title: "Eastron SDM630"
description: "Trofazno brojilo Eastron SDM630 s Modbus RTU (RS-485). Predložak TapHome daje 12 brojila: ukupna energija, po fazama, preuzeta i predana energija."
url: "https://taphome.com/hr/compatibility/eastron-sdm630/"
language: hr
lastmod: 2026-03-20
generator: hugo
ai:
  topics: ["modbus-rtu","electric-meter","rs485","3-phase","energy-metering","din-rail"]
  questions: ["Kako integrirati Eastron SDM630 sa sustavom TapHome?","Što mjeri predložak TapHome za Eastron SDM630?","Kako spojiti Eastron SDM630 preko RS-485 na TapHome?","Kako sa SDM630 zasebno pratiti preuzetu i predanu energiju?","Koji su servisni atributi dostupni u predlošku SDM630?","Kako na Eastron SDM630 postaviti Modbus adresu (Slave ID)?"]
---

# Eastron SDM630

Komunikacija: Modbus RTU

- [Službena stranica Eastron](https://www.eastroneurope.com)

## Upute za integraciju

Eastron SDM630 trofazno je brojilo električne energije za ugradnju na DIN šinu koje komunicira protokolom Modbus RTU preko RS-485. Predložak TapHome daje 12 uređaja brojila: ukupnu energiju sustava, energiju po fazama (L1/L2/L3), dvosmjerno mjerenje preuzete i predane energije te opsežne servisne atribute za napon, struju, faktor snage, jalovu snagu, frekvenciju i fazne kutove.

Brojilo podržava tri načina spajanja: trofazno četverovodno (3P4W), trofazno trovodno (3P3W) i jednofazno dvovodno (1P2W). Sve vrijednosti registara su IEEE 754 Float32 s redoslijedom bajtova Big Endian, a čitaju se Modbus funkcijom FC04 (input registers).

## Hardversko spajanje

### Ožičenje RS-485

SDM630 ima dvožilno sučelje RS-485 s dvije vijčane stezaljke. Spojite ga u linijskoj topologiji (daisy chain):

- **A** (stezaljka 27) na A+/D+ na TapHome RS-485
- **B** (stezaljka 28) na B-/D- na TapHome RS-485

> [!WARNING]
> Koristite samo **linijsku topologiju (daisy chain)**. Topologija zvijezde i odvojci (stub/tee) uzrokuju refleksije signala i oštećenje podataka. Oba kraja sabirnice zaključite **otpornikom od 120 Ω** (najmanje 0,25 W).

**Specifikacija kabela:**

- Vrsta: upredena parica, oklopljena (Belden 8761 ili jednakovrijedan)
- Impedancija: 120 Ω
- Najveća duljina kabela: **1200 m**
- Najveći broj uređaja na sabirnici: **32**

### Načini spajanja

Brojilo se mora konfigurirati za ispravan sustav spajanja preko holding registra 10 (zaštićen lozinkom):

| Vrsta sustava | Vrijednost | Opis |
|-------------|-------|-------------|
| 3P4W | 3 | Trofazno četverovodno (zadano) |
| 3P3W | 2 | Trofazno trovodno |
| 1P2W | 1 | Jednofazno dvovodno |

Neki su registri dostupni samo u određenim načinima spajanja. Na primjer, fazni naponi (faza – neutralni vodič) i struja neutralnog vodiča dostupni su samo u načinu 3P4W, a linijski naponi (faza – faza) zahtijevaju 3P4W ili 3P3W.

## Konfiguracija

### Komunikacijski parametri

Zadane Modbus postavke odgovaraju predlošku TapHome:

| Parametar | Zadano | Mogućnosti |
|-----------|---------|---------|
| Brzina prijenosa (baud rate) | 9600 | 2400, 4800, 9600, 19200, 38400 |
| Podatkovni bitovi | 8 | Fiksno |
| Paritet | nema | nema, parna, neparna |
| Stop bitovi | 2 | 1 (s paritetom) ili 2 (bez pariteta) |
| Slave ID | 1 | 1–247 |

Komunikacijske postavke mogu se promijeniti preko holding registara (FC03/FC16). Za zaštićene parametre, poput vrste sustava, potrebna je lozinka (zadano: 0000). Lozinka se upisuje u holding registar 24 i automatski se zaključava nakon 1 minute neaktivnosti.

### Slave ID

Kada je na istu sabirnicu RS-485 spojeno više brojila SDM630, svako brojilo mora imati jedinstveni Slave ID (holding registar 20, raspon 1–247). Nakon uvoza predloška TapHome prilagodite Slave ID u postavkama veze modula tako da odgovara brojilu.

> [!TIP]
> Svaki Modbus zahtjev može odjednom pročitati do 40 parametara (80 registara). Predložak TapHome čita brojila ukupne energije svakih 2,5 sekunde, a brojila po fazama svakih 15 sekundi, pa opterećenje sabirnice ostaje prihvatljivo i s više brojila.

## Mogućnosti uređaja

Predložak stvara 12 uređaja ModbusElectricityMeter podijeljenih u tri skupine: ukupna energija, predana energija (u mrežu) i preuzeta energija (iz mreže). Svaki uređaj javlja kumulativnu energiju (kWh) i trenutačnu snagu (kW).

### Mjerenje ukupne energije

Četiri uređaja prate ukupnu potrošnju djelatne energije:

- **Ukupna energija (3 faze)** — ukupna energija sustava (A:342, kWh) i ukupna snaga (A:52, W pretvoreno u kW). Ovaj uređaj ima 12 servisnih atributa s prosjecima i zbrojevima za cijeli sustav: prosječni linijski napon, prosječni fazni napon, prosječna i zbrojena struja faza, struja neutralnog vodiča, ukupna prividna snaga (VA), ukupna jalova snaga (VAr), ukupni faktor snage, ukupni fazni kut, frekvencija mreže (Hz), ukupna prividna energija (kVAh) i ukupna jalova energija (kVArh).
- **Ukupna energija L1** — ukupna djelatna energija faze 1 (A:358, kWh) i snaga faze 1 (A:12, W u kW). Servisni atributi uključuju fazni napon, struju, prividnu snagu, jalovu snagu, faktor snage, fazni kut i jalovu energiju faze 1.
- **Ukupna energija L2** — ukupna djelatna energija faze 2 (A:360, kWh) i snaga faze 2 (A:14, W u kW). Isti servisni atributi po fazi kao L1.
- **Ukupna energija L3** — ukupna djelatna energija faze 3 (A:362, kWh) i snaga faze 3 (A:16, W u kW). Isti servisni atributi po fazi kao L1.

### Predana energija (u mrežu)

Četiri uređaja prate energiju predanu u mrežu, što je korisno kod solarnih elektrana:

- **Predana energija (3 faze)** — ukupna predana energija (A:74, kWh) i snaga predaje izračunata iz negativnih očitanja ukupne snage sustava (A:52).
- **Predana energija L1** — predana energija faze 1 (A:352, kWh) i snaga predaje faze 1.
- **Predana energija L2** — predana energija faze 2 (A:354, kWh) i snaga predaje faze 2.
- **Predana energija L3** — predana energija faze 3 (A:356, kWh) i snaga predaje faze 3.

### Preuzeta energija (iz mreže)

Četiri uređaja prate energiju preuzetu iz mreže:

- **Preuzeta energija (3 faze)** — ukupna preuzeta energija (A:72, kWh) i snaga preuzimanja izračunata iz pozitivnih očitanja ukupne snage sustava (A:52).
- **Preuzeta energija L1** — preuzeta energija faze 1 (A:346, kWh) i snaga preuzimanja faze 1.
- **Preuzeta energija L2** — preuzeta energija faze 2 (A:348, kWh) i snaga preuzimanja faze 2.
- **Preuzeta energija L3** — preuzeta energija faze 3 (A:350, kWh) i snaga preuzimanja faze 3.

> [!TIP]
> Podjela na preuzetu i predanu energiju dobiva se čitanjem registra snage sustava s predznakom (A:52). Pozitivne vrijednosti znače potrošnju iz mreže (preuzimanje), a negativne predaju u mrežu. To je posebno korisno za praćenje vlastite potrošnje energije iz solarne elektrane i razmjene s mrežom.

### Dodatne mogućnosti

SDM630 ima i registre za linijske napone (L1-L2, L2-L3, L3-L1), ukupno harmonijsko izobličenje (THD) napona i struje za svaku fazu, prosječnu struju po fazi u intervalu mjerenja sa zabilježenim maksimumima, brojače preuzete i predane jalove energije te mjerenje ampersati. Oni se mogu dodati u nekom budućem ažuriranju predloška.

## Rješavanje problema

### Nema komunikacije

1. Provjerite je li ožičenje RS-485 izvedeno u linijskoj topologiji (ne kao zvijezda)
2. Provjerite spojeve stezaljki A/B — ako komunikacija ne radi, zamijenite A i B
3. Provjerite zaključenje sabirnice: otpornik od 120 Ω na svakom kraju sabirnice
4. Provjerite odgovara li brzina prijenosa u sustavu TapHome postavci brojila (zadano 9600, 8N2)
5. Provjerite odgovara li Slave ID u sustavu TapHome brojilu (zadano 1)

### Netočna očitanja

1. Provjerite odgovara li vrsta sustava spajanja (holding registar 10) stvarnoj instalaciji — pogrešna vrsta sustava daje nulte ili netočne vrijednosti
2. U načinu 3P3W registri faznih napona vraćaju nulu — to je očekivano ponašanje
3. Struja neutralnog vodiča (A:224) u načinu 3P3W iznosi nula — dostupna je samo u načinu 3P4W

### Redoslijed bajtova registara

SDM630 zadano koristi redoslijed bajtova Big Endian (najznačajniji registar prvi). Ako se očitanja prikazuju kao iznimno velike ili male brojke, provjerite postavku redoslijeda bajtova. Predložak TapHome koristi BigEndianFloat, što odgovara zadanoj postavci brojila.

## Dostupni uređaji 12

Ovi se uređaji pojavljuju u TapHomeu nakon uvoza.

Eastron SDM630 / SDM72D Modul

Ukupna energija (3 faze) Brojilo električne energije Samo za čitanje

Ukupna trofazna energija i snaga — ukupna potrošnja (kWh) i trenutačna snaga sustava (kW), s 12 servisnih atributa za napon, struju, faktor snage, frekvenciju i jalovu energiju

Registar: A:342 (readtotalconsumption), A:52 (readdemand) BigEndianFloat Jedinica: kWh / kW

Servisni atributi

|                               |
|-------------------------------|
| Prosječni linijski napon      |
| Prosječni fazni napon         |
| Prosječna struja faza         |
| Zbroj struja faza             |
| Struja neutralnog vodiča      |
| Ukupna prividna snaga sustava |
| Ukupna jalova snaga sustava   |
| Ukupni faktor snage sustava   |
| Ukupni fazni kut sustava      |
| Frekvencija mreže             |
| Ukupna prividna energija      |
| Ukupna jalova energija        |

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 342, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
MODBUSR(A, 52, BigEndianFloat) / 1000
```

Servisni atributi

Average line to line \[V]

```taphome
TOSTRING(MODBUSR(A, 206, BigEndianFloat), "F1")
```

Average line to neutral \[V]

```taphome
TOSTRING(MODBUSR(A, 42, BigEndianFloat), "F1")
```

Average line current \[A]

```taphome
TOSTRING(MODBUSR(A, 46, BigEndianFloat), "F2")
```

Sum of line currents \[A]

```taphome
TOSTRING(MODBUSR(A, 48, BigEndianFloat), "F2")
```

Neutral current \[A]

```taphome
TOSTRING(MODBUSR(A, 224, BigEndianFloat), "F2")
```

Total system volt amps \[VA]

```taphome
TOSTRING(MODBUSR(A, 56, BigEndianFloat), "F1")
```

Total system reactive power \[VAr]

```taphome
TOSTRING(MODBUSR(A, 60, BigEndianFloat), "F1")
```

Total system power factor

```taphome
TOSTRING(MODBUSR(A, 62, BigEndianFloat), "F3")
```

Total system phase angle

```taphome
TOSTRING(MODBUSR(A, 66, BigEndianFloat), "F1")
```

Frequency of supply voltages \[Hz]

```taphome
TOSTRING(MODBUSR(A, 70, BigEndianFloat), "F1")
```

Total VAh \[kVAh]

```taphome
TOSTRING(MODBUSR(A, 80, BigEndianFloat), "F1")
```

Total VArh \[kVArh]

```taphome
TOSTRING(MODBUSR(A, 344, BigEndianFloat), "F1")
```

Ukupna energija L1 Brojilo električne energije Samo za čitanje

Registar: A:358 (readtotalconsumption), A:12 (readdemand) BigEndianFloat Jedinica: kWh / kW

Servisni atributi

|                 |
|-----------------|
| Fazni napon     |
| Struja          |
| Prividna snaga  |
| Jalova snaga    |
| Faktor snage    |
| Fazni kut       |
| Jalova energija |

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 358, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
MODBUSR(A, 12, BigEndianFloat) / 1000
```

Servisni atributi

Line to neutral voltage \[V]

```taphome
TOSTRING(MODBUSR(A, 0, BigEndianFloat), "F1")
```

Current \[A]

```taphome
TOSTRING(MODBUSR(A, 6, BigEndianFloat), "F2")
```

Volt amps \[VA]

```taphome
TOSTRING(MODBUSR(A, 18, BigEndianFloat), "F1")
```

Reactive power \[VAr]

```taphome
TOSTRING(MODBUSR(A, 24, BigEndianFloat), "F1")
```

Power factor

```taphome
TOSTRING(MODBUSR(A, 30, BigEndianFloat), "F1")
```

Phase angle

```taphome
TOSTRING(MODBUSR(A, 36, BigEndianFloat), "F1")
```

Reactive Energy \[kVArh]

```taphome
TOSTRING(MODBUSR(A, 376, BigEndianFloat), "F1")
```

Ukupna energija L2 Brojilo električne energije Samo za čitanje

Registar: A:360 (readtotalconsumption), A:14 (readdemand) BigEndianFloat Jedinica: kWh / kW

Servisni atributi

|                 |
|-----------------|
| Fazni napon     |
| Struja          |
| Prividna snaga  |
| Jalova snaga    |
| Faktor snage    |
| Fazni kut       |
| Jalova energija |

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 360, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
MODBUSR(A, 14, BigEndianFloat) / 1000
```

Servisni atributi

Line to neutral voltage \[V]

```taphome
TOSTRING(MODBUSR(A, 2, BigEndianFloat), "F1")
```

Current \[A]

```taphome
TOSTRING(MODBUSR(A, 8, BigEndianFloat), "F2")
```

Volt amps \[VA]

```taphome
TOSTRING(MODBUSR(A, 20, BigEndianFloat), "F1")
```

Reactive power \[VAr]

```taphome
TOSTRING(MODBUSR(A, 26, BigEndianFloat), "F1")
```

Power factor

```taphome
TOSTRING(MODBUSR(A, 32, BigEndianFloat), "F1")
```

Phase angle

```taphome
TOSTRING(MODBUSR(A, 38, BigEndianFloat), "F1")
```

Reactive Energy \[kVArh]

```taphome
TOSTRING(MODBUSR(A, 378, BigEndianFloat), "F1")
```

Ukupna energija L3 Brojilo električne energije Samo za čitanje

Registar: A:362 (readtotalconsumption), A:16 (readdemand) BigEndianFloat Jedinica: kWh / kW

Servisni atributi

|                 |
|-----------------|
| Fazni napon     |
| Struja          |
| Prividna snaga  |
| Jalova snaga    |
| Faktor snage    |
| Fazni kut       |
| Jalova energija |

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 362, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
MODBUSR(A, 16, BigEndianFloat) / 1000
```

Servisni atributi

Line to neutral voltage \[V]

```taphome
TOSTRING(MODBUSR(A, 4, BigEndianFloat), "F1")
```

Current \[A]

```taphome
TOSTRING(MODBUSR(A, 10, BigEndianFloat), "F2")
```

Volt amps \[VA]

```taphome
TOSTRING(MODBUSR(A, 22, BigEndianFloat), "F1")
```

Reactive power \[VAr]

```taphome
TOSTRING(MODBUSR(A, 28, BigEndianFloat), "F1")
```

Power factor

```taphome
TOSTRING(MODBUSR(A, 34, BigEndianFloat), "F1")
```

Phase angle

```taphome
TOSTRING(MODBUSR(A, 40, BigEndianFloat), "F1")
```

Reactive Energy \[kVArh]

```taphome
TOSTRING(MODBUSR(A, 380, BigEndianFloat), "F1")
```

Predana energija (3 faze) Brojilo električne energije Samo za čitanje

Energija predana u mrežu — ukupna predana energija u kWh i trenutačna snaga predaje izračunata iz negativnih očitanja snage sustava

Registar: A:74 (readtotalconsumption), A:52 (readdemand) BigEndianFloat Jedinica: kWh / kW

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 74, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
var demand := MODBUSR(A, 52, BigEndianFloat) / 1000;
if (demand < 0, return(demand * -1), return(0));
```

Predana energija L1 Brojilo električne energije Samo za čitanje

Registar: A:352 (readtotalconsumption), A:12 (readdemand) BigEndianFloat Jedinica: kWh / kW

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 352, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
var demand := MODBUSR(A, 12, BigEndianFloat) / 1000;
if (demand < 0, return(demand * -1), return(0));
```

Predana energija L2 Brojilo električne energije Samo za čitanje

Registar: A:354 (readtotalconsumption), A:14 (readdemand) BigEndianFloat Jedinica: kWh / kW

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 354, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
var demand := MODBUSR(A, 14, BigEndianFloat) / 1000;
if (demand < 0, return(demand * -1), return(0));
```

Predana energija L3 Brojilo električne energije Samo za čitanje

Registar: A:356 (readtotalconsumption), A:12 (readdemand) BigEndianFloat Jedinica: kWh / kW

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 356, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
var demand := MODBUSR(A, 12, BigEndianFloat) / 1000;
if (demand < 0, return(demand * -1), return(0));
```

Preuzeta energija (3 faze) Brojilo električne energije Samo za čitanje

Energija preuzeta iz mreže (potrošnja) — ukupna preuzeta energija u kWh i trenutačna snaga preuzimanja izračunata iz pozitivnih očitanja snage sustava

Registar: A:72 (readtotalconsumption), A:52 (readdemand) BigEndianFloat Jedinica: kWh / kW

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 72, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
var demand := MODBUSR(A, 52, BigEndianFloat) / 1000;
if (demand < 0, return(0), return(demand));
```

Preuzeta energija L1 Brojilo električne energije Samo za čitanje

Registar: A:346 (readtotalconsumption), A:12 (readdemand) BigEndianFloat Jedinica: kWh / kW

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 346, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
var demand := MODBUSR(A, 12, BigEndianFloat) / 1000;
if (demand < 0, return(0), return(demand));
```

Preuzeta energija L2 Brojilo električne energije Samo za čitanje

Registar: A:348 (readtotalconsumption), A:14 (readdemand) BigEndianFloat Jedinica: kWh / kW

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 348, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
var demand := MODBUSR(A, 14, BigEndianFloat) / 1000;
if (demand < 0, return(0), return(demand));
```

Preuzeta energija L3 Brojilo električne energije Samo za čitanje

Registar: A:350 (readtotalconsumption), A:16 (readdemand) BigEndianFloat Jedinica: kWh / kW

Čitanje ukupne potrošnje

```taphome
MODBUSR(A, 350, BigEndianFloat)
```

Čitanje zahtjeva

```taphome
var demand := MODBUSR(A, 16, BigEndianFloat) / 1000;
if (demand < 0, return(0), return(demand));
```

**Povezivanje:** Modbus RTU • 9600 baud• 8N1 • Slave ID: $\[SlaveId]

Moguća poboljšanja (30)

- A:76 Total Import kVArh — Separate import reactive energy counter
- A:78 Total Export kVArh — Separate export reactive energy counter
- A:82 Ah — Ampere-hours counter
- A:84 Total System Power Demand — Demand-averaged system power (W) — template uses A:52 (instantaneous) instead
- A:86 Max Total System Power Demand — Maximum recorded system power demand in VA
- A:100 Total System VA Demand — Current system apparent power demand
- A:102 Max Total System VA Demand — Maximum recorded system VA demand
- A:104 Neutral Current Demand — 3Ø4W wiring only
- A:106 Max Neutral Current Demand — 3Ø4W wiring only
- A:200 L1–L2 Voltage — Line-to-line voltage, 3-phase only
- A:202 L2–L3 Voltage — Line-to-line voltage, 3-phase only
- A:204 L3–L1 Voltage — Line-to-line voltage, 3-phase only
- A:234 Phase 1 L/N Voltage THD — Total harmonic distortion, %
- A:236 Phase 2 L/N Voltage THD — Total harmonic distortion, %
- A:238 Phase 3 L/N Voltage THD — Total harmonic distortion, %
- A:240 Phase 1 Current THD — Total harmonic distortion, %
- A:242 Phase 2 Current THD — Total harmonic distortion, %
- A:244 Phase 3 Current THD — Total harmonic distortion, %
- A:248 Average L/N Voltage THD — Total harmonic distortion, %
- A:250 Average Line Current THD — Total harmonic distortion, %
- A:258 Phase 1 Current Demand — Demand-averaged phase current
- A:260 Phase 2 Current Demand — Demand-averaged phase current
- A:262 Phase 3 Current Demand — Demand-averaged phase current
- A:264 Max Phase 1 Current Demand — Maximum recorded phase 1 current demand
- A:266 Max Phase 2 Current Demand — Maximum recorded phase 2 current demand
- A:268 Max Phase 3 Current Demand — Maximum recorded phase 3 current demand
- A:334 L1–L2 Voltage THD — Line-to-line THD, %
- A:336 L2–L3 Voltage THD — Line-to-line THD, %
- A:338 L3–L1 Voltage THD — Line-to-line THD, %
- A:340 Average L-L Voltage THD — Line-to-line THD, %

## Parametri uvoza

Ove vrijednosti unosite pri uvozu XML-a.

| Pitanje u aplikaciji | Zadano        |
|----------------------|---------------|
| Slave Id             | `1`           |
| IP address           | `192.168.1.0` |

## Izvori

- SDM630 Modbus Protocol V1.8
  
  [www.eastroneurope.com](https://www.eastroneurope.com/images/uploads/products/protocol/SDM630_MODBUS_Protocol.pdf) 2026-03-12
- HA SDM630 Custom Integration
  
  [github.com](https://github.com/partach/ha_sdm630) 2026-03-12
- sdm\_modbus Python Library
  
  [github.com](https://github.com/nmakel/sdm_modbus) 2026-03-12

## Povezana dokumentacija

- [Modbus Integration](https://taphome.com/hr/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/hr/docs/integration/modbus/)
- [Jednostavna konfiguracija pomoću predložaka](https://taphome.com/hr/docs/integration/modbus/templates/)
- [Skripte Modbus i prefetch](https://taphome.com/hr/docs/script/modbus-scripts/)
- [Funkcije Modbus](https://taphome.com/hr/docs/script/modbus/)
- [Tipovi podataka Modbus](https://taphome.com/hr/docs/script/modbus-data-types/)