSWNE(H, 101+q, Uint32, ex);
MODBUSWNE(H, 103+q, Int16, sp*10);
MODBUSWNE(H, 104+q, Bool, he);
```

Set Intensive

Parametri: Supply flow \[m3/h] (0–200000 sf), Extract flow \[m3/h] (0–200000 ex), Setpoint °C (5–40 sp), Heating (${general\_on} / ${general\_off})

```taphome
var q := 12;
MODBUSWNE(H, 99+q, Uint32, sf);
MODBUSWNE(H, 101+q, Uint32, ex);
MODBUSWNE(H, 103+q, Int16, sp*10);
MODBUSWNE(H, 104+q, Bool, he);
```

Set Boost

Parametri: Supply flow \[m3/h] (0–200000 sf), Extract flow \[m3/h] (0–200000 ex), Setpoint °C (5–40 sp), Heating (1–100 he)

```taphome
var q := 18;
MODBUSWNE(H, 99+q, Uint32, sf);
MODBUSWNE(H, 101+q, Uint32, ex);
MODBUSWNE(H, 103+q, Int16, sp*10);
MODBUSWNE(H, 104+q, Bool, he);
```

Temperatură setată — Normal Termostat Citire și scriere

Termostat cu citirea temperaturii curente și temperatură setată reglabilă pentru modul Normal (5–40 °C)

Registru: H:902 → H:109 Int16 Unitate: °C numeric

Atribute de service

|                        |
|------------------------|
| Controlul temperaturii |
| Senzor de cameră       |

Acțiuni de service

|                        |
|------------------------|
| Controlul temperaturii |
| Senzor de cameră       |

Citirea temperaturii

```taphome
MODBUSR(H, 902, Int16) / 10
```

Citirea temperaturii dorite

```taphome
MODBUSR(H, 109, Int16)/10;
```

Scrierea temperaturii dorite

```taphome
MODBUSW(H, 109, Int16, Se*10);
```

Atribute de service

Temperature Control

```taphome
SWITCH(MODBUSR(H, 10, Uint16), 
0, "Supply",
1, "Extract",
2, "Balance",
3, "Room",
"Error"
);
```

Room sensor

```taphome
SWITCH(MODBUSR(H, 38, Uint16), 
0, "Panel temperature(1)",
1, "Panel temperature(2)",
"Error"
);
```

Acțiuni de service

Temperature Control

Parametri: Temperature Control

```taphome
MODBUSW(H, 10, Uint16, tc);
```

Room Sensor

Parametri: Panel Temperature

```taphome
MODBUSW(H, 38, Uint16, pt);
```

Temperatură exterioară Senzor de temperatură Doar citire

Registru: H:903 Int16 Unitate: °C numeric

Citirea temperaturii

```taphome
MODBUSR(H, 903, Int16) / 10
```

Controlul puterii de recuperare Dimmer Citire și scriere

Dimmer pentru nivelul puterii de recuperare a căldurii — poate necesita configurarea manuală a scripturilor

Citirea nivelului

```taphome
SWITCH(MODBUSR(H, 4, Uint16),
 1,MODBUSR(H, 99, Uint32) /100,
  2,MODBUSR(H, 105, Uint32) /100,
   3,MODBUSR(H, 111, Uint32) /100,
    4,MODBUSR(H, 117, Uint32) /100,
0);
```

Scrierea nivelului

```taphome
MODBUSW(H, 99, Uint32, Le * 100);
MODBUSW(H, 101, Uint32, Le * 100);
MODBUSW(H, 105, Uint32, Le * 100);
MODBUSW(H, 107, Uint32, Le * 100);
MODBUSW(H, 111, Uint32, Le * 100);
MODBUSW(H, 113, Uint32, Le * 100);
MODBUSW(H, 117, Uint32, Le * 100);
MODBUSW(H, 119, Uint32, Le * 100);
```

Pornit/Oprit Comutator Citire și scriere

Registru: H:0 Bool

Valori / Stări: ON · OFF

Citirea stării comutatorului

```taphome
MODBUSR(H, 0, Bool)
```

Scrierea stării comutatorului

```taphome
MODBUSW(H, 0, Bool, St);
```

Consum de energie Contor electric Doar citire

Consumul total de energie (kWh) și puterea consumată actuală (kW)

Registru: H:930 UInt32 Unitate: kWh numeric

Citirea consumului total

```taphome
MODBUSR(H, 930, UInt32) / 1000
```

Citirea cererii

```taphome
MODBUSR(H, 920, Uint16) / 1000
```

Filtru Intrare analogică Doar citire

Monitorizarea stării filtrului, cu acțiune de resetare a contorului de colmatare

Acțiuni de service

|                 |
|-----------------|
| Resetare filtru |

Citirea nivelului de intrare

```taphome
MODBUSR(H, 916, Uint16) / 100
```

Acțiuni de service

Filter reset

```taphome
modbusw(H, 1050, Uint16, 1)
```

**Conexiune:** Modbus RTU • 19200 baud• 8E1 • Slave ID: $\[SlaveId]

Îmbunătățiri posibile (18)

- H:904 Outdoor Temperature (true) — Register 904 = Outdoor temp (x10 °C). Template reads H:903 (Extract temp) as Outdoor — may be intentional mapping or an offset
- H:905 Water Temperature — Return water temperature sensor (x10 °C) for water heater/cooler coil
- H:900 Status Icon Bit Mask — Bitmask: Starting, Stopping, Fan, Rotor, Heating, Cooling, HeatingDenied, CoolingDenied, FlowDown, FreeHeating, FreeCooling, AlarmF, AlarmW
- H:912 Heat Exchanger Level — Heat exchanger operating level (x10 %, 0-100%)
- H:913 Electric Heater Level — Electric heater operating level (x10 %, 0-100%)
- H:914 Water Heater Level — Water heater operating level (x10 %, 0-100%)
- H:915 Water Cooler Level — Water cooler operating level (x10 %, 0-100%)
- H:917 Filters Impurity — Filter clogging percentage (0-100%). Filter device exists but has no read script for this register
- H:924 Heat Exchanger Efficiency — Heat recovery efficiency percentage (0-100%)
- H:921 Power Consumption (W) — Instantaneous power consumption in Watts. Template reads H:920 which is Extract pressure per source docs
- H:946 Panel 1 Temperature — Panel 1 room temperature (x10 °C)
- H:947 Panel 1 Humidity — Panel 1 room humidity (0-100%)
- H:952 Air Quality Sensor 1 — CO2 (ppm) or VOC or RH from B8 sensor
- H:961 Exhaust Temperature — Exhaust air temperature after heat exchanger (x10 °C)
- H:12 Flow Control Mode — Flow control mode: 0=CAV, 1=VAV, 2=DCV, 3=OFF
- H:205 Air Quality Enable — Enables/disables air quality function (0=Disabled, 1=Enabled)
- H:206 Air Quality Temperature Setpoint — Temperature setpoint for air quality mode (x10 °C, 5-40)
- H:300-H:555 Scheduler Programs — Full scheduler programming (weekday masks, events with mode/start/stop times). Complex multi-register structure not implemented

## Parametri de import

Introduceți aceste valori când importați XML-ul.

| Solicitat în aplicație | Implicit      |
|------------------------|---------------|
| Slave ID               | `254`         |
| Adresă IP              | `192.168.0.1` |

## Surse

- Komfovent C6/C6M Controller Modbus Manual
  
  [www.komfovent.com](https://www.komfovent.com/en/downloads/MODBUS_connection_C6_EN.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/komfovent-air-recovery/MODBUS_connection_C6_EN.pdf)
- Komfovent C6 Controller Product Page
  
  [www.komfovent.com](https://www.komfovent.com/en/end-user/control/c6-controller/) 2026-03-20
- Komfovent DOMEKT Residential Ventilation Units
  
  [www.komfovent.com](https://www.komfovent.com/en/c-page/products/air-handling-units/domekt-residential-ventilation-units) 2026-03-20
- Komfovent C6.1/C6.2 Electrical Installation and Operation Manual
  
  [www.komfovent.com](https://www.komfovent.com/en/downloads/C6_manual_EN.pdf)
- Komfovent DOMEKT C6M Automation Installation Manual
  
  [www.komfovent.com](https://www.komfovent.com/en/downloads/DOMEKT_C6M_installation_manual_EN.pdf)
- TapHome Modbus Template - Komfovent Air Recovery

Documentele producătorilor sunt © ale proprietarilor respectivi. Sunt furnizate așa cum au fost publicate de producător, doar ca referință.

## Documentație asociată

- [Modbus Integration](https://taphome.com/ro/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/ro/docs/integration/modbus/)
- [Configurare simplă cu ajutorul șabloanelor](https://taphome.com/ro/docs/integration/modbus/templates/)
- [Scripturi Modbus și prefetch](https://taphome.com/ro/docs/script/modbus-scripts/)
- [Funcții Modbus](https://taphome.com/ro/docs/script/modbus/)
- [Tipuri de date Modbus](https://taphome.com/ro/docs/script/modbus-data-types/)