  questions: ["Kako integrirati Komfovent DOMEKT sa sustavom TapHome?","Čime upravlja predložak TapHome Komfovent Air Recovery?","Kako spojiti regulator Komfovent C6/C6M na TapHome preko RS-485?","Kako konfigurirati postavke Modbus RTU na regulatoru Komfovent C6?","Kako preko sustava TapHome mijenjati načine ventilacije na uređaju Komfovent?","Kako preko sustava TapHome pratiti potrošnju energije i stanje filtra na uređaju Komfovent?"]
---

# Komfovent Air Recovery

Komunikacija: Modbus RTU

- [Stranica proizvoda Komfovent DOMEKT](https://www.komfovent.com/en/c-page/products/air-handling-units/domekt-residential-ventilation-units)
- [Službena stranica Komfovent](https://www.komfovent.com)

## Upute za integraciju

Predložak Komfovent Air Recovery povezuje stambene ventilacijske jedinice DOMEKT s regulatorom C6 ili C6M sa sustavom TapHome preko Modbus RTU na RS-485. Predložak omogućuje odabir načina ventilacije, podešavanje zadane temperature, uključivanje načina ECO, praćenje temperature (odsisnog i vanjskog zraka), mjerenje potrošnje energije i održavanje filtra.

Kompatibilni modeli su DOMEKT R 450 V, DOMEKT R 400 V, DOMEKT R 400 H, DOMEKT CF 400 V i DOMEKT CF 500 F, odnosno svaka jedinica DOMEKT s regulatorom C6 ili C6M.

## Hardversko spajanje

### Fizičko spajanje

Regulator C6/C6M ima stezaljke za vanjske priključke u upravljačkoj kutiji ventilacijske jedinice. Sučelje RS-485 Modbus RTU koristi stezaljke **A** (stezaljka 1 na C6, stezaljka 41 na C6M) i **B** (stezaljka 2 na C6, stezaljka 42 na C6M).

![Regulatori Komfovent C6 i C6M sa stezaljkama za spajanje](https://taphome.com/images/compatibility/komfovent-air-recovery/controller-terminals_hu_1475247556964512.jpg)

### Shema spajanja C6

![Shema spajanja vanjskih elemenata na Komfovent C6 s RS-485, senzorima, ulazima i izlazima](https://taphome.com/images/compatibility/komfovent-air-recovery/wiring-c6-terminals_hu_ee6049e54cbfa979.jpg)

### Shema spajanja C6M

![Shema spajanja vanjskih elemenata na Komfovent C6M sa stezaljkama RS-485 41-42](https://taphome.com/images/compatibility/komfovent-air-recovery/wiring-c6m-p005_hu_565fdaf33397514d.jpg)

### Ožičenje RS-485

Za spajanje koristite **upredenu paricu**:

- **Stezaljka A** → A+/D+ na TapHome RS-485
- **Stezaljka B** → B-/D- na TapHome RS-485

| Parametar | Vrijednost |
|-----------|-------|
| Vrsta kabela | Upredena parica (preporučeno CAT5) |
| Najveća duljina kabela | **150 m** |

> [!WARNING]
> **Važno: zajednička masa**
>
> Ako je udaljenost između sučelja RS-485 veća od **10 m**, točka mase regulatora C6/C6M i točka mase TapHome **moraju** biti međusobno spojene. Bez ispravnog spoja mase mogu se pojaviti pogreške u komunikaciji.

## Konfiguracija

### Postavke Modbus RTU

Zadane postavke sučelja RS-485:

| Parametar | Zadana vrijednost |
|-----------|---------------|
| Brzina prijenosa | **19200** |
| Duljina riječi | 8 |
| Paritet | **parna (Even)** |
| Stop bitovi | 1 |
| Slave ID | **254** |

Ove postavke mogu se promijeniti u web-sučelju regulatora C6/C6M. U pregledniku otvorite zadanu IP adresu regulatora **192.168.0.60**. Prijavite se korisničkim imenom `user` i lozinkom `user`. U izborniku **Settings → Connectivity** pronađite i promijenite postavke sučelja RS-485 i ID protokola Modbus RTUla.

![Postavke povezivanja u web-sučelju Komfovent C6 s Modbus ID-om, brzinom prijenosa RS-485 i paritetom](https://taphome.com/images/compatibility/komfovent-air-recovery/web-settings-p003_hu_7e7ec5178aaea75.jpg)

IP adresu i mrežnu masku moguće je promijeniti i na **dodirnom panelu C6.1**: pritisnite tipku **Menu**, zatim pritisnite i držite tipku **Settings** dulje od 5 sekundi da se otvori prozor **Advanced Settings**. Odaberite **Connectivity** za pregled i uređivanje mrežnih parametara.

### Konfiguracija u sustavu TapHome

Pri uvozu predloška u TapHome potrebna su dva parametra:

- **Slave ID** — mora odgovarati Modbus ID-u postavljenom na regulatoru (zadano: **254**)
- **IP adresa** — koristi se za TCP veze (zadano: **192.168.0.1**). Za RTU vezu preko RS-485 ovaj se parametar ne koristi

> [!TIP]
> Najkraći interval očitavanja treba biti **najmanje 500 ms**. Kad je više jedinica Komfovent spojeno na istu Modbus mrežu, preporučuje se interval očitavanja od najmanje **1 sekunde**.

### Praćenje alarma

Skripta ReadScript modula predloška prati aktivne alarme čitanjem registara H:599–H:609. Kad su alarmi aktivni, TapHome ih prikazuje kao pogreške s brojem alarma i pojedinačnim kodovima alarma. Kodovi alarma prate kodiranje Komfovent: kodovi tipa F (1–127) označavaju alarme kvara, a kodovi tipa W (129–255) alarme upozorenja.

Za poništavanje aktivnih alarma upišite vrijednost `0x9C5` u registar H:600 preko sustava TapHome.

### Inicijalizacijska skripta

Inicijalizacijska skripta predloška postavlja jedinicu protoka na **m3/h** (registar H:27 = 0) kako bi očitanja protoka zraka na svim uređajima bila ujednačena.

## Mogućnosti uređaja

### Pregled sustava

![Pregled sustava Komfovent C6/C6M s mapom registara za dijelove ventilacijske jedinice](https://taphome.com/images/compatibility/komfovent-air-recovery/system-diagram-p006_hu_cf38ec7254e908bb.jpg)

### Uključivanje i isključivanje

- **ON/OFF** (H:0) — glavna sklopka ventilacijske jedinice. Upis vrijednosti 1 uključuje jedinicu, a 0 je isključuje.

### Način ventilacije

**Način ventilacije** (H:4) odabire aktivni način rada preko prekidača s više vrijednosti s 10 mogućnosti:

- **Stanje pripravnosti** (0) — jedinica u stanju pripravnosti
- **Odsutnost** (1) — slaba ventilacija kad nikoga nema
- **Normalno** (2) — uobičajena svakodnevna ventilacija
- **Intenzivno** (3) — pojačana ventilacija pri većoj potrebi
- **Boost** (4) — najjača ventilacija
- **Kuhinja** (5), **Kamin** (6), **Prednost** (7), **Odmor** (8) — posebni načini
- **Kvaliteta zraka** (9) — ventilacija prema senzorima

Pri upisu načina 1–4 (Odsutnost, Normalno, Intenzivno, Boost) predložak automatski postavlja i odgovarajuće postotke protoka dovodnog i odsisnog zraka (redom 20 %, 50 %, 70 % i 100 %).

Svaki način ima podesive parametre dostupne preko **servisnih radnji** (Postavi Odsutnost, Postavi Normalno, Postavi Intenzivno, Postavi Boost):
- **Protok dovodnog zraka** (m3/h)
- **Protok odsisnog zraka** (m3/h)
- **Zadana temperatura** (°C, raspon 5–40)
- **Grijanje** (uklj./isklj.)

**19 servisnih atributa** prikazuje trenutačne postavke za sva četiri podesiva načina (protok dovodnog/odsisnog zraka, zadana temperatura, grijanje za Odsutnost, Normalno, Intenzivno i Boost) te sljedeći planirani način, njegovo vrijeme početka i dan u tjednu.

### Načini AUTO i ECO

- **Način AUTO** (H:3) — uključuje automatsku ventilaciju kojom upravlja raspored ili senzori kvalitete zraka. Dva servisna atributa prikazuju trenutačni izvor upravljanja načinom AUTO (raspored ili kvaliteta zraka) i aktivni program rasporeda (Kod kuće, Radni tjedan, Ured, Prilagođeno). Servisna radnja omogućuje promjenu programa rasporeda.

- **Način ECO** (H:2) — uključuje način uštede energije s ograničenjima temperature dovodnog zraka i mogućim pasivnim grijanjem/hlađenjem. Šest servisnih atributa prikazuje trenutačne postavke načina ECO (minimalna/maksimalna temperatura dovodnog zraka, pasivno grijanje/hlađenje, grijanje zabranjeno, hlađenje zabranjeno, stalni povrat topline). Servisna radnja **Postavke načina ECO** postavlja sve parametre odjednom.

### Praćenje temperature

- **Temperatura odsisnog zraka** (H:902) — senzor temperature odsisnog zraka s pretvorbom /10 u °C. Tri servisna atributa prikazuju trenutačni protok odsisnog zraka (m3/h), intenzitet odsisnog ventilatora (%) i tlak odsisnog zraka (Pa).

- **Vanjska temperatura** (H:903) — senzor temperature vanjskog zraka s pretvorbom /10 u °C.

- **Zadana temperatura (Normalno)** — termostat koji čita trenutačnu temperaturu iz H:902 (/10 °C) te čita i upisuje zadanu temperaturu za način Normalno preko H:109 (/10 °C, raspon 5–40 °C). Dva servisna atributa prikazuju način regulacije temperature (dovodni zrak, odsisni zrak, ravnoteža, prostorija) i izvor sobnog senzora (panel 1 ili panel 2). Servisne radnje omogućuju promjenu obiju postavki.

### Upravljanje snagom povrata topline

**Upravljanje snagom povrata topline** — dimer za upravljanje razinom snage povrata topline. To je uređaj bez dovršene konfiguracije, pa može zahtijevati ručno podešavanje skripti za čitanje i upis u sustavu TapHome.

### Potrošnja energije

**Potrošnja energije** (H:930) — brojilo koje čita ukupnu potrošnju energije iz H:930 (UInt32, Wh → kWh s pretvorbom /1000) i trenutačnu snagu iz H:920 (UInt16, W → kW s pretvorbom /1000).

### Održavanje filtra

**Filtar** — prati stanje filtra i ima servisnu radnju **Poništavanje brojača filtra** koja upisuje vrijednost 1 u registar H:1050 i tako poništava brojač začepljenosti filtra. Poništavanje radi samo ako je zaprljanost filtra veća od 1 %.

### Servisni atributi modula

Modul predloška daje osam servisnih atributa:

- **Vrijeme sustava** — trenutačni datum i vrijeme iz regulatora (H:28–H:31)
- **Dan u tjednu** — trenutačni dan u tjednu
- **DHCP** — stanje DHCP-a (uklj./isklj.), sa servisnom radnjom za uključivanje i isključivanje
- **IP adresa**, **Mrežna maska**, **Pristupnik** — trenutačna mrežna konfiguracija
- **Ponovno pokretanje nakon požarnog alarma** — način ponovnog pokretanja (ručno/automatski), sa servisnom radnjom za promjenu
- **Jedinice protoka** — trenutačna jedinica protoka zraka (m3/h ili l/s)

### Dodatne mogućnosti

Regulator C6/C6M daje i registre za vanjsku temperaturu (H:904), temperaturu vode (H:905), temperaturu otpadnog zraka (H:961), razinu i učinkovitost izmjenjivača topline (H:912, H:924), razine električnog/vodenog grijača i hladnjaka (H:913–H:916), postotak zaprljanosti filtra (H:917), sobnu temperaturu i vlažnost na panelu (H:946–H:951), senzore kvalitete zraka (H:952–H:953), statusnu bitmasku (H:900), trenutačnu snagu (H:921), način regulacije protoka (H:12), postavke kvalitete zraka (H:205–H:214) i opsežno programiranje rasporeda (H:300–H:555). Mogu se dodati u budućem ažuriranju predloška.

> [!TIP]
> Razina zaprljanosti filtra dostupna je u registru H:917 (0–100 %), ali uređaj Filtar u predlošku nema postavljenu skriptu za čitanje. Za praćenje začepljenosti filtra dodajte prilagođeni Modbus uređaj koji čita H:917 kao UInt8.

## Rješavanje problema

### Nema Modbus komunikacije

1. **Provjerite kabele RS-485:**
   - Stezaljka A ispravno spojena na A+/D+ na TapHome
   - Stezaljka B ispravno spojena na B-/D- na TapHome
   - **Masa spojena** ako je kabel dulji od 10 m
2. Provjerite odgovara li Slave ID Modbus ID-u u web-sučelju regulatora (zadano: 254)
3. Provjerite je li TapHome postavljen na: **19200 baud, parni paritet, 1 stop bit, 8 podatkovnih bitova**
4. Provjerite je li najkraći interval očitavanja najmanje 500 ms (1 s kod više jedinica)

### Web-sučelje nije dostupno

1. Provjerite jesu li uređaj i računalo u **istoj podmreži** (zadana IP adresa regulatora: 192.168.0.60)
2. Ako je spoj izravan, isključite DHCP i postavite statičku IP adresu u istoj podmreži (npr. 192.168.0.61)
3. Provjerite je li u pregledniku uključen JavaScript
4. Provjerite da vezu ne blokira proxy poslužitelj ni vatrozid

### Očitanja temperature pokazuju netočne vrijednosti

1. Provjerite jesu li jedinice protoka postavljene na m3/h (registar H:27 = 0) — inicijalizacijska skripta predloška to postavlja automatski
2. Provjerite odgovara li način regulacije temperature (H:10) očekivanom izvoru senzora
3. Imajte na umu da registri temperature koriste kodiranje ×10 (npr. 215 = 21,5 °C)

### Kodovi alarma

Kodovi alarma koje prikazuje TapHome koriste kodiranje Komfovent. Alarmi kvara (tip F) imaju kodove 1–127, a alarmi upozorenja (tip W) kodove 129–255. Česti kodovi:

| Kod | Tip | Poruka |
|------|------|---------|
| 1 | F1 | Protok dovodnog zraka nije postignut |
| 2 | F2 | Protok otpadnog zraka nije postignut |
| 3 | F3 | Temperatura vode B5 preniska |
| 9 | F9 | Unutarnji požar |
| 10 | F10 | Vanjski požar |
| 129 | W1 | Zamijenite filtar zraka |
| 130 | W2 | Servisni način |

Potpuni popis kodova alarma nalazi se u priručniku Komfovent C6/C6M Modbus.

## Dostupni uređaji 10

Ovi se uređaji pojavljuju u TapHomeu nakon uvoza.

Komfovent Air Recovery Modul

Servisni atributi

|                                          |
|------------------------------------------|
| Vrijeme sustava                          |
| Dan u tjednu                             |
| DHCP                                     |
| IP adresa                                |
| Mrežna maska                             |
| Pristupnik                               |
| Ponovno pokretanje nakon požarnog alarma |
| Jedinice protoka                         |

Servisne radnje

|                                                    |
|----------------------------------------------------|
| DHCP                                               |
| Postavka ponovnog pokretanja nakon požarnog alarma |

Inicijalizacija

```taphome
MODBUSWNE(H, 27, Uint16, 0);
```

Čitanje (modul)

```taphome
var alarm:= MODBUSR(H, 599, Uint16);
If(alarm>0, ADDERROR("There are " + alarm + " active alarms"));
If(alarm>0, ADDERROR(MODBUSR(H, 600, Uint16), "Alarm 1 active"));
If(alarm>1, ADDERROR(MODBUSR(H, 601, Uint16), "Alarm 2 active"));
If(alarm>2, ADDERROR(MODBUSR(H, 602, Uint16), "Alarm 3 active"));
If(alarm>3, ADDERROR(MODBUSR(H, 603, Uint16), "Alarm 4 active"));
If(alarm>4, ADDERROR(MODBUSR(H, 604, Uint16), "Alarm 5 active"));
If(alarm>5, ADDERROR(MODBUSR(H, 605, Uint16), "Alarm 6 active"));
If(alarm>6, ADDERROR(MODBUSR(H, 606, Uint16), "Alarm 7 active"));
If(alarm>7, ADDERROR(MODBUSR(H, 607, Uint16), "Alarm 8 active"));
If(alarm>8, ADDERROR(MODBUSR(H, 608, Uint16), "Alarm 9 active"));
If(alarm>9, ADDERROR(MODBUSR(H, 609, Uint16), "Alarm 10 active"));
```

Servisni atributi

System Time

```taphome
var time := MODBUSR(H, 28, Uint16);
var date := MODBUSR(H, 30, Uint16);

GETBITS(time, 8,8) + ":" + GETBITS(time, 0, 8) + " " + GETBITS(date, 0,8) + "." + GETBITS(date, 8,8) + "." + MODBUSR(H, 29, Uint16);
```

Weekday

```taphome
SWITCH(MODBUSR(H, 31, Uint16), 
1,"Monday",
2,"Tuesday",
3,"Wednesday",
4,"Thursday",
5,"Friday",
6,"Saturday",
7,"Sunday",
"Error"
)
```

DHCP

```taphome
IF(MODBUSR(H, 34, Bool), "On", "Off"); 
```

IP adress

```taphome
var reg := MODBUSR(H, 22, Uint32);
var first := GETBITS(reg, 0, 8);
var second := GETBITS(reg, 8, 8);
var third := GETBITS(reg, 16, 8);
var last := GETBITS(reg, 24, 8);
RETURN (last + "." + third + "." + second + "." + first)
```

Mask

```taphome
var reg := MODBUSR(H, 24, Uint32);
var first := GETBITS(reg, 0, 8);
var second := GETBITS(reg, 8, 8);
var third := GETBITS(reg, 16, 8);
var last := GETBITS(reg, 24, 8);
RETURN (last + "." + third + "." + second + "." + first)
```

Gateway

```taphome
var reg := MODBUSR(H, 26, Uint32);
var first := GETBITS(reg, 0, 8);
var second := GETBITS(reg, 8, 8);
var third := GETBITS(reg, 16, 8);
var last := GETBITS(reg, 24, 8);
RETURN (last + "." + third + "." + second + "." + first)
```

Fire Alarm Restart

```taphome
SWITCH(MODBUSR(H, 41, Uint16), 
1, "Auto",
0, "Manual",
"Error");
```

Flow units

```taphome
SWITCH(MODBUSR(H, 27, Uint16),
 1, "l/s",
 0, "m3/h",
 "Error");
```

Servisne radnje

DHCP

Parametri: DHCP (On / Off)

```taphome
MODBUSW(H, 34, Bool, dhcp);
```

Fire Alarm Restart Setting

Parametri: Restart setting (Auto / Manual)

```taphome
MODBUSW(H, 41, Bool, rs);
```

Način AUTO Sklopka Čitanje i pisanje

Automatski način ventilacije — prema programu rasporeda ili prema senzoru kvalitete zraka

Registar: H:3 Bool

Vrijednosti / stanja: ON · OFF

Servisne radnje

|                   |
|-------------------|
| Program rasporeda |

Čitanje stanja sklopke

```taphome
MODBUSR(H, 3, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 3, Bool, St)
```

Servisni atributi

Auto Mode Control

```taphome
SWITCH(MODBUSR(H, 1, Uint16), 1, "Air Quality", 0, "Scheduling", "Error");
```

Scheduler Operation Mode

```taphome
SWITCH(MODBUSR(H, 5, Uint16),
0, "Stay at home",
1, "Working Week",
2, "Office",
3, "Custom",
"Error"
);
```

Servisne radnje

Scheduler Operation Mode

Parametri: Scheduler Operation Mode

```taphome
MODBUSW(H, 5, Uint16, som);
```

Način ECO Sklopka Čitanje i pisanje

Način uštede energije s ograničenjima temperature dovodnog zraka i mogućim pasivnim grijanjem/hlađenjem

Registar: H:2 Bool

Vrijednosti / stanja: ON · OFF

Servisne radnje

|                     |
|---------------------|
| Postavke načina ECO |

Čitanje stanja sklopke

```taphome
MODBUSR(H, 2, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 2, Bool, St)
```

Servisni atributi

Minimum supply air temperature

```taphome
MODBUSR(H, 199, Uint16)/10 + " °C";
```

Maximum supply air temperature

```taphome
MODBUSR(H, 200, Uint16)/10 + " °C";
```

Free heating/cooling

```taphome
SWITCH(MODBUSR(H, 201, Uint16), 0, "Off", 1,"On", "Error");
```

Heating enable denied

```taphome
SWITCH(MODBUSR(H, 202, Uint16), 0, "Off", 1,"On", "Error");
```

Cooling enable denied

```taphome
SWITCH(MODBUSR(H, 203, Uint16), 0, "Off", 1,"On", "Error");
```

Constant heat recovery

```taphome
SWITCH(MODBUSR(H, 216, Uint16), 0, "Off", 1,"On", "Error");
```

Servisne radnje

Eco mode setup

Parametri: Minimum supply air temp (5–40 minAirT), Maximum Supply Air Temp (5–40 maxAirT), Free Heating/Cooling (${general\_on} / ${general\_off}), Heating enable denied (${general\_on} / ${general\_off}), Cooling enable denied (${general\_on} / ${general\_off}), Constant Heat Recovery (${general\_on} / ${general\_off})

```taphome
MODBUSWNE(H, 199, Uint16, minAirT*10);
MODBUSWNE(H, 200, Uint16, maxAirT*10);
MODBUSWNE(H, 201, Uint16, freeHT);
MODBUSWNE(H, 202, Uint16, hed);
MODBUSWNE(H, 203, Uint16, ced);
MODBUSWNE(H, 216, Uint16, chr);
```

Temperatura odsisnog zraka Senzor temperature Samo za čitanje

Temperatura odsisnog zraka iz ventilacijske jedinice s praćenjem protoka odsisnog zraka i intenziteta ventilatora

Registar: H:902 Int16 Jedinica: °C numeric

Servisni atributi

|                                            |
|--------------------------------------------|
| Trenutačni protok odsisnog zraka           |
| Trenutačni intenzitet odsisnog ventilatora |
| Tlak odsisnog zraka                        |

Čitanje temperature

```taphome
MODBUSR(H, 902, Int16) / 10
```

Servisni atributi

Current extract flow

```taphome
MODBUSR(H, 907, Uint32) +  " m3/h"
```

Current extract fan intesivity

```taphome
MODBUSR(H, 910, Uint16)/10 + " %"
```

Extract Pressure

```taphome
MODBUSR(H, 919, Uint16) + " Pa";
```

Način ventilacije Prekidač s više vrijednosti Čitanje i pisanje

Odabir načina rada — stanje pripravnosti, odsutnost, normalno, intenzivno, Boost, kuhinja, kamin, prednost, odmor, kvaliteta zraka

Registar: H:4 UInt16 multi\_value

Vrijednosti / stanja: Standby · •Away · •Normal · •Intensive · •Boost

Servisne radnje

|                    |
|--------------------|
| Postavi Odsutnost  |
| Postavi Normalno   |
| Postavi Intenzivno |
| Postavi Boost      |

Čitanje stanja sklopke

```taphome
MODBUSR(H, 4, UInt16)
```

Zapis stanja sklopke

```taphome
SWITCH(Mu,
0, 0,
5,5,
6,6,
7,7,
8,8,
9,9,
10,10,
MODBUSW(H, 4, UInt16, Mu));

IF(Mu = 1, MODBUSW(H, 99, Uint32, 20));
IF(Mu = 1, MODBUSW(H, 101, Uint32, 20));
IF(Mu = 2, MODBUSW(H, 105, Uint32, 50));
IF(Mu = 2, MODBUSW(H, 107, Uint32, 50));
IF(Mu = 3, MODBUSW(H, 111, Uint32, 70));
IF(Mu = 3, MODBUSW(H, 113, Uint32, 70));
IF(Mu = 4, MODBUSW(H, 117, Uint32, 100));
IF(Mu = 4, MODBUSW(H, 119, Uint32, 100));
```

Servisni atributi

Next Mode

```taphome
SWITCH(MODBUSR(H, 6, Uint16),
0,"Standby",
1, "Away",
2, "Normal",
3, "Intensive",
4, "Boost",
5, "Kitchen",
6, "Fireplace",
7, "Override",
8, "Holidays",
"Error"
);
```

Next Mode Start Time

```taphome
var time:= MODBUSR(H, 7, Uint16);
var hours:= FLOOR(time/60);
var minutes:= MOD(time, 60);
IF(time = 0, RETURN ("Not set"));
RETURN (hours + ":"+ minutes);
```

Next Mode Weekday

```taphome
SWITCH(MODBUSR(H, 8, Uint16), 
0, "None",
1, "Monday",
2, "Tuesday",
3, "Wednesday",
4, "Thursday",
5, "Friday",
6, "Saturday",
7, "Sunday",
"Error"
);
```

Away Supply flow

```taphome
MODBUSR(H, 99, Uint32) + " %";
```

Away Extract flow

```taphome
MODBUSR(H, 101, Uint32) + " %";
```

Away Setpoint

```taphome
MODBUSR(H, 103, Int16)/10 + " °C";
```

Away Heating

```taphome
SWITCH(MODBUSR(H, 104, Uint16), 1, "On", 0, "Off", "Error");
```

Normal Supply flow

```taphome
MODBUSR(H, 105, Uint32) + " %";
```

Normal Extract flow

```taphome
MODBUSR(H, 107, Uint32) + " %";
```

Normal Setpoint

```taphome
MODBUSR(H, 109, Int16)/10 + " °C";
```

Normal Heating

```taphome
SWITCH(MODBUSR(H, 110, Uint16), 1, "On", 0, "Off", "Error");
```

Intensive Supply flow

```taphome
MODBUSR(H, 111, Uint32) + " %";
```

Intensive Extract flow

```taphome
MODBUSR(H, 113, Uint32) + " %";
```

Intensive Setpoint

```taphome
MODBUSR(H, 115, Int16)/10 + " °C";
```

Intensive Heating

```taphome
SWITCH(MODBUSR(H, 116, Uint16), 1, "On", 0, "Off", "Error");
```

Boost Supply flow

```taphome
MODBUSR(H, 117, Uint32) + " %";
```

Boost Extract flow

```taphome
MODBUSR(H, 119, Uint32) + " %";
```

Boost Setpoint

```taphome
MODBUSR(H, 121, Int16)/10 + " °C";
```

Boost Heating

```taphome
SWITCH(MODBUSR(H, 122, Uint16), 1, "On", 0, "Off", "Error");
```

Servisne radnje

Set Away

Parametri: Supply flow \[m3/h] (0–200000 sf), Extract flow \[m3/h] (0–200000 ex), Setpoint °C (5–40 sp), Heating (${general\_on} / ${general\_off})

```taphome
MODBUSWNE(H, 99, Uint32, sf);
MODBUSWNE(H, 101, Uint32, ex);
MODBUSWNE(H, 103, Int16, sp*10);
MODBUSWNE(H, 104, Bool, he);
```

Set Normal

Parametri: Supply flow \[m3/h] (0–200000 sf), Extract flow \[m3/h] (0–200000 ex), Setpoint °C (5–40 sp), Heating (${general\_on} / ${general\_off})

```taphome
var q := 6;
MODBUSWNE(H, 99+q, Uint32, sf);
MODBUSWNE(H, 101+q, Uint32, ex);
MODBUSWNE(H, 103+q, Int16, sp*10);
MODBUSWNE(H, 104+q, Bool, he);
```

Set Intensive

Parametri: Supply flow \[m3/h] (0–200000 sf), Extract flow \[m3/h] (0–200000 ex), Setpoint °C (5–40 sp), Heating (${general\_on} / ${general\_off})

```taphome
var q := 12;
MODBUSWNE(H, 99+q, Uint32, sf);
MODBUSWNE(H, 101+q, Uint32, ex);
MODBUSWNE(H, 103+q, Int16, sp*10);
MODBUSWNE(H, 104+q, Bool, he);
```

Set Boost

Parametri: Supply flow \[m3/h] (0–200000 sf), Extract flow \[m3/h] (0–200000 ex), Setpoint °C (5–40 sp), Heating (1–100 he)

```taphome
var q := 18;
MODBUSWNE(H, 99+q, Uint32, sf);
MODBUSWNE(H, 101+q, Uint32, ex);
MODBUSWNE(H, 103+q, Int16, sp*10);
MODBUSWNE(H, 104+q, Bool, he);
```

Zadana temperatura (Normalno) Termostat Čitanje i pisanje

Termostat s očitanjem trenutačne temperature i podesivom zadanom temperaturom za način Normalno (5–40 °C)

Registar: H:902 → H:109 Int16 Jedinica: °C numeric

Servisni atributi

|                        |
|------------------------|
| Regulacija temperature |
| Sobni senzor           |

Servisne radnje

|                        |
|------------------------|
| Regulacija temperature |
| Sobni senzor           |

Čitanje temperature

```taphome
MODBUSR(H, 902, Int16) / 10
```

Čitanje željene temperature

```taphome
MODBUSR(H, 109, Int16)/10;
```

Zapis željene temperature

```taphome
MODBUSW(H, 109, Int16, Se*10);
```

Servisni atributi

Temperature Control

```taphome
SWITCH(MODBUSR(H, 10, Uint16), 
0, "Supply",
1, "Extract",
2, "Balance",
3, "Room",
"Error"
);
```

Room sensor

```taphome
SWITCH(MODBUSR(H, 38, Uint16), 
0, "Panel temperature(1)",
1, "Panel temperature(2)",
"Error"
);
```

Servisne radnje

Temperature Control

Parametri: Temperature Control

```taphome
MODBUSW(H, 10, Uint16, tc);
```

Room Sensor

Parametri: Panel Temperature

```taphome
MODBUSW(H, 38, Uint16, pt);
```

Vanjska temperatura Senzor temperature Samo za čitanje

Registar: H:903 Int16 Jedinica: °C numeric

Čitanje temperature

```taphome
MODBUSR(H, 903, Int16) / 10
```

Upravljanje snagom povrata topline Dimer Čitanje i pisanje

Dimer za upravljanje snagom povrata topline — može zahtijevati ručno podešavanje skripti

Čitanje razine

```taphome
SWITCH(MODBUSR(H, 4, Uint16),
 1,MODBUSR(H, 99, Uint32) /100,
  2,MODBUSR(H, 105, Uint32) /100,
   3,MODBUSR(H, 111, Uint32) /100,
    4,MODBUSR(H, 117, Uint32) /100,
0);
```

Zapis razine

```taphome
MODBUSW(H, 99, Uint32, Le * 100);
MODBUSW(H, 101, Uint32, Le * 100);
MODBUSW(H, 105, Uint32, Le * 100);
MODBUSW(H, 107, Uint32, Le * 100);
MODBUSW(H, 111, Uint32, Le * 100);
MODBUSW(H, 113, Uint32, Le * 100);
MODBUSW(H, 117, Uint32, Le * 100);
MODBUSW(H, 119, Uint32, Le * 100);
```

ON/OFF Sklopka Čitanje i pisanje

Registar: H:0 Bool

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 0, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 0, Bool, St);
```

Potrošnja energije Brojilo električne energije Samo za čitanje

Ukupna potrošnja energije (kWh) i trenutačna snaga (kW)

Registar: H:930 UInt32 Jedinica: kWh numeric

Čitanje ukupne potrošnje

```taphome
MODBUSR(H, 930, UInt32) / 1000
```

Čitanje zahtjeva

```taphome
MODBUSR(H, 920, Uint16) / 1000
```

Filtar Analogni ulaz Samo za čitanje

Praćenje stanja filtra s radnjom za poništavanje brojača začepljenosti

Servisne radnje

|                             |
|-----------------------------|
| Poništavanje brojača filtra |

Čitanje razine ulaza

```taphome
MODBUSR(H, 916, Uint16) / 100
```

Servisne radnje

Filter reset

```taphome
modbusw(H, 1050, Uint16, 1)
```

**Povezivanje:** Modbus RTU • 19200 baud• 8E1 • Slave ID: $\[SlaveId]

Moguća poboljšanja (18)

- H:904 Outdoor Temperature (true) — Register 904 = Outdoor temp (x10 °C). Template reads H:903 (Extract temp) as Outdoor — may be intentional mapping or an offset
- H:905 Water Temperature — Return water temperature sensor (x10 °C) for water heater/cooler coil
- H:900 Status Icon Bit Mask — Bitmask: Starting, Stopping, Fan, Rotor, Heating, Cooling, HeatingDenied, CoolingDenied, FlowDown, FreeHeating, FreeCooling, AlarmF, AlarmW
- H:912 Heat Exchanger Level — Heat exchanger operating level (x10 %, 0-100%)
- H:913 Electric Heater Level — Electric heater operating level (x10 %, 0-100%)
- H:914 Water Heater Level — Water heater operating level (x10 %, 0-100%)
- H:915 Water Cooler Level — Water cooler operating level (x10 %, 0-100%)
- H:917 Filters Impurity — Filter clogging percentage (0-100%). Filter device exists but has no read script for this register
- H:924 Heat Exchanger Efficiency — Heat recovery efficiency percentage (0-100%)
- H:921 Power Consumption (W) — Instantaneous power consumption in Watts. Template reads H:920 which is Extract pressure per source docs
- H:946 Panel 1 Temperature — Panel 1 room temperature (x10 °C)
- H:947 Panel 1 Humidity — Panel 1 room humidity (0-100%)
- H:952 Air Quality Sensor 1 — CO2 (ppm) or VOC or RH from B8 sensor
- H:961 Exhaust Temperature — Exhaust air temperature after heat exchanger (x10 °C)
- H:12 Flow Control Mode — Flow control mode: 0=CAV, 1=VAV, 2=DCV, 3=OFF
- H:205 Air Quality Enable — Enables/disables air quality function (0=Disabled, 1=Enabled)
- H:206 Air Quality Temperature Setpoint — Temperature setpoint for air quality mode (x10 °C, 5-40)
- H:300-H:555 Scheduler Programs — Full scheduler programming (weekday masks, events with mode/start/stop times). Complex multi-register structure not implemented

## Parametri uvoza

Ove vrijednosti unosite pri uvozu XML-a.

| Pitanje u aplikaciji | Zadano        |
|----------------------|---------------|
| Slave ID             | `254`         |
| IP adresa            | `192.168.0.1` |

## Izvori

- Komfovent C6/C6M Controller Modbus Manual
  
  [www.komfovent.com](https://www.komfovent.com/en/downloads/MODBUS_connection_C6_EN.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/komfovent-air-recovery/MODBUS_connection_C6_EN.pdf)
- Komfovent C6 Controller Product Page
  
  [www.komfovent.com](https://www.komfovent.com/en/end-user/control/c6-controller/) 2026-03-20
- Komfovent DOMEKT Residential Ventilation Units
  
  [www.komfovent.com](https://www.komfovent.com/en/c-page/products/air-handling-units/domekt-residential-ventilation-units) 2026-03-20
- Komfovent C6.1/C6.2 Electrical Installation and Operation Manual
  
  [www.komfovent.com](https://www.komfovent.com/en/downloads/C6_manual_EN.pdf)
- Komfovent DOMEKT C6M Automation Installation Manual
  
  [www.komfovent.com](https://www.komfovent.com/en/downloads/DOMEKT_C6M_installation_manual_EN.pdf)
- TapHome Modbus Template - Komfovent Air Recovery

Dokumenti proizvođača zaštićeni su autorskim pravom (©) svojih vlasnika. Dostupni su onako kako ih je proizvođač objavio, samo za informaciju.

## Povezana dokumentacija

- [Modbus Integration](https://taphome.com/hr/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/hr/docs/integration/modbus/)
- [Jednostavna konfiguracija pomoću predložaka](https://taphome.com/hr/docs/integration/modbus/templates/)
- [Skripte Modbus i prefetch](https://taphome.com/hr/docs/script/modbus-scripts/)
- [Funkcije Modbus](https://taphome.com/hr/docs/script/modbus/)
- [Tipovi podataka Modbus](https://taphome.com/hr/docs/script/modbus-data-types/)