Flexit EcoNordic WH4 / W4

A Flexit EcoNordic egy klimakozpont, amely egyensulyi szellozest hovisszanyeressel, hasznalati melegviz-termelest es vizes futest (WH4 modell) kombinat. A TapHome-mal Modbus RTU-n keresztul kommunikal RS-485-on, lehetove teve a szellozesi modok vezerleset, homerseklet-beallitasokat, melegviz-kezelest es a hoszivattyú mukodesenek felugyelet.

Ket modell tamogatott: EcoNordic WH4 (szellozes + futes + melegviz) es EcoNordic W4 (szellozes + melegviz). A WH4 tovabbi futesi kor erzekelokkel es vezerlesekkel rendelkezik, amelyek a W4-en nem erhetek el.

Hardveres csatlakozas

Az EcoNordic beepitett Modbus RTU interfeszszel rendelkezik, RS-485-on keresztul erheto el. Csatlakoztassa a TapHome Core-t az EcoNordic RS-485 portjahoz sodrott erparral es GND-vel.

Az elerheto dokumentacioban nem talalhato bekotesi rajz. Az RS-485 csatlakozok pontos helyet az EcoNordic telepitesi kezikonyveben talaja, vagy forduljon a Flexit tamogatashoz. Az opcionalis Modbus kabel (HP Res) tartozek a Flexittol szerezheto be kulso vezerlokhoz.

Konfiguracio

Allitsa be a Modbus kapcsolatot a TapHome-ban az alabbi parametrekkel:

ParameterErtek
Baud rate9600
Adatbitek8
ParitasEven
Stop bitek1
Slave ID1 (alapertelmezett)

Az EcoNordic sajat Modbus regiszterterkepet hasznalja az 1-3037 cimtartomanyban. Ez elter a regebbi Flexit Nordic S2-S4 / CL2-CL4 modellek altal hasznalt CI66 regiszterterkeptol — CI66 adapter nem szukseges.

Az EcoNordic a Flexit GO mobilalkalmazassal (Android/iOS) is vezérelheto. A TapHome es a Flexit GO alkalmazas egyidejuleg mukodhet — mindketto fuggetlenul kommunikal az egyseggel.

Eszkozkepes segek

Szellozesi mod vezerles

Az Uzemmod (H:2013) az elsodleges szellozesvezerles negy moddal:

  • Stop — ventilatorok kikapcsolva, nincs szellozes
  • Away — csokentett szellozes lakatlan epulethez
  • Home — normalis napi uzem
  • High — ideiglenesen fokozott szellozes

Ket specialis trigger tovabbi szellozesi modokat biztosit:

  • Gyors szellozes (H:3006) — ideiglenes nagysebessegu szellozest aktival gyors legcserere (fozes, latogatok, para). Az idotartam szervizmuveleten keresztul allithato (1-360 perc)
  • Kandallo szellozes (H:3007) — pozitiv belteri nyomast hoz letre, hogy megakadalyozza a fust behatolasat a helyisegbe a kandallo meggyujtasakor. Az idotartam szervizmuveleten keresztul allithato (0-360 perc)

A Comfort gomb (H:2040) atkapcsolja a komfort modot az egysegen, amely ideiglenesen noveli a szellozest es modosithatja a homerseklet-beallitasokat.

Homerseklet-felugyeletes es beallitasok

A sablon ot homerseklet-erzekelot biztosit:

  • Kulso levego homerseklete (A:1) — kulteri levego homerseklete a beszivo nyilasnal
  • Befuvo levego homerseklete (A:5) — friss levego az epuletbe juttatva hovisszanyeres es utofutes utan
  • Elszivo levego homerseklete (A:9) — az epuletbol elszivott levego hovisszanyeres elott
  • Kifuvo levego homerseklete (A:13) — a kulteri levegobe kifujt levego hovisszanyeres utan
  • Futesi kor eloremenoi homerseklet (A:97) — viz homerseklete a futesi kor eloremeno csoveben (csak WH4)
  • Futesi kor visszatero homerseklet (A:101) — viz homerseklete a futesi kor visszatero csoveben (csak WH4)

Ket termosztat vezerli a befuvo levego homerseklet-beallitasait:

  • Homerseklet Home modban (H:1155) — beallitas Home modhoz, tartomany 10-30°C
  • Homerseklet Away modban (H:1163) — beallitas Away modhoz, tartomany 10-30°C
Melegviz-kezeles

A Melegviz mod (H:3017) kivalasztja a hasznalati melegviz futesi strategiajat:

  • Comfort — tolti a tartalyt kb. 50% maradek melegviznel, 15% alatt elektromos tartalek futot hasznal
  • Economy — legtakarekosabb mod, csak kb. 15% maradeknal tolt, elektromos tartalek nelkul

A Melegviz boost (H:3019) ideiglenes maximalis melegviz-termelest indit az elektromos tartalek futovel. Az idotartam szervizmuveleten keresztul allithato (0-300 perc).

Hoszivattyú es rendszerfelugyeletes

A modul kilenc szervizattributumot kinal a rendszerallapot felugyeletehez:

  • Hoszivattyú allapota (A:3028) — aktualis hoszivattyú mukodes: Keszenleti, Legtelenites, Inditas, Normalis mukodes, Leallitas, Olvasztas, Hibas keszenleti, Kezi es Kenyszeritett mukodes
  • Hasznalati melegviz allapota (A:3005) — melegviz-termeles allapota: Comfort, Economy, Nincs hasznlatban, Ideiglenes boost, Kenyszeritett toltes, Economy kesleltetes vagy Legionella megelozes
  • Hovisszanyero szellozes allapota (A:3034) — az aktualis szellozesi allapotot mutatja, beleertve az Uzemmodon keresztul kozvetlenul nem allithato modokat (pl. Paraelszivo es Kandallo)
  • Hoszivattyú uzemmodja (H:2061) — reszletes 17 allapotu enum, amely mutatja mit csinal a hoszivattyú (tartaly toltes, terfutes, szellozesi futes, Legionella megelozes es kombinalt modok)
  • Hoszivattyú utofutotest (A:3029) — az utofutotest aktiv-e
  • Hoszivattyú fagyvedelme (A:3031) — a fagyvedelem aktiv-e
  • Csepptalca melgito allapota (A:3036) — a csepptalca melegito aktiv-e
  • Hoszivattyú vizko figyelmeztes (A:3037) — figyelmeztes vizko lerakodas eszlelesekor
  • Hoszivattyú csappantyu pozicioja (H:29) — csappantyu pozicio szazalekban

Tovabbi szervizattributumok erhetek el az egyes eszkozokon: elszivo ventilator sebesseg, csappantyu parancsok, forgo hocsrelo sebesseg, hoszivattyú beallitott eloremeno homerseklet, termikus teljesitmeny, futesi kor keringteto szivattyú sebesseg es tarolotartaly fogyasztoi szelep pozicioja.

Riasztaskezeles

A ReadScript modul ket riasztasi csatornat figyel — Alarm A es Alarm B. Amikor egy riasztas aktiv (allapot = 2), a TapHome hibakent jelenti a riasztasi ertekkel es a nyugtazasi allapottal (Nyugtazott/Nem nyugtazott/Zarolt).

Harom szervizmuvelet erheto el a riasztaskezeleshez:

  • Alarm A nyugtazasa — nem nyugtazott riasztas nyugtazasa
  • Alarm B nyugtazasa — nem nyugtazott riasztas nyugtazasa
  • Osszes inaktiv riasztas eltavolitasa — torli az osszes inaktiv/nyugtazott riasztast a rendszerbol
Tovabbi kepessegek

Az EcoNordic tamogatja a szuroidozitokat, a hovisszanyeresi hatekonysag szamitast, a befuvo ventilator sebesseg felugyeletet es a futesi gorbe beallitasokat (WH4). A hovisszanyero szellozes allapota tovabbi modokat mutat (Paraelszivo, Kandallo, Ideiglenesen magas) az Uzemmod vezerles altal kozvetlenul kinaltakon tul. Ezek a kepessegek egy jovobeni sablonfrissitesben adhatoak hozza.

Az EcoNordic -25°C kulteri homersekletig mukodik CO2 hoszivattyujaval. A forgo hocsrelo akar 90%-os homersekleti hatekonyagot biztosit a hovisszanyereshez. Kovesse nyomon a befuvo es elszivo levego homerseklete kozti kulonbseget a hovisszanyeres teljesitmenyenek megiteleshez.

Hibaelharitas

Nincs Modbus kommunikacio
  1. Ellenorizze az RS-485 kabelkapcsolatokat a TapHome es az EcoNordic egyseg kozott
  2. Erositise meg a kommunikacios parametreket: 9600 baud, 8-E-1 (Even paritas, nem None)
  3. Ellenorizze, hogy a Slave ID a TapHome-ban megegyezik-e az egyseg konfiguracioval (alapertelmezett: 1)
  4. Bizonyosodjon meg rola, hogy az EcoNordic be van kapcsolva es mukodokepes
Futesi kor erzekelok nem mutatnak adatot (WH4)

A futesi kor eloremeno es visszatero homerseklet erzekelok csak a WH4 modellnel erhetek el. Ha W4-et hasznal (csak szellozes + melegviz), ezek az erzekelok nem jelentenek ertekeket.

Riasztasok jelentese a TapHome-ban
  1. Ellenorizze a riasztasi reszleteket a TapHome szervizattributumokban — a riasztasi ertek es allapot megjelenik
  2. Hasznalja a Riasztas nyugtazasa szervizmuveletet az aktiv riasztas nyugtazasahoz
  3. A riasztasi kodok ertelmezesehez nezze meg a Flexit GO alkalmazast vagy a felhasznaloi kezikonyvet
  4. Gyakori okok: eldugult szurok, leallo rotor, tulmelgedesi vedelem kioldasa, vizrendszer problemak

Elérhető eszközök

Flexit EcoNordic Modul
Szerviz attribútumok
Hoszivattyú allapotaHoszivattyú uzemallpota — Keszenleti, Legtelenites, Inditas, Normalis mukodes, Stop, Olvasztas, Hiba, Kezi, Kenyszeritett ventilator/szivattyú
Hasznalati melegviz allapotaAktualis melegviz-termeles allapot — Comfort, Economy, Nincs hasznlatban, Boost, Kenyszeritett toltes, Legionella megelozes
Hovisszanyero szellozes allapotaAktualis szellozesi allapot — Ki, Away, Home, High, Paraelszivo, Kandallo, Ideiglenesen magas
Hoszivattyú uzemmodjaHoszivattyú uzemmod — mutatja mit csinal a hoszivattyú (tartaly toltes, terfutes, szellozesi futes, Legionella megelozes)
Hoszivattyú utofutotest
Hoszivattyú fagyvedelme
Csepptalca melegito allapota
Hoszivattyú vizko figyelmeztes
Hoszivattyú csappantyu pozicioja
Szerviz műveletek
Osszes inaktiv riasztas eltavolitasa
Alarm A nyugtazasa
Alarm B nyugtazasa

Flexit Econordic

Olvasás (modul)
IF MODBUSR(A,3001, Uint16) = 2
ADDERROR(MODBUSR(A, 1021, float), "Alarm A: " + 
SWITCH(MODBUSR(A,3002, Uint16),
1, "Acknowledged, unlocked ",
2, "Unacknowledged",
3, "Locked",
"Unknown" ));
END

IF MODBUSR(A,3003, Uint16) = 2
ADDERROR(MODBUSR(A, 1023, float), "Alarm B: " + 
SWITCH(MODBUSR(A,3004, Uint16),
1, "Acknowledged, unlocked ",
2, "Unacknowledged",
3, "Locked",
"Unknown" ));
END
Szerviz attribútumok
Heat Pump Status
SWITCH(MODBUSR(A, 3028, Uint16), 
1, "Standby", 
2, "Air Purge process",
3, "Startup process",
4, "Normal operation",
5, "Stop process", 
6, "Defrost operation",
7, "Standby when error",
8, "Manual operation",
9, "Forced fan operation",
10, "Forced pump operation",
11, "State 10",
12, "State 11",
13, "State 12",
14, "State 13",
15, "State 14",
16, "State 15",
"Unknown"
)
Domestic hot water state
SWITCH(MODBUSR(A, 3005, Uint16),
1, "Comfort",
2, "Economy", 
3, "Not in Use",
4, "Temporary Boost",
5, "Forced Charge",
6, "Economy delay",
7, "Legionella prevention",
"Unknown"
);
Heat recovery ventilation state
SWITCH(MODBUSR(A, 3034, Uint16),
1, "Off", 
2 , "Away" , 
3 , "Home" , 
4 , "High", 
5 , "Fume hood", 
 6 , "Fireplace", 
 7 , "Temporary high",
 "Unknown");
Plant operating mode for heat pump
SWITCH(MODBUSR(H, 2061, Uint16), 
1 , "Off" , 
2 , "Vent.heating from tank" , 
3 , "Load tank" ,
4 , "Load tank & vent.heating" ,
5 , "Space heating from tank" , 
6 , "Space heat.& vent.heat.from tank",
7 , "Load tank & space heat" , 
8 , "Load tank & space heat.& vent" , 
9 , "HP not available" , 
10 , "Swi-off delay flow through heat",
11 , "Legionella prev.vent.heat" , 
12 , "Legionella prev.space heat" , 
13 , "Space heat.with HP" ,
14 , "Space heat.& vent.with HP" , 
15 , "Load tank & space heat.with HP" , 
16 , "Load tank & vent.& space with HP", 
17 , "Legionella prev.tank",
"Unknown")
Heat Pump Reheating Coil
Switch (MODBUSR(A, 3029, Uint16), 1, "Active", 0, "Inactive", "Unknown");
Heat Pump Frost Protection
Switch (MODBUSR(A, 3031, Uint16), 1, "Active", 0, "Inactive", "Unknown");
Drain Pan Heater State
Switch (MODBUSR(A, 3036, Uint16), 1, "Active", 0, "Inactive", "Unknown");
Heat pump warning limescale
Switch (MODBUSR(A, 3037, Uint16), 1, "Active", 0, "Inactive", "Unknown");
Heat Pump Connection Dumper position
MODBUSR(H, 29, Float, 2) + " %"
Szerviz műveletek
Remove All Inactive Alarms
MODBUSW(H, 3004, Uint16, 3);
Acknowledge Alarm A
MODBUSW(H, 3002, Uint16, 2)
Acknowledge Alarm B
MODBUSW(H, 3003, Uint16, 2)
Comfort gomb Kapcsoló
Regiszter: H:2040 Bool
Értékek / Állapotok: Active · Inactive

Comfort gomb

Kapcsoló állapot olvasása
MODBUSR(H, 2040, Bool)
Kapcsoló állapot írása
MODBUSW(H, 2040, Bool, St)
Kifuvo levego homerseklete Hőmérséklet-érzékelő Csak olvasható

A hovisszanyeres utan a szabadba kifujt levego homerseklete

Regiszter: A:13 Float Egység: °C numeric
Szerviz attribútumok
Elszivo ventilator sebesseg
Kifuvo levego csappantyu parancs
Hoszivattyú kifuvo levego csappantyu parancs

Kifuvo levego homerseklete

Hőmérséklet olvasása
MODBUSR(A, 13, Float, 2)
Szerviz attribútumok
Exhaust Air Fan Speed
 ROUND(MODBUSR(H, 9, Float, 2)) + " %"
Exhaust Air Damper Command
Switch (MODBUSR(H, 2010, Uint16), 1, "Active", 0, "Inactive", "Unknown");
Heat pump exhaust air damper command
Elszivo levego homerseklete Hőmérséklet-érzékelő Csak olvasható

Az epuletbol hovisszanyeres elott elszivott levego homerseklete

Regiszter: A:9 Float Egység: °C numeric
Szerviz attribútumok
Hoszivattyú kifuvo levego csappantyu parancs

Elszivo levego homerseklete

Hőmérséklet olvasása
MODBUSR(A, 9, Float , 2)
Szerviz attribútumok
Heat pump exhaust air damper command
Switch (MODBUSR(H, 2064, Uint16), 1, "Active", 0, "Inactive", "Unknown");
Futesi kor eloremeno homerseklet Hőmérséklet-érzékelő Csak olvasható

Viz homerseklete a futesi kor eloremeno csoveben — csak WH4 modell

Regiszter: A:97 Float Egység: °C numeric
Szerviz attribútumok
Forgo hocsrelo sebesseg
Hoszivattyú beallitott eloremeno homerseklet
Hoszivattyú termikus teljesitmeny

Futesi kor eloremeno homerseklet

Hőmérséklet olvasása
MODBUSR(A, 97, Float, 2)
Szerviz attribútumok
Rotary heat exchanger speed
 ROUND(MODBUSR(H, 1, Float, 2)) + " %"
Heat pump setpoint flow temperature
MODBUSR(H, 73, Float, 2) + " °C"
Heat Pump Thermic Power Output
MODBUSR(H, 65, Float, 2) + " kW"
Futesi kor visszatero homerseklet Hőmérséklet-érzékelő Csak olvasható

Viz homerseklete a futesi kor visszatero csoveben — csak WH4 modell

Regiszter: A:101 Float Egység: °C numeric

Futesi kor visszatero homerseklet

Hőmérséklet olvasása
MODBUSR(A, 101, Float, 2)
Melegviz boost Többértékű kapcsoló

Ideiglenes maximalis melegviz-termeles — Kesz, Start, Stop

Regiszter: H:3019 UInt16 numeric
Értékek / Állapotok: Ready · Start · Stop
Szerviz műveletek
Boost idotartama

Melegviz boost

Kapcsoló állapot olvasása
MODBUSR(H, 3019, UInt16)
Kapcsoló állapot írása
MODBUSWNE(H, 3019, UInt16, Mu)
Szerviz attribútumok
Duration of boost
MODBUSR(H, 1513, Uint32) + " min";
Szerviz műveletek
Duration of boost
Paraméterek: Duration [0-300 min] (0–300 dur)
MODBUSW(H, 1513, Uint32, dur);
Melegviz mod Többértékű kapcsoló

Hasznalati melegviz strategia — Comfort (50%-nal tolt) vagy Economy (15%-nal tolt)

Regiszter: H:3017 UInt16 numeric
Értékek / Állapotok: Comfort · Economy

Melegviz mod

Kapcsoló állapot olvasása
MODBUSR(H, 3017, UInt16)
Kapcsoló állapot írása
MODBUSW(H, 3017, UInt16, Mu)
Szerviz attribútumok
Heating circuit pump speed
MODBUSR(H, 61, Float, 2) + " %"
Storage tank consumer valve position
 ROUND(MODBUSR(H, 57, Float, 2)) + " %"
Uzemmod Többértékű kapcsoló

Szellozesi uzemmod — Stop, Away, Home, High

Regiszter: H:2013 UInt16 numeric
Értékek / Állapotok: Stop · Away · Home · High

Uzemmod

Kapcsoló állapot olvasása
MODBUSR(H, 2013, Uint16)
Kapcsoló állapot írása
MODBUSW(H, 2013, Uint16, Mu)
Kulso levego homerseklete Hőmérséklet-érzékelő Csak olvasható
Regiszter: A:1 Float Egység: °C numeric

Kulso levego homerseklete

Hőmérséklet olvasása
MODBUSR(A, 1, Float)
Befuvo levego homerseklete Hőmérséklet-érzékelő Csak olvasható

Az epuletbe juttatott friss levego homerseklete hovisszanyeres es utofutes utan

Regiszter: A:5 Float Egység: °C numeric

Befuvo levego homerseklete

Hőmérséklet olvasása
MODBUSR(A, 5, Float, 2)
Homerseklet Away modban Termosztát

Befuvo levego homerseklet-beallitas Away modhoz (10-30°C)

Regiszter: H:1163 Float Egység: °C numeric

Homerseklet Away modban

Kívánt hőmérséklet olvasása
MODBUSR(H, 1163, Float, 2)
Kívánt hőmérséklet írása
MODBUSW(H, 1163, Float, Se)
Homerseklet Home modban Termosztát

Befuvo levego homerseklet-beallitas Home modhoz (10-30°C)

Regiszter: H:1155 Float Egység: °C numeric

Homerseklet Home modban

Kívánt hőmérséklet olvasása
MODBUSR(H, 1155, Float, 2)
Kívánt hőmérséklet írása
MODBUSW(H, 1155, Float, Se)
Kandallo szellozes Többértékű kapcsoló

Tulnyomasi modot aktival a fust behatolasanak megakadalyozasara a kandallo meggyujtasakor — Kesz, Inditas

Regiszter: H:3007 UInt16 numeric
Értékek / Állapotok: Ready · Trigger
Szerviz műveletek
Kandallo szellozes futasi ido

Kandallo szellozes

Kapcsoló állapot olvasása
MODBUSR(H, 3007,UInt16)
Kapcsoló állapot írása
MODBUSWNE(H, 3007, UInt16, Mu)
Szerviz attribútumok
Fireplace Ventilation Runtime
MODBUSR(H, 1105, Uint32) + " min"
Szerviz műveletek
Fireplace Ventilation Runtime
Paraméterek: duration [0 - 360 min] (0–360 dur)
MODBUSW(H, 1105, Uint32, dur)
Gyors szellozes Többértékű kapcsoló

Ideiglenes nagysebessegu szellozes gyors legcserehez — Kesz, Inditas

Regiszter: H:3006 UInt16 numeric
Értékek / Állapotok: Ready · Trigger
Szerviz műveletek
Gyors szellozes futasi ido

Gyors szellozes

Kapcsoló állapot olvasása
MODBUSR(H, 3006, UInt16)
Kapcsoló állapot írása
MODBUSWNE(H, 3006, UInt16, Mu)
Szerviz attribútumok
Rapid ventilation runtime
MODBUSR(H, 1103, Uint32) + " min"
Szerviz műveletek
Rapid Ventilation Runtime
Paraméterek: Duration [1-360 min] (1–360 dur)
MODBUSW(H, 1103, Uint32, dur)
Kapcsolat: Modbus RTU • 9600 baud• 8E1 • Slave ID: $[SlaveId]
Lehetséges fejlesztések (7)
  • pyflexit CI66 Register Map (Nordic S2–S4, CL2–CL4) — Complete CI66 adapter register map (addresses 0–48) for Nordic models — NOT applicable to EcoNordic which uses proprietary registers
  • H:2013 value 5+ Fume Hood and Calendar Modes — Heat Recovery Ventilation State shows values 5=Fume hood, 6=Fireplace, 7=Temporary high — but Operating Mode (H:2013) only exposes Stop/Away/Home/High (1–4). Fume hood may require separate trigger register
  • unknown Filter Timer / Filter Alarm — CI66 has filter operating hours (reg 8), filter alarm (reg 27), filter alarm period (reg 46). EcoNordic likely has equivalent registers but they are not in the XML template
  • unknown Heat Recovery Efficiency — CI66 exposes heat recovery percentage (0–100%). EcoNordic may have equivalent register — can be calculated from supply/extract/outside temperatures
  • unknown Supply Air Fan Speed — Exhaust fan speed is exposed (H:9) but supply fan speed is missing from the template. EcoNordic likely has this register
  • unknown Heating Circuit Setpoint Temperature — WH4 heating set value and parallel shift for the heat curve — not exposed in the template
  • doc 2882 (404) Full EcoNordic Modbus Register Map — Official Flexit Modbus EcoNordic Basic XLSX register map returned 404 — may contain additional registers not in the XML template