  questions: ["Kako integrirati Systemair SAVE VTR 700 sa sustavom TapHome?","Čime upravlja predložak TapHome Systemair SAVE VTR 700?","Kako spojiti Systemair SAVE VTR 700 na TapHome preko RS-485?","Kako konfigurirati komunikaciju Modbus na jedinicama Systemair SAVE?","Koji su korisnički načini dostupni za Systemair SAVE VTR 700 preko sustava TapHome?","Kako u sustavu TapHome pratiti razinu CO₂ i vlage na jedinici Systemair SAVE?"]
---

# Systemair SAVE VTR 700

Komunikacija: Modbus RTU

- [Službena stranica Systemair](https://www.systemair.com)

## Upute za integraciju

Systemair SAVE VTR 700 je stambeni rekuperator (HRV) koji sa sustavom TapHome komunicira preko Modbus RTU na trožilnoj vezi RS-485 (A, B, GND). Predložak omogućuje upravljanje korisničkim načinima, brzinom ventilatora, načinom ECO i pasivnim hlađenjem te prati temperature, razinu CO₂, vlažnost i broj okretaja ventilatora. Opsežno praćenje alarma javlja više od 30 alarmnih stanja izravno u sustavu TapHome.

SAVE VTR 700 pripada obitelji Systemair SAVE. Ostali modeli SAVE (VSR 300, VSR 500, VTC, VTR) s istom upravljačkom platformom trebali bi biti kompatibilni s ovim predloškom jer dijele istu mapu registara Modbus.

## Hardversko spajanje

### Ožičenje RS-485

Spojite **trožilnu vezu RS-485** na priključnu ploču (Connection Board, CB) unutar jedinice:

- **A** → A+/D+ na TapHome RS-485
- **B** → B-/D- na TapHome RS-485
- **GND** → GND na napajanju TapHome (**obavezno**)

> [!WARNING]
> **Važno: zajednička masa**
>
> Vodič GND **mora** biti spojen između jedinice Systemair i napajanja TapHome. Bez ispravnog spoja mase mogu se pojaviti pogreške u komunikaciji.

### Tehničke specifikacije

- **Protokol:** Modbus RTU Slave, RS-485
- **Brzina prijenosa:** od 9600 do 115200 (podesivo)
- **Zadana brzina prijenosa:** 115200
- **Paritet:** nema, parna ili neparna (podesivo)
- **Stop bitovi:** 1
- **Slave adresa:** 1–247 (podesivo)
- **Svi registri:** 16-bitni cijeli brojevi

## Konfiguracija

### Uključivanje komunikacije Modbus

Modbus RTU je standardno dostupan na priključnoj ploči (CB). Komunikacijski parametri mogu se promijeniti na upravljačkoj ploči jedinice:

1. Otvorite **Service → Communication → Modbus**
2. Postavite **Slave adresu** (zadano: 1)
3. Postavite **brzinu prijenosa** (zadano u predlošku: 115200)
4. Postavite **paritet** (zadano u predlošku: nema)
5. Potvrdite i po potrebi ponovno pokrenite jedinicu

**Za TapHome:** postavite TapHome tako da odgovara postavkama jedinice: 115200 baud, bez pariteta, 1 stop bit, isti Slave ID.

> [!TIP]
> **Alternativa Modbus TCP** — Systemair kao dodatnu opremu nudi Internet Access Module (IAM, art. br. 211243), koji omogućuje pristup Modbus TCP preko Etherneta na portu 502. Može se koristiti umjesto izravnog ožičenja RS-485.

### Inicijalizacijska skripta

Predložak pokreće inicijalizacijsku skriptu koja vrstu regulacije brzine ventilatora postavlja na „Manual %” (H:1273=0) i uključuje otkrivanje zaustavljanja ventilatora (H:1352=1). Ove se postavke primjenjuju automatski kad se TapHome poveže s jedinicom.

## Mogućnosti uređaja

### Upravljanje korisničkim načinom

**Aktivni korisnički način** — prekidač s više vrijednosti koji trenutačni način čita iz I:1160, a promjene načina upisuje preko H:1161. Dostupno je deset načina rada:

| Vrijednost | Način | Opis |
|-------|------|-------------|
| 0 | Auto | Automatska ventilacija prema potrebi (senzori CO₂/RH) |
| 1 | Manual | Stalna brzina ventilatora koju postavlja uređaj Brzina ventilatora |
| 2 | Crowded | Pojačana ventilacija za prostore s mnogo ljudi (na određeno vrijeme) |
| 3 | Refresh | Kratkotrajna najjača ventilacija (na određeno vrijeme) |
| 4 | Fireplace | Smanjeni odsis zraka radi stvaranja nadtlaka za kamin (na određeno vrijeme) |
| 5 | Away | Smanjena ventilacija tijekom odsutnosti (na određeno vrijeme) |
| 6 | Holiday | Najslabija ventilacija za dulju odsutnost (na određeno vrijeme) |
| 7 | Cooker Hood | Pojačani odsis za ventilaciju kuhinje (na određeno vrijeme) |
| 8 | Vacuum Cleaner | Prilagođeni protok zraka za centralni usisavač (na određeno vrijeme) |
| 9 | Pressure Guard | Održava ravnotežu tlaka kad vanjski uređaji utječu na protok zraka |

Svaki način ima podesive brzine dovodnog i odsisnog ventilatora koje se prikazuju kao servisni atributi (ukupno 22). Oni pokazuju stvarni postotak brzine ventilatora dovodnog zraka (SAF) i ventilatora odsisnog zraka (EAF) u svakom načinu.

### Upravljanje brzinom ventilatora

**Brzina ventilatora** — prekidač s više vrijednosti s 4 razine (H:1130) i pretvorbom uz pomak (čitanje: −1, upis: +1):

| Vrijednost | Razina |
|-------|-------|
| 0 | Off |
| 1 | Low |
| 2 | Normal |
| 3 | High |

Brzina ventilatora vrijedi kad je jedinica u načinu Manual. U ostalim načinima brzinu ventilatora određuje konfiguracija aktivnog korisničkog načina.

**Brzina dovodnog ventilatora** i **Brzina odsisnog ventilatora** — uređaji analognog ulaza koji prate trenutačni rad ventilatora. Svaki ima servisni atribut sa stvarnim brojem okretaja ventilatora sa senzora TACHO (I:12400 za dovodni, I:12401 za odsisni).

### Praćenje temperature

Predložak sadrži dva senzora temperature s automatskom pretvorbom °C × 10:

- **Temperatura vanjskog zraka** (H:12101) — temperatura vanjskog zraka sa senzora zaštite od smrzavanja. Servisni atribut: temperatura zraka u prostoriji (I:12103, dodatni senzor)
- **Temperatura dovodnog zraka** (H:12102) — temperatura dovodnog zraka iza izmjenjivača topline. Tri servisna atributa: temperatura odsisnog zraka (I:12104), temperatura zaštite od smrzavanja (I:12100) i temperatura pregrijavanja (I:12107)

### Praćenje kvalitete zraka

- **Najviša razina CO₂** (H:1001) — najviša izmjerena vrijednost od svih spojenih senzora CO₂, u ppm. Pet servisnih atributa prikazuje vrijednosti pojedinih senzora (I:12150–I:12154)
- **Najviša vlažnost** (H:1000) — najviša izmjerena vrijednost od svih spojenih senzora RH, u % (pretvorba vrijednost ÷ 100)

### Način ECO

**Način ECO** (H:2504) — logička sklopka koja uključuje rad s uštedom energije. Kad je aktivan, način ECO smanjuje potrošnju energije za grijanje primjenom podesivog pomaka temperature na zadanu temperaturu grijanja.

- Servisni atribut: **Pomak grijanja u načinu ECO** (H:2503, ÷10, °C) — prikazuje trenutačni pomak
- Servisna radnja: **Postavi pomak temperature** — postavlja pomak grijanja (1–10 °C)

### Pasivno hlađenje

**Uključivanje pasivnog hlađenja** (H:4100) — logička sklopka koja uključuje noćno pasivno hlađenje (free cooling). Kad je vanjska temperatura dovoljno niska, jedinica hladnim vanjskim zrakom unaprijed hladi zgradu bez rada aktivnog sustava hlađenja.

- Servisni atribut: **Pasivno hlađenje aktivno** (I:4110) — pokazuje provodi li se trenutačno pasivno hlađenje

### Praćenje alarma

Modul preko skripte ReadScript prati više od 30 alarmnih stanja. Aktivan alarm javlja se u sustavu TapHome kao pogreška. Praćeni alarmi uključuju:

- **Alarmi ventilatora:** upravljanje SAF/EAF, okretaji SAF/EAF
- **Zaštitni alarmi:** zaštita od smrzavanja, odleđivanje, pregrijavanje, požar
- **Alarmi senzora:** senzori temperature FPT, OAT, SAT, RAT, EAT, ECT, EFT, OHT, EMT
- **Alarmi sustava:** RGS (nadzor rotacije), BYS (bypass), sekundarni zrak, filtar, vanjsko zaustavljanje
- **Alarmi kvalitete zraka:** RH, CO₂, niska SAT
- **Ostalo:** izlazi pod ručnim upravljanjem, senzori PDM, ručno zaustavljanje ventilatora

Servisna radnja **Poništi sve alarme** upisuje vrijednost u svih 30 registara za poništavanje alarma i tako odjednom poništava sva alarmna stanja.

### Servisna dijagnostika

Modul nudi pet servisnih atributa za praćenje stanja sustava:

- **Vrijeme sustava** (H:6001–H:6006) — trenutačni datum i vrijeme u obliku HH:MM DD.MM.YYYY
- **Trenutačno godišnje doba** (H:1038) — Summer ili Winter
- **Razina kvalitete unutarnjeg zraka (IAQ)** (I:1122) — Economic, Good ili Improving
- **Vrsta regulacije brzine ventilatora** (H:1273) — Manual %, Manual RPM, Constant Pressure, Constant Flow ili External
- **Regulacija prema potrebi** (I:1003) — CO₂ ili RH

Dvije servisne radnje omogućuju podešavanje sata jedinice:

- **Postavi datum** — upisuje godinu (2020–2999), mjesec (1–12) i dan (1–31)
- **Postavi vrijeme** — upisuje sat (0–23), minutu (0–59) i sekundu (0–59)

Servisna radnja **Postavi vrstu regulacije brzine ventilatora** omogućuje prebacivanje između načina regulacije Manual %, Manual RPM, Pressure, Flow i External.

### Dodatne mogućnosti

SAVE VTR 700 nudi i registre Modbus za regulaciju zadane temperature (H:2001, raspon 12–30 °C s odabirom regulacije prema dovodnom zraku, prostoriji ili odsisnom zraku), zaseban registar za uključivanje načina ECO, stanje aktivnosti funkcije ECO, stvarne izlazne postotke brzine ventilatora (SAF/EAF 0–100 %), praćenje razdoblja zamjene filtra s preostalim vremenom, zasebne senzore temperature i relativne vlažnosti odsisnog zraka te potpuni tjedni raspored za 7 dana s dva razdoblja dnevno i pomacima temperature. Oni se mogu dodati u budućem ažuriranju predloška.

> [!TIP]
> Registar zadane temperature (H:2001) nije uključen u trenutačni predložak. Za upravljanje zadanom temperaturom dovodnog zraka može se u sustavu TapHome dodati kao vlastiti uređaj Modbus s holding registrom 2001 i rasponom vrijednosti 120–300 (što odgovara 12,0–30,0 °C uz pretvorbu ÷10).

## Rješavanje problema

### Nema komunikacije Modbus

1. **Provjerite kabele RS-485:**
   - A ispravno spojen na A+/D+ na TapHome
   - B ispravno spojen na B-/D- na TapHome
   - **GND spojen na masu napajanja TapHome** — najčešći problem
2. Provjerite odgovara li Slave adresa Modbus na jedinici adresi u sustavu TapHome
3. Provjerite je li TapHome postavljen na 115200 baud, bez pariteta, 1 stop bit (ili na parametre postavljene na jedinici)
4. Provjerite ispravnost spoja stezaljki RS-485 na priključnoj ploči (CB)

### Korisnički način se ne mijenja

1. Provjerite da jedinica nije u načinu na određeno vrijeme (Crowded, Refresh, Fireplace, Away, Holiday) — takav način mora isteći ili se mora ručno prekinuti prije prebacivanja
2. Provjerite reagira li registar za upis (H:1161) — registar za čitanje (I:1160) i registar za upis imaju različite adrese
3. Vrijednost načina 12 (PressureGuard) predložak automatski preslikava na vrijednost 9

### Netočna očitanja temperature

1. Vrijednosti temperature koriste pretvorbu ÷10 — izvorna vrijednost 215 znači 21,5 °C
2. Provjerite je li spojen ispravan senzor: vanjski zrak koristi H:12101 (senzor zaštite od smrzavanja), dovodni zrak H:12102
3. Dodatni senzori (zrak u prostoriji, odsisni zrak) isporučuju se kao dodatna oprema i treba ih ugraditi

## Dostupni uređaji 10

Ovi se uređaji pojavljuju u TapHomeu nakon uvoza.

Systemair SAVE VTR 700 Modul

Servisni atributi

|                                         |
|-----------------------------------------|
| Vrijeme sustava                         |
| Trenutačno godišnje doba                |
| Razina kvalitete unutarnjeg zraka (IAQ) |
| Vrsta regulacije brzine ventilatora     |
| Regulacija prema potrebi                |

Servisne radnje

|                                             |
|---------------------------------------------|
| Postavi datum                               |
| Postavi vrijeme                             |
| Postavi vrstu regulacije brzine ventilatora |
| Poništi sve alarme                          |

Inicijalizacija

```taphome
MODBUSWNE(H, 1273, Uint16, 0);
MODBUSWNE(H, 1352, Uint16, 1);
```

Čitanje (modul)

```taphome
#alarms
IF(MODBUSR(H, 15001, Uint16) = 1, ADDERROR("SAF_CTRL_ALARM"));
IF(MODBUSR(H, 15008, Uint16) = 1, ADDERROR("EAF_CTRL_ALARM"));
IF(MODBUSR(H, 15015, Uint16) = 1, ADDERROR("FROST_PROT_ALARM"));
IF(MODBUSR(H, 15022, Uint16) = 1, ADDERROR("DEFROSTING_ALARM"));
IF(MODBUSR(H, 15029, Uint16) = 1, ADDERROR("SAF_RPM_ALARM"));
IF(MODBUSR(H, 15036, Uint16) = 1, ADDERROR("EAF_RPM_ALARM"));
IF(MODBUSR(H, 15057, Uint16) = 1, ADDERROR("FTP_ALARM"));
IF(MODBUSR(H, 15064, Uint16) = 1, ADDERROR("OAT_ALARM"));
IF(MODBUSR(H, 15071, Uint16) = 1, ADDERROR("SAT_ALARM"));
IF(MODBUSR(H, 15078, Uint16) = 1, ADDERROR("RAT_ALARM"));
IF(MODBUSR(H, 15085, Uint16) = 1, ADDERROR("EAT_ALARM"));
IF(MODBUSR(H, 15092, Uint16) = 1, ADDERROR("ECT_ALARM"));
IF(MODBUSR(H, 15099, Uint16) = 1, ADDERROR("EFT_ALARM"));
IF(MODBUSR(H, 15106, Uint16) = 1, ADDERROR("OHT_ALARM"));
IF(MODBUSR(H, 15113, Uint16) = 1, ADDERROR("EMT_ALARM"));
IF(MODBUSR(H, 15120, Uint16) = 1, ADDERROR("RGS_ALARM"));
IF(MODBUSR(H, 15127, Uint16) = 1, ADDERROR("BYS_ALARM"));
IF(MODBUSR(H, 15134, Uint16) = 1, ADDERROR("SECONDARY_AIR_ALARM"));
IF(MODBUSR(H, 15141, Uint16) = 1, ADDERROR("FILTER_ALARM"));
IF(MODBUSR(H, 15148, Uint16) = 1, ADDERROR("EXTRA_CONTROLLER_ALARM"));
IF(MODBUSR(H, 15155, Uint16) = 1, ADDERROR("EXTERNAL_STOP_ALARM"));
IF(MODBUSR(H, 15162, Uint16) = 1, ADDERROR("RH_ALARM"));
IF(MODBUSR(H, 15169, Uint16) = 1, ADDERROR("CO2_ALARM"));
IF(MODBUSR(H, 15176, Uint16) = 1, ADDERROR("LOW_SAT_ALARM"));
IF(MODBUSR(H, 15501, Uint16) = 1, ADDERROR("MANUAL_OVERRIDE_OUTPUTS_ALARM"));
IF(MODBUSR(H, 15508, Uint16) = 1, ADDERROR("PDM_RHS_ALARM"));
IF(MODBUSR(H, 15515, Uint16) = 1, ADDERROR("PDM_EAT_ALARM"));
IF(MODBUSR(H, 15522, Uint16) = 1, ADDERROR("MANUAL_FAN_STOP_ALARM"));
IF(MODBUSR(H, 15529, Uint16) = 1, ADDERROR("OVERHEAT_TEMPERATURE_ALARM"));
IF(MODBUSR(H, 15536, Uint16) = 1, ADDERROR("FIRE_ALARM"));
```

Servisni atributi

System Time

```taphome
var year := MODBUSR(H, 6000, Uint16);
var month := MODBUSR(H, 6001, Uint16);
var day := MODBUSR(H, 6002, Uint16);
var hour := MODBUSR(H, 6003, Uint16);
var minute := MODBUSR(H, 6004, Uint16);
var second := MODBUSR(H, 6005, Uint16);
RETURN(hour + ":" + minute + "  " 
+ day + ". " + month + ". " + year);
```

Actual season

```taphome
SWITCH(MODBUSR(H, 1038, uint16), 0, "Summer", 1, "Winter", "Error")
```

Indoors IAQ level

```taphome
SWITCH(MODBUSR(A, 1122, Uint16), 0, "Economic", 1, "Good", 2, "Improving", "Error");
```

Type of fan speed regulation

```taphome
SWITCH(MODBUSR(H, 1273, Uint16),
 0, "Manual %",
 1, "Manual RPM",
 2, "Constant Pressure", 
 3, "Constant Flow",
 4, "External",
 "Error");
```

Demand Control

```taphome
SWITCH(MODBUSR(A, 1003, Uint16), 0, "CO₂", 1, "RH", "Error")
```

Servisne radnje

Set Date

Parametri: Year (2020–2999 y), Month (1–12 mo), Day (1–31 da)

```taphome
MODBUSW(H, 6000, Uint16, y);
MODBUSW(H, 6001, Uint16, mo);
MODBUSW(H, 6002, Uint16, da);
```

Set Time

Parametri: Hour (0–23 ho), Minute (0–59 mi), Second (0–59 se)

```taphome
MODBUSW(H, 6003, Uint16, ho);
MODBUSW(H, 6004, Uint16, mi);
MODBUSW(H, 6005, Uint16, se);
```

Set Fan Speed Regulation Type

Parametri: Regulation\_unit

```taphome
MODBUSW(H, 1273, Uint16, ru);
```

Clear all alarms

```taphome
MODBUSW(H, 15002, Uint16, 1);
MODBUSW(H, 15009, Uint16, 1);
MODBUSW(H, 15016, Uint16, 1);
MODBUSW(H, 15023, Uint16, 1);
MODBUSW(H, 15030, Uint16, 1);
MODBUSW(H, 15037, Uint16, 1);
MODBUSW(H, 15058, Uint16, 1);
MODBUSW(H, 15065, Uint16, 1);
MODBUSW(H, 15072, Uint16, 1);
MODBUSW(H, 15079, Uint16, 1);
MODBUSW(H, 15086, Uint16, 1);
MODBUSW(H, 15093, Uint16, 1);
MODBUSW(H, 15100, Uint16, 1);
MODBUSW(H, 15107, Uint16, 1);
MODBUSW(H, 15114, Uint16, 1);
MODBUSW(H, 15121, Uint16, 1);
MODBUSW(H, 15128, Uint16, 1);
MODBUSW(H, 15135, Uint16, 1);
MODBUSW(H, 15142, Uint16, 1);
MODBUSW(H, 15149, Uint16, 1);
MODBUSW(H, 15156, Uint16, 1);
MODBUSW(H, 15163, Uint16, 1);
MODBUSW(H, 15170, Uint16, 1);
MODBUSW(H, 15177, Uint16, 1);
MODBUSW(H, 15184, Uint16, 1);
MODBUSW(H, 15502, Uint16, 1);
MODBUSW(H, 15509, Uint16, 1);
MODBUSW(H, 15510, Uint16, 1);
MODBUSW(H, 15516, Uint16, 1);
MODBUSW(H, 15523, Uint16, 1);
MODBUSW(H, 15530, Uint16, 1);
MODBUSW(H, 15537, Uint16, 1);
MODBUSW(H, 15544, Uint16, 1);
```

Aktivni korisnički način Prekidač s više vrijednosti Čitanje i pisanje

Način rada ventilacije — Auto, Manual, Crowded, Refresh, Fireplace, Away, Holiday, Cooker Hood, Vacuum Cleaner, Pressure Guard

Registar: I:1160 → H:1161 UInt16 multi-value

Vrijednosti / stanja: Auto · Manual · Crowded · Refresh · Fireplace · Away · Holiday

Čitanje stanja sklopke

```taphome
var mod := MODBUSR(A, 1160, uInt16);
if(mod = 12, 9, mod);
```

Zapis stanja sklopke

```taphome
MODBUSWNE(H, 1161 ,Uint16, Mu+1)
```

Servisni atributi

Crowded Supply Speed

```taphome
MODBUSR(A, 1204, Uint16) + " %";
```

Crowded Extract Speed

```taphome
MODBUSR(A, 1205, Uint16) + " %";
```

Refresh Supply Speed

```taphome
MODBUSR(A, 1206, Uint16) + " %";
```

Refresh Extract Speed

```taphome
MODBUSR(A, 1207, Uint16) + " %";
```

Fireplace Supply Speed

```taphome
MODBUSR(A, 1208, Uint16) + " %";
```

Fireplace Extract Speed

```taphome
MODBUSR(A, 1209, Uint16) + " %";
```

Away Supply Speed

```taphome
MODBUSR(A, 1210, Uint16) + " %";
```

Away Extract Speed

```taphome
MODBUSR(A, 1211, Uint16) + " %";
```

Holiday Supply Speed

```taphome
MODBUSR(A, 1212, Uint16) + " %";
```

Holiday Extract Speed

```taphome
MODBUSR(A, 1213, Uint16) + " %";
```

Cooker Supply Speed

```taphome
MODBUSR(A, 1215, Uint16) + " %";
```

Cooker Extract Speed

```taphome
MODBUSR(A, 1216, Uint16) + " %";
```

Vacuum Supply Speed

```taphome
MODBUSR(A, 1217, Uint16) + " %";
```

Vacuum Extract Speed

```taphome
MODBUSR(A, 1218, Uint16) + " %";
```

Supply Active User Mode

```taphome
MODBUSR(A, 1230, Uint16) + " %";
```

Extract Active User Mode

```taphome
MODBUSR(A, 1231, Uint16) + " %";
```

Manual Supply Speed

```taphome
MODBUSR(A, 1200, Uint16) + " %";
```

Manual Extract Speed

```taphome
MODBUSR(A, 1201, Uint16) + " %";
```

Auto Supply Speed

```taphome
MODBUSR(A, 1202, Uint16) + " %";
```

Auto Extract Speed

```taphome
MODBUSR(A, 1203, Uint16) + " %";
```

Low Fan Supply Speed

```taphome
MODBUSR(A, 1218, Uint16) + " %";
```

Low Fan Extract Speed

```taphome
MODBUSR(A, 1219, Uint16) + " %";
```

Način ECO Sklopka Čitanje i pisanje

Način uštede energije — smanjuje grijanje primjenom podesivog pomaka temperature

Registar: H:2504 Bool

Vrijednosti / stanja: ON · OFF

Servisne radnje

|                                 |
|---------------------------------|
| Postavi pomak temperature \[°C] |

Čitanje stanja sklopke

```taphome
MODBUSR(H, 2504, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 2504, Bool, St)
```

Servisni atributi

Heating offset during ECO mode

```taphome
MODBUSR(H, 2503, Uint16)/10 + " °C";
```

Servisne radnje

Set temperature offset \[°C]

Parametri: Offset (1–10 off)

```taphome
MODBUSW(H, 2503, Uint16, off*10);
```

Brzina odsisnog ventilatora Analogni ulaz Samo za čitanje

Brzina ventilatora odsisnog zraka s praćenjem broja okretaja sa senzora TACHO

UInt16 numeric

Servisni atributi

|                                       |
|---------------------------------------|
| Okretaji odsisnog ventilatora (r/min) |

Čitanje razine ulaza

```taphome
MODBUSR(H, 14001, uint16)/100
```

Servisni atributi

Extract Fan r/min

```taphome
MODBUSR(A, 12401, Uint16) + " rpm";
```

Brzina ventilatora Prekidač s više vrijednosti Čitanje i pisanje

Razina brzine ventilatora u načinu Manual — Off, Low, Normal, High

Registar: H:1130 UInt16 multi-value

Vrijednosti / stanja: ${level\_0Of3} · ${level\_1Of3} · Normal · ${level\_3Of3}

Čitanje stanja sklopke

```taphome
MODBUSR(H, 1130, Uint16)-1
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 1130, Uint16, Mu+1)
```

Uključivanje pasivnog hlađenja Sklopka Čitanje i pisanje

Noćno pasivno hlađenje vanjskim zrakom za prethodno hlađenje zgrade

Registar: H:4100 Bool

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 4100, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 4100, Bool, St)
```

Servisni atributi

Free Cooling Active

```taphome
IF(MODBUSR(A, 4110, Uint16) = 1, "Yes", "No")
```

Najviša razina CO₂ Varijabla Samo za čitanje

Najviša izmjerena vrijednost CO₂ od svih spojenih senzora, s vrijednostima pojedinih senzora

Registar: H:1001 UInt16 Jedinica: ppm numeric

Servisni atributi

|          |
|----------|
| Senzor 1 |
| Senzor 2 |
| Senzor 3 |
| Senzor 4 |
| Senzor 5 |

Čitanje

```taphome
MODBUSR(H, 1001, Uint16)
```

Servisni atributi

Sensor 1

```taphome
MODBUSR(A, 12150, Uint16) + " ppm";
```

Sensor 2

```taphome
MODBUSR(A, 12151, Uint16) + " ppm";
```

Sensor 3

```taphome
MODBUSR(A, 12152, Uint16) + " ppm";
```

Sensor 4

```taphome
MODBUSR(A, 12153, Uint16) + " ppm";
```

Sensor 5

```taphome
MODBUSR(A, 12154, Uint16) + " ppm";
```

Najviša vlažnost Varijabla Samo za čitanje

Najviša izmjerena relativna vlažnost od svih spojenih senzora RH

Registar: H:1000 UInt16 Jedinica: % numeric

Čitanje

```taphome
MODBUSR(H, 1000, UInt16)/100
```

Temperatura vanjskog zraka Senzor temperature Samo za čitanje

Registar: H:12101 Int16 Jedinica: °C numeric

Servisni atributi

|                                       |
|---------------------------------------|
| Senzor temperature zraka u prostoriji |

Čitanje temperature

```taphome
MODBUSR(H, 12101, Int16) / 10
```

Servisni atributi

Room Air Temperature sensor

```taphome
MODBUSR(A, 12103, Uint16)/10 + "°C";
```

Temperatura dovodnog zraka Senzor temperature Samo za čitanje

Registar: H:12102 Int16 Jedinica: °C numeric

Servisni atributi

|                                          |
|------------------------------------------|
| Senzor temperature odsisnog zraka        |
| Senzor temperature zaštite od smrzavanja |
| Senzor temperature pregrijavanja         |

Čitanje temperature

```taphome
MODBUSR(H, 12102, Int16) / 10
```

Servisni atributi

Extract Air Temperature sensor

```taphome
MODBUSR(A, 12104, Uint16)/10 + "°C";
```

Frost Protection Temperature Sensor

```taphome
MODBUSR(A, 12100, Uint16)/10 + "°C";
```

Overheat Temperature sensor

```taphome
MODBUSR(A, 12107, Uint16)/10 + "°C";
```

Brzina dovodnog ventilatora Analogni ulaz Samo za čitanje

Brzina ventilatora dovodnog zraka s praćenjem broja okretaja sa senzora TACHO

UInt16 numeric

Servisni atributi

|                                       |
|---------------------------------------|
| Okretaji dovodnog ventilatora (r/min) |

Čitanje razine ulaza

```taphome
MODBUSR(H, 14000, Uint16)/100
```

Servisni atributi

Supply fan r/min

```taphome
MODBUSR(A, 12400, Uint16) + " rpm"
```

**Povezivanje:** Modbus RTU • 115200 baud• 8N1 • Slave ID: $\[SlaveId]

Moguća poboljšanja (11)

- H:2001 Temperature Setpoint — REG\_TC\_SP (H:2001, 12.0–30.0°C, /10 conversion) — primary temperature setpoint for supply air temperature control
- H:2031 Temperature Control Mode — REG\_TC\_CONTROL\_MODE (H:2031); 0=Supply, 1=Room, 2=Extract — selects which temperature sensor drives the control loop
- H:1162 User Mode Change Request — REG\_USERMODE\_HMI\_CHANGE\_REQUEST (H:1162); direct mode switch 0–7 without multi-value switch — alternative to Active User Mode device
- I:1111/1112 User Mode Remaining Time — 32-bit value (low + high word) showing remaining time for timed user modes (Holiday, Away, Fireplace, Refresh, Crowded)
- H:2505 ECO Mode Enable — REG\_ECO\_MODE\_ON\_OFF (H:2505); separate from ECO offset — template uses H:2504 (offset) as the switch
- I:2506 ECO Function Active — REG\_ECO\_FUNCTION\_ACTIVE (I:2506); indicates if ECO mode conditions are currently met
- I:14001/14002 SAF/EAF Fan Speed Output — REG\_OUTPUT\_SAF (I:14001) and REG\_OUTPUT\_EAF (I:14002); actual fan speed output 0–100%
- H:7001 Filter Replacement Period — REG\_FILTER\_PERIOD (H:7001, 3–15 months) and remaining time (I:7005/7006) — filter maintenance tracking
- I:12105 Extract Air Temperature — REG\_SENSOR\_EAT (H:12105, /10 °C); extract air temperature — available as accessory sensor
- I:12109 Relative Humidity Sensor — REG\_SENSOR\_RHS (H:12109, 0–100%); relative humidity — accessory sensor, useful alongside Highest Humidity device
- H:5001–5114 Week Schedule — Complete 7-day, 2-period schedule with temperature offsets and fan levels — complex multi-register configuration

## Parametri uvoza

Ove vrijednosti unosite pri uvozu XML-a.

| Pitanje u aplikaciji | Zadano        |
|----------------------|---------------|
| Slave ID             | `1`           |
| IP adresa            | `192.168.1.0` |

## Izvori

- Systemair SAVE Modbus Variable List Rev.36
  
  2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/systemair-save-vtr-700/manufacturer/SAVE_MODBUS_VARIABLE_LIST_REV36.pdf)
- Home Assistant Systemair Integration
  
  [github.com](https://github.com/an3orik/systemair) 2026-03-20

Dokumenti proizvođača zaštićeni su autorskim pravom (©) svojih vlasnika. Dostupni su onako kako ih je proizvođač objavio, samo za informaciju.

## Povezana dokumentacija

- [Modbus Integration](https://taphome.com/hr/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/hr/docs/integration/modbus/)
- [Jednostavna konfiguracija pomoću predložaka](https://taphome.com/hr/docs/integration/modbus/templates/)
- [Skripte Modbus i prefetch](https://taphome.com/hr/docs/script/modbus-scripts/)
- [Funkcije Modbus](https://taphome.com/hr/docs/script/modbus/)
- [Tipovi podataka Modbus](https://taphome.com/hr/docs/script/modbus-data-types/)