  questions: ["Come integrare l'inverter Sofar Solar HYD KTL-3PH con TapHome?","Cosa monitora il template TapHome per Sofar Solar HYD KTL-3PH?","Come collegare il Sofar Solar HYD KTL-3PH tramite RS-485 a TapHome?","Come cablare più inverter Sofar Solar su un singolo bus RS-485?","Quali parametri della batteria legge il template TapHome per Sofar Solar?","Come monitorare la produzione FV e l'energia di rete con TapHome?"]
---

# Sofar Solar HYD KTL-3PH

Comunicazione: Modbus RTU

- [Sito ufficiale Sofar Solar](https://www.sofarsolar.com)

## Guida all'integrazione

Il Sofar Solar HYD 5/6/8/10/15/20KTL-3PH è una serie di inverter ibridi trifase che combinano la produzione fotovoltaica con l'accumulo di energia a batteria. TapHome si connette tramite Modbus RTU su RS-485 utilizzando il connettore COM a 16 pin dell'inverter, leggendo i registri holding per la potenza FV in tempo reale, lo stato della batteria, la potenza di rete, le tensioni per fase e i contatori energetici.

L'inverter supporta fino a 31 dispositivi su un singolo bus RS-485 con cablaggio daisy-chain. Ogni inverter richiede un Modbus Slave ID univoco (configurabile, predefinito 1). I parametri di comunicazione sono fissi: 9600 baud, 8N1.

## Connessione hardware

### Interfacce di comunicazione

![Posizione delle interfacce di comunicazione Sofar Solar HYD KTL-3PH](https://taphome.com/images/compatibility/sofarsolar-inverter-3p/communication-interfaces_hu_5a569478a95349ec.jpg)

La connessione RS-485 per il monitoraggio TapHome utilizza la **porta COM** — un connettore multifunzionale a 16 pin nella parte inferiore dell'inverter.

### Pinout della porta COM

![Pinout del connettore COM a 16 pin del Sofar Solar HYD KTL-3PH](https://taphome.com/images/compatibility/sofarsolar-inverter-3p/com-port-pinout_hu_1534b25dbbb0b858.jpg)

**Pin rilevanti per la connessione TapHome:**

| Pin | Funzione | Nota |
|-----|----------|------|
| **1** | RS485A1-1 (+) | Segnale RS-485 A di monitoraggio/controllo |
| **2** | RS485A1-2 (+) | Secondo connettore per daisy-chain |
| **3** | RS485B1-1 (-) | Segnale RS-485 B |
| **4** | RS485B1-2 (-) | Secondo connettore per daisy-chain |
| 5 | RS485A2 (+) | Smart meter — bus separato |
| 6 | RS485B2 (-) | Smart meter — bus separato |
| 7 | CAN0_H | Comunicazione BMS (CAN) |
| 8 | CAN0_L | Comunicazione BMS (CAN) |

Collega TapHome ai **pin 1+3** (o 2+4):
- **Pin 1 (RS485A1)** → A+/D+ sull'RS-485 di TapHome
- **Pin 3 (RS485B1)** → B-/D- sull'RS-485 di TapHome

> [!WARNING]
> **Non utilizzare i pin 5+6** — sono dedicati allo smart meter su un bus RS-485 separato. TapHome deve essere collegato ai pin 1+3 (o 2+4) per il monitoraggio Modbus.

### Cablaggio RS-485 daisy-chain

![Cablaggio RS-485 daisy-chain per più inverter Sofar Solar](https://taphome.com/images/compatibility/sofarsolar-inverter-3p/wiring-rs485-daisy-chain_hu_1365fa6dd95340c6.jpg)

Quando si collegano più inverter, cablarli in daisy-chain sul bus RS-485. Posizionare un **resistore di terminazione da 120 Ohm** tra il Pin 1 e il Pin 4 sul primo e sull'ultimo dispositivo del bus.

**Specifiche del cavo:**
- Tipo: Doppino intrecciato schermato, sezione rame > 0,5 mm²
- Lunghezza massima: **1200 m**
- Mantenere i cavi lontano dai cavi di potenza e dai campi elettrici

## Configurazione

### Parametri di comunicazione Modbus

I parametri di comunicazione RS-485 sono fissi e non richiedono configurazione sul lato inverter:

| Parametro | Valore |
|-----------|--------|
| Baud rate | 9600 bps |
| Bit di dati | 8 |
| Parità | Nessuna |
| Bit di stop | 1 |
| Slave ID | 1 (predefinito, configurabile 1–31) |

Con più inverter sullo stesso bus, ciascuno deve avere uno Slave ID univoco. Lo Slave ID può essere configurato tramite il menu LCD dell'inverter o l'app SolarMAN.

## Funzionalità del dispositivo

### Monitoraggio batteria

Il template fornisce il monitoraggio dello stato di carica (SOC) per un massimo di due pacchi batteria. Il SOC Batteria 1 è disponibile su tutti i modelli HYD KTL-3PH, il SOC Batteria 2 sui modelli HYD 10–20KTL-3PH con ingresso batteria duale.

Ogni dispositivo SOC batteria include cinque attributi di servizio per la diagnostica dettagliata: temperatura, tensione, corrente di carica/scarica, potenza di carica/scarica e stato di salute (SOH).

Due dispositivi contatore energia tracciano la carica e la scarica giornaliera della batteria in kWh, ciascuno con un attributo di servizio per il totale a vita.

### Monitoraggio produzione FV

Il template legge la potenza da un massimo di tre stringhe FV individuali (PV1, PV2, PV3), ciascuna con attributi di servizio per tensione e corrente della stringa. Un dispositivo combinato PV Power Total mostra la potenza aggregata di tutte le stringhe.

Due dispositivi contatore energia tracciano la produzione FV — totali giornalieri e a vita in kWh.

### Energia di rete e carico

Tre dispositivi contatore energia forniscono letture giornaliere per l'interazione con la rete e il consumo del carico:
- **Energy Purchase Today** — energia acquistata dalla rete (kWh)
- **Energy Selling Today** — energia venduta alla rete (kWh)
- **Load Consumption Today** — consumo totale del carico (kWh)

Ogni contatore giornaliero include un attributo di servizio con il totale a vita.

### Monitoraggio uscita AC

Il template fornisce tre dispositivi di tensione per fase (fase R/S/T, corrispondenti a L1/L2/L3), ciascuno con un attributo di servizio per la corrente di fase. La frequenza di rete è riportata in Hz.

Due dispositivi di potenza monitorano l'uscita dell'inverter in diversi punti di misura:
- **Total Active Power Output** — potenza attiva in uscita dall'inverter in kW, con attributi di servizio per la potenza reattiva (kVAR) e la potenza apparente (kVA)
- **Total Active Power PCC** — potenza al punto di connessione comune (punto di connessione alla rete) in kW, con attributi di servizio per potenza reattiva e apparente. Questa misura viene utilizzata per la limitazione dell'immissione in rete e le funzioni del regolatore di centrale.

### Attributi di servizio del modulo

Il modulo espone tre attributi di servizio per la diagnostica dell'inverter:
- **Product Code** — identificazione del prodotto inverter
- **System State** — stato operativo corrente: In attesa, Rilevamento, Connesso alla rete, Alimentazione di emergenza, Guasto recuperabile, Guasto permanente, Aggiornamento o Auto-ricarica
- **Ambient Temperature** — temperatura interna dell'inverter in °C

Il modulo ReadScript monitora anche tre registri bitmask di errore (H:0x0405–H:0x0407), che riportano guasti di protezione della rete, errori di campionamento e guasti hardware come errori in TapHome.

### Funzionalità aggiuntive

Gli inverter HYD KTL-3PH espongono anche registri per l'accensione/spegnimento remoto, la selezione della modalità di accumulo energia (Autoconsumo, Fasce orarie, Temporizzazione, Passivo, Taglio dei picchi, Isola) e il controllo passivo di carica/scarica batteria per sistemi di gestione energetica esterni. Potenza attiva per fase e fattore di potenza, monitoraggio uscita isola/EPS, ingressi stringa FV aggiuntivi (PV4+), conteggi cicli batteria, temperatura del dissipatore e parametri per le batterie 3–6 sono anch'essi disponibili tramite Modbus. Questi possono essere aggiunti in un futuro aggiornamento del template.

> [!TIP]
> I registri della modalità passiva (H:0x1110 e H:0x1187) consentono il controllo Modbus esterno della potenza di carica/scarica della batteria. Questo è particolarmente utile per le smart rule di TapHome per implementare strategie di gestione energetica come la ricarica delle batterie durante i periodi a tariffa bassa.

## Risoluzione dei problemi

### Nessuna comunicazione Modbus

1. Verificare che il cavo RS-485 sia collegato ai **pin 1+3** (o 2+4) sulla porta COM — non ai pin 5+6 (bus smart meter)
2. Controllare la polarità del cavo: Pin 1 (A+) a TapHome A+, Pin 3 (B-) a TapHome B-
3. Confermare che TapHome è configurato per 9600 baud, nessuna parità, 1 bit di stop
4. Verificare che lo Slave ID corrisponda tra inverter e TapHome
5. Controllare il resistore di terminazione da 120 Ohm sul primo e ultimo dispositivo del bus

### Errori di comunicazione intermittenti

1. Assicurarsi che il cavo RS-485 sia un doppino intrecciato schermato con sezione rame > 0,5 mm²
2. Mantenere i cavi RS-485 lontano dai cavi di potenza e dal cablaggio DC
3. Verificare che la lunghezza totale del bus non superi 1200 m
4. Assicurarsi che non ci siano Slave ID duplicati sul bus

### System State mostra un guasto

1. Controllare l'attributo di servizio System State per il codice di stato specifico (4 = Guasto recuperabile, 5 = Guasto permanente)
2. Esaminare i dettagli dei registri di errore nella diagnostica di servizio TapHome — il template legge tre registri bitmask di errore che coprono protezione della rete, errori di campionamento e guasti hardware
3. Consultare il display LCD dell'inverter o l'app SolarMAN per i codici di errore dettagliati

## Dispositivi disponibili 19

Questi dispositivi compaiono in TapHome dopo l'importazione.

Sofar Solar HYD KTL-3PH Modulo

Attributi di servizio

|                      |                                                                                                                                                                              |
|----------------------|------------------------------------------------------------------------------------------------------------------------------------------------------------------------------|
| Codice prodotto      |                                                                                                                                                                              |
| Stato del sistema    | Stato operativo dell'inverter — In attesa, Rilevamento, Connesso alla rete, Alimentazione di emergenza, Guasto recuperabile, Guasto permanente, Aggiornamento, Auto-ricarica |
| Temperatura ambiente | Temperatura interna dell'inverter in °C                                                                                                                                      |

Lettura (modulo)

```taphome
#fault 1
var fault :=MODBUSR(H, 0x0405, Uint16);
IF fault !=0 
IF(GETBIT(fault, 0) != 0, ADDERROR("Grid over-voltage"));
IF(GETBIT(fault, 1) != 0, ADDERROR("Grid undervoltage"));
IF(GETBIT(fault, 2) != 0, ADDERROR("Grid overfrequency"));
IF(GETBIT(fault, 3) != 0, ADDERROR("Grid underfrequency"));
IF(GETBIT(fault, 4) != 0, ADDERROR("Leakage current fault"));
IF(GETBIT(fault, 5) != 0, ADDERROR("High penetration error"));
IF(GETBIT(fault, 6) != 0, ADDERROR("Low penetration error"));
IF(GETBIT(fault, 7) != 0, ADDERROR("Islanding error"));
IF(GETBIT(fault, 8) != 0, ADDERROR("Grid voltage transient value overvoltage 1"));
IF(GETBIT(fault, 9) != 0, ADDERROR("Grid voltage transient value overvoltage 2"));
IF(GETBIT(fault, 10) != 0, ADDERROR("Grid line voltage error"));
IF(GETBIT(fault, 11) != 0, ADDERROR("Inverter voltage error"));
IF(GETBIT(fault, 12) != 0, ADDERROR("Anti-backflow overload"));
END

#fault 2
fault :=MODBUSR(H, 0x0406, Uint16);
IF fault !=0 
IF(GETBIT(fault, 0) != 0, ADDERROR("Grid current sampling error"));
IF(GETBIT(fault, 1) != 0, ADDERROR("Grid current DC component sampling error (AC side)"));
IF(GETBIT(fault, 2) != 0, ADDERROR("Grid voltage sampling error (DC side)"));
IF(GETBIT(fault, 3) != 0, ADDERROR("Grid voltage sampling error (AC side)"));
IF(GETBIT(fault, 4) != 0, ADDERROR("Leakage current sampling error (DC side)"));
IF(GETBIT(fault, 5) != 0, ADDERROR("Leakage current sampling error (AC side)"));
IF(GETBIT(fault, 6) != 0, ADDERROR("Load voltage DC component sampling error"));
IF(GETBIT(fault, 7) != 0, ADDERROR("DC input current sampling error"));
IF(GETBIT(fault, 8) != 0, ADDERROR("DC component sampling error of grid current (DC side)"));
IF(GETBIT(fault, 9) != 0, ADDERROR("DC input branch current sampling error"));
IF(GETBIT(fault, 12) != 0, ADDERROR("Leakage current consistency error"));
IF(GETBIT(fault, 13) != 0, ADDERROR("Grid voltage consistency error"));
IF(GETBIT(fault, 14) != 0, ADDERROR("DCI consistency error"));
END

#fault 3
fault :=MODBUSR(H, 0x0407, Uint16);
IF fault !=0 
IF(GETBIT(fault, 0) != 0, ADDERROR("SPI communication error (DC side)"));
IF(GETBIT(fault, 1) != 0, ADDERROR("SPI communication error (AC side)"));
IF(GETBIT(fault, 2) != 0, ADDERROR("Chip error (DC side)"));
IF(GETBIT(fault, 3) != 0, ADDERROR("Chip error (AC side)"));
IF(GETBIT(fault, 4) != 0, ADDERROR("Auxiliary power error"));
IF(GETBIT(fault, 5) != 0, ADDERROR("Inverter soft start failure"));
IF(GETBIT(fault, 8) != 0, ADDERROR("Relay detection failure"));
IF(GETBIT(fault, 9) != 0, ADDERROR("Low insulation impedance"));
IF(GETBIT(fault, 10) != 0, ADDERROR("Grounding error"));
IF(GETBIT(fault, 11) != 0, ADDERROR("Input mode setting error"));
IF(GETBIT(fault, 12) != 0, ADDERROR("CT error"));
IF(GETBIT(fault, 13) != 0, ADDERROR("Input reversal error"));
IF(GETBIT(fault, 14) != 0, ADDERROR("Parallel error"));
IF(GETBIT(fault, 15) != 0, ADDERROR("Serial number error"));
END
```

Attributi di servizio

Product Code

```taphome
MODBUSR(H, 0x2000, Uint16);
```

System State

```taphome
SWITCH(MODBUSR(H, 0x0404, Uint16),
0, "Waiting",
1, "Detection",
2, "Grid-connected",
3, "Emergency power supply",
4, "Recoverable fault",
5, "Permanent fault",
6, "Upgrade",
7, "Self-charging",
"Fault")
```

Ambient Temperature

```taphome
MODBUSR(H, 0x0418, Int16) + "°C";
```

Batteria 1 SOC Ingresso analogico Solo lettura

Stato di carica batteria 1 in percentuale — include attributi di servizio per temperatura, tensione, corrente, potenza e SOH

Registro: H:0x0608 Uint16 Unità: % numeric

Attributi di servizio

|             |
|-------------|
| Temperatura |
| Tensione    |
| Corrente    |
| Potenza     |
| SOH         |

Lettura livello ingresso

```taphome
MODBUSR(H, 0x0608, Uint16)
```

Attributi di servizio

Temperature

```taphome
MODBUSR(H, 0x0607, Int16) + "°C";
```

Voltage

```taphome
MODBUSR(H, 0x0604, Uint16) + " V";
```

Current

```taphome
MODBUSR(H, 0x0605, Int16)/100 + " A";
```

Power

```taphome
MODBUSR(H, 0x0606, Int16)/100 + " kW";
```

SOH

```taphome
MODBUSR(H, 0x0609, Uint16) + " %";
```

Batteria 2 SOC Ingresso analogico Solo lettura

Stato di carica batteria 2 in percentuale — disponibile sui modelli HYD 10–20KTL-3PH con ingresso batteria duale

Registro: H:0x060F Uint16 Unità: % numeric

Attributi di servizio

|             |
|-------------|
| Temperatura |
| Tensione    |
| Corrente    |
| Potenza     |
| SOH         |

Lettura livello ingresso

```taphome
MODBUSR(H, 0x060F, uint16)
```

Attributi di servizio

Temperature

```taphome
MODBUSR(H, 0x060E, Int16) + " °C";
```

Voltage

```taphome
MODBUSR(H, 0x060B, Uint16) + " V";
```

Current

```taphome
MODBUSR(H, 0x060C, Int16) + " A";
```

Power

```taphome
MODBUSR(H, 0x060D, Int16) + " kW";
```

SOH

```taphome
MODBUSR(H, 0x0610, Uint16) + " %";
```

Scarica batteria oggi Variabile Solo lettura

Energia giornaliera di scarica batteria in kWh — include il totale a vita

Registro: H:0x0698 Uint32 Unità: kWh numeric

Attributi di servizio

|                         |
|-------------------------|
| Scarica batteria totale |

Lettura

```taphome
MODBUSR(H, 0x0698, Uint32)/100
```

Attributi di servizio

Battery Discharge Total

```taphome
MODBUSR(H, 0x069A, Uint32)/10
```

Carica batteria oggi Variabile Solo lettura

Energia giornaliera di carica batteria in kWh — include il totale a vita

Registro: H:0x0694 Uint32 Unità: kWh numeric

Attributi di servizio

|                        |
|------------------------|
| Carica batteria totale |

Lettura

```taphome
MODBUSR(H, 0x0694, Uint32)/100
```

Attributi di servizio

Battery Charge Total

```taphome
MODBUSR(H, 0x0696, Uint32)/10
```

Acquisto energia oggi Variabile Solo lettura

Energia giornaliera acquistata dalla rete in kWh — include il totale a vita

Registro: H:0x068C Uint32 Unità: kWh numeric

Attributi di servizio

|                         |
|-------------------------|
| Acquisto energia totale |

Lettura

```taphome
MODBUSR(H, 0x068C, Uint32)/100
```

Attributi di servizio

Energy Purchase Total

```taphome
MODBUSR(H, 0x068E, Uint32)/10 + " kWh"
```

Vendita energia oggi Variabile Solo lettura

Energia giornaliera venduta alla rete in kWh — include il totale a vita

Registro: H:0x0690 Uint32 Unità: kWh numeric

Attributi di servizio

|                        |
|------------------------|
| Vendita energia totale |

Lettura

```taphome
MODBUSR(H, 0x0690, Uint32)/100
```

Attributi di servizio

Energy Selling Total

```taphome
MODBUSR(H, 0x0692, Uint32)/10
```

Frequenza di rete Variabile Solo lettura

Registro: H:0x0484 UInt16 Unità: Hz numeric

Lettura

```taphome
MODBUSR(H, 0x484, UInt16)/100
```

Consumo carico oggi Variabile Solo lettura

Consumo giornaliero del carico in kWh — include il totale a vita

Registro: H:0x0688 Int32 Unità: kWh numeric

Attributi di servizio

|                       |
|-----------------------|
| Consumo carico totale |

Lettura

```taphome
MODBUSR(H, 0x0688, Int32)/100
```

Attributi di servizio

Load Consumption Total

```taphome
MODBUSR(H, 0x068A, Int32)/100 + "kWh"
```

Potenza FV totale Variabile Solo lettura

Potenza combinata di tutte le stringhe FV in kW

Registro: H:0x05C4 Uint16 Unità: kW numeric

Lettura

```taphome
MODBUSR(H, 0x05C4, Uint16)/10
```

PV1 potenza Variabile Solo lettura

Registro: H:0x0586 Uint16 Unità: kW numeric

Attributi di servizio

|          |
|----------|
| Tensione |
| Corrente |

Lettura

```taphome
MODBUSR(H, 0x0586, Uint16)/100
```

Attributi di servizio

Voltage

```taphome
MODBUSR(H, 0x0584, Uint16)/10 + " V";
```

Current

```taphome
MODBUSR(H, 0x0585, Uint16)/100 + " A";
```

PV2 potenza Variabile Solo lettura

Registro: H:0x0589 Uint16 Unità: kW numeric

Attributi di servizio

|          |
|----------|
| Tensione |
| Corrente |

Lettura

```taphome
MODBUSR(H, 0x0589, Uint16)/100
```

Attributi di servizio

Voltage

```taphome
MODBUSR(H, 0x0587, Uint16)/10 + " V";
```

Current

```taphome
MODBUSR(H, 0x0588, Uint16)/100 + " A";
```

PV3 potenza Variabile Solo lettura

Registro: H:0x058A Uint16 Unità: kW numeric

Attributi di servizio

|          |
|----------|
| Tensione |
| Corrente |

Lettura

```taphome
MODBUSR(H, 0x058A, Uint16)/100
```

Attributi di servizio

Voltage

```taphome
MODBUSR(H, 0x058A, Uint16)/10 + " V";
```

Current

```taphome
MODBUSR(H, 0x058B, Uint16)/100 + " A"
```

Produzione FV oggi Variabile Solo lettura

Produzione FV giornaliera in kWh

Registro: H:0x0684 Int32 Unità: kWh numeric

Lettura

```taphome
MODBUSR(H, 0x0684, Int32)/100
```

Produzione FV totale Variabile Solo lettura

Produzione FV totale a vita in kWh

Registro: H:0x0686 Int32 Unità: kWh numeric

Lettura

```taphome
MODBUSR(H, 0x0686, Int32)/100
```

Tensione fase R Variabile Solo lettura

Tensione di rete fase L1/R in V — include attributo di servizio per la corrente di fase

Registro: H:0x048D Uint16 Unità: V numeric

Attributi di servizio

|            |
|------------|
| Corrente R |

Lettura

```taphome
MODBUSR(H, 0x048D, Uint16)/10
```

Attributi di servizio

Current R

```taphome
MODBUSR(H, 0x048E, Uint16)/100 + " A";
```

Tensione fase S Variabile Solo lettura

Tensione di rete fase L2/S in V — include attributo di servizio per la corrente di fase

Registro: H:0x0498 Uint16 Unità: V numeric

Attributi di servizio

|            |
|------------|
| Corrente S |

Lettura

```taphome
MODBUSR(H, 0x0498, Uint16)/10
```

Attributi di servizio

Current S

```taphome
MODBUSR(H, 0x0499, Uint16)/100 + " A"
```

Tensione fase T Variabile Solo lettura

Tensione di rete fase L3/T in V — include attributo di servizio per la corrente di fase

Registro: H:0x04A3 Uint16 Unità: V numeric

Attributi di servizio

|            |
|------------|
| Corrente T |

Lettura

```taphome
MODBUSR(H, 0x04A3, Uint16)/10
```

Attributi di servizio

Current T

```taphome
MODBUSR(H, 0x04A4, Uint16)/100 + " A"
```

Potenza attiva totale in uscita Variabile Solo lettura

Potenza attiva totale in uscita dall'inverter in kW — include potenza reattiva e apparente

Registro: H:0x0485 Int16 Unità: kW numeric

Attributi di servizio

|                             |
|-----------------------------|
| Potenza reattiva in uscita  |
| Potenza apparente in uscita |

Lettura

```taphome
MODBUSR(H, 0x0485, Int16)/100
```

Attributi di servizio

Reactive Power Output

```taphome
MODBUSR(H, 0x0486, Int16)/100 + " kW" ;
```

Apparent Power Output

```taphome
MODBUSR(H, 0x0487, Int16)/100 + " kW" ;
```

Potenza attiva totale PPC Variabile Solo lettura

Potenza attiva al punto di connessione comune (punto di connessione alla rete) in kW — utilizzata per la limitazione dell'immissione

Registro: H:0x0488 Int16 Unità: kW numeric

Attributi di servizio

|                       |
|-----------------------|
| Potenza reattiva PPC  |
| Potenza apparente PPC |

Lettura

```taphome
MODBUSR(H, 0x0488, Int16)/100
```

Attributi di servizio

Reactive Power PPC

```taphome
MODBUSR(H, 0x0489, Int16)/100 + " kW" ;
```

Apparent Power PPC

```taphome
MODBUSR(H, 0x048A, Int16)/100 + " kW" ;
```

**Connessione:** Modbus RTU • 9600 baud• 8N1 • Slave ID: $\[SlaveId]

Possibili miglioramenti (12)

- H:0x1104 Remote Switch On/Off — Remote inverter on/off control — useful for TapHome automation
- H:0x1110 Energy Storage Mode — Operating mode selection: Self-use, Time-of-Use, Timing, Passive, Peak Shaving, Off-grid
- H:0x1187 Passive Battery Charge/Discharge — S32, external Modbus control of battery charge/discharge power — enables TapHome smart rule energy management
- H:0x0200 Running State — 0=Wait, 1=CheckState, 2=Normal, 3=CheckDischarge, 4=Discharge, 5=EPS, 6=Fault, 7=Permanent — older register range, covered by H:0x0404 System State in module
- H:0x0504 Off-Grid Active Power — EPS/backup output power (S16, 0.01 kW) — relevant for off-grid/backup scenarios
- H:0x050A-0x0522 Off-Grid Per-Phase Voltage/Current/Power — L1/L2/L3 off-grid output monitoring — 9 registers for 3-phase EPS output
- H:0x0507 Off-Grid Frequency — EPS output frequency (U16, 0.01 Hz)
- H:0x048F-0x04A7 Per-Phase Active/Reactive Power and Power Factor — L1/L2/L3 individual active power, reactive power, and power factor — template only reads voltage+current per phase
- H:0x058D-0x058F PV4 Voltage/Current/Power — PV string 4 input — template supports up to PV3. HA integration supports up to PV10
- H:0x0612-0x0627 Battery 3–6 Parameters — Additional battery packs (voltage, current, power, temperature, SOC, SOH, cycles) — template supports battery 1–2 only
- H:0x022C Battery Cycle Count — Battery cycle times (Uint16, 0–65536) — available at 0x060A per battery in HA integration
- H:0x0419 Heatsink Temperature — Inverter heatsink temperature (S16, °C) — template reads inner temperature (0x0418) only

## Parametri di importazione

Inserisci questi valori quando importi l'XML.

| Richiesto nell'app | Predefinito   |
|--------------------|---------------|
| Slave ID           | `1`           |
| Indirizzo IP       | `192.168.1.0` |

## Fonti

- SOFARSOLAR ModBus-RTU Communication Protocol
  
  [community.openenergymonitor.org](https://community.openenergymonitor.org/uploads/short-url/dF8j79PsvtCS0xQ5aPxHXO4HZDE.pdf) 2026-03-28
  
  [PDF](https://taphome.com/compatibility/devices/sofarsolar-inverter-3p/manufacturer/sofarsolar-modbus-rtu-protocol.pdf)
- HYD 5/6/8/10/15/20KTL-3PH User Manual
  
  [www.sofarsolar.com](https://www.sofarsolar.com/upload/file/20240321/1710982866939025487.pdf) 2026-03-28
  
  [PDF](https://taphome.com/compatibility/devices/sofarsolar-inverter-3p/manufacturer/hyd-5-20ktl-3ph-user-manual.pdf)
- Home Assistant SolaX/Sofar Modbus Integration
  
  [github.com](https://github.com/wills106/homeassistant-solax-modbus) 2026-03-28

I documenti del produttore sono © dei rispettivi proprietari. Sono forniti così come pubblicati dal produttore, solo a titolo informativo.

## Documentazione correlata

- [Modbus Integration](https://taphome.com/it/compatibility/modbus-guide/)
- [Modbus - Configurazione](https://taphome.com/it/docs/integration/modbus/)
- [Configurazione semplice utilizzando modelli](https://taphome.com/it/docs/integration/modbus/templates/)
- [Script Modbus e prefetch](https://taphome.com/it/docs/script/modbus-scripts/)
- [Funzioni Modbus](https://taphome.com/it/docs/script/modbus/)
- [Tipi di dati Modbus](https://taphome.com/it/docs/script/modbus-data-types/)