title: "Jablotron Futura L+"
description: "Upravljanje ventilacijom, praćenje temperature, vlažnosti i istrošenosti filtra te pokretanje funkcija Boost, Cirkulacija i Nadtlak preko Modbus TCP."
url: "https://taphome.com/hr/compatibility/jablotron-futura-l/"
language: hr
lastmod: 2026-10-08
generator: hugo
ai:
  topics: ["modbus-tcp","air-recovery","heat-recovery-ventilation","ethernet","zone-ventilation"]
  questions: ["Kako integrirati Jablotron Futura L+ sa sustavom TapHome?","Što mjeri i čime upravlja predložak TapHome za Jablotron Futura L+?","Kako spojiti Jablotron Futura L+ na TapHome preko Modbus TCP?","Koja je razlika između mapa registara Futura L+ i Futura L/M/S?","Kako preko sustava TapHome uključiti ventilaciju Boost ili Nadtlak na Jablotron Futura L+?","Zašto Jablotron Futura L+ odbija moje Modbus upise?","Kako koristiti senzore CO₂ sustava TapHome za zonsku ventilaciju Jablotron Futura L+?","Zašto vrijednosti zonskih senzora Jablotron Futura L+ u sustavu TapHome pokazuju 0?"]
---

# Jablotron Futura L+

Komunikacija: Modbus TCP

- [Stranica proizvoda Jablotron Futura](https://www.jablotron.com/en/products-and-services/other-products-and-services/energy-recovery-ventilation-of-houses)

> Adresa u mreži
> 
> TapHome komunicira s uređajem na adresi unesenoj pri uvozu. Dodijelite uređaju stalnu adresu — rezervaciju IP adrese u usmjerivaču ili njegovo mDNS ime ako ga podržava — inače integracija prestaje raditi kada usmjerivač promijeni adresu.
> 
> [Priprema mreže](https://taphome.com/hr/docs/setup/network-preparation/)

## Upute za integraciju

Jablotron Futura L+ je rekuperator (MVHR, ventilacija s povratom topline) s entalpijskim protustrujnim izmjenjivačem, koji JABLOTRON LIVING TECHNOLOGY CZ proizvodi za stambene zgrade. TapHome se na jedinicu spaja izravno protokolom **Modbus TCP preko Etherneta**, bez pristupnika ili dodatnog modula.

Predložak nudi odabir načina ventilacije, vremenski ograničene funkcije Boost, Cirkulacija i Nadtlak, istrošenost filtra, temperaturu i vlažnost dovodnog, otpadnog i vanjskog zraka, podatke o povratu topline i snazi, sklopke za uključivanje funkcija (bypass, grijanje, hlađenje, zaštita od radona, automatska cirkulacija), zadanu temperaturu te čitanje i upis za 8 zona vanjskih senzora i 8 zona vanjskih tipki.

> [!WARNING]
> **Futura L+** ima sažeti adresni prostor registara koji se razlikuje od **Futura L/M/S**. Za starije modele postoji zaseban predložak TapHome (`Jablotron Futura L, M, S`). Uvoz pogrešnog predloška uzrokuje greške `ILLEGAL_DATA_ADDRESS` ili čitanje besmislenih vrijednosti bez dojave greške. Prije uvoza provjerite model jedinice.

## Spajanje hardvera

Jedinica Futura ima jedan Ethernet konektor RJ45 na glavnoj upravljačkoj ploči (**X1** — LAN). Spojite ga standardnim Ethernet kabelom u istu lokalnu mrežu kao centralnu jedinicu TapHome Core; za integraciju s TapHome nije potreban dodatni pristupnik, pretvornik ni pribor.

Za TapHome je važan samo **LAN konektor (X1)**. Sabirnice RS-485 (X2, X3) i sabirnica AA (X6) rezervirane su za vlastiti pribor Jablotron (upravljačke ploče Alfa, zidni senzori, CoolBreeze, VarioBreeze) i nisu dostupne za vanjski BMS.

### Konektori upravljačke ploče

![Raspored konektora upravljačke ploče Jablotron Futura (X1-X6 i tipka T1)](https://taphome.com/images/compatibility/jablotron-futura-l/pcb-connectors_hu_3cbf1801a8cb78df.jpg)

| Konektor | Vrsta | Funkcija |
|-----------|------|----------|
| **X1** | RJ45 | LAN: Modbus TCP prema sustavu TapHome, oblak MyJABLOTRON |
| **X2** | Phoenix Contact, 3 pina | Sabirnica RS-485: rezervirano / ne koristi se |
| **X3** | Phoenix Contact, 4 pina | Sabirnica RS-485 za ploče Alfa, senzore CO₂, CoolBreeze |
| **X4** | Phoenix Contact, 2 pina | Senzor vanjske temperature NTC 10 kΩ |
| **X5** | Phoenix Contact, 5 pinova | IN/OUT: LED, BST (boost), IN2, IN1 (0–10 V ili kontakt), GND |
| **X6** | Phoenix Contact, 2 pina | Sabirnica AA (starija sabirnica za jednu ploču) |
| **T1** | Tipka na tiskanoj pločici | Kratki pritisak = inicijalizacija filtra, dugi pritisak = servisni način Bluetooth |

> [!NOTE]
> Analogni ulazi **IN1/IN2** na X5 (0–10 V ili beznaponski kontakt) dodatni su paralelni kanal za BMS. Prema uputama za ugradnju analogno upravljanje ima prednost pred senzorima CO₂ (nadjačava ih), što je korisno kad Modbus TCP nije moguć, ali integracija s TapHome koristi samo LAN priključak.

## Konfiguracija

Za uključivanje Modbus TCP na Futura L+ nije potrebna aktivacija, DIP sklopka ni servisni izbornik. TCP poslužitelj je aktivan prema zadanim postavkama čim je jedinica pod napajanjem i spojena na LAN.

Pri uvozu predloška u TapHome unesite:

- **IP adresa**: IP adresa jedinice u lokalnoj mreži
- **Adresa uređaja (Unit ID)**: Modbus slave adresa (fiksna vrijednost: `1`)

Parametri veze:

| Parametar | Vrijednost |
|-----------|-------|
| Protokol | Modbus TCP |
| Port | 502 |
| Adresa uređaja | 1 |
| Dostupne utičnice (socket) | 1 (samo jedan istodobni klijent) |
| Minimalni firmver | FLA.P.01.06 |
| Raspon registara | IR:0–IR:26, HR:0–HR:273 |

> [!WARNING]
> Futura L+ prihvaća **samo jednog Modbus TCP klijenta istodobno**. Ako je već spojen drugi sustav (Home Assistant, vlastiti Modbus klijent, druga centralna jedinica TapHome Core), TapHome neće moći otvoriti utičnicu. Prije uvoza predloška odspojite ostale Modbus TCP klijente. Veza s oblakom MyJABLOTRON koristi odlazni HTTPS i ne zauzima Modbus utičnicu.

> [!NOTE]
> Složeni registri (uint32, int32) moraju se čitati i upisivati jednom Modbus operacijom, a djelomično čitanje vraća `ILLEGAL_DATA_ADDRESS`. Predložak TapHome ispravno grupira čitanja, pa ta greška tijekom normalnog rada obično znači da je uvezena pogrešna varijanta predloška (L/M/S umjesto L+).

### Dodatna zaštita lozinkom

Holding registar **HR:920** (`user_password`) prema zadanim postavkama ima vrijednost **65535 = isključeno**, što znači da se Modbus upisi prihvaćaju bez provjere autentičnosti. Ako je instalater uključio zaštitu lozinkom u aplikaciji MyJABLOTRON / MyCOMPANY, Modbus upisi ne uspijevaju, bez dojave greške, dok se pristupni kod ne upiše u HR:900 prije isteka vremena prijave (zadano 300 s, HR:922). Kod uobičajenih instalacija TapHome lozinku ostavite isključenu.

## Mogućnosti uređaja

Predložak nudi 84 uređaja: podatke za cijelu jedinicu, vremenski ograničene funkcije, sklopke funkcija, zadanu temperaturu te 8 zona vanjskih senzora i 8 zona vanjskih tipki.

### Način ventilacije

- **Način ventilacije**: odabir snage ventilatora preko holding registra HR:0. Dostupne vrijednosti: Isključeno (0), ručni Stupanj 1–5 (1–5), Automatski (6). Predložak nudi i brojčane vrijednosti 7–9, koje u mapi registara nemaju dokumentirano značenje i treba ih smatrati rezerviranima.

### Vremenski ograničene funkcije

Tri vremenski ograničene funkcije dostupne su kao prekidači s više vrijednosti s 10 unaprijed zadanih trajanja (isključeno, 30 s, 60 s, 5 min, 10 min, 15 min, 30 min, 1 h, 1,5 h, 2 h). Svaka funkcija ima i servisni atribut **Preostalo vrijeme [s]** te servisnu radnju koja prihvaća vlastitu vrijednost odbrojavanja (1–7200 s):

- **Funkcija Boost** (HR:1): najjača ventilacija tijekom odabranog vremena
- **Funkcija Cirkulacija** (HR:2): recirkulacija zraka (unutarnji krug) bez povrata topline
- **Funkcija Nadtlak** (HR:3): dovod > odsis, korisno pri paljenju kamina

Čitanje registra vraća preostalo vrijeme u sekundama, a upis pokreće funkciju.

### Senzori na putu zraka

Dostupna su tri mjerna mjesta na putu zraka kroz jedinicu, a svako objedinjuje temperaturu i vlažnost iz zasebnih ulaznih registara. Uz njih je dostupna i opcionalna vanjska sonda NTC:

| Uređaj | Temperatura | Vlažnost | Opis |
|--------|-------------|----------|-------------|
| Vanjski zrak | IR:12 | IR:16 | Vanjski zrak prije povrata topline |
| Dovodni zrak | IR:13 | IR:17 | Svježi zrak koji se dovodi u zgradu |
| Otpadni zrak | IR:15 | IR:19 | Otpadni zrak koji izlazi iz zgrade |
| Vanjski NTC senzor | IR:20 | — | Dodatna vanjska NTC sonda 10 kΩ na X4 |

Temperature su pohranjene u koracima od 0,1 °C (`int16`) i predložak ih preračunava u °C; vrijednosti vlažnosti preračunavaju se iz neobrađenog očitanja (u koracima od 0,1 %) u udio (0–1).

> [!NOTE]
> **Vanjski NTC senzor** javlja `-99` kad na konektor X4 nije spojena sonda. Predložak tu oznaku preslikava na NaN, kako se vrijednost u sustavu TapHome ne bi prikazala kao valjana temperatura.

### Praćenje učinka

- **Povrat topline** (IR:23): trenutačna toplina prenesena iz odsisnog u dovodni zrak, u W
- **Električna snaga** (IR:22): ukupna električna snaga koju jedinica troši, u W
- **Snaga grijanja** (IR:24): trenutačna snaga koju troši unutarnji električni dogrijač od 350 W, u W
- **Protok zraka** (IR:25): zbirni volumni protok dovodnog i odsisnog zraka, u m³/h
- **Istrošenost filtra** (IR:21): razina onečišćenosti filtra: 0 % = čist, 100 % = potrebna zamjena. Prikazuje se kao razina poput dimera (0,0–1,0).

### Zadana temperatura

- **Željena temperatura** (HR:4): zadana unutarnja temperatura za unutarnju regulaciju jedinice, u °C. Čitanje i upis skaliraju se ×10 (razlučivost 0,1 °C).

### Sklopke za uključivanje funkcija

Binarne sklopke za uključivanje i isključivanje koje upravljaju radom jedinice:

- **Uključivanje bypassa** (HR:7): automatski bypass izmjenjivača topline kad je korisno pasivno hlađenje
- **Uključivanje hlađenja** (HR:9): uključuje modul hlađenja CoolBreeze (potreban je dodatni pribor)
- **Uključivanje grijanja** (HR:15): uključuje unutarnji električni dogrijač od 350 W
- **Uključivanje zaštite od radona** (HR:6): smanjena recirkulacija sprječava nakupljanje radona
- **Automatska cirkulacija** (HR:10): funkcija automatske recirkulacije zraka
- **Vremenski program** (HR:5): tjedni vremenski program

### Vanjski zonski senzori (zone 1–8)

Futura L+ prihvaća vrijednosti do 8 vanjskih senzora CO₂/temperature/vlažnosti, po jedan za svaku zonu. To su ulazi jedinice Futura: TapHome u njih upisuje vrijednosti, a ne očitava iz njih vrijednosti senzora Jablotron (pogledajte niže **Korištenje senzora TapHome za zonsku ventilaciju**). Za svaku od 8 zona predložak nudi:

- **Senzor prisutan**: uključuje ulaz senzora za zonu
- **Temperatura**: vanjska vrijednost temperature (od −20 °C do 100 °C, razlučivost 0,1 °C)
- **Vlažnost**: relativna vlažnost (0–100 %)
- **CO₂**: razina CO₂ (0–10 000 ppm)

Blokovi holding registara zonskih senzora nalaze se na HR:100–175 (10 registara po zoni, korak 10).

Izmjereni CO₂, temperatura i vlažnost zona 1–8 (IR:100–173) dostupni su u Modbus mapi L+, ali ne i u predlošku. Mogu se dodati kao Modbus varijable.

### Vanjske zonske tipke (zone 1–8)

Futura L+ podržava i 8 vanjskih zidnih tipki za brzo pokretanje funkcije Boost ili kuhinjske nape. Po zoni:

- **Tipka prisutna**: uključuje ulaz tipke
- **Način tipke**: odabir između funkcije Boost (0) i Kuhinjska napa / Digestoř (1)
- **Odbrojavanje tipke**: odbrojavanje (0–10 800 s)
- **Aktivacija tipke**: pokreće radnju tipke (vremensko ograničenje 3 sata)

Blokovi holding registara zonskih tipki nalaze se na HR:200–273 (10 registara po zoni, korak 10).

### Servisni atributi modula

Na razini modula dostupna su dva dijagnostička atributa:

- **MAC adresa** (IR:2–IR:4): Ethernet MAC adresa jedinice, sastavljena iz tri 16-bitna registra i oblikovana kao heksadecimalni niz
- **Verzija firmvera** (IR:0): verzija firmvera L+ (`uint32`)

## Korištenje senzora TapHome za zonsku ventilaciju

Kod ventilacije po prostorijama VarioBreeze jedinica Futura povezuje komponente zone prema istoj postavci DIP sklopke (zona 1–8). Preko Modbusa nudi i ulaz za vanjski senzor za svaku od 8 zona, pa vrijednosti zone mogu davati senzori sustava TapHome, na primjer zidni prekidač s ugrađenim senzorom CO₂. Smjer je **TapHome → Futura**.

Za svaku prostoriju:

1. **Broj zone**: postavka DIP sklopke na ventilu te prostorije (1–8). Koristite zonske uređaje s istim brojem.
2. Uključite **Zona N – Senzor prisutan** (u aplikaciji: *Zona N - Přítomnost externích čidel*).
3. Za svaku vrijednost zone dodajte smart rule **Formula**:
   - **Zona N – CO₂** (*Zona N - CO₂*) = senzor CO₂ u prostoriji, u ppm
   - **Zona N – Temperatura** (*Zona N - Teplota*) = temperatura u prostoriji, u °C
   - **Zona N – Vlažnost** (*Zona N - vlhkost*) = vlažnost u prostoriji **× 100**
4. **Način ventilacije** (*Výkon větrání*) postavite na **Automatski**; stupnjevi 1–5 su ručni stupnjevi ventilatora.

> [!WARNING]
> TapHome pohranjuje vlažnost kao udio (0–1), a Futura očekuje postotak (0–100). Bez **× 100** u formuli vlažnost 0,45 upisuje se kao 0 %.

> [!NOTE]
> Popunite sve tri vrijednosti svake zone kojoj je uključen **Senzor prisutan**. Zonski uređaj bez smart rule zadržava vrijednost 0 i TapHome je upisuje u Futuru, pa zona tada javlja 0 °C i 0 %.

## Rješavanje problema

### Vrijednosti zonskih senzora su 0

TapHome pri svakom očitavanju upisuje trenutačnu vrijednost svakog zonskog uređaja u Futuru. Zonski uređaj bez smart rule zadržava vrijednost 0, pa Futura prima 0 ppm, 0 °C ili 0 %. Dodajte smart rule za svaku vrijednost aktivne zone, a za zone koje se ne koriste ostavite **Senzor prisutan** isključen. Ako je 0 samo vlažnost, u formuli nedostaje **× 100**.

### Futura ne reagira na zonske senzore

1. **Način ventilacije** postavljen je na **Automatski**; stupnjevi 1–5 su ručni
2. **Zona N – Senzor prisutan** uključen je za tu zonu
3. Broj zone u sustavu TapHome odgovara postavci DIP sklopke na ventilu zone

### Nema Modbus komunikacije

1. Provjerite je li Ethernet kabel spojen na **X1 (LAN)** na glavnoj ploči, a ne na neku stezaljku Phoenix Contact
2. Provjerite IP adresu jedinice u tablici DHCP zakupa usmjerivača ili u aplikaciji MyJABLOTRON; centralna jedinica TapHome Core i Futura moraju biti u istoj podmreži
3. Provjerite ne blokira li vatrozid TCP port 502 između sustava TapHome i jedinice
4. Provjerite ne zauzima li neki drugi Modbus TCP klijent (Home Assistant, dijagnostički alat, druga centralna jedinica TapHome Core) jedinu dostupnu utičnicu; odspojite takvog klijenta i pokušajte ponovno
5. Provjerite je li firmver **FLA.P.01.06** ili noviji (vidljivo u aplikaciji MyJABLOTRON)

### Greške ILLEGAL_DATA_ADDRESS

Složeni registri (bitovne mape uint32, vremenske oznake int32) moraju se čitati jednom Modbus operacijom. U praksi ta greška tijekom normalnog očitavanja u sustavu TapHome znači da je **uvezena pogrešna varijanta predloška**. Predložak L/M/S adresira registre IR:30–52 / HR:0–17 koji u mapi L+ ne postoje (L+ počinje na IR:0 i HR:0 sa sažetim rasporedom). Ponovno uvezite ispravan predložak `Jablotron Futura L+`.

### Modbus upisi nemaju učinka

Ako jedinica odgovara na čitanja, ali zanemaruje upise (promjene načina rada, pokretanje odbrojavanja, uključivanje funkcija), instalater je možda uključio korisničku lozinku u aplikaciji MyJABLOTRON. Isključite lozinku (upišite 65535 u HR:920 dok ste prijavljeni) ili ponovno upišite pristupni kod u HR:900 prije isteka vremena zadanog u HR:922. Kod uobičajenih instalacija TapHome lozinka treba ostati isključena.

### Vrijednosti temperature ili vlažnosti izgledaju pogrešno

Futura L+ temperature i vlažnost kodira u koracima od 0,1 °C i 0,1 %. Predložak TapHome već primjenjuje ispravno skaliranje (÷10 za temperaturu, ÷1000 za vlažnost u uređajima za dovodni, otpadni i vanjski zrak). Ako vrijednosti odstupaju 10 ili 1000 puta, uvezen je pogrešan predložak (L/M/S), jer se faktori skaliranja razlikuju između varijanti.

## Dostupni uređaji 84

Ovi se uređaji pojavljuju u TapHomeu nakon uvoza.

Jablotron Futura L+ Modul

Servisni atributi

|                  |
|------------------|
| MAC adresa       |
| Verzija firmvera |

Čitanje (modul)

```taphome
var Code := MODBUSR(A,6, UInt32);
IF (GETBIT(Code,0), ADDINFO(0,"Aktivní funkce Boost"));
IF (GETBIT(Code,1), ADDINFO(1,"Aktivní funkce Cirkulace"));
IF (GETBIT(Code,2), ADDINFO(2,"Aktivní časový program"));
IF (GETBIT(Code,3), ADDINFO(3,"Aktivní funkce Přetlak"));
IF (GETBIT(Code,4), ADDINFO(4,"Aktivní funkce Dovolená"));
IF (GETBIT(Code,5), ADDINFO(5,"Aktivní funkce Párty"));
IF (GETBIT(Code,6), ADDINFO(6,"Aktivní funkce Noční režim"));
IF (GETBIT(Code,7), ADDINFO(7,"Aktivní funkce Protiradonová ochrana"));
IF (GETBIT(Code,8), ADDINFO(8,"Zařízení je zapnuto, není v režimu snížené spotřeby"));
IF (GETBIT(Code,9), ADDINFO(9,"Probíhá kontrola filtrů"));
IF (GETBIT(Code,10), ADDINFO(10,"Probíhá vysoušení"));
IF (GETBIT(Code,11), ADDINFO(11,"Otevřený Bypass"));
IF (GETBIT(Code,12), ADDINFO(12,"Nízká venkovní teplota, omezená funkce větrání"));
IF (GETBIT(Code,13), ADDINFO(13,"Odstavení po chybě"));
IF (GETBIT(Code,14), ADDINFO(14,"Zařízení se spouští"));
IF (GETBIT(Code,15), ADDINFO(15,"Aktivní servisní režim"));
IF (GETBIT(Code,16), ADDINFO(16,"Teplota odpadního vzduchu < -3°C (splněna podmínka ochrany před zamrznutím)"));
IF (GETBIT(Code,17), ADDINFO(17,"Nouzové vypnutí"));
IF (GETBIT(Code,18), ADDINFO(18,"Nouzové vypnutí"));
IF (GETBIT(Code,19), ADDINFO(19,"Odměřování tlakové ztráty"));
IF (GETBIT(Code,20), ADDINFO(20,"Stand-by"));
IF (GETBIT(Code,21), ADDINFO(21,"Zónový boost"));
IF (GETBIT(Code,22), ADDINFO(22,"Odměřování tlakové ztráty zón"));

Code := MODBUSR(A,8, UInt32);
IF (GETBIT(Code,0), ADDERROR(0,"Chyba senzoru ambient"));
IF (GETBIT(Code,1), ADDERROR(1,"Chyba senzoru indoor"));
IF (GETBIT(Code,2), ADDERROR(2,"Chyba senzoru fresh"));
IF (GETBIT(Code,3), ADDERROR(3,"Chyba senzoru waste"));
IF (GETBIT(Code,4), ADDERROR(4,"Chyba přívodního ventilátoru"));
IF (GETBIT(Code,5), ADDERROR(5,"Chyba odtahového ventilátoru"));
IF (GETBIT(Code,6), ADDERROR(6,"Chyba komunikace s výměníkem"));
IF (GETBIT(Code,7), ADDERROR(7,"Chyba polohy klapek výměníku"));
IF (GETBIT(Code,8), ADDERROR(8,"Chyba komunikace s IO deskou"));
IF (GETBIT(Code,9), ADDERROR(9,"Zablokovaný přívodní ventilátor"));
IF (GETBIT(Code,10), ADDERROR(10,"Zablokovaný odtahový ventilátor"));
IF (GETBIT(Code,11), ADDERROR(11,"Chyba komunikace s Coolbreeze"));
IF (GETBIT(Code,12), ADDERROR(12,"Chyba venkovní jednotky Coolbreeze"));

Code := MODBUSR(A,10, UInt32);
IF (GETBIT(Code,0), ADDWARNING(0,"Neinicializovaný filtr"));
IF (GETBIT(Code,1), ADDWARNING(1,"Filtr je příliš zanesený"));
IF (GETBIT(Code,2), ADDWARNING(2,"Filtr se používá příliš dlouho"));
IF (GETBIT(Code,3), ADDWARNING(3,"Nízké napětí RTC baterie"));
IF (GETBIT(Code,4), ADDWARNING(4,"Příliš vysoké otáčky přívodního ventilátoru"));
IF (GETBIT(Code,5), ADDWARNING(5,"Příliš vysoké otáčky odtahového ventilátoru"));
IF (GETBIT(Code,8), ADDWARNING(8,"Příliš nízká venkovní teplota, omezená funkce větrání"));
IF (GETBIT(Code,9), ADDWARNING(9,"Nesprávná konfigurace zónového větrání - přívod"));
IF (GETBIT(Code,10), ADDWARNING(10,"Nesprávná konfigurace zónového větrání - odtah"));
IF (GETBIT(Code,11), ADDWARNING(11,"Nouzové vypnutí"));
IF (GETBIT(Code,12), ADDWARNING(12,"Chyba komunikace se SuperBreeze"));
IF (GETBIT(Code,13), ADDWARNING(13,"Obecná chyba SuperBreeze"));
```

Servisni atributi

MAC adresa

```taphome
var macA := MODBUSR(A, 2, Uint16);
var macB := MODBUSR(A, 3, Uint16);
var macC := MODBUSR(A, 4, Uint16);
TOSTRING(GETBYTE(macA, 0), "X2") + ":" +
TOSTRING(GETBYTE(macA, 1), "X2") + ":" +
TOSTRING(GETBYTE(macB, 0), "X2") + ":" +
TOSTRING(GETBYTE(macB, 1), "X2") + ":" +
TOSTRING(GETBYTE(macC, 0), "X2") + ":" +
TOSTRING(GETBYTE(macC, 1), "X2");
```

Verze firmware

```taphome
MODBUSR(A, 0, Uint32)
```

Povrat topline Varijabla Samo za čitanje

Trenutačna toplina prenesena iz odsisnog u dovodni zrak, u vatima

Registar: IR:23 UInt16 Jedinica: W

Čitanje

```taphome
MODBUSR(A, 23, Uint16)
```

Električna snaga Varijabla Samo za čitanje

Trenutačna električna snaga koju jedinica troši (ventilatori + elektronika + dogrijač), u vatima

Registar: IR:22 UInt16 Jedinica: W

Čitanje

```taphome
MODBUSR(A, 22, Uint16)
```

Protok zraka Varijabla Samo za čitanje

Zbirni protok dovodnog i odsisnog zraka, u m³/h

Registar: IR:25 UInt16 Jedinica: m3/h

Čitanje

```taphome
MODBUSR(A, 25, Uint16)
```

Automatska cirkulacija Sklopka Čitanje i pisanje

Uključuje automatsku recirkulaciju zraka (unutarnji krug) kad je to potrebno

Registar: HR:10 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 10, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 10, Bool, St)
```

Vremenski program Sklopka Čitanje i pisanje

Uključuje tjedni vremenski program postavljen na jedinici

Registar: HR:5 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 5, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 5, Uint16, St)
```

Dovodni zrak Senzor temperature Samo za čitanje

Temperatura i vlažnost svježeg zraka koji se dovodi u zgradu (nakon povrata topline)

Registar: IR:13 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 17, Int16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 13, Int16) / 10
```

Vanjski NTC senzor Senzor temperature Samo za čitanje

Dodatna vanjska NTC sonda 10 kΩ za vanjsku temperaturu na konektoru X4; kad nije spojena, očitava -99

Registar: IR:20 Int16 Jedinica: °C direct, /10

Čitanje temperature

```taphome
var x:= MODBUSR(A, 20, Int16) / 10;
if (x = -99, NaN, x)
```

Funkcija Boost Prekidač s više vrijednosti Čitanje i pisanje

Maksimalna ventilacija na određeno vrijeme: odaberite unaprijed zadano trajanje; očitanje vraća preostalo vrijeme

Registar: HR:1 UInt16 Jedinica: s numeric

Vrijednosti / stanja: Isključeno · 30 s · 60 s · 5 min · 10 min · 15 min · 30 min · 1 h · 1,5 h · 2 h

Servisne radnje

|                |
|----------------|
| Funkcija Boost |

Čitanje stanja sklopke

```taphome
var x := MODBUSR(H, 1, Uint16);
IF(x = 0, RETURN(0));
IF(x > 5400, RETURN(9));
IF(x > 3600, RETURN(8));
IF(x > 1800, RETURN(7));
IF(x > 900, RETURN(6));
IF(x > 600, RETURN(5));
IF(x > 300, RETURN(4));
IF(x > 60, RETURN(3));
IF(x > 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Zapis stanja sklopke

```taphome
IF(Mu = 0, MODBUSW(H, 1, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 1, Uint16, 30));
IF(Mu = 2, MODBUSW(H, 1, Uint16, 60));
IF(Mu = 3, MODBUSW(H, 1, Uint16, 300));
IF(Mu = 4, MODBUSW(H, 1, Uint16, 600));
IF(Mu = 5, MODBUSW(H, 1, Uint16, 900));
IF(Mu = 6, MODBUSW(H, 1, Uint16, 1800));
IF(Mu = 7, MODBUSW(H, 1, Uint16, 3600));
IF(Mu = 8, MODBUSW(H, 1, Uint16, 5400));
IF(Mu = 9, MODBUSW(H, 1, Uint16, 7200));
```

Servisni atributi

Zbývající čas \[s]

```taphome
MODBUSR(H, 1, Uint16)
```

Servisne radnje

Funkce Boost

Parametri: Čas (1–7200 sec)

```taphome
MODBUSW(H, 1, Uint16, sec)
```

Funkcija Cirkulacija Prekidač s više vrijednosti Čitanje i pisanje

Recirkulacija zraka na određeno vrijeme (unutarnji krug, bez povrata topline); očitanje vraća preostalo vrijeme

Registar: HR:2 UInt16 Jedinica: s numeric

Vrijednosti / stanja: Isključeno · 30 s · 60 s · 5 min · 10 min · 15 min · 30 min · 1 h · 1,5 h · 2 h

Servisne radnje

|                      |
|----------------------|
| Funkcija Cirkulacija |

Čitanje stanja sklopke

```taphome
var x := MODBUSR(H, 2, Uint16);
IF(x = 0, RETURN(0));
IF(x > 5400, RETURN(9));
IF(x > 3600, RETURN(8));
IF(x > 1800, RETURN(7));
IF(x > 900, RETURN(6));
IF(x > 600, RETURN(5));
IF(x > 300, RETURN(4));
IF(x > 60, RETURN(3));
IF(x > 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Zapis stanja sklopke

```taphome
IF(Mu = 0, MODBUSW(H, 2, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 2, Uint16, 30));
IF(Mu = 2, MODBUSW(H, 2, Uint16, 60));
IF(Mu = 3, MODBUSW(H, 2, Uint16, 300));
IF(Mu = 4, MODBUSW(H, 2, Uint16, 600));
IF(Mu = 5, MODBUSW(H, 2, Uint16, 900));
IF(Mu = 6, MODBUSW(H, 2, Uint16, 1800));
IF(Mu = 7, MODBUSW(H, 2, Uint16, 3600));
IF(Mu = 8, MODBUSW(H, 2, Uint16, 5400));
IF(Mu = 9, MODBUSW(H, 2, Uint16, 7200));
```

Servisni atributi

Zbývající čas \[s]

```taphome
MODBUSR(H, 2, Uint16)
```

Servisne radnje

Funkce Cirkulace

Parametri: Čas (1–7200 sec)

```taphome
MODBUSW(H, 2, Uint16, sec)
```

Funkcija Nadtlak Prekidač s više vrijednosti Čitanje i pisanje

Način nadtlaka na određeno vrijeme (dovod &gt; odsis), koristan pri paljenju kamina; očitanje vraća preostalo vrijeme

Registar: HR:3 UInt16 Jedinica: s numeric

Vrijednosti / stanja: Isključeno · 30 s · 60 s · 5 min · 10 min · 15 min · 30 min · 1 h · 1,5 h · 2 h

Servisne radnje

|                  |
|------------------|
| Funkcija Nadtlak |

Čitanje stanja sklopke

```taphome
var x := MODBUSR(H, 3, Uint16);
IF(x = 0, RETURN(0));
IF(x > 5400, RETURN(9));
IF(x > 3600, RETURN(8));
IF(x > 1800, RETURN(7));
IF(x > 900, RETURN(6));
IF(x > 600, RETURN(5));
IF(x > 300, RETURN(4));
IF(x > 60, RETURN(3));
IF(x > 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Zapis stanja sklopke

```taphome
IF(Mu = 0, MODBUSW(H, 3, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 3, Uint16, 30));
IF(Mu = 2, MODBUSW(H, 3, Uint16, 60));
IF(Mu = 3, MODBUSW(H, 3, Uint16, 300));
IF(Mu = 4, MODBUSW(H, 3, Uint16, 600));
IF(Mu = 5, MODBUSW(H, 3, Uint16, 900));
IF(Mu = 6, MODBUSW(H, 3, Uint16, 1800));
IF(Mu = 7, MODBUSW(H, 3, Uint16, 3600));
IF(Mu = 8, MODBUSW(H, 3, Uint16, 5400));
IF(Mu = 9, MODBUSW(H, 3, Uint16, 7200));
```

Servisni atributi

Zbývající čas \[s]

```taphome
MODBUSR(H, 3, Uint16)
```

Servisne radnje

Funkce Přetlak

Parametri: Čas (1–7200 sec)

```taphome
MODBUSW(H, 3, Uint16, sec)
```

Istrošenost filtra Dimer Samo za čitanje

Razina onečišćenosti filtra: 0 % = čist, 100 % = potrebna zamjena

Registar: IR:21 UInt16 Jedinica: % numeric, /100

Čitanje razine

```taphome
MODBUSR(A, 21, Uint16) / 100
```

Otpadni zrak Senzor temperature Samo za čitanje

Temperatura i vlažnost otpadnog zraka koji izlazi iz zgrade (prije izmjenjivača topline)

Registar: IR:15 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 19, Int16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 15, Int16) / 10
```

Uključivanje bypassa Sklopka Čitanje i pisanje

Uključuje automatski bypass izmjenjivača topline kad je korisno pasivno hlađenje

Registar: HR:7 UInt16 boolean

Vrijednosti / stanja: Povoleno · Zakázáno

Čitanje stanja sklopke

```taphome
MODBUSR(H, 7, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 7, Uint16, St)
```

Uključivanje hlađenja Sklopka Čitanje i pisanje

Uključuje modul aktivnog hlađenja CoolBreeze (potreban je dodatni pribor)

Registar: HR:9 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 9, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 9, Uint16, St)
```

Uključivanje zaštite od radona Sklopka Čitanje i pisanje

Uključuje zaštitu od radona: smanjena recirkulacija sprječava nakupljanje radona

Registar: HR:6 UInt16 boolean

Vrijednosti / stanja: Povoleno · Zakázáno

Čitanje stanja sklopke

```taphome
MODBUSR(H, 6, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 6, Uint16, St)
```

Uključivanje grijanja Sklopka Čitanje i pisanje

Uključuje unutarnji električni dogrijač od 350 W za regulaciju temperature dovodnog zraka

Registar: HR:15 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 15, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 15, Uint16, St)
```

Željena temperatura Termostat Čitanje i pisanje

Zadana unutarnja temperatura za unutarnju regulaciju jedinice

Registar: HR:4 UInt16 Jedinica: °C direct, /10

Čitanje željene temperature

```taphome
MODBUSR(H, 4, Uint16) / 10
```

Zapis željene temperature

```taphome
MODBUSW(H, 4, Uint16, Se * 10)
```

Vanjski zrak Senzor temperature Samo za čitanje

Temperatura i vlažnost vanjskog zraka (prije povrata topline)

Registar: IR:12 Int16 Jedinica: °C direct, /10

Čitanje vlažnosti

```taphome
MODBUSR(A, 16, Int16) / 1000
```

Čitanje temperature

```taphome
MODBUSR(A, 12, Int16) / 10
```

Snaga grijanja Varijabla Samo za čitanje

Trenutačna snaga koju troši unutarnji električni dogrijač od 350 W, u vatima

Registar: IR:24 UInt16 Jedinica: W

Čitanje

```taphome
MODBUSR(A, 24, Uint16)
```

Način ventilacije Prekidač s više vrijednosti Čitanje i pisanje

Odabir snage ventilatora: isključeno, ručni stupanj 1–5 ili automatski (prema CO₂/vlažnosti)

Registar: HR:0 UInt16 numeric

Vrijednosti / stanja: Isključeno · Stupanj 1 · Stupanj 2 · Stupanj 3 · Stupanj 4 · Stupanj 5 · Automatski

Čitanje stanja sklopke

```taphome
MODBUSR(H, 0, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 0, Uint16, Mu)
```

Zona 1 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:104 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 104, Uint16)
```

Zapis

```taphome
MODBUSW(H, 104, Uint16, round(Va))
```

Zona 1 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:100 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 100, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 100, Bool, St)
```

Zona 1 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:102 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 102, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 102, Int16, round(Va * 10))
```

Zona 1 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:103 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 103, Uint16)
```

Zapis

```taphome
MODBUSW(H, 103, Uint16, round(Va))
```

Zona 2 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:114 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 114, Uint16)
```

Zapis

```taphome
MODBUSW(H, 114, Uint16, round(Va))
```

Zona 2 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:110 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 110, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 110, Bool, St)
```

Zona 2 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:112 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 112, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 112, Int16, round(Va * 10))
```

Zona 2 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:113 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 113, Uint16)
```

Zapis

```taphome
MODBUSW(H, 113, Uint16, round(Va))
```

Zona 3 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:124 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 124, Uint16)
```

Zapis

```taphome
MODBUSW(H, 124, Uint16, round(Va))
```

Zona 3 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:120 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 120, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 120, Bool, St)
```

Zona 3 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:122 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 122, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 122, Int16, round(Va * 10))
```

Zona 3 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:123 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 123, Uint16)
```

Zapis

```taphome
MODBUSW(H, 123, Uint16, round(Va))
```

Zona 4 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:134 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 134, Uint16)
```

Zapis

```taphome
MODBUSW(H, 134, Uint16, round(Va))
```

Zona 4 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:130 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 130, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 130, Bool, St)
```

Zona 4 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:132 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 132, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 132, Int16, round(Va * 10))
```

Zona 4 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:133 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 133, Uint16)
```

Zapis

```taphome
MODBUSW(H, 133, Uint16, round(Va))
```

Zona 5 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:144 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 144, Uint16)
```

Zapis

```taphome
MODBUSW(H, 144, Uint16, round(Va))
```

Zona 5 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:140 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 140, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 140, Bool, St)
```

Zona 5 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:142 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 142, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 142, Int16, round(Va * 10))
```

Zona 5 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:143 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 143, Uint16)
```

Zapis

```taphome
MODBUSW(H, 143, Uint16, round(Va))
```

Zona 6 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:154 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 154, Uint16)
```

Zapis

```taphome
MODBUSW(H, 154, Uint16, round(Va))
```

Zona 6 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:150 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 150, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 150, Bool, St)
```

Zona 6 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:152 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 152, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 152, Int16, round(Va * 10))
```

Zona 6 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:153 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 153, Uint16)
```

Zapis

```taphome
MODBUSW(H, 153, Uint16, round(Va))
```

Zona 7 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:164 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 164, Uint16)
```

Zapis

```taphome
MODBUSW(H, 164, Uint16, round(Va))
```

Zona 7 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:160 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 160, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 160, Bool, St)
```

Zona 7 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:162 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 162, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 162, Int16, round(Va * 10))
```

Zona 7 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:163 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 163, Uint16)
```

Zapis

```taphome
MODBUSW(H, 163, Uint16, round(Va))
```

Zona 8 — CO₂ Varijabla Čitanje i pisanje

Registar: HR:174 UInt16 Jedinica: ppm

Čitanje

```taphome
MODBUSR(H, 174, Uint16)
```

Zapis

```taphome
MODBUSW(H, 174, Uint16, round(Va))
```

Zona 8 — Senzor prisutan Sklopka Čitanje i pisanje

Registar: HR:170 Bool boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 170, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 170, Bool, St)
```

Zona 8 — Temperatura Varijabla Čitanje i pisanje

Registar: HR:172 Int16 Jedinica: °C direct, /10

Čitanje

```taphome
MODBUSR(H, 172, Int16) / 10
```

Zapis

```taphome
MODBUSW(H, 172, Int16, round(Va * 10))
```

Zona 8 — Vlažnost Varijabla Čitanje i pisanje

Registar: HR:173 UInt16 Jedinica: %

Čitanje

```taphome
MODBUSR(H, 173, Uint16)
```

Zapis

```taphome
MODBUSW(H, 173, Uint16, round(Va))
```

Zona 1 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:203 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 203, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 203, Uint16, St)
```

Zona 1 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:202 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 202, Uint16)
```

Zapis

```taphome
MODBUSW(H, 202, Uint16, Va)
```

Zona 1 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:200 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 200, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 200, Uint16, St)
```

Zona 1 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:201 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 201, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 201, Uint16, St)
```

Zona 2 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:213 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 213, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 213, Uint16, St)
```

Zona 2 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:212 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 212, Uint16)
```

Zapis

```taphome
MODBUSW(H, 212, Uint16, Va)
```

Zona 2 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:210 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 210, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 210, Uint16, St)
```

Zona 2 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:211 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 211, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 211, Uint16, St)
```

Zona 3 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:223 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 223, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 223, Uint16, St)
```

Zona 3 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:222 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 222, Uint16)
```

Zapis

```taphome
MODBUSW(H, 222, Uint16, Va)
```

Zona 3 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:220 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 220, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 220, Uint16, St)
```

Zona 3 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:221 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 221, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 221, Uint16, St)
```

Zona 4 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:233 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 233, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 233, Uint16, St)
```

Zona 4 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:232 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 232, Uint16)
```

Zapis

```taphome
MODBUSW(H, 232, Uint16, Va)
```

Zona 4 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:230 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 230, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 230, Uint16, St)
```

Zona 4 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:231 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 231, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 231, Uint16, St)
```

Zona 5 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:243 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 243, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 243, Uint16, St)
```

Zona 5 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:242 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 242, Uint16)
```

Zapis

```taphome
MODBUSW(H, 242, Uint16, Va)
```

Zona 5 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:240 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 240, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 240, Uint16, St)
```

Zona 5 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:241 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 241, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 241, Uint16, St)
```

Zona 6 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:253 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 253, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 253, Uint16, St)
```

Zona 6 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:252 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 252, Uint16)
```

Zapis

```taphome
MODBUSW(H, 252, Uint16, Va)
```

Zona 6 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:250 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 250, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 250, Uint16, St)
```

Zona 6 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:251 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 251, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 251, Uint16, St)
```

Zona 7 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:263 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 263, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 263, Uint16, St)
```

Zona 7 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:262 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 262, Uint16)
```

Zapis

```taphome
MODBUSW(H, 262, Uint16, Va)
```

Zona 7 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:260 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 260, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 260, Uint16, St)
```

Zona 7 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:261 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 261, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 261, Uint16, St)
```

Zona 8 — Aktivacija tipke Sklopka Čitanje i pisanje

Registar: HR:273 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 273, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 273, Uint16, St)
```

Zona 8 — Odbrojavanje tipke Varijabla Čitanje i pisanje

Registar: HR:272 UInt16 Jedinica: s

Čitanje

```taphome
MODBUSR(H, 272, Uint16)
```

Zapis

```taphome
MODBUSW(H, 272, Uint16, Va)
```

Zona 8 — Tipka prisutna Sklopka Čitanje i pisanje

Registar: HR:270 UInt16 boolean

Vrijednosti / stanja: ON · OFF

Čitanje stanja sklopke

```taphome
MODBUSR(H, 270, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 270, Uint16, St)
```

Zona 8 — Način tipke Sklopka Čitanje i pisanje

Registar: HR:271 UInt16 boolean

Vrijednosti / stanja: Digestoř · Boost

Čitanje stanja sklopke

```taphome
MODBUSR(H, 271, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 271, Uint16, St)
```

**Povezivanje:** Modbus TCP • Slave ID: $\[SlaveId]

Moguća poboljšanja (12)

- IR:6-7 Operation Mode Bitmap (fut\_mode) — UInt32, bitmap of 24 active mode/status bits — template parses this in readscript for info/error/warning ADDINFO calls but does not expose a dedicated device
- IR:8-9 Error Bitmap (fut\_error) — UInt32, 22 error bits (sensor errors, fan errors, exchanger errors) — parsed in readscript as ADDERROR, not exposed as device
- IR:10-11 Warning Bitmap (fut\_warning) — UInt32, 18 warning bits (filter, battery, zone config) — parsed in readscript as ADDWARNING, not exposed as device
- IR:14 Indoor Air Temperature (fut\_temp\_indoor) — Int16, 0.1°C — indoor/extract air temperature upstream of the exchanger
- IR:18 Indoor Air Humidity (fut\_humi\_indoor) — Int16, 0.1% — indoor/extract air humidity
- IR:26 Heating/Cooling Status (fut\_heat\_cool\_status) — UInt16, bitmask: inner heating, CoolBreeze heating/cooling active; L+ only
- HR:8 Heating Enable (cfg\_heating\_enable, per register map) — UInt16, 0/1 — register map documents L+ cfg\_heating\_enable at HR:8. Template uses HR:15 instead (see Inconsistency Report)
- HR:101, 111, …, 171 External Sensor Invalidate (ext\_sens\_invalidate\[1–8]) — UInt16 bitmask per zone — bit0=temp, bit1=humidity, bit2=CO2, bit3=floor temp invalidation flags
- HR:105, 115, …, 175 External Floor Temperature (ext\_sens\_t\_floor\[1–8]) — Int16, 0.1°C per zone — floor temperature sensor channel, R/W
- HR:900 Access Code — UInt16 — write to unlock service registers after user\_password is set
- HR:920 User Password — UInt16, 65535 = disabled — gates Modbus writes when enabled by installer
- HR:922 Password Timeout — UInt16, default 300 s — auto-logout after inactivity

## Parametri uvoza

Ove vrijednosti unosite pri uvozu XML-a.

| Pitanje u aplikaciji | Zadano        |
|----------------------|---------------|
| Slave ID             | `1`           |
| IP adresa            | `192.168.1.0` |

## Izvori

- Jablotron Futura Modbus TCP Register Map
  
  2026-04-22
  
  [PDF](https://taphome.com/compatibility/devices/jablotron-futura-l/manufacturer/FU_TCP_TXT_EN.pdf)
- Jablotron Futura Installation Manual (EN, v6.2)
  
  [www.jablotron.com](https://www.jablotron.com/file/edee/ke-stazeni/_jlt/_en/fu_doc_im_en62.pdf) 2026-04-22
  
  [PDF](https://taphome.com/compatibility/devices/jablotron-futura-l/manufacturer/futura-installation-manual.pdf)
- Home Assistant Jablotron Futura Integration
  
  [github.com](https://github.com/tomas-kulhanek/ha-jablotron-futura) 2026-04-22

Dokumenti proizvođača zaštićeni su autorskim pravom (©) svojih vlasnika. Dostupni su onako kako ih je proizvođač objavio, samo za informaciju.

## Povezana dokumentacija

- [Modbus Integration](https://taphome.com/hr/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/hr/docs/integration/modbus/)
- [Jednostavna konfiguracija pomoću predložaka](https://taphome.com/hr/docs/integration/modbus/templates/)
- [Skripte Modbus i prefetch](https://taphome.com/hr/docs/script/modbus-scripts/)
- [Funkcije Modbus](https://taphome.com/hr/docs/script/modbus/)
- [Tipovi podataka Modbus](https://taphome.com/hr/docs/script/modbus-data-types/)