  questions: ["Hogyan integrálható a Wattsonic Gen3 hibrid inverter a TapHome-mal?","Mit figyel és vezérel a Wattsonic G3 TapHome sablon?","Hogyan csatlakoztatható a Wattsonic G3 inverter RS-485-ön a TapHome-hoz?","Mi a különbség a Wattsonic G3 és a WTS regiszter-címek között?","Hogyan korlátozható a hálózati export teljesítmény Wattsonic G3-on a TapHome-on keresztül?","Hogyan engedélyezhető az EPS/UPS backup a Wattsonic G3-on Modbus-on keresztül?"]
---

# Wattsonic Hybrid Inverter G3

Kommunikáció: Modbus RTU

- [Wattsonic hivatalos weboldal](https://www.wattsonic.com)

A Wattsonic Hybrid Inverter G3 egy Gen3 Li-HV háromfázisú hibrid inverter sorozat, hat modellben érhető el: 6K-25-3P, 8K-25-3P, 10K-25-3P (25A akkumulátor-áram) és 12K-40-3P, 15K-40-3P, 20K-40-3P (40A akkumulátor-áram). Kettős MPPT PV bemeneteket támogat (legfeljebb 1000 V DC), lítium akkumulátoros tárolást (inverterenkénti legfeljebb 92 kWh), hálózati és szigetüzemi működést, valamint háromfázisú biztonsági kimenetet 10 ms-nál rövidebb átkapcsolási idővel.

A TapHome Modbus RTU protokollon keresztül, RS-485-ön kommunikál az inverterrel az EMS porton át. A sablon monitorozást biztosít az akkumulátor állapotához, hálózati teljesítményáramláshoz, PV termelési energiához, fázismérésekhez és belső hőmérsékletekhez, valamint vezérlést nyújt az EPS/UPS backuphoz, hálózati export korlátokhoz, AC teljesítménykimenet beállításokhoz, csúcsterhelés-eltoláshoz és szigetüzemi aszimmetrikus kimenethez.

> [!NOTE]
> A Wattsonic Gen3 **eltérő regisztertérképet** használ (10xxx–53xxx tartomány), mint a régebbi WTS/Gen2 sorozat (1xxxx–5xxxx). A két sorozat nem felcserélhető — használd az inverter generációjának megfelelő sablont. Az azonos Gen3 regiszterprotokollt használó kompatibilis márkák: Sunways, Solinteg, A-Tronix és St-ems.

## Hardveres csatlakozás

### RS-485 EMS csatlakozás

Csatlakoztasd a TapHome-ot az EMS RS-485 tűkhöz az inverter alján lévő Multi-COM kapocssínén:

| Multi-COM tű | Meghatározás | TapHome csatlakozás |
|--------------|--------------|---------------------|
| **13** | **485 B1** | B-/D- a TapHome RS-485-ön |
| **14** | **485 A1** | A+/D+ a TapHome RS-485-ön |

> [!WARNING]
> A Multi-COM csatlakozó vízálló kábeltömítő szerelvényt használ. A kábel átmérője 4–6,5 mm, keresztmetszete 0,5–1,5 mm² kell legyen. A külső szigetelést 55 mm-re, a belső huzalszigetelést 8 mm-re kell lehúzni.

### Műszaki adatok

| Paraméter | Érték |
|-----------|-------|
| Védelmi fokozat | IP65 |
| Működési hőmérséklet | -30°C – +60°C |
| Kommunikáció | CAN, RS485, WiFi/LAN (opcionális) |
| Max. hatásfok | 98,1–98,4% (modellfüggő) |
| Max. PV bemeneti feszültség | 1000 V DC |
| MPPT nyomkövetők | 2 |
| Biztonsági átkapcsolás | < 10 ms |

## Konfiguráció

### Kommunikációs paraméterek

| Paraméter | Érték |
|-----------|-------|
| Átviteli sebesség | 9600 |
| Adatbitek | 8 |
| Paritás | Nincs |
| Stop bitek | 1 |
| Slave cím (RTU) | 247 |
| Slave cím (TCP) | 255 |
| TCP port | 502 |

Az EMS RS-485 port alapértelmezés szerint aktív. Csatlakoztasd az RS-485 vezetékeket a Multi-COM csatlakozó 13. és 14. tűjéhez, és állítsd be a 247-es Slave ID-t a TapHome-ban.

> [!TIP]
> TCP/IP kapcsolat is támogatott (502-es port, 255-ös Slave ID), de Gen3-nál kevésbé dokumentált. Az RS-485 RTU 247-es Slave ID-vel az ajánlott csatlakozási módszer.

## Eszköz képességek

### Akkumulátor monitorozás

A **Battery Mode** az aktuális töltési/kisütési irányt jeleníti meg többértékű kapcsolóként — Discharge (0) vagy Charge (1). Három szerviz attribútum részletes akkumulátor méréseket biztosít:

- **Battery Voltage** — DC feszültség V-ban (regiszter /10)
- **Battery Current** — DC áram A-ban (pozitív = töltés, negatív = kisütés)
- **Battery Power** — azonnali teljesítmény kW-ban

### Inverter állapot

A **Running Status** valós idejű inverter üzemelési állapotot mutat: Wait, Self-check, On Grid, Fault, Flash/Firmware Update vagy Off Grid. Ez egy csak olvasható többértékű kapcsoló — az írási szkript le van tiltva a sablonban.

### EPS/UPS és rendszerkapcsolók

Három be/ki kapcsoló vezérli az inverter funkciókat:

- **EPS/UPS Switch** — biztonsági tápellátást engedélyez az akkumulátorból hálózatkimaradás esetén
- **Off-Grid Asymmetric Output Switch** — aszimmetrikus teljesítménykimenetet engedélyez a fázisok között szigetüzemi módban
- **Peak Load Shifting Switch** — engedélyezi az akkumulátor pótlását, ha a terhelés meghaladja a hálózati teljesítménykorlátot (v3+ firmware)

### Hálózati export vezérlés

A **Grid Export Limit Switch** engedélyezi vagy tiltja a hálózati export korlátot. A **Grid Export Limit Setting** egy dimmer (0–100%), amely a hálózatba exportálható névleges teljesítmény maximális százalékát állítja be. A skálázási tényező ×1000, 0,1%-os felbontáshoz.

### AC teljesítménykimenet beállítása

Az **AC Power Setting** a teljesítménykimenet módot választja ki: Off, Total Power Setting vagy Power on Each Phase Setting. Négy szerviz attribútum jeleníti meg a jelenlegi fázisenkénti és összesített teljesítmény beállításokat, négy szervizakció pedig lehetővé teszi az új értékek írását:

- **Set Total AC Power** — összesített AC kimenet kW-ban (×100 skálázás)
- **Set Phase A/B/C Power** — egyedi fázis teljesítmény beállítások kW-ban

### Fázisenkénti hálózati mérés

Három villamos mérő eszköz (**Phase A/B/C Power on Meter**) a külső hálózati mérőből biztosítja a fázisenkénti azonnali aktív teljesítményt kW-ban. Ezek csak olvashatók, csak pillanatnyi leolvasásokkal (összesített fogyasztás letiltva).

A **Total Power on Meter** az összes fázis összegét adja — a pozitív értékek hálózati importot, a negatívak exportot jeleznek.

### Napi energiaszámlálók

Hat villamos mérő eszköz követi a napi energiatermelést és -fogyasztást:

- **Grid Injection Energy Today** — hálózatba exportált energia (mérőről)
- **Grid Purchasing Energy Today** — hálózatból vásárolt energia (mérőről)
- **Energy from Grid Today** — hálózatból vett energia az inverter oldalán
- **PV Generation Energy Today** — napi PV termelés
- **Loading Energy Today** — terhelések által összesen felhasznált energia
- **Total PV Generation Today** — napi PV számláló (H:11018, /10)

Minden napi számláló /10 skálázást használ kWh-ban.

### Kumulatív energiaösszegek

Kilenc villamos mérő eszköz követi az élettartamra vetített energiaszámlálókat:

- **Total Energy Injected to Grid** — kumulatív hálózati export (H:31102, /10)
- **Total Energy from Grid (Meter)** — kumulatív hálózati import a mérőről (H:31104, /10)
- **Total Energy from Grid (Inverter)** — kumulatív hálózati import az inverter oldalán (H:31118, /10)
- **Total Output Energy on Backup Port** — kumulatív biztonsági energia (H:31106, /10)
- **Total Loading Energy (Grid Side)** — kumulatív terhelési fogyasztás (H:31114, /10)
- **Total PV Generation** — kumulatív PV energia (H:31112, /10)
- **Total PV Generation from Installation** — alternatív PV számláló (H:11020, nyers kWh), tartalmaz egy szerviz attribútumot a **Total PV Generation Time**-hoz órában
- **Total Grid-Injection Energy on Meter** — hálózati export a mérőről (H:11002, /100)
- **Total Purchasing Energy on Meter** — hálózati import a mérőről (H:11004, /100)

> [!NOTE]
> A skálázási tényezők eltérnek: a 31xxx tartományú regiszterek /10-et használnak; a 11xxx tartományban a H:11002 és a H:11004 /100-at, a H:11018 /10-et használ, a H:11020 pedig nyers kWh értékként olvasódik.

### Rendszerdiagnosztika

A modul ReadScript figyeli a H:10112 és H:10114 hibajel regisztereket (UInt32 bitmaszkok), és egyedi hibaállapotokat jelez: Mains Lost, Grid Voltage/Frequency Fault, DCI Fault, ISO Over Limitation, GFCI Fault, PV Over Voltage, Bus Voltage Fault, Inverter Over Temperature, SPI/E2 Fault, GFCI Device Fault, AC Transducer Fault, Relay Check Fail, valamint Internal/External Fan Fault.

A modul szintű szerviz attribútumok további diagnosztikát biztosítanak:

- **Inverter SN** — sorozatszám
- **Equipment Info** és **Firmware Version** — hardver/szoftver azonosítás
- **Grid Regulation** — konfigurált hálózati szabvány kód
- **Fault FLAG1/FLAG2/FLAG3** és **ARM Fault FLAG1** — nyers hibabitmaszkok haladó hibakereséshez
- **Grid Phase A/B/C Voltage and Current**, **Grid Lines A/B, B/C, C/A Voltage** — fázisenkénti hálózati mérések
- **Grid Frequency** — hálózati frekvencia Hz-ben
- **Inverter AC Power (P_AC)** — összesített AC kimenet kW-ban
- **Temperature Sensor 1–4** — inverter belső hőmérsékletek °C-ban
- **Max Grid Power Setting** — jelenlegi maximális hálózati teljesítmény kVA-ban, szervizakcióval az érték módosításához

### További képességek

A Wattsonic Gen3 inverterek regisztereket tesznek elérhetővé az üzemmód választóhoz (General, UPS, Peak Shift, Feed-In, Off-Grid, ToU), PV string feszültségekhez és áramokhoz (PV1/PV2), PV bemeneti összteljesítményhez, biztonsági terhelés összteljesítményéhez, BMS diagnosztikához (SOC, SOH, csomag hőmérséklet, cellaenkénti feszültségek, hiba-/figyelmeztetési kódok, szoftver-/hardver verziók), akkumulátor töltési/kisütési napi és összesített energiaszámlálókhoz, akkumulátor teljesítmény beállításokhoz AC teljesítmény korlátokkal, prioritásos teljesítménykimenethez (PV/akkumulátor), akkumulátor konfigurációhoz, SOC védelemhez konfigurálható végső SOC értékkel hálózati és szigetüzemi üzemmódhoz, töltési/kisütési áramkorlátokhoz, valamint Economy/ToU üzemmód ütemezéséhez legfeljebb 6 időszakkal. Ezek egy jövőbeli sablon frissítésben adhatók hozzá.

## Hibaelhárítás

### Nincs Modbus kommunikáció

1. Ellenőrizd a bekötést: 13. tű (485 B1) B-/D--hez és 14. tű (485 A1) A+/D+-hoz a TapHome-on. A felcserélt A/B vezetékek a leggyakoribb csatlakozási probléma.
2. Erősítsd meg, hogy a TapHome-ban **247-es Slave ID** van beállítva (nem 1 — a Gen3 alapértelmezés szerint 247-et használ, ellentétben a WTS-sel, amelynek alapértelmezése 1).
3. Erősítsd meg a kommunikációs paramétereket: 9600 baud, 8 adatbit, nincs paritás, 1 stop bit.
4. Ha hosszú RS-485 kábelt használsz, engedélyezd a lezáró ellenállást az utolsó eszközön. A TapHome Core beépített 100 Ohm lezáró ellenállással rendelkezik a BUS csatlakozóin.

### Regiszter cím megjegyzés

A közösségi dokumentáció szerint a Gen3 regiszterek olvasásakor szükség lehet +1 hozzáadására a hivatalos protokolltáblázatban felsorolt címekhez. A TapHome sablon ezt már figyelembe veszi — nincs szükség manuális kiigazításra.

### Hibajel regiszter eltérés

A sablon ReadScript a Fault Flag3-at H:10120 címen hivatkozza, míg egyes forrás dokumentációk H:10116-ot jelölnek. Mindkettő érvényes lehet a firmware verziótól függően. Ha a hibajel-jelentés inkonzisztens, ellenőrizd a megfelelő címet a saját firmware-edhez.

### Cloud app és Modbus vezérlési ütközések

A Wattsonic cloud alkalmazáson (WattDesk) keresztül és a Modbus helyi írásokon keresztül végzett változtatások nem feltétlenül szinkronizálnak kétirányban. Amikor a TapHome-ot használod az inverter vezérlésére, kerüld az ütköző változtatásokat a cloud alkalmazáson keresztül egyidejűleg.

## Elérhető eszközök

Wattsonic Hybrid Inverter G3 Modul

Szerviz attribútumok

|                                        |
|----------------------------------------|
| Inverter sorozatszám                   |
| Eszközinformáció                       |
| Firmware-verzió                        |
| Hálózati szabvány                      |
| Hibajel FLAG1                          |
| Hibajel FLAG2                          |
| Hibajel FLAG3                          |
| Hálózati A/B vezetéken lévő feszültség |
| Hálózati B/C vezetéken lévő feszültség |
| Hálózati C/A vezetéken lévő feszültség |
| Hálózati A fázis feszültsége           |
| Hálózati A fázis áramerőssége          |
| Hálózati B fázis feszültsége           |
| Hálózati B fázis áramerőssége          |
| Hálózati C fázis feszültsége           |
| Hálózati C fázis áramerőssége          |
| Hálózati frekvencia                    |
| Inverter AC teljesítménye              |
| 1\. hőmérséklet-érzékelő               |
| 2\. hőmérséklet-érzékelő               |
| 3\. hőmérséklet-érzékelő               |
| 4\. hőmérséklet-érzékelő               |
| ARM hibajel FLAG1                      |
| Max. hálózati teljesítmény beállítása  |

Szerviz műveletek

|                                       |
|---------------------------------------|
| Max. hálózati teljesítmény beállítása |

Olvasás (modul)

```taphome
#GEN3-Wattsonic Hybrid Inverter MODBUS RTU Protocol- page 17/27, table 3.3 Fault Registers Map
var flag1 := MODBUSR(H, 10112, Uint32);
IF(GETBIT(flag1, 0) = 1, ADDERROR("Mains Lost", 1));
IF(GETBIT(flag1, 1) = 1, ADDERROR("Grid Voltage Fault", 2));
IF(GETBIT(flag1, 2) = 1, ADDERROR("Grid Frequency Fault", 3));
IF(GETBIT(flag1, 3) = 1, ADDERROR("DCI Fault", 4));
IF(GETBIT(flag1, 4) = 1, ADDERROR("ISO Over Limitation", 5));
IF(GETBIT(flag1, 5) = 1, ADDERROR("GFCI Fault", 6));
IF(GETBIT(flag1, 6) = 1, ADDERROR("PV Over Voltage", 7));
IF(GETBIT(flag1, 7) = 1, ADDERROR("Bus Voltage Fault", 8));
IF(GETBIT(flag1, 8) = 1, ADDERROR("Inverter Over Temperature", 9));
var flag2 := MODBUSR(H, 10114, Uint32);
IF(GETBIT(flag2, 1) = 1, ADDERROR("SPI Fault", 34));
IF(GETBIT(flag2, 2) = 1, ADDERROR("E2 Fault", 35));
IF(GETBIT(flag2, 3) = 1, ADDERROR("GFCI Device Fault",36 ));
IF(GETBIT(flag2, 4) = 1, ADDERROR("AC Transducer Fault", 37));
IF(GETBIT(flag2, 5) = 1, ADDERROR("Relay Check Fail", 38));
IF(GETBIT(flag2, 6) = 1, ADDERROR("Internal Fan Fault", 39));
IF(GETBIT(flag2, 7) = 1, ADDERROR("External Fan Fault", 40));
```

Szerviz attribútumok

Inverter SN

```taphome
modbusr(h,10000,string,8)
```

Equipment info

```taphome
modbusr(h,10008,uint16)
```

Firmware version

```taphome
modbusr(h,10011,uint32)
```

Grid regulation

```taphome
modbusr(H,10104,uint16)
```

Fault FLAG1

```taphome
modbusr(H,10112,uint32)
```

Fault FLAG2

```taphome
modbusr(h,10114,uint32)
```

Fault FLAG3

```taphome
modbusr(h, 10120,uint32)
```

Grid Lines A/B Voltage \[V]

```taphome
modbusr(h,11006,uint16) /10
```

Grid Lines B/C Voltage \[V]

```taphome
modbusr(h,11007,uint16) /10
```

Grid Lines C/A Voltage \[V]

```taphome
modbusr(h,11008,uint16)/10
```

Grid Phase A Voltage \[V]

```taphome
modbusr(h,11009,uint16)/10
```

Grid Phase A Current \[A]

```taphome
modbusr(h,11010,uint16)/10
```

Grid Phase B Voltage \[V]

```taphome
modbusr(h,11011,uint16)/10
```

Grid Phase B Current \[A]

```taphome
modbusr(h,11012,uint16)/10
```

Grid Phase C Voltage \[V]

```taphome
modbusr(h,11013,uint16)/10
```

Grid Phase C Current \[A]

```taphome
modbusr(h, 11014, uint16)/10
```

Grid Frequency \[Hz]

```taphome
modbusr(h,11015,uint16)/100
```

P\_AC \[kW]

```taphome
modbusr(h,11016,int32)/1000
```

Temperature Sensor 1 \[C]

```taphome
modbusr(h,11032,int16)/10
```

Temperature Sensor 2 \[C]

```taphome
modbusr(h,11033,int16)/10
```

Temperature Sensor 3 \[C]

```taphome
modbusr(h,11034,int16)/10
```

Temperature Sensor 4 \[C]

```taphome
modbusr(h,11035,int16)/10
```

ARM Fault FLAG1

```taphome
modbusr(h,18000,uint32)
```

Max. Grid Power Value Setting \[kVA]

```taphome
modbusr(h, 50009, uint16)/10
```

Szerviz műveletek

Set Max. Grid Power Value Setting

Paraméterek: Parameter1 (1–1e+06 Abr1)

```taphome
modbusw(h,50009,uint16,Abr1*10)
```

Akkumulátor üzemmód Többértékű kapcsoló Csak olvasható

Az akkumulátor aktuális töltési/kisütési iránya — Kisütés vagy Töltés, feszültség, áram és teljesítmény szervizattribútumokkal

Regiszter: H:30256 UInt16 numeric

Értékek / Állapotok: Discharge · Charge

Kapcsoló állapot olvasása

```taphome
MODBUSR(H, 30256, uInt16)
```

Szerviz attribútumok

Battery\_V \[V]

```taphome
modbusr(h,30254,uint16)/10
```

Battery\_I \[I]

```taphome
modbusr(h,30255,int16)/10
```

Battery\_I \[kW]

```taphome
modbusr(h,30258,int32)/1000
```

Mai hálózatból vett energia Villanyóra Csak olvasható

Regiszter: H:31008 UInt16 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31008, uInt16) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

EPS/UPS kapcsoló Kapcsoló

Akkumulátoros tartalék tápellátást engedélyez hálózatkiesés esetén

Regiszter: H:50001 UInt16

Értékek / Állapotok: ON · OFF

Kapcsoló állapot olvasása

```taphome
MODBUSR(h, 50001, uint16)
```

Kapcsoló állapot írása

```taphome
MODBUSW(h, 50001, uint16, St)
```

Mai hálózatba betáplált energia Villanyóra Csak olvasható

Regiszter: H:31000 UInt16 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31000, uInt16) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Hálózati export korlát beállítása Fényerőszabályzó

A névleges teljesítmény százalékában megadott maximális hálózati export teljesítmény (0–100%)

Regiszter: H:25103 UInt16 Egység: % numeric

Szint olvasása

```taphome
MODBUSR(H, 25103, uInt16) / 1000
```

Szint írása

```taphome
MODBUSW(H, 25103, uInt16, Le * 1000)
```

Hálózati export korlát kapcsoló Kapcsoló

Regiszter: H:25100 UInt16

Értékek / Állapotok: ON · OFF

Kapcsoló állapot olvasása

```taphome
MODBUSR(h, 25100, uint16)
```

Kapcsoló állapot írása

```taphome
MODBUSW(h, 25100, uint16, St)
```

Mai hálózatból vásárolt energia Villanyóra Csak olvasható

Regiszter: H:31001 UInt16 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31001, uInt16) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

AC teljesítmény beállítása Többértékű kapcsoló

AC teljesítménykimenet módja — Ki, Összes teljesítmény beállítása vagy Teljesítmény fázonként, fázisszintű teljesítménykonfigurációval

Regiszter: H:50202 UInt16 numeric

Értékek / Állapotok: Off · Total Power Setting · Power on each Phase Setting

Szerviz műveletek

|                                     |
|-------------------------------------|
| Összes AC teljesítmény beállítása   |
| A fázis teljesítményének beállítása |
| B fázis teljesítményének beállítása |
| C fázis teljesítményének beállítása |

Kapcsoló állapot olvasása

```taphome
MODBUSR(H, 50202, uInt16)
```

Kapcsoló állapot írása

```taphome
MODBUSW(H, 50202, uInt16, Mu)
```

Szerviz attribútumok

Total AC Power Setting \[kW]

```taphome
modbusr(h,50203,int16)/100
```

Phase A Power Setting \[kW]

```taphome
modbusr(h,50204,int16)/100
```

Phase B Power Setting \[kW]

```taphome
modbusr(h,50205,int16)/100
```

Power C Power Setting \[kW]

```taphome
modbusr(h,50206,int16)/100
```

Szerviz műveletek

Set Total AC Power Setting

Paraméterek: kW (1–1e+06 x)

```taphome
modbusw(h,50203,int16,x*100)
```

Set Phase A Power Setting

Paraméterek: kW (1–1e+06 x)

```taphome
modbusw(h,50204,int16,x*100)
```

Set Phase B Power Setting

Paraméterek: kW (1–1e+07 x)

```taphome
modbusw(h,50205,int16,x*100)
```

Set Power C Power Setting

Paraméterek: kW (1–1e+06 x)

```taphome
modbusw(h,50206,int16,x*100)
```

Működési állapot Többértékű kapcsoló Csak olvasható

Az inverter aktuális működési állapota — Várakozás, Öndiagnosztika, Hálózatra kapcsolva, Hiba, Flash/Firmware-frissítés, Szigetüzem

Regiszter: H:10105 UInt16 numeric

Értékek / Állapotok: Wait · Self-check · On grid · Fault · Flash/Firmware update · Off grid

Kapcsoló állapot olvasása

```taphome
MODBUSR(H, 10105, uInt16)
```

Kapcsoló állapot írása

```taphome
#MODBUSW(H, -1, Int16, Mu)
```

Mai terhelési energia Villanyóra Csak olvasható

Regiszter: H:31006 UInt16 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31006, uInt16) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Szigetüzemi aszimmetrikus kimenet kapcsoló Kapcsoló

Kiegyensúlyozatlan teljesítménykimenetet tesz lehetővé három fázison át a szigetüzemi módban

Regiszter: H:50006 UInt16

Értékek / Állapotok: ON · OFF

Kapcsoló állapot olvasása

```taphome
MODBUSR(h, 50006, uint16)
```

Kapcsoló állapot írása

```taphome
MODBUSW(h, 50006, uint16,st)
```

Csúcsterhelés-eltolás kapcsoló Kapcsoló

Lehetővé teszi az akkumulátoros pótlást, ha a terhelés meghaladja a hálózati teljesítménykorlátot

Regiszter: H:50007 UInt16

Értékek / Állapotok: ON · OFF

Kapcsoló állapot olvasása

```taphome
MODBUSR(h, 50007, uint16)
```

Kapcsoló állapot írása

```taphome
MODBUSW(h, 50007, uint16,st)
```

A fázis teljesítménye a mérőn Villanyóra Csak olvasható

Regiszter: H:10994 Int32 Egység: kW numeric

Összes fogyasztás olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Igény olvasása

```taphome
MODBUSR(H, 10994, Int32)/1000
```

B fázis teljesítménye a mérőn Villanyóra Csak olvasható

Regiszter: H:10996 Int32 Egység: kW numeric

Összes fogyasztás olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Igény olvasása

```taphome
MODBUSR(H, 10996, Int32) / 1000
```

C fázis teljesítménye a mérőn Villanyóra Csak olvasható

Regiszter: H:10998 Int32 Egység: kW numeric

Összes fogyasztás olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Igény olvasása

```taphome
MODBUSR(H, 10998, Int32) / 1000
```

Mai PV termelési energia Villanyóra Csak olvasható

Regiszter: H:31005 UInt16 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31005, uInt16) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Hálózatba betáplált összes energia Villanyóra Csak olvasható

Regiszter: H:31102 UInt32 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31102, uInt32) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Hálózatból vett összes energia (inverter) Villanyóra Csak olvasható

Regiszter: H:31118 UInt32 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31118, uInt32) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Hálózatból vett összes energia (mérő) Villanyóra Csak olvasható

Regiszter: H:31104 UInt32 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31104, uInt32) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Hálózatba betáplált összes energia a mérő szerint Villanyóra Csak olvasható

Regiszter: H:11002 UInt32 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 11002, uInt32) / 100
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Összes terhelési energia (hálózati oldal) Villanyóra Csak olvasható

Regiszter: H:31114 UInt32 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31114, uInt32) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Összes kimeneti energia a tartalék porton Villanyóra Csak olvasható

Regiszter: H:31106 UInt32 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31106, uInt32) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Összes teljesítmény a mérőn Villanyóra Csak olvasható

A külső mérőről vett azonnali összes hálózati teljesítmény — pozitív az import, negatív az export

Regiszter: H:11000 Int32 Egység: kW numeric

Összes fogyasztás olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Igény olvasása

```taphome
MODBUSR(H, 11000, Int32) / 1000
```

Összes vásárolt energia a mérő szerint Villanyóra Csak olvasható

Regiszter: H:11004 UInt32 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 11004, uInt32) / 100
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Összes PV termelés Villanyóra Csak olvasható

Regiszter: H:31112 UInt32 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 31112, uInt32) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Összes PV termelés a telepítés óta Villanyóra Csak olvasható

Kumulatív PV energiaszámláló kWh-ban (nyers érték, skálázás nélkül), a teljes termelési idővel órában

Regiszter: H:11020 UInt32 Egység: kWh numeric

Szerviz attribútumok

|                         |
|-------------------------|
| Összes PV termelési idő |

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 11020, uInt32)
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

Szerviz attribútumok

Total PV Generation Time from Installation \[H]

```taphome
modbusr(h,11022,uint32)
```

Mai összes PV termelés Villanyóra Csak olvasható

Regiszter: H:11018 UInt32 Egység: kWh numeric

Összes fogyasztás olvasása

```taphome
MODBUSR(H, 11018, uInt32) / 10
```

Igény olvasása

```taphome
#MODBUSR(H, -1, Int16) / 100
```

**Kapcsolat:** Modbus RTU • 9600 baud• 8N1 • Slave ID: $\[SlaveId]

Lehetséges fejlesztések (37)

- H:50000 Hybrid Inverter Working Mode Setting — 257=General, 258=Economic, 259=UPS, 260=PeakShift, 261=FeedIn, 512=OffGrid, 1024=ToU. Critical working mode selector — surprisingly missing from template
- H:10116 Fault Flag3 — Int32 fault bitmask — referenced in readscript comment but uses 10120 instead of 10116. Sources list 10116 as the correct address
- H:11028 PV Input Total Power — Int32 /1000 kW — total PV input power (both MPPT trackers combined)
- H:11038 PV1 Voltage — Int16 /10 V — PV string 1 DC voltage
- H:11039 PV1 Current — Int16 /10 A — PV string 1 DC current
- H:11040 PV2 Voltage — Int16 /10 V — PV string 2 DC voltage
- H:11041 PV2 Current — Int16 /10 A — PV string 2 DC current
- H:11062 PV1 Input Power — Int32 /1000 kW — PV string 1 power
- H:11064 PV2 Input Power — Int32 /1000 kW — PV string 2 power
- H:30230 Total Backup Power — Int32 /1000 kW — total backup/EPS load power
- H:33000 Battery SOC — Int16 /100 % — battery state of charge. Critical for energy management
- H:33001 Battery SOH — Int16 /100 % — battery state of health
- H:33002 BMS Status — Int16 — BMS operational status
- H:33003 BMS Pack Temperature — Int16 /10 °C — battery pack temperature
- H:33013 Max Cell Voltage — Int16 /1000 V — highest cell voltage in pack
- H:33015 Min Cell Voltage — Int16 /1000 V — lowest cell voltage in pack
- H:33016 BMS Error Code — Int32 — BMS error code bitmask
- H:33018 BMS Warn Code — Int32 — BMS warning code bitmask
- H:31002 Backup Output Energy Today — Int16 /10 kWh — daily energy delivered through backup port
- H:31003 Battery Charge Energy Today — Int16 /10 kWh — daily energy charged to battery
- H:31004 Battery Discharge Energy Today — Int16 /10 kWh — daily energy discharged from battery
- H:31108 Total Battery Charge Energy — Int32 /10 kWh — cumulative total battery charge energy
- H:31110 Total Battery Discharge Energy — Int32 /10 kWh — cumulative total battery discharge energy
- H:50207 Battery Power Setting — Int16 /100 kW — configurable battery power setpoint
- H:50208 Battery Max AC Power Limit Setting — Int16 /100 kW — maximum AC power limit for battery
- H:50209 Battery Min AC Power Limit Setting — Int16 /100 kW — minimum AC power limit for battery
- H:50210 Priority Power Output Setting — UInt16 — 0=PV Priority, 1=Battery Priority
- H:52500 Battery Configuration — Int16 — 1=Solinteg, 2=EMS, 10=Wattsonic Li-HV
- H:52502 On-grid Battery SOC Protection Switch — UInt16 — 0=Off, 1=On. Protects battery from over-discharge on grid
- H:52503 On-grid Battery End SOC — Int16 /10 % — minimum SOC before battery stops discharging (on-grid)
- H:52504 Off-grid Battery SOC Protection Switch — UInt16 — 0=Off, 1=On. Protects battery from over-discharge off-grid
- H:52505 Off-grid Battery End SOC — Int16 /10 % — minimum SOC before battery stops discharging (off-grid)
- H:52601 Charge Current Limit — Int16 /10 A — maximum battery charge current (default 200A)
- H:52603 Discharge Current Limit — Int16 /10 A — maximum battery discharge current (default 200A)
- H:53006 Ecomode Period Enable Flag — Int16 — bitmask bit0-bit5 enable periods 1-6 for Economy/ToU scheduling
- H:32003 BMS Software Version — Int16 — BMS firmware version
- H:32004 BMS Hardware Version — Int16 — BMS hardware version

## Források

- Wattsonic Li-HV Residential Three Phase Hybrid Series Datasheet
  
  [oss.wattsonic.com](https://oss.wattsonic.com/wattsonic/docs/Wattsonic%20Li-HV%20Residential%20Three%20Phase%20Hybrid%20Series_DS_EN.pdf) 2026-03-28
  
  [PDF](https://taphome.com/compatibility/devices/wattsonic-hybrid-inverter-g3/manufacturer/wattsonic-g3-datasheet.pdf)

## Kapcsolódó dokumentáció

- [Modbus Integration](https://taphome.com/hu/compatibility/modbus-guide/)
- [Modbus útmutató a TapHome készülékekhez](https://taphome.com/hu/docs/integration/modbus/)
- [Egyszerű konfiguráció sablonok használatával](https://taphome.com/hu/docs/integration/modbus/templates/)
- [Modbus szkriptek és prefetch](https://taphome.com/hu/docs/script/modbus-scripts/)
- [Modbus függvények](https://taphome.com/hu/docs/script/modbus/)
- [Modbus adattípusok](https://taphome.com/hu/docs/script/modbus-data-types/)