title: "Huawei SUN2000 (Modbus RTU)"
description: "Solarni izmjenjivač Huawei SUN2000 3-10KTL povezan sa sustavom TapHome preko Modbus RTU na RS-485."
url: "https://taphome.com/hr/compatibility/huawei-sun2000-rtu/"
language: hr
lastmod: 2026-03-28
generator: hugo
ai:
  topics: ["modbus-rtu","inverter","solar","rs485","pv-monitoring","battery-storage","grid-power-meter"]
  questions: ["Kako spojiti Huawei SUN2000 na TapHome preko RS-485 Modbus RTU?","Što mjeri i čime upravlja predložak TapHome za Huawei SUN2000 RTU?","Koje pinove COM priključka koristiti za Modbus RTU na Huawei SUN2000?","Mogu li na SUN2000 istodobno koristiti Modbus RTU i WLAN Smart Dongle?","Kako preko sustava TapHome pratiti SOC baterije i snagu mreže na SUN2000?","Koja je razlika između predložaka TCP i RTU za Huawei SUN2000?"]
---

# Huawei SUN2000 (Modbus RTU)

Komunikacija: Modbus RTU

- [Huawei FusionSolar](https://solar.huawei.com/en/products/residential/inverters)

## Upute za integraciju

Huawei SUN2000 3-10KTL serija je trofaznih string izmjenjivača (invertera) za kućne solarne elektrane, nazivne snage od 3 kW do 10 kW. Ovaj predložak spaja se na izmjenjivač preko **Modbus RTU na RS-485**, putem COM priključka na donjoj strani izmjenjivača. Za razliku od varijante TCP (koja za mrežnu vezu koristi Smart Dongle), varijanta RTU komunicira izravno preko serijske sabirnice RS-485.

Predložak omogućuje praćenje djelatne snage s radnjama za upravljanje snagom, ulazne DC snage s mjerenjima na strani mreže, struje i napona fotonaponskih stringova, mrežnog brojila (preko Smart Power Sensora), stanja napunjenosti baterije, dnevnih i kumulativnih brojača energije te detaljnog stanja izmjenjivača s dekodiranjem alarma.

> [!WARNING]
> Huawei upozorava da komunikacija Modbus RTU može postati nestabilna kad izmjenjivač preko WLAN Smart Donglea komunicira s poslužiteljima u oblaku. Prije korištenja Modbus RTU **odspojite WLAN Smart Dongle** kako biste izbjegli CRC pogreške i prekide komunikacije na sabirnici RS-485.

## Hardversko spajanje

Izmjenjivač SUN2000 ima 16-pinski COM priključak (#8) na donjoj ploči. COM priključak daje dvije zasebne sabirnice RS-485:

| Sabirnica | Pinovi | Namjena |
|-----|------|---------|
| **Sabirnica 1** | Pin 1 (485A1-1), Pin 3 (485B1-1) | Kaskadno spajanje izmjenjivača, SmartLogger, **spoj s TapHome** |
| **Sabirnica 2** | Pin 7 (485A2), Pin 9 (485B2) | Smart Power Sensor, spremnik energije |

Za Modbus RTU spoj s TapHome koristite **sabirnicu 1**:

- **Pin 1 (485A1-1)** — spojite na RS-485 **A+** centralne jedinice TapHome Core
- **Pin 3 (485B1-1)** — spojite na RS-485 **B-** centralne jedinice TapHome Core
- **Pin 5 (PE)** — uzemljenje oklopa (nije obvezno, ali se preporučuje)

### Položaj priključaka na izmjenjivaču

![Donja ploča izmjenjivača SUN2000 s COM priključkom (#8) i priključkom Smart Dongle (#9)](https://taphome.com/images/compatibility/huawei-sun2000-rtu/inverter-ports_hu_5491645494580c3c.jpg)

COM priključak (#8) nalazi se na donjoj ploči, pokraj AC izlaznog priključka (#7) i priključka Smart Dongle (#9).

### Raspored pinova COM priključka

![16-pinski konektor COM priključka SUN2000 s numeracijom pinova](https://taphome.com/images/compatibility/huawei-sun2000-rtu/com-port-pinout_hu_38f30b1cd140d65d.jpg)

| Pin | Oznaka | Funkcija |
|-----|------------|----------|
| 1 | 485A1-1 | RS-485 A+ (sabirnica 1) — **spojite na TapHome A+** |
| 2 | 485A1-2 | RS-485 A+ (sabirnica 1) — za kaskadno spajanje na sljedeći izmjenjivač |
| 3 | 485B1-1 | RS-485 B- (sabirnica 1) — **spojite na TapHome B-** |
| 4 | 485B1-2 | RS-485 B- (sabirnica 1) — za kaskadno spajanje na sljedeći izmjenjivač |
| 5 | PE | Uzemljenje sloja oklopa |
| 7 | 485A2 | RS-485 A+ (sabirnica 2) — Smart Power Sensor |
| 9 | 485B2 | RS-485 B- (sabirnica 2) — Smart Power Sensor |

### Ugradnja kabela RS-485

![Umetanje signalnog kabela RS-485 u konektor COM priključka s položajima pinova 485A1-1, 485B1-1 i PE](https://taphome.com/images/compatibility/huawei-sun2000-rtu/wiring-rs485-cable_hu_5288d173273787db.jpg)

Koristite oklopljenu upredenu paricu za vanjsku ugradnju. Skinite vanjski plašt na približno 55 mm, a unutarnju izolaciju na 12–14 mm. Umetnite vodiče na ispravne položaje pinova u konektoru signalnog kabela, zatim umetnite konektor u COM priključak i zakrenite ga u smjeru kazaljke na satu kako bi se zaključao. Učvrstite ga vijkom M3 (moment pritezanja: 0,55 N.m).

> [!TIP]
> Signalni kabel RS-485 vodite odvojeno od energetskih kabela kako biste spriječili elektromagnetske smetnje.

## Konfiguracija

### Komunikacijski parametri

| Parametar | Vrijednost |
|-----------|-------|
| Protokol | Modbus RTU |
| Brzina prijenosa | 9600 bps |
| Podatkovni bitovi | 8 |
| Paritet | nema |
| Stop bitovi | 1 |
| Slave ID | 1 (zadano, može se promijeniti u aplikaciji FusionSolar) |

### Postavljanje Slave ID-a

Zadana Modbus adresa (slave) je **1**. Za promjenu:

1. Povežite se s izmjenjivačem preko aplikacije FusionSolar (početna Wi-Fi lozinka: **Changeme**)
2. Prijavite se kao instalater (početna lozinka: **00000a**)
3. Otvorite postavke komunikacije i promijenite adresu RS-485
4. Odmah nakon prve prijave promijenite zadanu lozinku

> [!NOTE]
> Za stabilnu komunikaciju Modbus RTU WLAN Smart Dongle mora biti odspojen. Ako je dongle ugrađen za praćenje u oblaku FusionSolar, uklonite ga nakon konfiguracije, a prije spajanja sustava TapHome preko RS-485.

## Mogućnosti uređaja

Predložak daje sljedeće uređaje:

### Djelatna snaga

Uređaj brojilo koji očitava trenutačnu AC izlaznu snagu izmjenjivača u kW (registar H:32080, Int32, podijeljeno s 1000). To je glavni uređaj za praćenje snage i omogućuje i čitanje i upis.

Servisni atributi uključuju najveću djelatnu snagu danas (H:32078), jalovu snagu u kVar (H:32082), nazivnu snagu, najveću djelatnu snagu, najveću prividnu snagu i najveću jalovu snagu (predanu u mrežu i preuzetu iz mreže).

Tri servisne radnje omogućuju upravljanje snagom:

- **Kompenzacija jalove snage (PF)** — postavlja faktor snage od -1,0 do 1,0 (upisuje u H:40122)
- **Kompenzacija jalove snage (Q/S)** — postavlja omjer jalove snage od -1,0 do 1,0 (upisuje u H:40123)
- **Smanjenje djelatne snage u postocima (%)** — ograničava izlaznu snagu u postocima 0–100 % (upisuje u H:40125)

### Baterija

Prikazuje stanje napunjenosti baterije u postocima (registar H:37760, UInt16, podijeljeno s 1000). Servisni atribut prikazuje radno stanje baterije (H:37762) s vrijednostima: Offline, Standby, Running, Fault ili Sleep Mode.

> [!NOTE]
> Uređaj Baterija radi samo kad je na izmjenjivač spojena baterija LUNA2000. Bez baterije radno stanje prikazuje „Offline”, a SOC je nula.

### Mrežno brojilo

Očitava djelatnu snagu mreže iz Smart Power Sensora u kW (registar H:37113, Int32, podijeljeno s 1000) i energiju predanu u mrežu u kWh (registar H:37119, Int32, podijeljeno sa 100). Pozitivne vrijednosti znače snagu predanu u mrežu, negativne snagu preuzetu iz mreže.

Servisni atributi prikazuju stanje brojila (Normal/Offline) i vrstu brojila (trofazno/jednofazno).

> [!NOTE]
> Uređaj Mrežno brojilo zahtijeva Huawei Smart Power Sensor (DTSU666-H) spojen na izmjenjivač preko sabirnice RS-485 2 (pinovi 7 i 9 na COM priključku). Ovaj uređaj ne postoji u varijanti TCP.

### Ulazna DC snaga

Senzor samo za čitanje koji prikazuje ukupnu DC snagu svih fotonaponskih stringova zajedno u kW (registar H:32064, Int32, podijeljeno s 1000).

Servisni atributi daju mjerenja na strani mreže: frekvenciju mreže (H:32085), fazne napone A/B/C (H:32069-32071), fazne struje A/B/C (H:32072-32076) i linijske napone AB/BC/CA (H:32066-32068).

### Dnevna energija i ukupna energija

Dva brojača energije samo za čitanje:

- **Dnevna energija** — energija proizvedena danas u kWh (registar H:32114, podijeljeno sa 100), svakodnevno se poništava
- **Ukupna energija** — kumulativna energija od puštanja u rad u kWh (registar H:32106, podijeljeno sa 100)

### Struje fotonaponskih stringova (PV1-PV2)

Dva zasebna senzorska uređaja, po jedan za svaki fotonaponski string, očitavaju DC struju u amperima (registri H:32017 i H:32019, Int16, podijeljeno sa 100). Svaki uređaj ima servisni atribut za napon odgovarajućeg stringa (H:32016 i H:32018, podijeljeno s 10).

> [!NOTE]
> Predložak RTU sadrži 2 uređaja za fotonaponske stringove (PV1-PV2), dok varijanta TCP ima 4. Mapa registara podržava do 24 stringa; dodatni uređaji za fotonaponske stringove mogu se po potrebi dodati ručno.

### Stanje izmjenjivača

Prekidač s više vrijednosti (samo za čitanje) koji prikazuje trenutačno radno stanje izmjenjivača iz registra H:32089:

| Vrijednost | Stanje | Opis |
|-------|-------|-------------|
| 0 | Stanje izmjenjivača | Početno / nepoznato |
| 1 | Mirovanje | Detekcija ISO, ozračenja ili mreže |
| 2 | Pokretanje | Izmjenjivač se pokreće |
| 3 | Na mreži | Uobičajena proizvodnja energije |
| 4 | Isključivanje | Kvar, naredba, OVGR ili isključena DC sklopka |
| 5 | Mrežni dispečing | Aktivna krivulja cos(Phi)-P ili Q-U |
| 6 | IV skeniranje | Skeniranje I-V krivulje fotonaponskog stringa |
| 7 | Provjera mreže | U tijeku je provjera mreže (spot-check) |
| 8 | Inspekcija | Način inspekcije |
| 9 | Detekcija DC ulaza | Detekcija DC ulaza |

Servisni atributi daju detaljne podatke o stanju: Potpuno stanje (prošireno stanje s podstanjima), Priključak na mrežu, Telesignalizacija (IEC104), Stanje zaključavanja, Stanje fotonaponskog spoja te vremena pokretanja i isključivanja.

### Praćenje alarma

Skripta za čitanje na razini modula prati registre alarma H:32008 i H:32009 (Bitfield16). Svaki bit odgovara određenom kvaru ili upozorenju:

| Registar | Bit | Alarm |
|----------|-----|-------|
| H:32008 | 0 | Visok napon stringa |
| H:32008 | 1 | DC lučni kvar |
| H:32008 | 2 | Obrnuti polaritet stringa |
| H:32008 | 3 | Neispravan string (upozorenje) |
| H:32008 | 7 | Ispad električne mreže |
| H:32008 | 8-9 | Podnapon / prenapon mreže |
| H:32008 | 11-13 | Kvarovi frekvencije mreže |
| H:32008 | 14-15 | Izlazna nadstruja / DC komponenta |
| H:32009 | 0 | Neuobičajena struja odvoda |
| H:32009 | 1-2 | Kvarovi uzemljenja / izolacije |
| H:32009 | 3-4 | Visoka temperatura / kvar uređaja |
| H:32009 | 9 | Neispravan uređaj za pohranu energije |
| H:32009 | 10-11 | Aktivni/pasivni otočni rad |

### Dijagnostika na razini modula

Modul daje servisne atribute za identifikaciju uređaja i dijagnostiku:

| Atribut | Registar | Opis |
|-----------|----------|-------------|
| Naziv modela | H:30000 | Model s natpisne pločice izmjenjivača |
| SN | H:30015 | Serijski broj |
| PN | H:30025 | Šifra proizvoda |
| ID modela | H:30070 | Brojčani identifikator modela |
| Broj stringova | H:30071 | Spojeni fotonaponski stringovi |
| Broj MPPT | H:30072 | Broj MPP regulatora |
| Vremenska zona | H:43006 | Pomak od UTC |
| Učinkovitost izmjenjivača | H:32086 | Učinkovitost pretvorbe (%) |
| Temperatura kućišta | H:32087 | Unutarnja temperatura |
| Otpor izolacije | H:32088 | Izolacija fotonaponskog polja |
| Prikupljanje podataka DSP | H:32002 | Stanje prikupljanja podataka |

Servisna radnja **Vremenska zona** omogućuje postavljanje pomaka izmjenjivača od UTC (upisuje u H:43006).

### Dodatne mogućnosti

Izmjenjivač SUN2000 daje i dodatne registre koji još nisu ugrađeni u predložak. To su verzija firmvera, registar koda kvara, brže osvježavano očitanje djelatne snage, brojač ukupne ulazne DC energije, mjesečni i godišnji brojači energije, snaga punjenja/pražnjenja baterije, energija predana u mrežu bez predznaka, akumulirana energija mreže te naredbe za daljinsko uključivanje/isključivanje. Mogu se dodati u budućem ažuriranju predloška.

### Razlike u odnosu na varijantu TCP

Predložak RTU sadrži dva uređaja kojih nema u varijanti TCP: **Mrežno brojilo** (očitanja Smart Power Sensora) i **Baterija** s očitanjem SOC. S druge strane, predložak RTU sadrži samo 2 uređaja za fotonaponske stringove (PV1-PV2), dok varijanta TCP ima 4. Mapa registara je identična, razlikuje se samo prijenosni sloj (serijski RS-485 umjesto TCP/IP preko Smart Donglea).

## Rješavanje problema

### Nema Modbus komunikacije

1. Provjerite je li kabel RS-485 spojen na ispravne pinove COM priključka: Pin 1 (485A1-1) = A+, Pin 3 (485B1-1) = B-
2. Provjerite je li WLAN Smart Dongle **odspojen** od izmjenjivača
3. Provjerite je li u sustavu TapHome brzina prijenosa postavljena na 9600, a paritet na „nema” (8N1)
4. Provjerite je li Slave ID ispravan (zadano: 1)
5. Provjerite je li konektor signalnog kabela potpuno umetnut i zaključan u COM priključku

### Povremeni prekidi komunikacije

Najčešći uzrok je WLAN Smart Dongle koji ometa sabirnicu RS-485. Unutarnja komunikacija donglea s Huaweijevim poslužiteljima u oblaku uzrokuje CRC pogreške na serijskoj sabirnici. Za stabilan rad RTU uklonite dongle.

### Vrijednosti fotonaponskih stringova su nula

Nekorišteni ulazi fotonaponskih stringova uvijek će pokazivati 0 A / 0 V. To je uobičajeno ako model izmjenjivača ima manje MPPT ulaza nego što ih predviđa predložak (npr. model 3KTL može koristiti samo PV1 i PV2).

### Uređaj Baterija prikazuje „Offline”

Registri baterije LUNA2000 popunjavaju se samo kad je kompatibilna baterija fizički spojena na izmjenjivač. Bez baterije radno stanje prikazuje „Offline”, a SOC je nula.

### Stanje izmjenjivača ostaje na „Mirovanje”

Noću ili pri slabom ozračenju izmjenjivač prelazi u mirovanje. To je uobičajeno: prijeći će u stanje „Na mreži” čim detektira dovoljno sunčevog zračenja. Izmjenjivač u stanju pripravnosti može imati i ograničenu dostupnost podataka.

### Mrežno brojilo pokazuje nulu

Uređaj Mrežno brojilo zahtijeva Huawei Smart Power Sensor (DTSU666-H) spojen preko sabirnice RS-485 2 (pinovi 7 i 9). Ako brojilo nije ugrađeno, vrijednosti će biti nula, a stanje brojila prikazat će „Offline”.

## Dostupni uređaji 9

Ovi se uređaji pojavljuju u TapHomeu nakon uvoza.

SUN2000 Modul

Servisni atributi

|                           |                                                                             |
|---------------------------|-----------------------------------------------------------------------------|
| Naziv modela              |                                                                             |
| SN                        |                                                                             |
| PN                        |                                                                             |
| ID modela                 |                                                                             |
| Broj stringova            |                                                                             |
| Broj MPPT                 |                                                                             |
| Vremenska zona            | Pomak izmjenjivača od UTC — očitava i prikazuje postavljenu vremensku zonu  |
| Učinkovitost izmjenjivača | Učinkovitost pretvorbe DC u AC u postocima                                  |
| Temperatura kućišta       | Unutarnja temperatura kućišta izmjenjivača                                  |
| Otpor izolacije           | Otpor izolacije fotonaponskog polja u megaomima — prati sigurnost izolacije |
| Prikupljanje podataka DSP | Stanje prikupljanja podataka — Yes (aktivno) ili No (neaktivno)             |

Servisne radnje

|                |                                                                        |
|----------------|------------------------------------------------------------------------|
| Vremenska zona | Postavlja pomak izmjenjivača od UTC — odabir od UTC-12:00 do UTC+14:00 |

Čitanje (modul)

```taphome
var a1 := MODBUSR(H, 32008, Uint16);
var a2 := MODBUSR(H, 32009, Uint16);
IF(GETBIT(a1,0) = 1, ADDERROR("High String Voltage", 2001));
IF(GETBIT(a1,1) = 1, ADDERROR("DC Arc Fault", 2002));
IF(GETBIT(a1,2) = 1, ADDERROR("String Reversed", 2011));
IF(GETBIT(a1,3) = 1, ADDWARNING("PV String Backfeed ", 2012));
IF(GETBIT(a1,4) = 1, ADDWARNING("Abnormal String", 2013));
IF(GETBIT(a1,5) = 1, ADDERROR("AFCI Self-test Fault", 2021));
IF(GETBIT(a1,6)= 1, ADDERROR("Short circuit between phase to PE ", 2021));
IF(GETBIT(a1,7) = 1, ADDERROR("Power Grid Failure ", 2032));
IF(GETBIT(a1,8) = 1, ADDERROR("Grid Undervoltage ", 2033));
IF(GETBIT(a1,9) = 1, ADDERROR("Grid Overvoltage", 2034));
IF(GETBIT(a1,10) = 1, ADDERROR("Unbalanced Grid Voltage", 2035));
IF(GETBIT(a1,11) = 1, ADDERROR("Grid Overfrequency", 2036));
IF(GETBIT(a1,12) = 1, ADDERROR("Grid Underfrequency", 2037));
IF(GETBIT(a1,13) = 1, ADDERROR("Grid Frequency Instability", 2038));
IF(GETBIT(a1,14) = 1, ADDERROR("Output Overcurrent ", 2039));
IF(GETBIT(a1,15) = 1, ADDERROR("Large DC of Output current ", 2040));
IF(GETBIT(a2,0) = 1, ADDERROR("Abnormal Leakage Current ", 2051));
IF(GETBIT(a2,1) = 1, ADDERROR("Abnormal Ground.", 2061));
IF(GETBIT(a2,2) = 1, ADDERROR("Low Insulation Res. ", 2062));
IF(GETBIT(a2,3) = 1, ADDERROR("High Temperature", 2063));
IF(GETBIT(a2,4) = 1, ADDERROR("Abnormal Equipment", 2064));
IF(GETBIT(a2,5) = 1, ADDERROR("Upgrade Failed", 2065));
IF(GETBIT(a2,6) = 1, ADDWARNING("License Expired", 2066));
IF(GETBIT(a2,7) = 1, ADDERROR("Abnormal Monitor Unit", 61440));
IF(GETBIT(a2,8) = 1, ADDERROR("Power collector fault ", 2067));
IF(GETBIT(a2,9) = 1, ADDERROR("Abnormal energy storage device", 2068));
IF(GETBIT(a2,10) = 1, ADDERROR("Active islanding", 2070));
IF(GETBIT(a2,11) = 1, ADDERROR("Passive islanding", 2071));
IF(GETBIT(a2,12) = 1, ADDERROR("Transient AC overvoltage", 2072));
IF(GETBIT(a2,15) = 1, ADDERROR("Abnormal PV module configuration", 2080));
```

Servisni atributi

Model Name

```taphome
MODBUSR(H, 30000, String, 15)
```

SN

```taphome
MODBUSR(H, 30015, String, 10)
```

PN

```taphome
MODBUSR(H, 30025, String, 10)
```

Model ID

```taphome
MODBUSR(H, 30070, Uint16)
```

Number of Strings

```taphome
MODBUSR(H, 30071, Uint16)
```

MPPT Number

```taphome
MODBUSR(H, 30072, Uint16)
```

Time Zone

```taphome
IF(MODBUSR(H, 43006, Int16) = 0, "UTC±00:00");
var time := MODBUSR(H, 43006, Int16)/0.6;
var zone := IF(MOD(time,100) = 0, time/100 + ":00", ROUND(time/100) + ":" + MOD(time,100));
RETURN (IF(time > 0, "UTC+" + zone, "UTC-" + zone ));
```

Inverter Efficiency

```taphome
 MODBUSR(H, 32086, Uint16)/100 + "%"
```

Cabinet Temperature

```taphome
MODBUSR(H, 32087, Int16) / 10 + " ℃ "
```

Insulation Resistance

```taphome
MODBUSR(H, 32088, Uint16)/1000 + "MΩ "
```

DSP data collection

```taphome
IF(GETBIT(MODBUSR(H, 32002, Uint16),0) = 1, "Yes", "No")
```

Servisne radnje

Time Zone

Parametri: Time Zone

```taphome
MODBUSWNE(H, 43006, Int16, timz*60)
```

Djelatna snaga Brojilo električne energije Čitanje i pisanje

Brojilo s djelatnom snagom (kW), jalovom snagom, faktorom snage i radnjama za smanjenje snage i kompenzaciju

Registar: H:32080 Int32 Jedinica: kW numeric

Servisni atributi

|                                                |
|------------------------------------------------|
| Najveća djelatna snaga danas                   |
| Jalova snaga                                   |
| Nazivna snaga                                  |
| Kompenzacija jalove snage (PF)                 |
| Kompenzacija jalove snage (Q/S)                |
| Smanjenje djelatne snage u postocima (0,1 %)   |
| Smanjenje djelatne snage (fiksna vrijednost W) |
| Najveća djelatna snaga                         |
| Najveća prividna snaga                         |
| Najveća jalova snaga (predana u mrežu)         |
| Najveća jalova snaga (preuzeta iz mreže)       |

Servisne radnje

|                                          |                                                                    |
|------------------------------------------|--------------------------------------------------------------------|
| Kompenzacija jalove snage (PF)           | Postavlja faktor snage od -1,0 do 1,0 za kompenzaciju jalove snage |
| Kompenzacija jalove snage (Q/S)          | Postavlja omjer jalove snage od -1,0 do 1,0                        |
| Smanjenje djelatne snage u postocima (%) | Ograničava izlaznu snagu izmjenjivača u postocima 0–100 %          |

Čitanje zahtjeva

```taphome
MODBUSR(H, 32080, Int32,2)/1000;
```

Servisni atributi

Active Power peak of this day

```taphome
MODBUSR(H, 32078, Int32, 2) + " kW"
```

Reactive Power

```taphome
MODBUSR(H, 32082, Int32, 2)/1000 + " kVar"
```

Rated Power

```taphome
MODBUSR(H, 30073, Uint32, 2)/1000 + " kW"
```

Reactive Power Compensation (PF)

```taphome
MODBUSR(H, 40122, Int16)/1000
```

Reactive Power Compensation (Q/S)

```taphome
MODBUSR(H, 40123, Int16)/1000
```

Active Power Derating percent (0.1%)

```taphome
MODBUSR(H, 40122, Int16)/10 + "%"
```

Active Power Derating (fixed value W)

```taphome
MODBUSR(H, 40126, Uint32, 2) + " W"
```

Maximum Active Power

```taphome
MODBUSR(H, 30075, Uint32, 2)/1000 + " kW"
```

Maximum Apparent Power

```taphome
MODBUSR(H, 30077, Uint32, 2)/1000 + " kVA"
```

Maximum reactive power (fed to grid)

```taphome
MODBUSR(H, 30079, Uint32, 2)/1000 + " kVar"
```

Maximum reactive power (absorbed from grid)

```taphome
MODBUSR(H, 30081, Uint32, 2)/1000 + " kVar"
```

Servisne radnje

Reactive Power Compensation (PF)

Parametri: Reactive power compensation

```taphome
MODBUSWNE(H, 40122, Int16, pf*1000);
```

Reactive Power Compensation (Q/S)

Parametri: Reactive power compensation (-1, 1] (-1–1 rpc)

```taphome
MODBUSW(H, 40123, Int16, rpc*1000);
```

Active Power Derating Percent(%)

Parametri: Active Power Derating Percent(%) (0–100 apdp)

```taphome
MODBUSW(H, 40125, Uint16, apdp*10)
```

Baterija Dimer Samo za čitanje

Stanje napunjenosti baterije (SOC) u postocima — prikazuje raspoloživu energiju u spremniku LUNA2000

Registar: H:37760 UInt16 Jedinica: % numeric

Servisni atributi

|        |                                                                         |
|--------|-------------------------------------------------------------------------|
| Stanje | Radno stanje baterije — Offline, Standby, Running, Fault ili Sleep Mode |

Čitanje razine

```taphome
MODBUSR(H, 37760, Uint16) / 1000
```

Servisni atributi

Status

```taphome
SWITCH(MODBUSR(H, 37762, Uint16), 0, "offline", 1, "standby", 2, "running", 3, "fault", 4, "sleep mode", "error");
```

Mrežno brojilo Brojilo električne energije Samo za čitanje

Djelatna snaga mreže (kW) i predana energija (kWh) iz Smart Power Sensora — pozitivne vrijednosti znače predaju u mrežu, negativne preuzimanje iz mreže

Registar: H:37113 Int32 Jedinica: kW numeric

Servisni atributi

|        |                                         |
|--------|-----------------------------------------|
| Stanje | Stanje brojila — Normal ili Offline     |
| Vrsta  | Vrsta brojila — trofazno ili jednofazno |

Čitanje ukupne potrošnje

```taphome
MODBUSR(H, 37119, Int32) / 100
```

Čitanje zahtjeva

```taphome
MODBUSR(H, 37113, Int32) / 1000
```

Servisni atributi

Status

```taphome
IF(MODBUSR(H, 37100, Uint16) = 1, "Normal", "Offline");
```

Type

```taphome
IF(MODBUSR(H, 37125, Uint16) = 1, "3 phase", "1 phase");
```

Dnevna energija Varijabla Samo za čitanje

Energija proizvedena danas u kWh — poništava se u ponoć

Registar: H:32114 Int32 Jedinica: kWh numeric

Čitanje

```taphome
MODBUSR(H, 32114, Int32, 2)/100
```

Ukupna energija Varijabla Samo za čitanje

Kumulativna ukupna energija proizvedena od puštanja u rad

Registar: H:32106 Int32 Jedinica: kWh numeric

Čitanje

```taphome
MODBUSR(H, 32106, Int32, 2)/100
```

Ulazna DC snaga Brojilo električne energije Samo za čitanje

Ukupna DC snaga svih fotonaponskih stringova zajedno (kW) s mjerenjima na strani mreže — fazni naponi, struje, linijski naponi i frekvencija

Registar: H:32064 Int32 Jedinica: kW numeric

Servisni atributi

|             |
|-------------|
| Napon A     |
| Napon B     |
| Napon C     |
| Struja A    |
| Struja B    |
| Struja C    |
| Napon AB    |
| Napon BC    |
| Napon CA    |
| Frekvencija |

Čitanje zahtjeva

```taphome
MODBUSR(H, 32064, Int32, 2)/1000
```

Servisni atributi

A Voltage

```taphome
MODBUSR(H, 32069, Int16)/10 + " V"
```

B Voltage

```taphome
MODBUSR(H, 32070, Int16)/10 + " V"
```

C Voltage

```taphome
MODBUSR(H, 32071, Int16)/10 + " V"
```

A Current

```taphome
MODBUSR(H, 32072, Int32, 2)/1000 + " A"
```

B Current

```taphome
MODBUSR(H, 32074, Int32, 2)/1000 + " A"
```

C Current

```taphome
MODBUSR(H, 32076, Int32, 2)/1000 + " A"
```

AB Voltage

```taphome
MODBUSR(H, 32066, Int16)/10 + " V"
```

BC Voltage

```taphome
MODBUSR(H, 32067, Int16)/10 + " V"
```

CA Voltage

```taphome
MODBUSR(H, 32068, Int16)/10 + " V"
```

Frequency

```taphome
MODBUSR(H, 32085, Uint16)/100 + " Hz"
```

Stanje izmjenjivača Prekidač s više vrijednosti Samo za čitanje

Radno stanje izmjenjivača — Mirovanje, Pokretanje, Na mreži, Isključivanje, Mrežni dispečing, IV skeniranje, Provjera mreže, Inspekcija, Detekcija DC ulaza

Registar: H:32089 UInt16 numeric

Vrijednosti / stanja: Initializing · Idle · Starting · On-Grid · Shutdown · Grid Dispatch · IV scanning · Spot-Check · Inspecting · DC input detection

Čitanje stanja sklopke

```taphome
var reg := MODBUSR(H, 32089, Uint16);
IF(reg = 0, 0,
IF(reg < 4 OR reg = 40960,1,
IF(reg = 256, 2, 
IF(reg < 515, 3, 
IF(reg < 775, 4,
IF(reg = 1025 OR reg = 1026, 5, 
IF(reg = 1280 OR reg = 1281, 7,
IF(reg = 1536, 8, 
IF(reg = 2048, 6,
IF(reg = 2304, 9
))))))))))
```

Servisni atributi

Full State

```taphome
var state := MODBUSR(H, 32089, Uint16);
SWITCH(state, 0, "Idle: Initializing",
 1,"Idle: Detecting ISO", 
 2,"Idle: Detecting irradiation", 
 3, "Idle: Grid Detecting", 
 256, "Starting", 
 512, "On-Grid", 
 513, "On-Grid: Power Limit", 
 514, "On-Grid: self-derating", 
 768, "Shutdown: Fault", 
 769, "Shutdown: Command", 
 770, "Shutdown: OVGR", 
 771,"Shutdown: Communication disconnected", 
 772, "Shutdown: Power Limit", 
 773, "Shutdown: Start manually", 
 774, "Shutdown: DC Switch OFF",
 1025, "Grid dispatch:cos(Phi)-P curve",
 1026, "Grid dispatch:Q-U curve",
40960, "Idle: No irradiation",
1280, "Spot-check",
1281, "Spot-checking",
1536, "Inspecting",
1792, "SFCI self-check",
2048, "IV scanning",
2304, "DC input detection",
"Unknown"
 );
```

Grid Connection

```taphome
var reg := MODBUSR(H, 32000,Uint16);
IF(GETBIT(reg,0) = 1, "Standby",
IF(GETBIT(reg,2) = 1 , "Normal Grid Connection",
IF(GETBIT(reg,3) = 1, "Grid connection with derating due to power rationing",
IF(GETBIT(reg,4) = 1, "Grid connection with derating due to inverter internal causes", "Not Connected"
)
)
)
)
```

Teleindication

```taphome
var reg := MODBUSR(H, 32000,Uint16);
IF(GETBIT(reg,0) = 1, "Standby",
IF(GETBIT(reg,5) = 1 , "Normal Stop",
IF(GETBIT(reg,6) = 1, "Stop due to faults",
IF(GETBIT(reg,7) = 1, "Stop due to power rationing",
IF(GETBIT(reg,8) = 1, "Shutdown",
IF(GETBIT(reg,9) = 1, "Spot check",
IF(GETBIT(reg,1) = 1, "Grid Connected",
"Unknown State")
)
)
)
)
)
)
```

Locking Status

```taphome
IF(GETBIT(MODBUSR(H, 32002, Uint16),0) = 1, "Unlocked", "Locked");
```

PV Connection Status

```taphome
IF(GETBIT(MODBUSR(H, 32002, Uint16),0) = 1, "Connected", "Disconnected");
```

Startup time

```taphome
var reg := MODBUSR(H, 32091, Uint32, 2);
var min := FLOOR(MOD(reg, 3600)/60);
var ho := FLOOR(MOD(reg,86400)/3600);
var minutes := IF(min<10, "0" + min, min);
var hours := IF(ho<10, "0" + ho, ho);
hours + ":" + minutes;
```

Shutdown time

```taphome
var reg := MODBUSR(H, 32093, Uint32, 2);
var min := FLOOR(MOD(reg, 3600)/60);
var ho := FLOOR(MOD(reg,86400)/3600);
var minutes := IF(min<10, "0" + min, min);
var hours := IF(ho<10, "0" + ho, ho);
hours + ":" + FLOOR(minutes);
```

Struja PV1 Varijabla Samo za čitanje

Registar: H:32017 Int16 Jedinica: A numeric

Servisni atributi

|           |
|-----------|
| Napon PV1 |

Čitanje

```taphome
MODBUSR(H, 32017, Int16)/100
```

Servisni atributi

PV1 Voltage

```taphome
MODBUSR(H, 32016, Int16)/10 + "V"
```

Struja PV2 Varijabla Samo za čitanje

Registar: H:32019 Int16 Jedinica: A numeric

Servisni atributi

|           |
|-----------|
| Napon PV2 |

Čitanje

```taphome
MODBUSR(H, 32019, Int16)/100
```

Servisni atributi

PV2 Voltage

```taphome
MODBUSR(H, 32018, Int16)/10
```

**Povezivanje:** Modbus RTU • 9600 baud• 8N1 • Slave ID: $\[SlaveId]

Moguća poboljšanja (13)

- H:30035 Firmware Version — STR, 15 regs, read-only — useful for diagnostics
- H:32010 Alarm 3 — Bitfield16, additional alarm bits not decoded in template readscript
- H:32090 Fault Code — U16, specific fault code when device is in fault state
- H:32095 Active Power (fast) — I32, kW, /1000, faster-updating active power reading
- H:32108 Total DC Input Energy — U32, kWh, /100, cumulative DC energy input
- H:32116 Monthly Energy — U32, kWh, /100, electricity generated this month
- H:32118 Yearly Energy — U32, kWh, /100, electricity generated this year
- H:37765 Battery Charge/Discharge Power — I32, W, positive=charging negative=discharging — would complement existing Battery SOC device
- H:37121 Grid Exported Energy (unsigned) — U32, kWh, /100, unsigned variant of grid exported energy — complements the signed I32 already in template at H:37119
- H:37123 Grid Accumulated Energy — U32, kWh, /100, total energy consumed from grid
- H:40200 Power On — WO, E16, remote inverter power-on command
- H:40201 Shutdown — WO, E16, remote inverter shutdown command
- RTU Variant Notes — Modbus RTU over RS-485. Default: 9600 baud, 8N1. COM port Bus 1: Pin 1 (485A1-1) = A+, Pin 3 (485B1-1) = B-. Do NOT use Modbus RTU with WLAN Smart Dongle connected — causes CRC errors. RTU template has 2 PV strings (vs TCP's 4) and includes Grid Power Meter (H:37113, H:37119) + Battery SOC (H:37760). Huawei warns against Modbus RTU due to internal server communication conflicts.

## Parametri uvoza

Ove vrijednosti unosite pri uvozu XML-a.

| Pitanje u aplikaciji | Zadano        |
|----------------------|---------------|
| Slave ID             | `1`           |
| IP adresa            | `192.168.1.0` |

## Izvori

- Solar Inverter Modbus Interface Definitions (V3.0)
  
  2026-03-28
  
  [PDF](https://taphome.com/compatibility/devices/huawei-sun2000-rtu/manufacturer/modbus-interface-definitions-v3.pdf)
- SUN2000-(5KTL, 6KTL)-M0 User Manual
  
  [solar.huawei.com](https://solar.huawei.com/-/media/Solar/attachment/pdf/au/service/residential/SUN2000-5-6KTL-M0-User_Manual.pdf) 2026-03-28
  
  [PDF](https://taphome.com/compatibility/devices/huawei-sun2000-rtu/manufacturer/user-manual-m0.pdf)
- huawei-solar-lib — Python Modbus Library
  
  [github.com](https://github.com/wlcrs/huawei-solar-lib) 2026-03-28

Dokumenti proizvođača zaštićeni su autorskim pravom (©) svojih vlasnika. Dostupni su onako kako ih je proizvođač objavio, samo za informaciju.

## Povezana dokumentacija

- [Modbus Integration](https://taphome.com/hr/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/hr/docs/integration/modbus/)
- [Jednostavna konfiguracija pomoću predložaka](https://taphome.com/hr/docs/integration/modbus/templates/)
- [Skripte Modbus i prefetch](https://taphome.com/hr/docs/script/modbus-scripts/)
- [Funkcije Modbus](https://taphome.com/hr/docs/script/modbus/)