  questions: ["Kako integrirati Flexit EcoNordic sa sustavom TapHome?","Čime upravlja predložak TapHome za Flexit EcoNordic?","Kako spojiti Flexit EcoNordic preko RS-485 na TapHome?","Koja je razlika između EcoNordic WH4 i W4 u TapHome?","Kako preko TapHome uključiti ventilaciju za kamin na uređaju Flexit EcoNordic?","Kako upravljati pripremom potrošne tople vode na uređaju Flexit EcoNordic?"]
---

# Flexit EcoNordic WH4 / W4

Komunikacija: Modbus RTU

- [Službena stranica Flexit](https://www.flexit.no)

## Upute za integraciju

Flexit EcoNordic je centralni uređaj za unutarnju klimu koji objedinjuje uravnoteženu ventilaciju s povratom topline, pripremu potrošne tople vode (PTV) i toplovodno grijanje (model WH4). Sa sustavom TapHome komunicira preko Modbus RTU putem RS-485 i omogućuje upravljanje načinima ventilacije, zadanim temperaturama i potrošnom toplom vodom te praćenje rada dizalice topline.

Podržana su dva modela: **EcoNordic WH4** (ventilacija + grijanje + PTV) i **EcoNordic W4** (ventilacija + PTV). WH4 ima dodatne senzore kruga grijanja i upravljanje krugom grijanja, kojih na W4 nema.

## Hardversko spajanje

EcoNordic ima ugrađeno sučelje Modbus RTU dostupno preko RS-485. Centralnu jedinicu TapHome Core spojite na port RS-485 uređaja EcoNordic upredenom paricom s GND.

> [!WARNING]
> U dostupnoj dokumentaciji nije pronađena shema spajanja. Točan položaj stezaljki RS-485 na uređaju potražite u uputama za ugradnju uređaja EcoNordic ili se obratite podršci tvrtke Flexit. Za spajanje vanjskih regulatora Flexit nudi dodatni pribor **Modbus cable (HP Res)**.

## Konfiguracija

Modbus vezu u TapHome konfigurirajte s ovim parametrima:

| Parametar | Vrijednost |
|-----------|-------|
| Brzina prijenosa | 9600 |
| Podatkovni bitovi | 8 |
| Paritet | parna |
| Stop bitovi | 1 |
| Slave ID | 1 (zadano) |

EcoNordic koristi vlastitu Modbus mapu registara u rasponu adresa 1–3037. Ona se razlikuje od mape registara CI66 koju koriste stariji modeli Flexit Nordic S2–S4 / CL2–CL4, pa adapter CI66 nije potreban.

> [!NOTE]
> Uređajem EcoNordic upravlja se i mobilnom aplikacijom **Flexit GO** (Android/iOS). TapHome i aplikacija Flexit GO mogu raditi istodobno: obje komuniciraju s uređajem neovisno jedna o drugoj.

## Mogućnosti uređaja

### Upravljanje načinom ventilacije

**Način rada** (H:2013) glavni je uređaj za upravljanje ventilacijom, s četiri načina:

- **Stop**: ventilatori isključeni, nema ventilacije
- **Away**: smanjena ventilacija kad u zgradi nikoga nema
- **Home**: uobičajeni svakodnevni rad
- **High**: privremeno pojačana ventilacija

Dva posebna okidača daju dodatne načine ventilacije:

- **Brza ventilacija** (H:3006): uključuje privremenu ventilaciju velikom brzinom za brzu izmjenu zraka (kuhanje, gosti, vlaga). Trajanje se postavlja servisnom radnjom (1–360 minuta)
- **Ventilacija za kamin** (H:3007): stvara nadtlak u prostoriji kako dim ne bi ulazio u prostoriju pri paljenju kamina. Trajanje se postavlja servisnom radnjom (0–360 minuta)

**Tipka Comfort** (H:2040) uključuje i isključuje način Comfort na uređaju, koji privremeno pojačava ventilaciju i može promijeniti zadane temperature.

### Praćenje temperature i zadane vrijednosti

Predložak sadrži šest senzora temperature:

- **Temperatura vanjskog zraka** (A:1): temperatura vanjskog zraka na usisu
- **Temperatura dovodnog zraka** (A:5): svježi zrak koji se dovodi u zgradu nakon povrata topline i dogrijavanja
- **Temperatura odsisnog zraka** (A:9): zrak koji se odsisava iz zgrade prije povrata topline
- **Temperatura otpadnog zraka** (A:13): zrak koji se nakon povrata topline izbacuje van
- **Temperatura polaza kruga grijanja** (A:97): temperatura vode u polaznoj cijevi kruga grijanja (samo WH4)
- **Temperatura povrata kruga grijanja** (A:101): temperatura vode u povratnoj cijevi kruga grijanja (samo WH4)

Dva termostata upravljaju zadanim temperaturama dovodnog zraka:

- **Temperatura u načinu Home** (H:1155): zadana vrijednost za način Home, raspon 10–30 °C
- **Temperatura u načinu Away** (H:1163): zadana vrijednost za način Away, raspon 10–30 °C

### Upravljanje potrošnom toplom vodom

**Način rada PTV-a** (H:3017) određuje način zagrijavanja potrošne tople vode:

- **Comfort**: spremnik se puni kad ostane približno 50 % PTV-a, ispod 15 % koristi se električni rezervni grijač
- **Economy**: najštedljiviji način, spremnik se puni tek kad ostane približno 15 %, bez električnog rezervnog grijača

**Pojačano zagrijavanje PTV-a** (H:3019) privremeno pokreće pripremu PTV-a najvećom snagom s pomoću električnog rezervnog grijača. Trajanje se postavlja servisnom radnjom (0–300 minuta).

### Praćenje dizalice topline i sustava

Modul nudi devet servisnih atributa za praćenje stanja sustava:

- **Stanje dizalice topline** (A:3028): trenutačni rad dizalice topline: Standby, Air Purge, Startup, Normal operation, Stop, Defrost, Error standby te načini Manual i Forced
- **Stanje potrošne tople vode** (A:3005): stanje pripreme PTV-a: Comfort, Economy, Not in Use, Temporary Boost, Forced Charge, Economy delay ili Legionella prevention
- **Stanje ventilacije s povratom topline** (A:3034): pokazuje stvarno stanje ventilacije, uključujući načine koji se ne mogu izravno postaviti uređajem Način rada (npr. Fume hood i Fireplace)
- **Način rada postrojenja dizalice topline** (H:2061): detaljan prikaz jednog od 17 stanja koji pokazuje što dizalica topline trenutačno radi (punjenje spremnika, grijanje prostora, grijanje ventilacijskog zraka, zaštita od legionele i kombinirani načini)
- **Dogrijač dizalice topline** (A:3029): je li dogrijač aktivan
- **Zaštita dizalice topline od smrzavanja** (A:3031): je li zaštita od smrzavanja aktivna
- **Stanje grijača posude za kondenzat** (A:3036): je li grijač posude za kondenzat aktivan
- **Upozorenje dizalice topline na kamenac** (A:3037): upozorava kad se otkrije nakupljanje kamenca
- **Položaj priključne zaklopke dizalice topline** (H:29): položaj zaklopke u postocima

Na pojedinim uređajima dostupni su dodatni servisni atributi: brzina ventilatora otpadnog zraka, upravljački signali zaklopki, brzina rotacijskog izmjenjivača topline, zadana temperatura polaza dizalice topline, toplinska snaga, brzina crpke kruga grijanja i položaj ventila potrošača spremnika.

### Upravljanje alarmima

ReadScript modula prati dva kanala alarma, **Alarm A** i **Alarm B**. Kad je alarm aktivan (status = 2), TapHome ga javlja kao grešku s vrijednošću alarma i stanjem potvrde (Acknowledged/Unacknowledged/Locked).

Za upravljanje alarmima dostupne su tri servisne radnje:

- **Potvrdi alarm A**: potvrđuje nepotvrđeni alarm
- **Potvrdi alarm B**: potvrđuje nepotvrđeni alarm
- **Ukloni sve neaktivne alarme**: briše iz sustava sve neaktivne / potvrđene alarme

### Dodatne mogućnosti

EcoNordic podržava i mjerače vremena filtara, izračun učinkovitosti povrata topline, praćenje brzine dovodnog ventilatora i podešavanje krivulje grijanja (WH4). Stanje ventilacije s povratom topline prikazuje dodatne načine (Fume hood, Fireplace, Temporary high) osim onih koje izravno nudi uređaj Način rada. Te se mogućnosti mogu dodati u budućem ažuriranju predloška.

> [!TIP]
> EcoNordic sa svojom CO₂ dizalicom topline radi do **-25 °C vanjske temperature**. Rotacijski izmjenjivač topline postiže do 90 % temperaturne učinkovitosti povrata topline. Učinkovitost povrata topline procijenite praćenjem razlike između temperature dovodnog i odsisnog zraka.

## Rješavanje problema

### Nema Modbus komunikacije

1. Provjerite spojeve kabela RS-485 između sustava TapHome i uređaja EcoNordic
2. Provjerite komunikacijske parametre: **9600 baud, 8-E-1** (parni paritet, ne bez pariteta)
3. Provjerite odgovara li Slave ID u TapHome konfiguraciji uređaja (zadano: 1)
4. Provjerite je li EcoNordic uključen i radi li

### Senzori kruga grijanja ne daju podatke (WH4)

Senzori temperature polaza i povrata kruga grijanja dostupni su samo na **modelu WH4**. Na modelu W4 (samo ventilacija + PTV) ti senzori ne javljaju vrijednosti.

### Alarmi javljeni u TapHome

1. Detalje alarma provjerite u servisnim atributima u TapHome: prikazuju se vrijednost i stanje alarma
2. Aktivni alarm potvrdite servisnom radnjom **Potvrdi alarm**
3. Značenje kodova alarma potražite u aplikaciji Flexit GO ili u korisničkim uputama
4. Česti uzroci: začepljeni filtri, zaustavljen rotor, aktivirana zaštita od pregrijavanja, problemi u vodenom sustavu

## Dostupni uređaji 14

Ovi se uređaji pojavljuju u TapHomeu nakon uvoza.

Flexit EcoNordic Modul

Servisni atributi

|                                              |                                                                                                                                                                                      |
|----------------------------------------------|--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------|
| Stanje dizalice topline                      | Radno stanje dizalice topline — Standby, Air Purge, Startup, Normal, Stop, Defrost, Error, Manual, Forced fan/pump                                                                   |
| Stanje potrošne tople vode                   | Trenutačno stanje pripreme PTV-a — Comfort, Economy, Not in Use, Boost, Forced Charge, Legionella prevention                                                                         |
| Stanje ventilacije s povratom topline        | Trenutačno stanje ventilacije — Off, Away, Home, High, Fume hood, Fireplace, Temporary high                                                                                          |
| Način rada postrojenja dizalice topline      | Način rada postrojenja dizalice topline — pokazuje što dizalica topline trenutačno radi (punjenje spremnika, grijanje prostora, grijanje ventilacijskog zraka, zaštita od legionele) |
| Dogrijač dizalice topline                    |                                                                                                                                                                                      |
| Zaštita dizalice topline od smrzavanja       |                                                                                                                                                                                      |
| Stanje grijača posude za kondenzat           |                                                                                                                                                                                      |
| Upozorenje dizalice topline na kamenac       |                                                                                                                                                                                      |
| Položaj priključne zaklopke dizalice topline |                                                                                                                                                                                      |

Servisne radnje

|                             |
|-----------------------------|
| Ukloni sve neaktivne alarme |
| Potvrdi alarm A             |
| Potvrdi alarm B             |

Čitanje (modul)

```taphome
IF MODBUSR(A,3001, Uint16) = 2
ADDERROR(MODBUSR(A, 1021, float), "Alarm A: " + 
SWITCH(MODBUSR(A,3002, Uint16),
1, "Acknowledged, unlocked ",
2, "Unacknowledged",
3, "Locked",
"Unknown" ));
END

IF MODBUSR(A,3003, Uint16) = 2
ADDERROR(MODBUSR(A, 1023, float), "Alarm B: " + 
SWITCH(MODBUSR(A,3004, Uint16),
1, "Acknowledged, unlocked ",
2, "Unacknowledged",
3, "Locked",
"Unknown" ));
END
```

Servisni atributi

Heat Pump Status

```taphome
SWITCH(MODBUSR(A, 3028, Uint16), 
1, "Standby", 
2, "Air Purge process",
3, "Startup process",
4, "Normal operation",
5, "Stop process", 
6, "Defrost operation",
7, "Standby when error",
8, "Manual operation",
9, "Forced fan operation",
10, "Forced pump operation",
11, "State 10",
12, "State 11",
13, "State 12",
14, "State 13",
15, "State 14",
16, "State 15",
"Unknown"
)
```

Domestic hot water state

```taphome
SWITCH(MODBUSR(A, 3005, Uint16),
1, "Comfort",
2, "Economy", 
3, "Not in Use",
4, "Temporary Boost",
5, "Forced Charge",
6, "Economy delay",
7, "Legionella prevention",
"Unknown"
);
```

Heat recovery ventilation state

```taphome
SWITCH(MODBUSR(A, 3034, Uint16),
1, "Off", 
2 , "Away" , 
3 , "Home" , 
4 , "High", 
5 , "Fume hood", 
 6 , "Fireplace", 
 7 , "Temporary high",
 "Unknown");
```

Plant operating mode for heat pump

```taphome
SWITCH(MODBUSR(H, 2061, Uint16), 
1 , "Off" , 
2 , "Vent.heating from tank" , 
3 , "Load tank" ,
4 , "Load tank & vent.heating" ,
5 , "Space heating from tank" , 
6 , "Space heat.& vent.heat.from tank",
7 , "Load tank & space heat" , 
8 , "Load tank & space heat.& vent" , 
9 , "HP not available" , 
10 , "Swi-off delay flow through heat",
11 , "Legionella prev.vent.heat" , 
12 , "Legionella prev.space heat" , 
13 , "Space heat.with HP" ,
14 , "Space heat.& vent.with HP" , 
15 , "Load tank & space heat.with HP" , 
16 , "Load tank & vent.& space with HP", 
17 , "Legionella prev.tank",
"Unknown")
```

Heat Pump Reheating Coil

```taphome
Switch (MODBUSR(A, 3029, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat Pump Frost Protection

```taphome
Switch (MODBUSR(A, 3031, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Drain Pan Heater State

```taphome
Switch (MODBUSR(A, 3036, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat pump warning limescale

```taphome
Switch (MODBUSR(A, 3037, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat Pump Connection Dumper position

```taphome
MODBUSR(H, 29, Float, 2) + " %"
```

Servisne radnje

Remove All Inactive Alarms

```taphome
MODBUSW(H, 3004, Uint16, 3);
```

Acknowledge Alarm A

```taphome
MODBUSW(H, 3002, Uint16, 2)
```

Acknowledge Alarm B

```taphome
MODBUSW(H, 3003, Uint16, 2)
```

Tipka Comfort Sklopka Čitanje i pisanje

Registar: H:2040 Bool

Vrijednosti / stanja: Active · Inactive

Čitanje stanja sklopke

```taphome
MODBUSR(H, 2040, Bool)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 2040, Bool, St)
```

Temperatura otpadnog zraka Senzor temperature Samo za čitanje

Temperatura zraka koji se nakon povrata topline izbacuje van

Registar: A:13 Float Jedinica: °C numeric

Servisni atributi

|                                                             |
|-------------------------------------------------------------|
| Brzina ventilatora otpadnog zraka                           |
| Upravljački signal zaklopke otpadnog zraka                  |
| Upravljački signal zaklopke otpadnog zraka dizalice topline |

Čitanje temperature

```taphome
MODBUSR(A, 13, Float, 2)
```

Servisni atributi

Exhaust Air Fan Speed

```taphome
 ROUND(MODBUSR(H, 9, Float, 2)) + " %"
```

Exhaust Air Damper Command

```taphome
Switch (MODBUSR(H, 2010, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat pump exhaust air damper command

```

```

Temperatura odsisnog zraka Senzor temperature Samo za čitanje

Temperatura zraka koji se odsisava iz zgrade prije povrata topline

Registar: A:9 Float Jedinica: °C numeric

Servisni atributi

|                                                             |
|-------------------------------------------------------------|
| Upravljački signal zaklopke otpadnog zraka dizalice topline |

Čitanje temperature

```taphome
MODBUSR(A, 9, Float , 2)
```

Servisni atributi

Heat pump exhaust air damper command

```taphome
Switch (MODBUSR(H, 2064, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Temperatura polaza kruga grijanja Senzor temperature Samo za čitanje

Temperatura vode u polaznoj cijevi kruga grijanja — samo model WH4

Registar: A:97 Float Jedinica: °C numeric

Servisni atributi

|                                            |
|--------------------------------------------|
| Brzina rotacijskog izmjenjivača topline    |
| Zadana temperatura polaza dizalice topline |
| Toplinska snaga dizalice topline           |

Čitanje temperature

```taphome
MODBUSR(A, 97, Float, 2)
```

Servisni atributi

Rotary heat exchanger speed

```taphome
 ROUND(MODBUSR(H, 1, Float, 2)) + " %"
```

Heat pump setpoint flow temperature

```taphome
MODBUSR(H, 73, Float, 2) + " °C"
```

Heat Pump Thermic Power Output

```taphome
MODBUSR(H, 65, Float, 2) + " kW"
```

Temperatura povrata kruga grijanja Senzor temperature Samo za čitanje

Temperatura vode u povratnoj cijevi kruga grijanja — samo model WH4

Registar: A:101 Float Jedinica: °C numeric

Čitanje temperature

```taphome
MODBUSR(A, 101, Float, 2)
```

Pojačano zagrijavanje PTV-a Prekidač s više vrijednosti Čitanje i pisanje

Privremena priprema PTV-a najvećom snagom — spremno, pokretanje, zaustavljanje

Registar: H:3019 UInt16 numeric

Vrijednosti / stanja: Ready · Start · Stop

Servisne radnje

|                    |
|--------------------|
| Trajanje pojačanja |

Čitanje stanja sklopke

```taphome
MODBUSR(H, 3019, UInt16)
```

Zapis stanja sklopke

```taphome
MODBUSWNE(H, 3019, UInt16, Mu)
```

Servisni atributi

Duration of boost

```taphome
MODBUSR(H, 1513, Uint32) + " min";
```

Servisne radnje

Duration of boost

Parametri: Duration \[0-300 min] (0–300 dur)

```taphome
MODBUSW(H, 1513, Uint32, dur);
```

Način rada PTV-a Prekidač s više vrijednosti Čitanje i pisanje

Način pripreme potrošne tople vode — Comfort (puni pri 50 %) ili Economy (puni pri 15 %)

Registar: H:3017 UInt16 numeric

Vrijednosti / stanja: Comfort · Economy

Čitanje stanja sklopke

```taphome
MODBUSR(H, 3017, UInt16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 3017, UInt16, Mu)
```

Servisni atributi

Heating circuit pump speed

```taphome
MODBUSR(H, 61, Float, 2) + " %"
```

Storage tank consumer valve position

```taphome
 ROUND(MODBUSR(H, 57, Float, 2)) + " %"
```

Način rada Prekidač s više vrijednosti Čitanje i pisanje

Način rada ventilacije — Stop, Away, Home, High

Registar: H:2013 UInt16 numeric

Vrijednosti / stanja: Stop · Away · Home · High

Čitanje stanja sklopke

```taphome
MODBUSR(H, 2013, Uint16)
```

Zapis stanja sklopke

```taphome
MODBUSW(H, 2013, Uint16, Mu)
```

Temperatura vanjskog zraka Senzor temperature Samo za čitanje

Registar: A:1 Float Jedinica: °C numeric

Čitanje temperature

```taphome
MODBUSR(A, 1, Float)
```

Temperatura dovodnog zraka Senzor temperature Samo za čitanje

Temperatura svježeg zraka koji se dovodi u zgradu nakon povrata topline i dogrijavanja

Registar: A:5 Float Jedinica: °C numeric

Čitanje temperature

```taphome
MODBUSR(A, 5, Float, 2)
```

Temperatura u načinu Away Termostat Čitanje i pisanje

Zadana temperatura dovodnog zraka za način Away (10–30 °C)

Registar: H:1163 Float Jedinica: °C numeric

Čitanje željene temperature

```taphome
MODBUSR(H, 1163, Float, 2)
```

Zapis željene temperature

```taphome
MODBUSW(H, 1163, Float, Se)
```

Temperatura u načinu Home Termostat Čitanje i pisanje

Zadana temperatura dovodnog zraka za način Home (10–30 °C)

Registar: H:1155 Float Jedinica: °C numeric

Čitanje željene temperature

```taphome
MODBUSR(H, 1155, Float, 2)
```

Zapis željene temperature

```taphome
MODBUSW(H, 1155, Float, Se)
```

Ventilacija za kamin Prekidač s više vrijednosti Čitanje i pisanje

Uključuje način nadtlaka kako dim ne bi ulazio u prostoriju pri paljenju kamina — Spremno, Pokreni

Registar: H:3007 UInt16 numeric

Vrijednosti / stanja: Ready · Trigger

Servisne radnje

|                               |
|-------------------------------|
| Trajanje ventilacije za kamin |

Čitanje stanja sklopke

```taphome
MODBUSR(H, 3007,UInt16)
```

Zapis stanja sklopke

```taphome
MODBUSWNE(H, 3007, UInt16, Mu)
```

Servisni atributi

Fireplace Ventilation Runtime

```taphome
MODBUSR(H, 1105, Uint32) + " min"
```

Servisne radnje

Fireplace Ventilation Runtime

Parametri: duration \[0 - 360 min] (0–360 dur)

```taphome
MODBUSW(H, 1105, Uint32, dur)
```

Brza ventilacija Prekidač s više vrijednosti Čitanje i pisanje

Privremena ventilacija velikom brzinom za brzu izmjenu zraka — Spremno, Pokreni

Registar: H:3006 UInt16 numeric

Vrijednosti / stanja: Ready · Trigger

Servisne radnje

|                           |
|---------------------------|
| Trajanje brze ventilacije |

Čitanje stanja sklopke

```taphome
MODBUSR(H, 3006, UInt16)
```

Zapis stanja sklopke

```taphome
MODBUSWNE(H, 3006, UInt16, Mu)
```

Servisni atributi

Rapid ventilation runtime

```taphome
MODBUSR(H, 1103, Uint32) + " min"
```

Servisne radnje

Rapid Ventilation Runtime

Parametri: Duration \[1-360 min] (1–360 dur)

```taphome
MODBUSW(H, 1103, Uint32, dur)
```

**Povezivanje:** Modbus RTU • 9600 baud• 8E1 • Slave ID: $\[SlaveId]

Moguća poboljšanja (7)

- pyflexit CI66 Register Map (Nordic S2–S4, CL2–CL4) — Complete CI66 adapter register map (addresses 0–48) for Nordic models — NOT applicable to EcoNordic which uses proprietary registers
- H:2013 value 5+ Fume Hood and Calendar Modes — Heat Recovery Ventilation State shows values 5=Fume hood, 6=Fireplace, 7=Temporary high — but Operating Mode (H:2013) only exposes Stop/Away/Home/High (1–4). Fume hood may require separate trigger register
- unknown Filter Timer / Filter Alarm — CI66 has filter operating hours (reg 8), filter alarm (reg 27), filter alarm period (reg 46). EcoNordic likely has equivalent registers but they are not in the XML template
- unknown Heat Recovery Efficiency — CI66 exposes heat recovery percentage (0–100%). EcoNordic may have equivalent register — can be calculated from supply/extract/outside temperatures
- unknown Supply Air Fan Speed — Exhaust fan speed is exposed (H:9) but supply fan speed is missing from the template. EcoNordic likely has this register
- unknown Heating Circuit Setpoint Temperature — WH4 heating set value and parallel shift for the heat curve — not exposed in the template
- doc 2882 (404) Full EcoNordic Modbus Register Map — Official Flexit Modbus EcoNordic Basic XLSX register map returned 404 — may contain additional registers not in the XML template

## Parametri uvoza

Ove vrijednosti unosite pri uvozu XML-a.

| Pitanje u aplikaciji | Zadano        |
|----------------------|---------------|
| Slave ID             | `1`           |
| IP adresa            | `192.168.1.0` |

## Izvori

- pyflexit — Flexit Modbus Python Library (register map)
  
  [github.com](https://github.com/Sabesto/pyflexit) 2026-03-20
- Home Assistant Flexit Integration
  
  [www.home-assistant.io](https://www.home-assistant.io/integrations/flexit/) 2026-03-20
- EcoNordic WH4/W4 User Manual (116927EN-07)
  
  [assets.ctfassets.net](http://assets.ctfassets.net/wzjhf3pmxyuk/1woGygq1Dvw0xDHElh4Sss/ce551d1f9cc20887831301048b1c2dce/EcoNordic_WH4_-_W4_Vartotojo_instrukcija_EN.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/flexit-econordic/manufacturer/econordic-user-manual.pdf)
- EcoNordic WH4 Product Data Sheet (117290EN-01)
  
  [nit.lt](https://nit.lt/wp-content/uploads/2019/02/flexit-EcoNordic-WH4-eng.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/flexit-econordic/manufacturer/econordic-assembly-manual.pdf)

Dokumenti proizvođača zaštićeni su autorskim pravom (©) svojih vlasnika. Dostupni su onako kako ih je proizvođač objavio, samo za informaciju.

## Povezana dokumentacija

- [Modbus Integration](https://taphome.com/hr/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/hr/docs/integration/modbus/)
- [Jednostavna konfiguracija pomoću predložaka](https://taphome.com/hr/docs/integration/modbus/templates/)
- [Skripte Modbus i prefetch](https://taphome.com/hr/docs/script/modbus-scripts/)
- [Funkcije Modbus](https://taphome.com/hr/docs/script/modbus/)
- [Tipovi podataka Modbus](https://taphome.com/hr/docs/script/modbus-data-types/)