title: "Jablotron Futura"
description: "Rekuperatori Jablotron Futura L/M/S i L+ spojeni na TapHome preko Modbus TCP."
url: "https://taphome.com/hr/compatibility/jablotron-futura/"
language: hr
lastmod: 2026-10-08
generator: hugo
ai:
  topics: ["modbus-tcp","air-recovery","heat-recovery-ventilation","ethernet","zone-ventilation"]
  questions: ["Kako integrirati Jablotron Futura sa sustavom TapHome?","Što mjeri i čime upravlja predložak TapHome za Jablotron Futura?","Kako spojiti Jablotron Futura na TapHome preko Modbus TCP?","Koja je razlika između predložaka za Futura L/M/S i L+?","Kako preko sustava TapHome uključiti način Boost ili Nadtlak na Jablotron Futura?","Kako pratiti zonske senzore i upravljače ALFA na Jablotron Futura?","Kako koristiti senzore CO₂ sustava TapHome za zonsku ventilaciju Jablotron Futura?","Zašto vrijednosti zonskih senzora Jablotron Futura u sustavu TapHome pokazuju 0?"]
---

# Jablotron Futura

Komunikacija: Modbus TCP

- [Stranica proizvoda Jablotron Futura](https://www.jablotron.com/en/products/comfort/futura/)

> Adresa u mreži
> 
> TapHome komunicira s uređajem na adresi unesenoj pri uvozu. Dodijelite uređaju stalnu adresu — rezervaciju IP adrese u usmjerivaču ili njegovo mDNS ime ako ga podržava — inače integracija prestaje raditi kada usmjerivač promijeni adresu.
> 
> [Priprema mreže](https://taphome.com/hr/docs/setup/network-preparation/)

## Upute za integraciju

Seriju Jablotron Futura (L, M, S, L+) čine rekuperatori (MVHR, ventilacija s povratom topline) tvrtke Jablotron Living Technology. TapHome se na jedinicu spaja izravno protokolom Modbus TCP preko Etherneta, bez dodatnog pristupnika.

Dostupna su dva zasebna predloška: jedan za modele **Futura L, M, S** (116 uređaja) i jedan za **Futura L+** (84 uređaja). Oba koriste isti Modbus TCP port i adresu uređaja, ali se adrese registara razlikuju između dviju varijanti. Uvezite predložak koji odgovara ugrađenoj jedinici.

## Mrežna veza

Jedinica Futura ima Ethernet priključak za komunikaciju Modbus TCP. Spojite je standardnim Ethernet kabelom u istu lokalnu mrežu kao centralnu jedinicu TapHome Core.

- **Protokol:** Modbus TCP
- **Port:** 502
- **Adresa uređaja:** 1
- **Dostupne utičnice (socket):** 1 (samo jedna istodobna veza)
- **Zahtjev za firmver:** Futura L/M/S: FUA.P.06.71 ili noviji, Futura L+: FLA.P.01.06 ili noviji

U sustavu TapHome firmver jedinice prikazuje se kao neobrađeni broj u servisnom atributu modula **Verzija firmvera** (u aplikaciji: *Verze firmware*), a model u atributu **Varijanta uređaja** (*Varianta zařízení*). Verzija u poznatom obliku (npr. FUA.P.06.71) prikazuje se u aplikaciji Jablotron.

> [!WARNING]
> Futura dopušta samo **jednu Modbus TCP utičnicu (socket)** istodobno. Ako je spojen drugi sustav (npr. Jablotron Connect LITE, Home Assistant), TapHome neće moći komunicirati. Prije korištenja sustava TapHome odspojite ostale Modbus TCP klijente.

## Konfiguracija

Pri uvozu predloška u TapHome unesite:

- **IP adresa**: IP adresa jedinice u lokalnoj mreži
- **Adresa uređaja**: Modbus adresa uređaja (zadano: 1)

Odaberite ispravnu varijantu predloška:

| Model | Naziv predloška | Uređaji |
|-------|--------------|---------|
| Futura L, M, S | Jablotron Futura L, M, S | 116 |
| Futura L+ | Jablotron Futura L+ | 84 |

Gumb za preuzimanje na dnu ove stranice nudi predložak **Futura L, M, S**. Predložak **Futura L+** [preuzmite ovdje](https://taphome.com/downloads/compatibility/jablotron-futura/jablotron-futura-l-plus.xml).

> [!NOTE]
> Složeni tipovi podataka (uint32, int32, float32) moraju se čitati i upisivati jednom Modbus operacijom. Firmver jamči cjelovitost podataka, pa djelomično čitanje ili upis vraća grešku ILLEGAL_DATA_ADDRESS. TapHome to automatski rješava kroz konfiguraciju predloška.

## Mogućnosti uređaja

Oba predloška nude iste osnovne funkcije s različitim adresama registara. Predložak L/M/S ima i dodatne mogućnosti koje L+ nema (način Noć, način Zabava, praćenje snage i broja okretaja ventilatora, željena vlažnost, univerzalni ulazi, upravljači ALFA).

### Upravljanje načinom ventilacije

- **Način ventilacije**: odabir vrijednosti Isključeno, Stupanj 1–5 ili Automatski preko holding registra HR:0. To je glavno upravljanje brzinom ventilatora jedinice.

### Praćenje temperature i vlažnosti

Četiri para senzora temperature i vlažnosti prate put zraka kroz jedinicu:

- **Vanjski zrak**: temperatura vanjskog zraka (IR:30 na L/M/S, IR:12 na L+) s vlažnošću
- **Dovodni zrak**: temperatura svježeg zraka koji se dovodi u zgradu (IR:31 / IR:13) s vlažnošću
- **Otpadni zrak**: temperatura otpadnog zraka koji izlazi iz zgrade (IR:33 / IR:15) s vlažnošću
- **Vanjski NTC senzor**: dodatna vanjska NTC sonda vanjske temperature (IR:38 / IR:20); kad nije spojena, očitava -99

### Praćenje učinka

- **Povrat topline**: trenutačna snaga povrata topline u vatima (IR:42 / IR:23)
- **Električna snaga**: ukupna električna snaga koju jedinica troši, u vatima (IR:41 / IR:22)
- **Protok zraka**: zbirni protok dovodnog i odsisnog zraka u m3/h (IR:44 / IR:25)
- **Snaga grijanja**: snaga koju troši unutarnji električni predgrijač, u vatima (IR:43 / IR:24)
- **Istrošenost filtra**: onečišćenost filtra u postocima; zamijenite ga kad se približi 100 % (IR:40 / IR:21)

### Praćenje ventilatora (samo L/M/S)

- **Snaga dovodnog ventilatora**: razina snage dovodnog ventilatora u postocima (IR:45) s očitanjem broja okretaja u servisnom atributu (IR:47)
- **Snaga odsisnog ventilatora**: razina snage odsisnog ventilatora u postocima (IR:46) s očitanjem broja okretaja u servisnom atributu (IR:48)
- **Napon univerzalnog ulaza 1/2**: dijagnostička očitanja napona na univerzalnim ulazima (IR:49, IR:50)

### Vremenski ograničene funkcije

Predložak nudi vremenski ograničene funkcije ventilacije kao prekidače s više vrijednosti s unaprijed zadanim trajanjima:

- **Funkcija Boost**: najjača ventilacija tijekom odabranog vremena (HR:1). Unaprijed zadana trajanja: isključeno, 30 s, 60 s, 5 min, 10 min, 15 min, 30 min, 1 h, 1,5 h, 2 h. Servisna radnja omogućuje postavljanje vlastitog odbrojavanja (1–7200 s). Preostalo vrijeme dostupno je kao servisni atribut.
- **Funkcija Cirkulacija**: cirkulacija zraka bez povrata topline (HR:2). Ista unaprijed zadana trajanja te ista servisna radnja i atribut kao kod funkcije Boost.
- **Funkcija Nadtlak**: način nadtlaka koji sprječava ulazak dima pri loženju kamina (HR:3). Ista unaprijed zadana trajanja.
- **Noćna funkcija** (samo L/M/S): smanjena ventilacija za tihi noćni rad (HR:4). Ista unaprijed zadana trajanja.
- **Funkcija Zabava** (samo L/M/S): pojačana ventilacija za okupljanja (HR:5). Unaprijed zadana trajanja: isključeno, 30 min, 1–8 h.

### Sklopke za uključivanje funkcija

Binarne sklopke za uključivanje i isključivanje funkcija sustava:

- **Vremenski program**: uključuje tjedni vremenski program (HR:12 / HR:5)
- **Uključivanje zaštite od radona**: stalna ventilacija niskom brzinom koja sprječava nakupljanje radona (HR:13 / HR:6)
- **Uključivanje bypassa**: uključuje automatski bypass izmjenjivača topline za pasivno hlađenje (HR:14 / HR:7)
- **Uključivanje grijanja**: uključuje unutarnji električni predgrijač dovodnog zraka (HR:15 / HR:8)
- **Uključivanje hlađenja**: uključuje aktivno hlađenje CoolBreeze, potreban je dodatni pribor CoolBreeze (HR:16 / HR:9)
- **Uključivanje komfornog grijanja** (samo L/M/S): uključuje komforno grijanje za regulaciju temperature dovodnog zraka (HR:17)
- **Automatska cirkulacija**: uključuje način automatske cirkulacije zraka (HR:18 / HR:10)

### Zadane vrijednosti temperature

- **Željena temperatura**: željena zadana unutarnja temperatura (HR:10 / HR:4)
- **Željena vlažnost** (samo L/M/S): željena razina vlažnosti: suho (25 %), ugodno (50 %) ili vlažno (75 %) (HR:11)

### Zonski senzori (zone 1–8)

Oba predloška podržavaju do 8 zona s vanjskim senzorima. Za svaku zonu:

- **Senzor prisutan**: uključuje ulaz vanjskog senzora za zonu
- **Temperatura**: vrijednost temperature iz vanjskog senzora (od -20 do 100 °C)
- **Vlažnost**: vrijednost vlažnosti iz vanjskog senzora (0–100 %)
- **CO₂**: vrijednost CO₂ iz vanjskog senzora (0–10 000 ppm)

Registri zonskih senzora nalaze se na HR:300–375 (L/M/S) ili HR:100–175 (L+), s razmakom od 10 registara po zoni.

To su ulazi jedinice Futura: TapHome u njih upisuje vrijednosti, a ne očitava iz njih vrijednosti senzora Jablotron. Kako u njih upisivati vrijednosti senzora sustava TapHome, opisano je niže u odjeljku **Korištenje senzora TapHome za zonsku ventilaciju**.

### Zonske tipke (zone 1–8)

Oba predloška podržavaju po jednu vanjsku tipku u svakoj od 8 zona. Za svaku zonu:

- **Tipka prisutna**: uključuje vanjsku tipku
- **Način tipke**: odabir između funkcije Boost (0) i Kuhinjska napa (1)
- **Odbrojavanje tipke**: vrijeme odbrojavanja (0–10 800 s)
- **Aktivacija tipke**: pokreće funkciju tipke (vremensko ograničenje 3 sata)

Registri zonskih tipki nalaze se na HR:400–473 (L/M/S) ili HR:200–273 (L+).

### Sobni upravljači ALFA (samo L/M/S)

Predložak L/M/S podržava do 8 zidnih sobnih upravljača ALFA. Za svaku jedinicu ALFA:

- **CO₂**: razina CO₂ u prostoriji u ppm
- **Temperatura zraka**: temperatura zraka u prostoriji s vlažnošću
- **NTC temperatura**: vanjski NTC senzor temperature spojen na upravljač ALFA

Registri upravljača ALFA nalaze se na IR:160–235, s razmakom od 10 registara po jedinici.

### Dodatne mogućnosti

Jedinice Futura nude i Modbus registre za stanje načina rada (24-bitna maska koja prikazuje aktivne načine kao što su Boost, cirkulacija, odsutnost, odmrzavanje, zaštita od zaleđivanja), bitovne maske grešaka i upozorenja (22 bita grešaka, 18 bitova upozorenja), temperaturu i vlažnost odsisnog zraka, napon pričuvne baterije, raspored načina odsutnosti (unix vremenske oznake), stanje digitalnih ulaza i identifikaciju uređaja. Varijanta L+ dodatno ima registar stanja grijanja/hlađenja. Mogu se dodati u predložak TapHome u nekom budućem ažuriranju.

Očitanja vlastitih sobnih senzora Jablotron dostupna su u Modbus mapi, ali ne i u predlošcima: na L/M/S zidne upravljačke ploče (CO₂, temperatura, vlažnost, IR:100–114) i zasebni zidni senzori CO₂ (IR:115–154), a na L+ izmjereni CO₂, temperatura i vlažnost zona 1–8 (IR:100–173). Mogu se dodati u predložak kao Modbus varijable.

## Korištenje senzora TapHome za zonsku ventilaciju

Kod ventilacije po prostorijama VarioBreeze jedinica Futura povezuje komponente zone prema istoj postavci DIP sklopke (zona 1–8). Preko Modbusa nudi i ulaz za vanjski senzor za svaku od 8 zona, pa vrijednosti zone mogu davati senzori sustava TapHome, na primjer zidni prekidač s ugrađenim senzorom CO₂. Smjer je **TapHome → Futura**.

Za svaku prostoriju:

1. **Broj zone**: postavka DIP sklopke na ventilu te prostorije (1–8). Koristite zonske uređaje s istim brojem.
2. Uključite **Zona N – Senzor prisutan** (u aplikaciji: *Zona N - Přítomnost externích čidel*).
3. Za svaku vrijednost zone dodajte smart rule **Formula**:
   - **Zona N – CO₂** (*Zona N - CO₂*) = senzor CO₂ u prostoriji, u ppm
   - **Zona N – Temperatura** (*Zona N - Teplota*) = temperatura u prostoriji, u °C
   - **Zona N – Vlažnost** (*Zona N - vlhkost*) = vlažnost u prostoriji **× 100**
4. **Način ventilacije** (*Výkon větrání*) postavite na **Automatski**; stupnjevi 1–5 su ručni stupnjevi ventilatora.

> [!WARNING]
> TapHome pohranjuje vlažnost kao udio (0–1), a Futura očekuje postotak (0–100). Bez **× 100** u formuli vlažnost 0,45 upisuje se kao 0 %.

> [!NOTE]
> Popunite sve tri vrijednosti svake zone kojoj je uključen **Senzor prisutan**. Zonski uređaj bez smart rule zadržava vrijednost 0 i TapHome je upisuje u Futuru, pa zona tada javlja 0 °C i 0 %.

## Rješavanje problema

### Vrijednosti zonskih senzora su 0

TapHome pri svakom očitavanju upisuje trenutačnu vrijednost svakog zonskog uređaja u Futuru. Zonski uređaj bez smart rule zadržava vrijednost 0, pa Futura prima 0 ppm, 0 °C ili 0 %. Dodajte smart rule za svaku vrijednost aktivne zone, a za zone koje se ne koriste ostavite **Senzor prisutan** isključen. Ako je 0 samo vlažnost, u formuli nedostaje **× 100**.

### Futura ne reagira na zonske senzore

1. **Način ventilacije** postavljen je na **Automatski**; stupnjevi 1–5 su ručni
2. **Zona N – Senzor prisutan** uključen je za tu zonu
3. Broj zone u sustavu TapHome odgovara postavci DIP sklopke na ventilu zone

### Nema Modbus komunikacije

1. Provjerite je li Ethernet kabel spojen na ispravan priključak jedinice Futura
2. Provjerite IP adresu jedinice u tablici DHCP zakupa usmjerivača
3. Provjerite jesu li centralna jedinica TapHome Core i jedinica Futura u istoj mreži/podmreži
4. Provjerite ne zauzima li neki drugi Modbus TCP klijent jedinu dostupnu utičnicu
5. Provjerite zadovoljava li verzija firmvera minimalni zahtjev (L/M/S: FUA.P.06.71, L+: FLA.P.01.06)

### Uvezen je pogrešan predložak

Modeli L/M/S i L+ koriste različite mape adresa registara. Ako vrijednosti senzora izgledaju pogrešno ili se javljaju greške komunikacije, provjerite je li uvezena ispravna varijanta predloška za model ugrađene jedinice.

### Sve sklopke za uključivanje javljaju ILLEGAL_DATA_ADDRESS

Ako svih sedam sklopki za uključivanje u predlošku L/M/S (Vremenski program, Zaštita od radona, Bypass, Grijanje, Hlađenje, Komforno grijanje, Automatska cirkulacija) istodobno javlja ILLEGAL_DATA_ADDRESS, Futura ima stariji firmver. TapHome te sklopke čita jednim zahtjevom (HR:12–18), a stariji firmver bez HR:17 i HR:18 odbija cijeli zahtjev. Modbus sučelje zahtijeva najmanje FUA.P.06.71 (L/M/S).

Zatražite od tvrtke Jablotron ažuriranje firmvera jedinice. Nakon ažuriranja greške prestaju bez ikakve promjene u sustavu TapHome. Rezultat provjerite u servisnom atributu modula **Verzija firmvera**.

### Greške djelomičnog čitanja registara

Firmver zahtijeva da se složeni registri (uint32, int32) čitaju jednom Modbus operacijom, a djelomično čitanje vraća ILLEGAL_DATA_ADDRESS. Standardni predložak TapHome čita ih jednom operacijom. Ako se ILLEGAL_DATA_ADDRESS pojavi na drugim uređajima, provjerite varijantu predloška i verziju firmvera (pogledajte iznad).

## Dostupni uređaji 116

Ovi se uređaji pojavljuju u TapHomeu nakon uvoza.

Jablotron Futura L+ Modul

Servisni atributi

|                                      |
|--------------------------------------|
| Preostalo vrijeme \[s]               |
| Preostalo vrijeme \[s]               |
| Preostalo vrijeme \[s]               |
| Verze firmware                       |
| Verze registrové mapy                |
| Varianta zařízení                    |
| Vnitřní topení je dostupné           |
| Chlazení Coolbreeze je dostupné      |
| Topení Coolbreeze je dostupné        |
| Funkce bypass je dostupná            |
| Napětí záložní baterie pro RTC \[mV] |

Čitanje (modul)

```taphome
var Code := MODBUSR(A,16, UInt32);
IF (GETBIT(Code,0), ADDINFO(0,"Aktivní funkce Boost"));
IF (GETBIT(Code,1), ADDINFO(1,"Aktivní funkce Cirkulace"));
IF (GETBIT(Code,2), ADDINFO(2,"Aktivní časový program"));
IF (GETBIT(Code,3), ADDINFO(3,"Aktivní funkce Přetlak"));
IF (GETBIT(Code,4), ADDINFO(4,"Aktivní funkce Dovolená"));
IF (GETBIT(Code,5), ADDINFO(5,"Aktivní funkce Párty"));
IF (GETBIT(Code,6), ADDINFO(6,"Aktivní funkce Noční režim"));
IF (GETBIT(Code,7), ADDINFO(7,"Aktivní funkce Protiradonová ochrana"));
IF (GETBIT(Code,8), ADDINFO(8,"Zařízení je zapnuto, není v režimu snížené spotřeby"));
IF (GETBIT(Code,9), ADDINFO(9,"Probíhá kontrola filtrů"));
IF (GETBIT(Code,10), ADDINFO(10,"Probíhá vysoušení"));
IF (GETBIT(Code,11), ADDINFO(11,"Otevřený Bypass"));
IF (GETBIT(Code,12), ADDINFO(12,"Nízká venkovní teplota, omezená funkce větrání"));
IF (GETBIT(Code,13), ADDINFO(13,"Odstavení po chybě"));
IF (GETBIT(Code,14), ADDINFO(14,"Zařízení se spouští"));
IF (GETBIT(Code,15), ADDINFO(15,"Aktivní servisní režim"));
IF (GETBIT(Code,16), ADDINFO(16,"Teplota odpadního vzduchu < -3°C (splněna podmínka ochrany před zamrznutím)"));
IF (GETBIT(Code,17), ADDINFO(17,"Nouzové vypnutí"));
IF (GETBIT(Code,18), ADDINFO(18,"Nouzové vypnutí"));
IF (GETBIT(Code,19), ADDINFO(19,"Odměřování tlakové ztráty"));
IF (GETBIT(Code,20), ADDINFO(20,"Stand-by"));
IF (GETBIT(Code,21), ADDINFO(21,"Zónový boost"));
IF (GETBIT(Code,22), ADDINFO(22,"Odměřování tlakové ztráty zón"));

Code := MODBUSR(A,18, UInt32);
IF (GETBIT(Code,0), ADDERROR(0,"Chyba senzoru ambient"));
IF (GETBIT(Code,1), ADDERROR(1,"Chyba senzoru indoor"));
IF (GETBIT(Code,2), ADDERROR(2,"Chyba senzoru fresh"));
IF (GETBIT(Code,3), ADDERROR(3,"Chyba senzoru waste"));
IF (GETBIT(Code,4), ADDERROR(4,"Chyba přívodního ventilátoru"));
IF (GETBIT(Code,5), ADDERROR(5,"Chyba odtahového ventilátoru"));
IF (GETBIT(Code,6), ADDERROR(6,"Chyba komunikace s výměníkem"));
IF (GETBIT(Code,7), ADDERROR(7,"Chyba polohy klapek výměníku"));
IF (GETBIT(Code,8), ADDERROR(8,"Chyba komunikace s IO deskou"));
IF (GETBIT(Code,9), ADDERROR(9,"Zablokovaný přívodní ventilátor"));
IF (GETBIT(Code,10), ADDERROR(10,"Zablokovaný odtahový ventilátor"));
IF (GETBIT(Code,11), ADDERROR(11,"Chyba komunikace s Coolbreeze"));
IF (GETBIT(Code,12), ADDERROR(12,"Chyba venkovní jednotky Coolbreeze"));

Code := MODBUSR(A,20, UInt32);
IF (GETBIT(Code,0), ADDWARNING(0,"Neinicializovaný filtr"));
IF (GETBIT(Code,1), ADDWARNING(1,"Filtr je příliš zanesený"));
IF (GETBIT(Code,2), ADDWARNING(2,"Filtr se používá příliš dlouho"));
IF (GETBIT(Code,3), ADDWARNING(3,"Nízké napětí RTC baterie"));
IF (GETBIT(Code,4), ADDWARNING(4,"Příliš vysoké otáčky přívodního ventilátoru"));
IF (GETBIT(Code,5), ADDWARNING(5,"Příliš vysoké otáčky odtahového ventilátoru"));
IF (GETBIT(Code,8), ADDWARNING(8,"Příliš nízká venkovní teplota, omezená funkce větrání"));
IF (GETBIT(Code,9), ADDWARNING(9,"Nesprávná konfigurace zónového větrání - přívod"));
IF (GETBIT(Code,10), ADDWARNING(10,"Nesprávná konfigurace zónového větrání - odtah"));
IF (GETBIT(Code,11), ADDWARNING(11,"Nouzové vypnutí"));
IF (GETBIT(Code,12), ADDWARNING(12,"Chyba komunikace se SuperBreeze"));
IF (GETBIT(Code,13), ADDWARNING(13,"Obecná chyba SuperBreeze"));
```

Servisni atributi

Sériové číslo

```taphome
MODBUSR(A, 1, Uint32)
```

MAC adresa

```taphome
var macA := MODBUSR(A, 3, Uint16);
var macB := MODBUSR(A, 4, Uint16);
var macC := MODBUSR(A, 5, Uint16);
TOSTRING(GETBYTE(macA, 0), "X2") + ":" +
TOSTRING(GETBYTE(macA, 1), "X2") + ":" +
TOSTRING(GETBYTE(macB, 0), "X2") + ":" +
TOSTRING(GETBYTE(macB, 1), "X2") + ":" +
TOSTRING(GETBYTE(macC, 0), "X2") + ":" +
TOSTRING(GETBYTE(macC, 1), "X2");
```

Verze hardware

```taphome
MODBUSR(A, 6, Uint32)
```

Verze firmware

```taphome
MODBUSR(A, 8, Uint32)
```

Verze registrové mapy

```taphome
MODBUSR(A, 12, Uint32)
```

Varianta zařízení

```taphome
SWITCH(MODBUSR(A, 14, Uint16),
0, "Futura L",
1, "Futura L",
2, "Futura M",
"--")
```

Vnitřní topení je dostupné

```taphome
IF(GETBIT(MODBUSR(A, 15, Uint16), 0), "Ano", "Ne")
```

Chlazení Coolbreeze je dostupné

```taphome
IF(GETBIT(MODBUSR(A, 15, Uint16), 1), "Ano", "Ne")
```

Topení Coolbreeze je dostupné

```taphome
IF(GETBIT(MODBUSR(A, 15, Uint16), 2), "Ano", "Ne")
```

Funkce bypass je dostupná

```taphome
IF(GETBIT(MODBUSR(A, 15, Uint16), 3), "Ano", "Ne")
```

Napětí záložní baterie pro RTC \[mV]

```taphome
MODBUSR(A, 52, Uint16)
```

Povrat topline Varijabla Samo za čitanje

Snaga povrata topline, energija iskorištena iz odsisnog zraka

Registar: IR:42 UInt16 Jedinica: W

Čitanje

```taphome
MODBUSR(A, 42, Uint16)
```

Električna snaga Varijabla Samo za čitanje

Ukupna električna snaga koju jedinica troši

Registar: IR:41 UInt16 Jedinica: W

Čitanje

```taphome
MODBUSR(A, 41, Uint16)
```

Protok zraka Varijabla Samo za čitanje

Zbirni protok dovodnog i odsisnog zraka

Registar: IR:44 UInt16 Jedinica: m3/h

Čitanje

```taphome
MODBUSR(A, 44, Uint16)
```

Automatska cirkulacija Sklopka Čitanje i pisanje

Uključuje način automatske cirkulacije zraka

Registar: HR:18 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 18, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 18, Bool, St)
```

Vremenski program Sklopka Čitanje i pisanje

Uključuje tjedni vremenski program

Registar: HR:12 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 12, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 12, Uint16, St)
```

Dovodni zrak Senzor temperature Samo za čitanje

Temperatura i vlažnost svježeg zraka koji se dovodi u zgradu

Registar: IR:31 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 35, Int16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 31, Int16) / 10
```

Vanjski NTC senzor Senzor temperature Samo za čitanje

Vanjski NTC senzor vanjske temperature (-99 = odspojen)

Registar: IR:38 Int16 Jedinica: °C direct, /10

Čitanje temperature

```taphome
var x:= MODBUSR(A, 38, Int16) / 10;
if (x = -99, NaN, x)
```

Funkcija Boost Prekidač s više vrijednosti Čitanje i pisanje

Maksimalna ventilacija na određeno vrijeme: odaberite trajanje ili postavite vlastito odbrojavanje

Registar: HR:1 UInt16 Jedinica: s numeric

Vrijednosti / stanja: Isključeno · 30 s · 60 s · 5 min · 10 min · 15 min · 30 min · 1 h · 1,5 h · 2 h

Servisne radnje

|                |
|----------------|
| Funkcija Boost |

Čitanje stanja sklopke

```taphome
var x := MODBUSR(H, 1, Uint16);
IF(x = 0, RETURN(0));
IF(x > 5400, RETURN(9));
IF(x > 3600, RETURN(8));
IF(x > 1800, RETURN(7));
IF(x > 900, RETURN(6));
IF(x > 600, RETURN(5));
IF(x > 300, RETURN(4));
IF(x > 60, RETURN(3));
IF(x > 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Zapis stanja sklopke

```taphome
IF(Mu = 0, MODBUSW(H, 1, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 1, Uint16, 30));
IF(Mu = 2, MODBUSW(H, 1, Uint16, 60));
IF(Mu = 3, MODBUSW(H, 1, Uint16, 300));
IF(Mu = 4, MODBUSW(H, 1, Uint16, 600));
IF(Mu = 5, MODBUSW(H, 1, Uint16, 900));
IF(Mu = 6, MODBUSW(H, 1, Uint16, 1800));
IF(Mu = 7, MODBUSW(H, 1, Uint16, 3600));
IF(Mu = 8, MODBUSW(H, 1, Uint16, 5400));
IF(Mu = 9, MODBUSW(H, 1, Uint16, 7200));
```

Servisni atributi

Zbývající čas \[s]

```taphome
MODBUSR(H, 1, Uint16)
```

Servisne radnje

Funkce Boost

Parametri: Čas (1–7200 sec)

```taphome
MODBUSW(H, 1, Uint16, sec)
```

Funkcija Cirkulacija Prekidač s više vrijednosti Čitanje i pisanje

Cirkulacija zraka bez povrata topline na određeno vrijeme

Registar: HR:2 UInt16 Jedinica: s numeric

Vrijednosti / stanja: Isključeno · 30 s · 60 s · 5 min · 10 min · 15 min · 30 min · 1 h · 1,5 h · 2 h

Servisne radnje

|                      |
|----------------------|
| Funkcija Cirkulacija |

Čitanje stanja sklopke

```taphome
var x := MODBUSR(H, 2, Uint16);
IF(x = 0, RETURN(0));
IF(x > 5400, RETURN(9));
IF(x > 3600, RETURN(8));
IF(x > 1800, RETURN(7));
IF(x > 900, RETURN(6));
IF(x > 600, RETURN(5));
IF(x > 300, RETURN(4));
IF(x > 60, RETURN(3));
IF(x > 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Zapis stanja sklopke

```taphome
IF(Mu = 0, MODBUSW(H, 2, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 2, Uint16, 30));
IF(Mu = 2, MODBUSW(H, 2, Uint16, 60));
IF(Mu = 3, MODBUSW(H, 2, Uint16, 300));
IF(Mu = 4, MODBUSW(H, 2, Uint16, 600));
IF(Mu = 5, MODBUSW(H, 2, Uint16, 900));
IF(Mu = 6, MODBUSW(H, 2, Uint16, 1800));
IF(Mu = 7, MODBUSW(H, 2, Uint16, 3600));
IF(Mu = 8, MODBUSW(H, 2, Uint16, 5400));
IF(Mu = 9, MODBUSW(H, 2, Uint16, 7200));
```

Servisni atributi

Zbývající čas \[s]

```taphome
MODBUSR(H, 2, Uint16)
```

Servisne radnje

Funkce Cirkulace

Parametri: Čas (1–7200 sec)

```taphome
MODBUSW(H, 2, Uint16, sec)
```

Noćna funkcija Prekidač s više vrijednosti Čitanje i pisanje

Smanjena ventilacija na određeno vrijeme za tihi noćni rad

Registar: HR:4 UInt16 Jedinica: s numeric

Vrijednosti / stanja: Isključeno · 30 s · 60 s · 5 min · 10 min · 15 min · 30 min · 1 h · 1,5 h · 2 h

Servisne radnje

|                |
|----------------|
| Noćna funkcija |

Čitanje stanja sklopke

```taphome
var x := MODBUSR(H, 4, Uint16);
IF(x = 0, RETURN(0));
IF(x > 5400, RETURN(9));
IF(x > 3600, RETURN(8));
IF(x > 1800, RETURN(7));
IF(x > 900, RETURN(6));
IF(x > 600, RETURN(5));
IF(x > 300, RETURN(4));
IF(x > 60, RETURN(3));
IF(x > 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Zapis stanja sklopke

```taphome
IF(Mu = 0, MODBUSW(H, 4, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 4, Uint16, 30));
IF(Mu = 2, MODBUSW(H, 4, Uint16, 60));
IF(Mu = 3, MODBUSW(H, 4, Uint16, 300));
IF(Mu = 4, MODBUSW(H, 4, Uint16, 600));
IF(Mu = 5, MODBUSW(H, 4, Uint16, 900));
IF(Mu = 6, MODBUSW(H, 4, Uint16, 1800));
IF(Mu = 7, MODBUSW(H, 4, Uint16, 3600));
IF(Mu = 8, MODBUSW(H, 4, Uint16, 5400));
IF(Mu = 9, MODBUSW(H, 4, Uint16, 7200));
```

Servisni atributi

Zbývající čas \[s]

```taphome
MODBUSR(H, 4, Uint16)
```

Servisne radnje

Funkce Noc

Parametri: Čas (1–7200 sec)

```taphome
MODBUSW(H, 4, Uint16, sec)
```

Funkcija Zabava Prekidač s više vrijednosti Čitanje i pisanje

Pojačana ventilacija na određeno vrijeme za okupljanja

Registar: HR:5 UInt16 Jedinica: s numeric

Vrijednosti / stanja: Isključeno · 30 min · 1 h · 2 h · 3 h · 4 h · 5 h · 6 h · 7 h · 8 h

Servisne radnje

|                 |
|-----------------|
| Funkcija Zabava |

Čitanje stanja sklopke

```taphome
var x := MODBUSR(H, 5, Uint16);
IF(x = 0, RETURN(0));
IF(x > 60 * 60 * 7, RETURN(9));
IF(x > 60 * 60 * 6, RETURN(8));
IF(x > 60 * 60 * 5, RETURN(7));
IF(x > 60 * 60 * 4, RETURN(6));
IF(x > 60 * 60 * 3, RETURN(5));
IF(x > 60 * 60 * 2, RETURN(4));
IF(x > 60 * 60 * 1, RETURN(3));
IF(x > 60 * 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Zapis stanja sklopke

```taphome
IF(Mu = 0, MODBUSW(H, 5, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 5, Uint16, 60 * 30));
IF(Mu = 2, MODBUSW(H, 5, Uint16, 60 * 60 * 1));
IF(Mu = 3, MODBUSW(H, 5, Uint16, 60 * 60 * 2));
IF(Mu = 4, MODBUSW(H, 5, Uint16, 60 * 60 * 3));
IF(Mu = 5, MODBUSW(H, 5, Uint16, 60 * 60 * 4));
IF(Mu = 6, MODBUSW(H, 5, Uint16, 60 * 60 * 5));
IF(Mu = 7, MODBUSW(H, 5, Uint16, 60 * 60 * 6));
IF(Mu = 8, MODBUSW(H, 5, Uint16, 60 * 60 * 7));
IF(Mu = 9, MODBUSW(H, 5, Uint16, 60 * 60 * 8));
```

Servisni atributi

Zbývající čas \[s]

```taphome
MODBUSR(H, 5, Uint16)
```

Servisne radnje

Funkce Party

Parametri: Čas (1–28800 sec)

```taphome
MODBUSW(H, 5, Uint16, sec)
```

Funkcija Nadtlak Prekidač s više vrijednosti Čitanje i pisanje

Način nadtlaka na određeno vrijeme koji sprječava ulazak dima pri loženju kamina

Registar: HR:3 UInt16 Jedinica: s numeric

Vrijednosti / stanja: Isključeno · 30 s · 60 s · 5 min · 10 min · 15 min · 30 min · 1 h · 1,5 h · 2 h

Servisne radnje

|                  |
|------------------|
| Funkcija Nadtlak |

Čitanje stanja sklopke

```taphome
var x := MODBUSR(H, 3, Uint16);
IF(x = 0, RETURN(0));
IF(x > 5400, RETURN(9));
IF(x > 3600, RETURN(8));
IF(x > 1800, RETURN(7));
IF(x > 900, RETURN(6));
IF(x > 600, RETURN(5));
IF(x > 300, RETURN(4));
IF(x > 60, RETURN(3));
IF(x > 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Zapis stanja sklopke

```taphome
IF(Mu = 0, MODBUSW(H, 3, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 3, Uint16, 30));
IF(Mu = 2, MODBUSW(H, 3, Uint16, 60));
IF(Mu = 3, MODBUSW(H, 3, Uint16, 300));
IF(Mu = 4, MODBUSW(H, 3, Uint16, 600));
IF(Mu = 5, MODBUSW(H, 3, Uint16, 900));
IF(Mu = 6, MODBUSW(H, 3, Uint16, 1800));
IF(Mu = 7, MODBUSW(H, 3, Uint16, 3600));
IF(Mu = 8, MODBUSW(H, 3, Uint16, 5400));
IF(Mu = 9, MODBUSW(H, 3, Uint16, 7200));
```

Servisni atributi

Zbývající čas \[s]

```taphome
MODBUSR(H, 3, Uint16)
```

Servisne radnje

Funkce Přetlak

Parametri: Čas (1–7200 sec)

```taphome
MODBUSW(H, 3, Uint16, sec)
```

Istrošenost filtra Dimer Samo za čitanje

Onečišćenost filtra u postocima; zamijenite ga kad se približi 100 %

Registar: IR:40 UInt16 Jedinica: %

Čitanje razine

```taphome
MODBUSR(A, 40, Uint16) / 100
```

Napon univerzalnog ulaza 1 Varijabla Samo za čitanje

Napon na univerzalnom ulazu 1 (dijagnostika)

Registar: IR:49 UInt16 Jedinica: V direct, /1000

Čitanje

```taphome
MODBUSR(A, 49, Uint16) / 1000
```

Napon univerzalnog ulaza 2 Varijabla Samo za čitanje

Napon na univerzalnom ulazu 2 (dijagnostika)

Registar: IR:50 UInt16 Jedinica: V direct, /1000

Čitanje

```taphome
MODBUSR(A, 50, Uint16) / 1000
```

Otpadni zrak Senzor temperature Samo za čitanje

Temperatura i vlažnost otpadnog zraka koji izlazi iz zgrade

Registar: IR:33 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 37, Int16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 33, Int16) / 10
```

Uključivanje bypassa Sklopka Čitanje i pisanje

Uključuje automatski bypass izmjenjivača topline za pasivno hlađenje

Registar: HR:14 UInt16 boolean

Vrijednosti / stanja: Povoleno · Zakázáno

Čitanje stanja sklopke

```taphome
MODBUSR(H, 14, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 14, Uint16, St)
```

Uključivanje hlađenja Sklopka Čitanje i pisanje

Uključuje aktivno hlađenje CoolBreeze (potreban je dodatni pribor)

Registar: HR:16 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 16, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 16, Uint16, St)
```

Uključivanje komfornog grijanja Sklopka Čitanje i pisanje

Uključuje komforno grijanje za regulaciju temperature dovodnog zraka

Registar: HR:17 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 17, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 17, Uint16, St)
```

Uključivanje zaštite od radona Sklopka Čitanje i pisanje

Stalna ventilacija niskom brzinom koja sprječava nakupljanje radona

Registar: HR:13 UInt16 boolean

Vrijednosti / stanja: Povoleno · Zakázáno

Čitanje stanja sklopke

```taphome
MODBUSR(H, 13, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 13, Uint16, St)
```

Uključivanje grijanja Sklopka Čitanje i pisanje

Uključuje unutarnji električni predgrijač dovodnog zraka

Registar: HR:15 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 15, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 15, Uint16, St)
```

Željena temperatura Termostat Čitanje i pisanje

Željena unutarnja temperatura

Registar: HR:10 UInt16 Jedinica: °C direct, /10

Čitanje željene temperature

```taphome
MODBUSR(H, 10, Uint16) / 10
```

Zapis željene temperature

```taphome
MODBUSW(H, 10, Uint16, Se * 10)
```

Željena vlažnost Dimer Čitanje i pisanje

Željena razina vlažnosti (suho / ugodno / vlažno)

Registar: HR:11 UInt16 Jedinica: % direct, /10

Čitanje razine

```taphome
MODBUSR(H, 11, Uint16) / 1000
```

Zapis razine

```taphome
MODBUSW(H, 11, Uint16, Le * 1000)
```

Vanjski zrak Senzor temperature Samo za čitanje

Temperatura i vlažnost vanjskog zraka

Registar: IR:30 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 34, Int16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 30, Int16) / 10
```

Snaga grijanja Varijabla Samo za čitanje

Snaga koju troši unutarnji električni predgrijač

Registar: IR:43 UInt16 Jedinica: W

Čitanje

```taphome
MODBUSR(A, 43, Uint16)
```

Snaga odsisnog ventilatora Dimer Samo za čitanje

Razina snage odsisnog ventilatora s očitanjem broja okretaja

Registar: IR:46 UInt16 Jedinica: %

Servisni atributi

|                           |
|---------------------------|
| Broj okretaja ventilatora |

Čitanje razine

```taphome
MODBUSR(A, 46, Uint16) / 100
```

Servisni atributi

Otáčky ventilátoru \[rpm]

```taphome
MODBUSR(A, 48, Uint16)
```

Snaga dovodnog ventilatora Dimer Samo za čitanje

Razina snage dovodnog ventilatora s očitanjem broja okretaja

Registar: IR:45 UInt16 Jedinica: %

Servisni atributi

|                           |
|---------------------------|
| Broj okretaja ventilatora |

Čitanje razine

```taphome
MODBUSR(A, 45, Uint16) / 100
```

Servisni atributi

Otáčky ventilátoru \[rpm]

```taphome
MODBUSR(A, 47, Uint16)
```

Način ventilacije Prekidač s više vrijednosti Čitanje i pisanje

Glavno upravljanje ventilacijom: isključeno, stupanj 1–5 ili automatski

Registar: HR:0 UInt16 numeric

Vrijednosti / stanja: Isključeno · Stupanj 1 · Stupanj 2 · Stupanj 3 · Stupanj 4 · Stupanj 5 · Automatski

Čitanje stanja sklopke

```taphome
MODBUSR(H, 0, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 0, Uint16, Mu)
```

Zona 1 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:304 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 304, Uint16)
```

Zapis

```taphome
MODBUSW(H, 304, Uint16, round(Va))
```

Zona 1 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:300 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 300, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 300, Bool, St)
```

Zona 1 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:302 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 302, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 302, Int16, round(Va * 10))
```

Zona 1 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:303 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 303, Uint16)
```

Zapis

```taphome
MODBUSW(H, 303, Uint16, round(Va))
```

Zona 2 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:314 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 314, Uint16)
```

Zapis

```taphome
MODBUSW(H, 314, Uint16, round(Va))
```

Zona 2 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:310 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 310, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 310, Bool, St)
```

Zona 2 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:312 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 312, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 312, Int16, round(Va * 10))
```

Zona 2 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:313 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 313, Uint16)
```

Zapis

```taphome
MODBUSW(H, 313, Uint16, round(Va))
```

Zona 3 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:324 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 324, Uint16)
```

Zapis

```taphome
MODBUSW(H, 324, Uint16, round(Va))
```

Zona 3 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:320 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 320, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 320, Bool, St)
```

Zona 3 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:322 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 322, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 322, Int16, round(Va * 10))
```

Zona 3 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:323 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 323, Uint16)
```

Zapis

```taphome
MODBUSW(H, 323, Uint16, round(Va))
```

Zona 4 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:334 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 334, Uint16)
```

Zapis

```taphome
MODBUSW(H, 334, Uint16, round(Va))
```

Zona 4 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:330 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 330, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 330, Bool, St)
```

Zona 4 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:332 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 332, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 332, Int16, round(Va * 10))
```

Zona 4 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:333 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 333, Uint16)
```

Zapis

```taphome
MODBUSW(H, 333, Uint16, round(Va))
```

Zona 5 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:344 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 344, Uint16)
```

Zapis

```taphome
MODBUSW(H, 344, Uint16, round(Va))
```

Zona 5 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:340 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 340, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 340, Bool, St)
```

Zona 5 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:342 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 342, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 342, Int16, round(Va * 10))
```

Zona 5 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:343 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 343, Uint16)
```

Zapis

```taphome
MODBUSW(H, 343, Uint16, round(Va))
```

Zona 6 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:354 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 354, Uint16)
```

Zapis

```taphome
MODBUSW(H, 354, Uint16, round(Va))
```

Zona 6 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:350 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 350, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 350, Bool, St)
```

Zona 6 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:352 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 352, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 352, Int16, round(Va * 10))
```

Zona 6 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:353 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 353, Uint16)
```

Zapis

```taphome
MODBUSW(H, 353, Uint16, round(Va))
```

Zona 7 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:364 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 364, Uint16)
```

Zapis

```taphome
MODBUSW(H, 364, Uint16, round(Va))
```

Zona 7 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:360 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 360, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 360, Bool, St)
```

Zona 7 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:362 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 362, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 362, Int16, round(Va * 10))
```

Zona 7 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:363 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 363, Uint16)
```

Zapis

```taphome
MODBUSW(H, 363, Uint16, round(Va))
```

Zona 8 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:374 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 374, Uint16)
```

Zapis

```taphome
MODBUSW(H, 374, Uint16, round(Va))
```

Zona 8 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:370 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 370, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 370, Bool, St)
```

Zona 8 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:372 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 372, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 372, Int16, round(Va * 10))
```

Zona 8 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:373 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 373, Uint16)
```

Zapis

```taphome
MODBUSW(H, 373, Uint16, round(Va))
```

Zona 1 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:403 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 403, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 403, Uint16, St)
```

Zona 1 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:402 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 402, Uint16)
```

Zapis

```taphome
MODBUSW(H, 402, Uint16, Va)
```

Zona 1 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:400 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 400, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 400, Uint16, St)
```

Zona 1 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:401 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 401, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 401, Uint16, St)
```

Zona 2 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:413 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 413, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 413, Uint16, St)
```

Zona 2 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:412 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 412, Uint16)
```

Zapis

```taphome
MODBUSW(H, 412, Uint16, Va)
```

Zona 2 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:410 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 410, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 410, Uint16, St)
```

Zona 2 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:411 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 411, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 411, Uint16, St)
```

Zona 3 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:423 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 423, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 423, Uint16, St)
```

Zona 3 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:422 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 422, Uint16)
```

Zapis

```taphome
MODBUSW(H, 422, Uint16, Va)
```

Zona 3 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:420 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 420, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 420, Uint16, St)
```

Zona 3 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:421 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 421, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 421, Uint16, St)
```

Zona 4 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:433 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 433, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 433, Uint16, St)
```

Zona 4 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:432 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 432, Uint16)
```

Zapis

```taphome
MODBUSW(H, 432, Uint16, Va)
```

Zona 4 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:430 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 430, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 430, Uint16, St)
```

Zona 4 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:431 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 431, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 431, Uint16, St)
```

Zona 5 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:443 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 443, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 443, Uint16, St)
```

Zona 5 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:442 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 442, Uint16)
```

Zapis

```taphome
MODBUSW(H, 442, Uint16, Va)
```

Zona 5 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:440 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 440, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 440, Uint16, St)
```

Zona 5 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:441 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 441, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 441, Uint16, St)
```

Zona 6 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:453 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 453, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 453, Uint16, St)
```

Zona 6 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:452 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 452, Uint16)
```

Zapis

```taphome
MODBUSW(H, 452, Uint16, Va)
```

Zona 6 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:450 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 450, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 450, Uint16, St)
```

Zona 6 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:451 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 451, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 451, Uint16, St)
```

Zona 7 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:463 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 463, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 463, Uint16, St)
```

Zona 7 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:462 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 462, Uint16)
```

Zapis

```taphome
MODBUSW(H, 462, Uint16, Va)
```

Zona 7 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:460 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 460, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 460, Uint16, St)
```

Zona 7 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:461 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 461, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 461, Uint16, St)
```

Zona 8 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:473 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 473, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 473, Uint16, St)
```

Zona 8 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:472 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 472, Uint16)
```

Zapis

```taphome
MODBUSW(H, 472, Uint16, Va)
```

Zona 8 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:470 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 470, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 470, Uint16, St)
```

Zona 8 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:471 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 471, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 471, Uint16, St)
```

ALFA 1 — CO₂ Varijabla Samo za čitanje

Registar: IR:162 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(A, 162, Uint16)
```

ALFA 1 — NTC temperatura Senzor temperature Samo za čitanje

Registar: IR:165 UInt16 Jedinica: °C direct, /10

Čitanje temperature

```taphome
MODBUSR(A, 165, Uint16) / 10
```

ALFA 1 — Temperatura zraka Senzor temperature Samo za čitanje

Registar: IR:163 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 164, Uint16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 163, Uint16) / 10
```

ALFA 2 — CO₂ Varijabla Samo za čitanje

Registar: IR:172 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(A, 172, Uint16)
```

ALFA 2 — NTC temperatura Senzor temperature Samo za čitanje

Registar: IR:175 UInt16 Jedinica: °C direct, /10

Čitanje temperature

```taphome
MODBUSR(A, 175, Uint16) / 10
```

ALFA 2 — Temperatura zraka Senzor temperature Samo za čitanje

Registar: IR:173 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 174, Uint16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 173, Uint16) / 10
```

ALFA 3 — CO₂ Varijabla Samo za čitanje

Registar: IR:182 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(A, 182, Uint16)
```

ALFA 3 — NTC temperatura Senzor temperature Samo za čitanje

Registar: IR:185 UInt16 Jedinica: °C direct, /10

Čitanje temperature

```taphome
MODBUSR(A, 185, Uint16) / 10
```

ALFA 3 — Temperatura zraka Senzor temperature Samo za čitanje

Registar: IR:183 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 184, Uint16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 183, Uint16) / 10
```

ALFA 4 — CO₂ Varijabla Samo za čitanje

Registar: IR:192 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(A, 192, Uint16)
```

ALFA 4 — NTC temperatura Senzor temperature Samo za čitanje

Registar: IR:195 UInt16 Jedinica: °C direct, /10

Čitanje temperature

```taphome
MODBUSR(A, 195, Uint16) / 10
```

ALFA 4 — Temperatura zraka Senzor temperature Samo za čitanje

Registar: IR:193 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 194, Uint16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 193, Uint16) / 10
```

ALFA 5 — CO₂ Varijabla Samo za čitanje

Registar: IR:202 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(A, 202, Uint16)
```

ALFA 5 — NTC temperatura Senzor temperature Samo za čitanje

Registar: IR:205 UInt16 Jedinica: °C direct, /10

Čitanje temperature

```taphome
MODBUSR(A, 205, Uint16) / 10
```

ALFA 5 — Temperatura zraka Senzor temperature Samo za čitanje

Registar: IR:203 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 204, Uint16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 203, Uint16) / 10
```

ALFA 6 — CO₂ Varijabla Samo za čitanje

Registar: IR:212 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(A, 212, Uint16)
```

ALFA 6 — NTC temperatura Senzor temperature Samo za čitanje

Registar: IR:215 UInt16 Jedinica: °C direct, /10

Čitanje temperature

```taphome
MODBUSR(A, 215, Uint16) / 10
```

ALFA 6 — Temperatura zraka Senzor temperature Samo za čitanje

Registar: IR:213 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 214, Uint16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 213, Uint16) / 10
```

ALFA 7 — CO₂ Varijabla Samo za čitanje

Registar: IR:222 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(A, 222, Uint16)
```

ALFA 7 — NTC temperatura Senzor temperature Samo za čitanje

Registar: IR:225 UInt16 Jedinica: °C direct, /10

Čitanje temperature

```taphome
MODBUSR(A, 225, Uint16) / 10
```

ALFA 7 — Temperatura zraka Senzor temperature Samo za čitanje

Registar: IR:223 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 224, Uint16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 223, Uint16) / 10
```

ALFA 8 — CO₂ Varijabla Samo za čitanje

Registar: IR:232 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(A, 232, Uint16)
```

ALFA 8 — NTC temperatura Senzor temperature Samo za čitanje

Registar: IR:235 UInt16 Jedinica: °C direct, /10

Čitanje temperature

```taphome
MODBUSR(A, 235, Uint16) / 10
```

ALFA 8 — Temperatura zraka Senzor temperature Samo za čitanje

Registar: IR:233 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 234, Uint16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 233, Uint16) / 10
```

**Povezivanje:** Modbus TCP • Slave ID: $\[SlaveId]

Moguća poboljšanja (17)

- IR:0 Product ID — UInt16, always 39 for Futura; L/M/S only
- IR:1-2 Serial Number — UInt32, globally unique ID; L/M/S only
- IR:14 Device Model — UInt16, 0-1=Futura L, 2=Futura M; L/M/S only
- IR:15 Available Features — UInt16, bitmask: heating, cooling, bypass, VarioBreeze, circulation support
- IR:16-17 Operation Modes — UInt32, bitmask with 24 mode/status bits (boost, circulation, away, defrost, etc.)
- IR:18-19 Errors — UInt32, 22 error bits (sensor errors, fan errors, exchanger errors)
- IR:20-21 Warnings — UInt32, 18 warning bits (filter, battery, fan RPM, zone config)
- IR:32 Extract Air Temperature — Int16, 0.1°C — indoor/extract air temperature
- IR:36 Extract Air Humidity — Int16, 0.1% — indoor/extract air humidity
- IR:52 Backup Battery Voltage — UInt16, 0.001 mV — RTC backup battery; L/M/S only
- IR:51 Digital Inputs — UInt16, bitmask: user button, factory button, boost input, UIN1/2; L/M/S only
- HR:6-9 Away Mode Schedule — UInt32 x2, begin/end unix timestamps for away mode; L/M/S only
- IR:26 Heating/Cooling Status — UInt16, bitmask: inner heating, CoolBreeze heating/cooling active; L+ only
- HR:20 Zone Auto Control Priority — UInt16, 0=temperature, 1=CO2 priority when CoolBreeze active; L/M/S only
- HR:21 Kitchen Hood Default State — UInt16, 0=closed, 1=opened normally; L/M/S only
- HR:22 Zone Boost Air Volume — UInt16, 50–150 m3/h increment per run; L/M/S only
- HR:23 Kitchen Hood Air Volume — UInt16, 50–150 m3/h increment per run; L/M/S only

## Parametri uvoza

Ove vrijednosti unosite pri uvozu XML-a.

| Pitanje u aplikaciji | Zadano        |
|----------------------|---------------|
| Slave ID             | `1`           |
| IP adresa            | `192.168.1.0` |

## Izvori

- Jablotron Futura Modbus TCP Register Map
  
  2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/jablotron-futura/manufacturer/FU_TCP_TXT_EN.pdf)
- Home Assistant Jablotron Futura Integration
  
  [github.com](https://github.com/tomas-kulhanek/ha-jablotron-futura) 2026-03-20

Dokumenti proizvođača zaštićeni su autorskim pravom (©) svojih vlasnika. Dostupni su onako kako ih je proizvođač objavio, samo za informaciju.

## Povezana dokumentacija

- [Modbus Integration](https://taphome.com/hr/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/hr/docs/integration/modbus/)
- [Jednostavna konfiguracija pomoću predložaka](https://taphome.com/hr/docs/integration/modbus/templates/)
- [Skripte Modbus i prefetch](https://taphome.com/hr/docs/script/modbus-scripts/)
- [Funkcije Modbus](https://taphome.com/hr/docs/script/modbus/)
- [Tipovi podataka Modbus](https://taphome.com/hr/docs/script/modbus-data-types/)