  questions: ["Jak zintegrowac Flexit EcoNordic z TapHome?","Co steruje szablon Flexit EcoNordic w TapHome?","Jak podlaczyc Flexit EcoNordic przez RS-485 do TapHome?","Jaka jest roznica miedzy EcoNordic WH4 a W4 w TapHome?","Jak aktywowac wentylacje kominkowa na Flexit EcoNordic przez TapHome?","Jak sterowac produkcja cieplej wody na Flexit EcoNordic?"]
---

# Flexit EcoNordic WH4 / W4

Komunikacja: Modbus RTU

- [Oficjalna strona Flexit](https://www.flexit.no)

## Poradnik integracji

Flexit EcoNordic to centrala klimatyczna laczaca wentylacje nawiewno-wywiewna z odzyskiem ciepla, produkcja cieplej wody uzytkowej oraz ogrzewaniem wodnym (model WH4). Komunikuje sie z TapHome przez Modbus RTU po RS-485, umozliwiajac sterowanie trybami wentylacji, nastawami temperatury, zarzadzanie ciepla woda oraz monitorowanie pracy pompy ciepla.

Obslugiwane sa dwa modele: **EcoNordic WH4** (wentylacja + ogrzewanie + ciepla woda) i **EcoNordic W4** (wentylacja + ciepla woda). WH4 zawiera dodatkowe czujniki i sterowanie obiegiem grzewczym, ktore nie sa dostepne w W4.

## Podlaczenie sprzetowe

EcoNordic posiada wbudowany interfejs Modbus RTU dostepny przez RS-485. Podlacz TapHome Core do portu RS-485 EcoNordic za pomoca skretki z GND.

> [!WARNING]
> W dostepnej dokumentacji nie znaleziono schematu polaczen. Dokladna lokalizacje zaciskow RS-485 na urzadzeniu mozna znalezc w instrukcji instalacji EcoNordic lub kontaktujac sie z obsluga Flexit. Opcjonalny **kabel Modbus (HP Res)** jest dostepny od Flexit do podlaczenia zewnetrznych kontrolerow.

## Konfiguracja

Skonfiguruj polaczenie Modbus w TapHome z nastepujacymi parametrami:

| Parametr | Wartosc |
|----------|---------|
| Baud rate | 9600 |
| Bity danych | 8 |
| Parzystosc | Even |
| Bity stopu | 1 |
| Slave ID | 1 (domyslnie) |

EcoNordic uzywa wlasnej mapy rejestrow Modbus w zakresie adresow 1-3037. Rozni sie ona od mapy rejestrow CI66 uzywanych przez starsze modele Flexit Nordic S2-S4 / CL2-CL4 — adapter CI66 nie jest potrzebny.

> [!NOTE]
> EcoNordic mozna sterowac rowniez przez aplikacje mobilna **Flexit GO** (Android/iOS). TapHome i aplikacja Flexit GO moga wspolistniec — obie komunikuja sie z urzadzeniem niezaleznie.

## Mozliwosci urzadzenia

### Sterowanie trybem wentylacji

**Tryb pracy** (H:2013) jest glownym sterowaniem wentylacja z czterema trybami:

- **Stop** — wentylatory wylaczone, brak wentylacji
- **Away** — zmniejszona wentylacja dla niezamieszkalego budynku
- **Home** — normalny dzienny tryb pracy
- **High** — tymczasowo zwiekszona wentylacja

Dwa specjalne wyzwalacze zapewniaja dodatkowe tryby wentylacji:

- **Szybka wentylacja** (H:3006) — aktywuje tymczasowa wentylacje o duzej predkosci dla szybkiej wymiany powietrza (gotowanie, goscie, wilgoc). Czas trwania jest konfigurowalny przez akcje serwisowa (1-360 minut)
- **Wentylacja kominkowa** (H:3007) — tworzy nadcisnienie wewnetrzne, aby zapobiec wciaganiu dymu do pomieszczenia podczas rozpalania kominka. Czas trwania jest konfigurowalny przez akcje serwisowa (0-360 minut)

**Przycisk Comfort** (H:2040) przelacza tryb komfortu na urzadzeniu, ktory tymczasowo zwieksza wentylacje i moze dostosowac nastawy temperatury.

### Monitorowanie temperatury i nastawy

Szablon udostepnia szesc czujnikow temperatury:

- **Temperatura powietrza zewnetrznego** (A:1) — temperatura powietrza zewnetrznego na czerpni
- **Temperatura powietrza nawiewanego** (A:5) — swieze powietrze dostarczane do budynku po odzysku ciepla i dogrzewaniu
- **Temperatura powietrza wyciagowego** (A:9) — powietrze wyciagane z budynku przed odzyskiem ciepla
- **Temperatura powietrza wyrzutowego** (A:13) — powietrze wyprowadzane na zewnatrz po odzysku ciepla
- **Temperatura zasilania obiegu grzewczego** (A:97) — temperatura wody w rurze zasilajacej obieg grzewczy (tylko WH4)
- **Temperatura powrotu obiegu grzewczego** (A:101) — temperatura wody w rurze powrotnej obiegu grzewczego (tylko WH4)

Dwa termostaty steruja nastawami temperatury powietrza nawiewanego:

- **Temperatura w trybie Home** (H:1155) — nastawa dla trybu Home, zakres 10-30°C
- **Temperatura w trybie Away** (H:1163) — nastawa dla trybu Away, zakres 10-30°C

### Zarzadzanie ciepla woda

**Tryb cieplej wody** (H:3017) wybiera strategie podgrzewania cieplej wody uzytkowej:

- **Comfort** — laduje zasobnik przy ok. 50% pozostalej cieplej wody, ponizej 15% uzywa elektrycznej grzalki rezerwowej
- **Economy** — najbardziej ekonomiczny tryb, laduje dopiero przy ok. 15% pozostalosci, bez elektrycznej grzalki rezerwowej

**Boost cieplej wody** (H:3019) uruchamia tymczasowa maksymalna produkcje cieplej wody za pomoca elektrycznej grzalki rezerwowej. Czas trwania jest konfigurowalny przez akcje serwisowa (0-300 minut).

### Monitorowanie pompy ciepla i systemu

Modul oferuje dziewiec atrybutow serwisowych do monitorowania stanu systemu:

- **Status pompy ciepla** (A:3028) — aktualna praca pompy ciepla: Gotowa, Odpowietrzanie, Rozruch, Normalna praca, Zatrzymanie, Odmrazanie, Gotowa przy bledzie, Reczna i Wymuszona praca
- **Stan cieplej wody uzytkowej** (A:3005) — stan produkcji cieplej wody: Comfort, Economy, Nie uzywana, Tymczasowy boost, Wymuszone ladowanie, Opoznienie Economy lub Zapobieganie legionelli
- **Stan wentylacji z odzyskiem ciepla** (A:3034) — odzwierciedla aktualny stan wentylacji w tym tryby niedostepne bezposrednio przez Tryb pracy (takie jak Okap i Kominek)
- **Tryb pracy instalacji pompy ciepla** (H:2061) — szczegolowy enum 17 stanow pokazujacy co pompa ciepla aktualnie robi (ladowanie zasobnika, ogrzewanie pomieszezen, ogrzewanie wentylacji, zapobieganie legionelli i tryby kombinowane)
- **Nagrzewnica wtorna pompy ciepla** (A:3029) — czy nagrzewnica wtorna jest aktywna
- **Ochrona przeciwmrozowa pompy ciepla** (A:3031) — czy ochrona przeciwmrozowa jest aktywna
- **Stan grzalki tacy skroplin** (A:3036) — czy grzalka tacy skroplin jest aktywna
- **Ostrzezenie o kamieniu pompy ciepla** (A:3037) — ostrzega gdy wykryto osadzanie sie kamienia
- **Pozycja przepustnicy pompy ciepla** (H:29) — pozycja przepustnicy w procentach

Dodatkowe atrybuty serwisowe sa dostepne na poszczegolnych urzadzeniach: predkosc wentylatora wyciagowego, polecenia przepustnic, predkosc obrotowego wymiennika ciepla, nastawa temperatury zasilania pompy ciepla, moc termiczna, predkosc pompy obiegu grzewczego i pozycja zaworu odbiorczego zasobnika.

### Zarzadzanie alarmami

Modul ReadScript monitoruje dwa kanaly alarmowe — **Alarm A** i **Alarm B**. Gdy alarm jest aktywny (stan = 2), TapHome raportuje go jako blad z wartoscia alarmu i stanem potwierdzenia (Potwierdzony/Niepotwierdzony/Zablokowany).

Trzy akcje serwisowe sa dostepne do zarzadzania alarmami:

- **Potwierdz Alarm A** — potwierdzenie niepotwierdzonego alarmu
- **Potwierdz Alarm B** — potwierdzenie niepotwierdzonego alarmu
- **Usun wszystkie nieaktywne alarmy** — usuwa wszystkie nieaktywne/potwierdzone alarmy z systemu

### Dodatkowe mozliwosci

EcoNordic obsluguje rowniez liczniki filtrow, obliczanie sprawnosci odzysku ciepla, monitorowanie predkosci wentylatora nawiewnego i regulacje krzywej grzewczej (WH4). Stan wentylacji z odzyskiem ciepla pokazuje dodatkowe tryby (Okap, Kominek, Tymczasowo wysoki) wykraczajace poza to, co bezposrednio oferuje sterowanie Trybem pracy. Te mozliwosci moga zostac dodane w przyszlej aktualizacji szablonu.

> [!TIP]
> EcoNordic dziala do **-25°C temperatury zewnetrznej** z pompa ciepla CO2. Obrotowy wymiennik ciepla zapewnia do 90% sprawnosci temperaturowej odzysku ciepla. Monitoruj roznice miedzy temperatura powietrza nawiewanego i wyciagowego, aby ocenic wydajnosc odzysku ciepla.

## Rozwiazywanie problemow

### Brak komunikacji Modbus

1. Sprawdz polaczenia kabla RS-485 miedzy TapHome a urzadzeniem EcoNordic
2. Potwierdz parametry komunikacji: **9600 baud, 8-E-1** (parzystosc Even, nie None)
3. Sprawdz, czy Slave ID w TapHome odpowiada konfiguracji urzadzenia (domyslnie: 1)
4. Upewnij sie, ze EcoNordic jest wlaczony i sprawny

### Czujniki obiegu grzewczego nie pokazuja danych (WH4)

Czujniki temperatury zasilania i powrotu obiegu grzewczego sa dostepne tylko w modelu **WH4**. W przypadku uzytkowania W4 (tylko wentylacja + ciepla woda) te czujniki nie beda raportowac wartosci.

### Alarmy raportowane w TapHome

1. Sprawdz szczegoly alarmu w atrybutach serwisowych TapHome — wyswietlana jest wartosc i stan alarmu
2. Uzyj akcji serwisowej **Potwierdz alarm** do potwierdzenia aktywnego alarmu
3. W celu interpretacji kodow alarmow sprawdz aplikacje Flexit GO lub instrukcje uzytkownika
4. Czeste przyczyny: zatkane filtry, zatrzymany wirnik, zadzialalala ochrona przed przegrzaniem, problemy z instalacja wodna

## Dostępne urządzenia 14

Te urządzenia pojawią się w TapHome po imporcie.

Flexit EcoNordic Moduł

Atrybuty serwisowe

|                                     |                                                                                                                                                                            |
|-------------------------------------|----------------------------------------------------------------------------------------------------------------------------------------------------------------------------|
| Status pompy ciepla                 | Stan pracy pompy ciepla — Gotowa, Odpowietrzanie, Rozruch, Normalna praca, Stop, Odmrazanie, Blad, Reczna, Wymuszony wentylator/pompa                                      |
| Stan cieplej wody uzytkowej         | Aktualny stan produkcji cieplej wody — Comfort, Economy, Nie uzywana, Boost, Wymuszone ladowanie, Zapobieganie legionelli                                                  |
| Stan wentylacji z odzyskiem ciepla  | Aktualny stan wentylacji — Wyl., Away, Home, High, Okap, Kominek, Tymczasowo wysoki                                                                                        |
| Tryb pracy instalacji pompy ciepla  | Tryb pracy instalacji pompy ciepla — pokazuje co pompa ciepla aktualnie robi (ladowanie zasobnika, ogrzewanie pomieszezen, ogrzewanie wentylacji, zapobieganie legionelli) |
| Nagrzewnica wtorna pompy ciepla     |                                                                                                                                                                            |
| Ochrona przeciwmrozowa pompy ciepla |                                                                                                                                                                            |
| Stan grzalki tacy skroplin          |                                                                                                                                                                            |
| Ostrzezenie o kamieniu pompy ciepla |                                                                                                                                                                            |
| Pozycja przepustnicy pompy ciepla   |                                                                                                                                                                            |

Akcje serwisowe

|                                  |
|----------------------------------|
| Usun wszystkie nieaktywne alarmy |
| Potwierdz Alarm A                |
| Potwierdz Alarm B                |

Odczyt (moduł)

```taphome
IF MODBUSR(A,3001, Uint16) = 2
ADDERROR(MODBUSR(A, 1021, float), "Alarm A: " + 
SWITCH(MODBUSR(A,3002, Uint16),
1, "Acknowledged, unlocked ",
2, "Unacknowledged",
3, "Locked",
"Unknown" ));
END

IF MODBUSR(A,3003, Uint16) = 2
ADDERROR(MODBUSR(A, 1023, float), "Alarm B: " + 
SWITCH(MODBUSR(A,3004, Uint16),
1, "Acknowledged, unlocked ",
2, "Unacknowledged",
3, "Locked",
"Unknown" ));
END
```

Atrybuty serwisowe

Heat Pump Status

```taphome
SWITCH(MODBUSR(A, 3028, Uint16), 
1, "Standby", 
2, "Air Purge process",
3, "Startup process",
4, "Normal operation",
5, "Stop process", 
6, "Defrost operation",
7, "Standby when error",
8, "Manual operation",
9, "Forced fan operation",
10, "Forced pump operation",
11, "State 10",
12, "State 11",
13, "State 12",
14, "State 13",
15, "State 14",
16, "State 15",
"Unknown"
)
```

Domestic hot water state

```taphome
SWITCH(MODBUSR(A, 3005, Uint16),
1, "Comfort",
2, "Economy", 
3, "Not in Use",
4, "Temporary Boost",
5, "Forced Charge",
6, "Economy delay",
7, "Legionella prevention",
"Unknown"
);
```

Heat recovery ventilation state

```taphome
SWITCH(MODBUSR(A, 3034, Uint16),
1, "Off", 
2 , "Away" , 
3 , "Home" , 
4 , "High", 
5 , "Fume hood", 
 6 , "Fireplace", 
 7 , "Temporary high",
 "Unknown");
```

Plant operating mode for heat pump

```taphome
SWITCH(MODBUSR(H, 2061, Uint16), 
1 , "Off" , 
2 , "Vent.heating from tank" , 
3 , "Load tank" ,
4 , "Load tank & vent.heating" ,
5 , "Space heating from tank" , 
6 , "Space heat.& vent.heat.from tank",
7 , "Load tank & space heat" , 
8 , "Load tank & space heat.& vent" , 
9 , "HP not available" , 
10 , "Swi-off delay flow through heat",
11 , "Legionella prev.vent.heat" , 
12 , "Legionella prev.space heat" , 
13 , "Space heat.with HP" ,
14 , "Space heat.& vent.with HP" , 
15 , "Load tank & space heat.with HP" , 
16 , "Load tank & vent.& space with HP", 
17 , "Legionella prev.tank",
"Unknown")
```

Heat Pump Reheating Coil

```taphome
Switch (MODBUSR(A, 3029, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat Pump Frost Protection

```taphome
Switch (MODBUSR(A, 3031, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Drain Pan Heater State

```taphome
Switch (MODBUSR(A, 3036, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat pump warning limescale

```taphome
Switch (MODBUSR(A, 3037, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat Pump Connection Dumper position

```taphome
MODBUSR(H, 29, Float, 2) + " %"
```

Akcje serwisowe

Remove All Inactive Alarms

```taphome
MODBUSW(H, 3004, Uint16, 3);
```

Acknowledge Alarm A

```taphome
MODBUSW(H, 3002, Uint16, 2)
```

Acknowledge Alarm B

```taphome
MODBUSW(H, 3003, Uint16, 2)
```

Przycisk Comfort Przełącznik Odczyt i zapis

Rejestr: H:2040 Bool

Wartości / Stany: Active · Inactive

Odczyt stanu przełącznika

```taphome
MODBUSR(H, 2040, Bool)
```

Zapis stanu przełącznika

```taphome
MODBUSW(H, 2040, Bool, St)
```

Temperatura powietrza wyrzutowego Czujnik temperatury Tylko do odczytu

Temperatura powietrza wyprowadzanego na zewnatrz po odzysku ciepla

Rejestr: A:13 Float Jednostka: °C numeric

Atrybuty serwisowe

|                                                           |
|-----------------------------------------------------------|
| Predkosc wentylatora wyciagowego                          |
| Polecenie przepustnicy powietrza wyrzutowego              |
| Polecenie przepustnicy powietrza wyrzutowego pompy ciepla |

Odczyt temperatury

```taphome
MODBUSR(A, 13, Float, 2)
```

Atrybuty serwisowe

Exhaust Air Fan Speed

```taphome
 ROUND(MODBUSR(H, 9, Float, 2)) + " %"
```

Exhaust Air Damper Command

```taphome
Switch (MODBUSR(H, 2010, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat pump exhaust air damper command

```

```

Temperatura powietrza wyciagowego Czujnik temperatury Tylko do odczytu

Temperatura powietrza wyciąganego z budynku przed odzyskiem ciepla

Rejestr: A:9 Float Jednostka: °C numeric

Atrybuty serwisowe

|                                                           |
|-----------------------------------------------------------|
| Polecenie przepustnicy powietrza wyrzutowego pompy ciepla |

Odczyt temperatury

```taphome
MODBUSR(A, 9, Float , 2)
```

Atrybuty serwisowe

Heat pump exhaust air damper command

```taphome
Switch (MODBUSR(H, 2064, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Temperatura zasilania obiegu grzewczego Czujnik temperatury Tylko do odczytu

Temperatura wody w rurze zasilajacej obieg grzewczy — tylko model WH4

Rejestr: A:97 Float Jednostka: °C numeric

Atrybuty serwisowe

|                                            |
|--------------------------------------------|
| Predkosc obrotowego wymiennika ciepla      |
| Nastawa temperatury zasilania pompy ciepla |
| Moc termiczna pompy ciepla                 |

Odczyt temperatury

```taphome
MODBUSR(A, 97, Float, 2)
```

Atrybuty serwisowe

Rotary heat exchanger speed

```taphome
 ROUND(MODBUSR(H, 1, Float, 2)) + " %"
```

Heat pump setpoint flow temperature

```taphome
MODBUSR(H, 73, Float, 2) + " °C"
```

Heat Pump Thermic Power Output

```taphome
MODBUSR(H, 65, Float, 2) + " kW"
```

Temperatura powrotu obiegu grzewczego Czujnik temperatury Tylko do odczytu

Temperatura wody w rurze powrotnej obiegu grzewczego — tylko model WH4

Rejestr: A:101 Float Jednostka: °C numeric

Odczyt temperatury

```taphome
MODBUSR(A, 101, Float, 2)
```

Boost cieplej wody Przełącznik wielowartościowy Odczyt i zapis

Tymczasowa maksymalna produkcja cieplej wody — Gotowy, Start, Stop

Rejestr: H:3019 UInt16 numeric

Wartości / Stany: Ready · Start · Stop

Akcje serwisowe

|                     |
|---------------------|
| Czas trwania boostu |

Odczyt stanu przełącznika

```taphome
MODBUSR(H, 3019, UInt16)
```

Zapis stanu przełącznika

```taphome
MODBUSWNE(H, 3019, UInt16, Mu)
```

Atrybuty serwisowe

Duration of boost

```taphome
MODBUSR(H, 1513, Uint32) + " min";
```

Akcje serwisowe

Duration of boost

Parametry: Duration \[0-300 min] (0–300 dur)

```taphome
MODBUSW(H, 1513, Uint32, dur);
```

Tryb cieplej wody Przełącznik wielowartościowy Odczyt i zapis

Strategia podgrzewania cieplej wody uzytkowej — Comfort (laduje przy 50%) lub Economy (laduje przy 15%)

Rejestr: H:3017 UInt16 numeric

Wartości / Stany: Comfort · Economy

Odczyt stanu przełącznika

```taphome
MODBUSR(H, 3017, UInt16)
```

Zapis stanu przełącznika

```taphome
MODBUSW(H, 3017, UInt16, Mu)
```

Atrybuty serwisowe

Heating circuit pump speed

```taphome
MODBUSR(H, 61, Float, 2) + " %"
```

Storage tank consumer valve position

```taphome
 ROUND(MODBUSR(H, 57, Float, 2)) + " %"
```

Tryb pracy Przełącznik wielowartościowy Odczyt i zapis

Tryb pracy wentylacji — Stop, Away, Home, High

Rejestr: H:2013 UInt16 numeric

Wartości / Stany: Stop · Away · Home · High

Odczyt stanu przełącznika

```taphome
MODBUSR(H, 2013, Uint16)
```

Zapis stanu przełącznika

```taphome
MODBUSW(H, 2013, Uint16, Mu)
```

Temperatura powietrza zewnetrznego Czujnik temperatury Tylko do odczytu

Rejestr: A:1 Float Jednostka: °C numeric

Odczyt temperatury

```taphome
MODBUSR(A, 1, Float)
```

Temperatura powietrza nawiewanego Czujnik temperatury Tylko do odczytu

Temperatura swiezego powietrza dostarczanego do budynku po odzysku ciepla i dogrzewaniu

Rejestr: A:5 Float Jednostka: °C numeric

Odczyt temperatury

```taphome
MODBUSR(A, 5, Float, 2)
```

Temperatura w trybie Away Termostat Odczyt i zapis

Nastawa temperatury powietrza nawiewanego dla trybu Away (10-30°C)

Rejestr: H:1163 Float Jednostka: °C numeric

Odczyt temperatury zadanej

```taphome
MODBUSR(H, 1163, Float, 2)
```

Zapis temperatury zadanej

```taphome
MODBUSW(H, 1163, Float, Se)
```

Temperatura w trybie Home Termostat Odczyt i zapis

Nastawa temperatury powietrza nawiewanego dla trybu Home (10-30°C)

Rejestr: H:1155 Float Jednostka: °C numeric

Odczyt temperatury zadanej

```taphome
MODBUSR(H, 1155, Float, 2)
```

Zapis temperatury zadanej

```taphome
MODBUSW(H, 1155, Float, Se)
```

Wentylacja kominkowa Przełącznik wielowartościowy Odczyt i zapis

Aktywuje tryb nadcisnienia, aby zapobiec wnikaniu dymu przy rozpalaniu kominka — Gotowy, Uruchom

Rejestr: H:3007 UInt16 numeric

Wartości / Stany: Ready · Trigger

Akcje serwisowe

|                                  |
|----------------------------------|
| Czas pracy wentylacji kominkowej |

Odczyt stanu przełącznika

```taphome
MODBUSR(H, 3007,UInt16)
```

Zapis stanu przełącznika

```taphome
MODBUSWNE(H, 3007, UInt16, Mu)
```

Atrybuty serwisowe

Fireplace Ventilation Runtime

```taphome
MODBUSR(H, 1105, Uint32) + " min"
```

Akcje serwisowe

Fireplace Ventilation Runtime

Parametry: duration \[0 - 360 min] (0–360 dur)

```taphome
MODBUSW(H, 1105, Uint32, dur)
```

Szybka wentylacja Przełącznik wielowartościowy Odczyt i zapis

Tymczasowa wentylacja o duzej predkosci dla szybkiej wymiany powietrza — Gotowy, Uruchom

Rejestr: H:3006 UInt16 numeric

Wartości / Stany: Ready · Trigger

Akcje serwisowe

|                                |
|--------------------------------|
| Czas pracy szybkiej wentylacji |

Odczyt stanu przełącznika

```taphome
MODBUSR(H, 3006, UInt16)
```

Zapis stanu przełącznika

```taphome
MODBUSWNE(H, 3006, UInt16, Mu)
```

Atrybuty serwisowe

Rapid ventilation runtime

```taphome
MODBUSR(H, 1103, Uint32) + " min"
```

Akcje serwisowe

Rapid Ventilation Runtime

Parametry: Duration \[1-360 min] (1–360 dur)

```taphome
MODBUSW(H, 1103, Uint32, dur)
```

**Połączenie:** Modbus RTU • 9600 baud• 8E1 • Slave ID: $\[SlaveId]

Możliwe ulepszenia (7)

- pyflexit CI66 Register Map (Nordic S2–S4, CL2–CL4) — Complete CI66 adapter register map (addresses 0–48) for Nordic models — NOT applicable to EcoNordic which uses proprietary registers
- H:2013 value 5+ Fume Hood and Calendar Modes — Heat Recovery Ventilation State shows values 5=Fume hood, 6=Fireplace, 7=Temporary high — but Operating Mode (H:2013) only exposes Stop/Away/Home/High (1–4). Fume hood may require separate trigger register
- unknown Filter Timer / Filter Alarm — CI66 has filter operating hours (reg 8), filter alarm (reg 27), filter alarm period (reg 46). EcoNordic likely has equivalent registers but they are not in the XML template
- unknown Heat Recovery Efficiency — CI66 exposes heat recovery percentage (0–100%). EcoNordic may have equivalent register — can be calculated from supply/extract/outside temperatures
- unknown Supply Air Fan Speed — Exhaust fan speed is exposed (H:9) but supply fan speed is missing from the template. EcoNordic likely has this register
- unknown Heating Circuit Setpoint Temperature — WH4 heating set value and parallel shift for the heat curve — not exposed in the template
- doc 2882 (404) Full EcoNordic Modbus Register Map — Official Flexit Modbus EcoNordic Basic XLSX register map returned 404 — may contain additional registers not in the XML template

## Parametry importu

Te wartości podajesz podczas importu pliku XML.

| Pytanie w aplikacji | Domyślnie     |
|---------------------|---------------|
| Slave ID            | `1`           |
| Adres IP            | `192.168.1.0` |

## Źródła

- pyflexit — Flexit Modbus Python Library (register map)
  
  [github.com](https://github.com/Sabesto/pyflexit) 2026-03-20
- Home Assistant Flexit Integration
  
  [www.home-assistant.io](https://www.home-assistant.io/integrations/flexit/) 2026-03-20
- EcoNordic WH4/W4 User Manual (116927EN-07)
  
  [assets.ctfassets.net](http://assets.ctfassets.net/wzjhf3pmxyuk/1woGygq1Dvw0xDHElh4Sss/ce551d1f9cc20887831301048b1c2dce/EcoNordic_WH4_-_W4_Vartotojo_instrukcija_EN.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/flexit-econordic/manufacturer/econordic-user-manual.pdf)
- EcoNordic WH4 Product Data Sheet (117290EN-01)
  
  [nit.lt](https://nit.lt/wp-content/uploads/2019/02/flexit-EcoNordic-WH4-eng.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/flexit-econordic/manufacturer/econordic-assembly-manual.pdf)

Dokumenty producentów są © ich właścicieli. Udostępniamy je w formie opublikowanej przez producenta, wyłącznie w celach informacyjnych.

## Powiązana dokumentacja

- [Modbus Integration](https://taphome.com/pl/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/pl/docs/integration/modbus/)
- [Prosta konfiguracja za pomocą szablonów](https://taphome.com/pl/docs/integration/modbus/templates/)
- [Skrypty Modbus i prefetch](https://taphome.com/pl/docs/script/modbus-scripts/)
- [Funkcje Modbus](https://taphome.com/pl/docs/script/modbus/)
- [Typy danych Modbus](https://taphome.com/pl/docs/script/modbus-data-types/)