title: "Atrea RD5 Air Recovery"
description: "Rekuperatori Atrea DUPLEX s regulatorom RD5 povezani sa sustavom TapHome preko Modbus TCP."
url: "https://taphome.com/hr/compatibility/atrea-rd5-air-recovery/"
language: hr
lastmod: 2026-03-15
generator: hugo
ai:
  topics: ["modbus-tcp","air-recovery","ventilation","hvac","temperature-monitoring"]
  questions: ["Kako integrirati ventilaciju Atrea DUPLEX sa sustavom TapHome?","Što mjeri i čime upravlja predložak TapHome za Atrea RD5?","Kako spojiti Atrea RD5 na TapHome preko Modbus TCP?","Kako iz sustava TapHome promijeniti način ventilacije na Atrea DUPLEX?","Kako preko sustava TapHome postaviti zadanu temperaturu na Atrea RD5?","Kako riješiti probleme s vezom Modbus TCP prema Atrea RD5?"]
---

# Atrea RD5 Air Recovery

Komunikacija: Modbus TCP

- [Službena stranica Atrea](https://www.atrea.eu/en/)
- [Dokumenti Atrea](https://atrea.eu/en/documents/)

> Adresa u mreži
> 
> TapHome komunicira s uređajem na adresi unesenoj pri uvozu. Dodijelite uređaju stalnu adresu — rezervaciju IP adrese u usmjerivaču ili njegovo mDNS ime ako ga podržava — inače integracija prestaje raditi kada usmjerivač promijeni adresu.
> 
> [Priprema mreže](https://taphome.com/hr/docs/setup/network-preparation/)

## Upute za integraciju

Atrea DUPLEX serija je rekuperatora (mehanička ventilacija s povratom topline, MVHR) kojima upravlja regulacijski sustav RD5. TapHome se izravno povezuje s regulatorom RD5 protokolom Modbus TCP preko Etherneta — dodatni pristupnik nije potreban.

Predložak daje upravljanje termostatom sa zadanom temperaturom, odabir načina rada (isključeno, automatski, ventilacija, cirkulacija, noćno prethlađenje, ravnotežni tlak, pretlak), podešavanje snage ventilatora (0–100 %), četiri temperaturna senzora (dovodni, unutarnji, vanjski i odsisni zrak) te opsežnu dijagnostiku s više od 45 registara pogrešaka i upozorenja.

## Mrežno povezivanje

Regulator RD5 ima ugrađeno Ethernet sučelje. Spojite ga standardnim Ethernet kabelom u istu lokalnu mrežu kao TapHome Core.

- **Protokol:** Modbus TCP
- **Port:** 502
- **Slave ID:** 1–255 (podesivo)
- **Kodiranje podataka:** Int16, vrijednosti temperature dijele se s 10

## Uključivanje Modbus TCP

Prije nego što TapHome može komunicirati s jedinicom, Modbus TCP treba izričito uključiti u servisnim postavkama regulatora RD5.

Idite na servisni parametar **3.15.1 Modbus TCP** i postavite ga na **YES**.

> [!WARNING]
> Ako Modbus TCP nije uključen (parametar 3.15.1 = NO), regulator RD5 neće odgovarati ni na kakve Modbus TCP zahtjeve na portu 502.

## Konfiguracija

Pri uvozu predloška u sustav TapHome unesite:

- **IP adresa** — IP adresa regulatora RD5 u lokalnoj mreži
- **Slave ID** — Modbus adresa uređaja (zadano: 1)

> [!NOTE]
> Proizvođač preporučuje korištenje upravljačke rutine **Manual** kada jedinicom upravlja BMS sustav poput sustava TapHome. Predložak upisuje upravljačke registre (H:10708, H:10709, H:10710) koji odgovaraju rutini Manual (H:10700–H:10703 = 0).

## Mogućnosti uređaja

Predložak daje sljedeće uređaje:

### Termostat

- **Atrea termostat** — regulacija temperature prostorije sa zadanom vrijednošću u rasponu 10–40 °C. Trenutačnu temperaturu čita iz I:10212 (T-SUP), željenu temperaturu iz H:10716, a zadanu vrijednost upisuje u H:10710. Sadrži 13 servisnih atributa koji prikazuju stanje grijanja i hlađenja (ventil vode, pumpa, dizalica topline, predgrijavanje, konfiguracija hlađenja) i 6 servisnih radnji za konfiguraciju primarnog i sekundarnog grijanja, predgrijavanja, hlađenja, zaštite kapilara od smrzavanja i odabira senzora za regulaciju prostorije.

### Upravljanje načinom rada

- **Upravljanje načinom rada** — prekidač s više vrijednosti za odabir načina rada preko registara H:10705 (čitanje) / H:10709 (upis). Dostupni načini: isključeno, automatski, ventilacija, cirkulacija + ventilacija, cirkulacija, noćno prethlađenje, ravnotežni tlak, pretlak.

### Upravljanje ventilatorima

- **Ventilacija** — dimer koji upravlja snagom ventilatora od 0 % (isključeno) do 100 % preko registara H:10704 (čitanje) / H:10708 (upis). Najmanja snaga ventilatora u radu je 12 %. Sadrži 4 servisna atributa (izlaz M1 %, izlaz M2 %, način regulacije, interval ventilacije) i 2 servisne radnje (odabir načina regulacije ventilatora, postavljanje intervala ventilacije 0–60 min).

### Praćenje temperatura

Predložak sadrži četiri temperaturna senzora:

| Senzor | Registar | Opis |
|--------|----------|-------------|
| **T-SUP** (dovod) | I:10212 | Temperatura dovodnog zraka — zrak koji se nakon povrata topline dovodi u prostorije |
| **T-IDA** (unutra) | I:10215 | Temperatura unutarnjeg zraka — kao izvor može se odabrati CP Touch, T-ETA, TRKn ili BMS |
| **T-ODA** (vani) | I:10211 | Vanjska temperatura zraka — ugrađeni senzor ili vrijednost iz BMS-a |
| **T-ETA** (odsis) | I:10213 | Temperatura odsisnog zraka — zrak koji se odsisava iz prostorija prije povrata topline |

> [!NOTE]
> Izvor senzora T-IDA može se konfigurirati servisnom radnjom na uređaju Temperatura unutarnjeg zraka. Senzor T-ODA može se prebaciti između ugrađenog senzora i vrijednosti iz BMS-a, uz podesiv položaj senzora (unutarnji/vanjski).

### Dijagnostika na razini modula

Predložak RD5 prati više od 45 diskretnih registara (D:11100–D:11184) za pogreške i upozorenja, uključujući:

- **Pogreške:** pregrijavanje uređaja, nepostavljena orijentacija, kvarovi senzora (TU1/TU2/TEa/TEb/TA2/T-ODA/T-ETA), kontakt STP, kvarovi manometra, komunikacija RD-IO, neuravnotežen protok, nedostaje konfiguracija, nedovoljno predgrijavanje, kvarovi modula, zaštita od smrzavanja
- **Upozorenja:** smrzavanje/odmrzavanje izmjenjivača topline, visoka tarifa, nedovoljan protok/grijanje, začepljen filtar, kvarovi alarmnog ulaza, jedinica nije puštena u rad, sigurnosni način rada, hlađenje/grijanje nije dostupno

Servisni atribut na razini modula prikazuje **orijentaciju jedinice** (koji je motor dovodni ventilator), a servisna radnja omogućuje konfiguraciju dodjele dovodnog ventilatora (M1 ili M2).

### Dodatne mogućnosti

Jedinice RD5 daju i Modbus registre za temperaturu otpadnog zraka (T-EHA), stanje prisilnog načina rada, sezonsko upravljanje, praćenje volumnog protoka (dovod/odsis), razdoblje zamjene filtra, poništavanje alarma/filtra i konfiguraciju upravljačke rutine. Oni se mogu dodati u predložak TapHome u nekom budućem ažuriranju.

## Rješavanje problema

### Nema Modbus komunikacije

1. Provjerite je li Modbus TCP uključen — parametar **3.15.1 Modbus TCP = YES** u servisnim postavkama
2. Provjerite IP adresu regulatora RD5 — pogledajte tablicu DHCP zakupa usmjerivača
3. Provjerite jesu li TapHome Core i regulator RD5 u istoj mreži/podmreži
4. Provjerite ne blokira li vatrozid port 502
5. Poštujte razmak od 5 sekundi između više operacija čitanja/upisa, kako preporučuje proizvođač

### Vrijednosti temperature izgledaju netočno

Registri temperature koriste kodiranje Int16, a vrijednost se dijeli s 10. Vrijednosti iznad 32767 predstavljaju negativne temperature: (vrijednost - 65536) / 10. Na primjer, vrijednost 65516 = (65516 - 65536) / 10 = -2,0 °C.

### Promjene načina rada se ne primjenjuju

Kada je jedinica u prisilnom načinu rada (pokretanje, zaustavljanje, odmrzavanje, aktivacija ulaza D1–D4), naredbe za upis načina rada mogu se zanemariti. Provjerite registar prisilnog načina rada H:10712 — vrijednost 0 znači da nijedan prisilni način rada nije aktivan.

Ako se koristi upravljačka rutina Schedule (H:10700–H:10703 = 1), prije upisa novog upravljačkog parametra najprije morate upisati vrijednost 2 u odgovarajući registar upravljačke rutine.

## Dostupni uređaji 7

Ovi se uređaji pojavljuju u TapHomeu nakon uvoza.

Atrea RD5 Modul

Servisni atributi

|                       |
|-----------------------|
| Orijentacija jedinice |

Servisne radnje

|                             |
|-----------------------------|
| Postavi orijentaciju dovoda |

Čitanje (modul)

```taphome
IF(ModbusR(D, 11100, Bool), ADDERROR("Device Overheating"));
IF(ModbusR(D, 11101, Bool), ADDERROR("Orientation not set"));
IF(ModbusR(D, 11102, Bool), ADDERROR("Type of Heater not set"));
IF(ModbusR(D, 11104, Bool), ADDERROR("STP Contact is active"));
IF(ModbusR(D, 11105, Bool), ADDERROR("Manometer DP1 failure"));
IF(ModbusR(D, 11106, Bool), ADDERROR("Manometer DP2 failure"));
IF(ModbusR(D, 11107, Bool), ADDERROR("Sensor TU1 failure"));
IF(ModbusR(D, 11108, Bool), ADDERROR("Sensor TU2 failure"));
IF(ModbusR(D, 11108, Bool), ADDERROR("Sensor TU2 failure"));
IF(ModbusR(D, 11109, Bool), ADDERROR("Sensor TEa failure"));
IF(ModbusR(D, 11110, Bool), ADDERROR("Sensor TEb failure"));
IF(ModbusR(D, 11111, Bool), ADDERROR("Sensor TA2 failure"));
IF(ModbusR(D, 11112, Bool), ADDERROR("RD-IO Communication failure"));
IF(ModbusR(D, 11114, Bool), ADDERROR("Unbalanced Flow"));
IF(ModbusR(D, 11116, Bool), ADDERROR("Indoor Sensor failure"));
IF(ModbusR(D, 11117, Bool), ADDWARNING("Recuperator Freezing"));
IF(ModbusR(D, 11118, Bool), ADDWARNING("Unfreezing Recuperator... "));
IF(ModbusR(D, 11119, Bool), ADDWARNING("High Tariff"));
IF(ModbusR(D, 11119, Bool), ADDWARNING("High Tariff"));
IF(ModbusR(D, 11120, Bool), ADDWARNING("Insufficient flow"));
IF(ModbusR(D, 11121, Bool), ADDWARNING("Insufficient primary heating output"));
IF(ModbusR(D, 11122, Bool), ADDWARNING("Clogged Filter"));
IF(ModbusR(D, 11123, Bool), ADDWARNING("Fault at AI input IN1"));
IF(ModbusR(D, 11124, Bool), ADDWARNING("Fault at AI input IN2"));
IF(ModbusR(D, 11125, Bool), ADDWARNING("Fault at AI input INk1/1"));
IF(ModbusR(D, 11126, Bool), ADDWARNING("Fault at AI input INk2/1"));
IF(ModbusR(D, 11127, Bool), ADDWARNING("Fault at AI input INk3/1"));
IF(ModbusR(D, 11128, Bool), ADDWARNING("Fault at AI input INk4/1"));
IF(ModbusR(D, 11129, Bool), ADDWARNING("Fault at AI input INk1/2"));
IF(ModbusR(D, 11130, Bool), ADDWARNING("Fault at AI input INk2/2"));
IF(ModbusR(D, 11131, Bool), ADDWARNING("Fault at AI input INk3/2"));
IF(ModbusR(D, 11132, Bool), ADDWARNING("Fault at AI input INk4/2"));
IF(ModbusR(D, 11140, Bool), ADDWARNING("Unit is not in Operation"));
IF(ModbusR(D, 11141, Bool), ADDERROR("Configuration File is Missing"));
IF(ModbusR(D, 11143, Bool), ADDERROR("Insufficient Pre-heating Power"));
IF(ModbusR(D, 11144, Bool), ADDERROR("This combination of heaters is not allowed"));
IF(ModbusR(D, 11145, Bool), ADDERROR("Manometer DP3 failure"));
IF(ModbusR(D, 11146, Bool), ADDERROR("External Manometer Failure"));
IF(ModbusR(D, 11147, Bool), ADDERROR("Modul RD5-K/1"));
IF(ModbusR(D, 11148, Bool), ADDERROR("Modul RD5-K/2"));
IF(ModbusR(D, 11149, Bool), ADDERROR("Unfreezing Heat Pump..."));
IF(ModbusR(D, 11160, Bool), ADDWARNING("Updating..."));
IF(ModbusR(D, 11162, Bool), ADDERROR("This cooler configuration is not allowed"));
IF(ModbusR(D, 11165, Bool), ADDWARNING("Safe Mode Active"));
IF(ModbusR(D, 11166, Bool), ADDERROR("Frost protection-capillary"));
IF(ModbusR(D, 11167, Bool), ADDERROR("Frost protection configuration"));
IF(ModbusR(D, 11168, Bool), ADDWARNING("Unfinished Unit Learning"));
IF(ModbusR(D, 11169, Bool), ADDERROR("T-ODA Sensor failure"));
IF(ModbusR(D, 11170, Bool), ADDERROR("T-ETA/T-IDA Sensor failure"));
IF(ModbusR(D, 11171, Bool), ADDWARNING("Cooling is not available"));
IF(ModbusR(D, 11172, Bool), ADDERROR("Heating is not available"));
IF(ModbusR(D, 11173, Bool), ADDWARNING("Evaporation on"));
IF(ModbusR(D, 11174, Bool), ADDWARNING("Increased ignition power"));
IF(ModbusR(D, 11175, Bool), ADDERROR("Illegal flow setting"));
IF(ModbusR(D, 11184, Bool), ADDWARNING("Filter test configuration"));
```

Servisni atributi

Unit Orientation

```taphome
SWITCH(MODBUSR(H, 10501, Uint16), 0, "Not Set", 1, "M1 Supply",2, "M2 Supply", "Unknown")
```

Servisne radnje

Set Supply Orientation

Parametri: Supply

```taphome
ModbusW(H, 10501, Uint16, Sup);
```

Atrea termostat Termostat Čitanje i pisanje

Regulacija temperature prostorije — zadana, trenutačna i željena temperatura

Registar: I:10212 (read current), H:10716 (read desired), H:10710 (write desired) Int16 Jedinica: °C numeric (value / 10 = °C)

Servisni atributi

|                                             |
|---------------------------------------------|
| Ventil vode za grijanje YV1                 |
| Pumpa vode za grijanje KK                   |
| Grijanje (vodeno ili električno) SA2        |
| Dizalica topline (grijanje) DA1             |
| Dizalica topline (grijanje) SE              |
| Dizalica topline (hlađenje) DA1             |
| Dizalica topline (hlađenje) SC              |
| Senzor za regulaciju temperature prostorije |
| Predgrijavanje                              |
| Hlađenje                                    |
| Smrzavanje kapilara                         |
| Primarno grijanje                           |
| Sekundarno grijanje                         |

Servisne radnje

|                                             |
|---------------------------------------------|
| Senzor za regulaciju temperature prostorije |
| Primarno grijanje                           |
| Sekundarno grijanje                         |
| Predgrijavanje                              |
| Hlađenje                                    |
| Smrzavanje kapilara                         |

Čitanje temperature

```taphome
MODBUSR(A, 10212, Int16) / 10
```

Čitanje željene temperature

```taphome
MODBUSR(H, 10716, Int16) / 10
```

Zapis željene temperature

```taphome
MODBUSWNE(H, 10710, Int16, Se * 10)
```

Servisni atributi

Heating Water Valve YV1

```taphome
IF(MODBUSR(C, 10201, Bool), "Open", "Closed")
```

Heating Water Pump KK

```taphome
IF(MODBUSR(C, 10200, Bool), "ON", "OFF")
```

Heating (Water or Electric) SA2

```taphome
var he := MODBUSR(H, 10203, Int16);
IF(he>0, "Active", "Inactive")
```

Heat Pump (Heating) DA1

```taphome
var da := MODBUSR(H, 10207, Int16);
IF(da>0, "ON", "OFF")
```

Heat Pump (Heating) SE

```taphome
IF(MODBUSR(C, 10215, Bool), "Active", "Inactive");
```

Heat Pump (Cooling) DA1

```taphome
IF(MODBUSR(H, 00205, Int16) > 0, "ON", "OFF")
```

Heat Pump (Cooling) SC

```taphome
IF(MODBUSR(C, 10216, Bool), "Active", "Inactive")
```

Temp. sensor for Room Control

```taphome
SWITCH(MODBUSR(H, 10514, Uint16), 0, "CP", 1, "T-ETA", 2, "TRKn", 3, "BMS", "Unknown" )
```

Preheating

```taphome
SWITCH(MODBUSR(H, 10504, Uint16), 0, "None", 1, "Electric", 2, "Liquid", "Unknown" );
```

Cooling

```taphome
SWITCH(MODBUSR(H, 10507, Uint16), 0, "None", 1, "Water", 2, "Direct", "Unknown")
```

Capillary freezing

```taphome
IF(MODBUSR(H, 10530, Uint16) > 0," DIsabled", "Enabled");
```

Primary Heating

```taphome
SWITCH (MODBUSR(H, 10503, Uint16), 0, "None", 1, "Contact-Water", 2, "Analog Water", 3, "PWM-electric", 4, "Contact-Electric", 5, "Thermal pump", "Unknown");
```

Secondary heating

```taphome
SWITCH(MODBUSR(H, 10517, Uint16),0 , "None", 1,  "Contact-Water", 2, "Analog water", 3, "PWM-electric", "Unknown");
```

Servisne radnje

Temp. sensor for Room Control

Parametri: Sensor

```taphome
MODBUSW(H, 10514, Uint16, sens);
```

Primary Heating

Parametri: Heating Source

```taphome
MODBUSW(H, 10503, Uint16, he)
```

Secondary heating

Parametri: Source

```taphome
MODBUSW(H, 10517, Uint16, Soc)
```

Preheating

Parametri: Preheating

```taphome
MODBUSW(H, 10504, Uint16, Pre);
```

Cooling

Parametri: Cooling

```taphome
MODBUSW(H, 10507, Uint16, Coo)
```

Capillary Freezing

Parametri: Capillary Freezing (Enabled / Disabled)

```taphome
MODBUSW(H, 10530, Uint16, CaF);
```

Temperatura dovodnog zraka (T-SUP) Senzor temperature Samo za čitanje

Registar: I:10212 Int16 Jedinica: °C numeric (value / 10 = °C)

Čitanje temperature

```taphome
MODBUSR(A, 10212, Int16) / 10
```

Temperatura unutarnjeg zraka (T-IDA) Senzor temperature Samo za čitanje

Temperatura unutarnjeg zraka — kao izvor može se odabrati panel CP Touch, T-ETA, TRKn ili BMS

Registar: I:10215 Int16 Jedinica: °C numeric (value / 10 = °C)

Servisni atributi

|       |
|-------|
| Izvor |

Servisne radnje

|             |
|-------------|
| Izvor T-IDA |

Čitanje temperature

```taphome
MODBUSR(A, 10215, Int16) / 10
```

Servisni atributi

Source

```taphome
var va := MODBUSR(H, 10514, Int16);
SWITCH(va, 0, "CP",1, "ETA", 2, "TRKn", 3, "BMS", "Unknown")
```

Servisne radnje

Source of T-IDA

Parametri: Source

```taphome
MODBUSW(H, 10514, Int16, So)
```

Upravljanje načinom rada Prekidač s više vrijednosti Čitanje i pisanje

Aktivni način rada — isključeno, automatski, ventilacija, cirkulacija, noćno prethlađenje, ravnotežni tlak ili pretlak

Registar: H:10705 (read), H:10709 (write) Int16 numeric

Vrijednosti / stanja: Isključeno · Automatski · Ventilacija · Cirkulacija &#43; ventilacija · Cirkulacija · Noćno prethlađenje · Ravnotežni tlak · Pretlak

Čitanje stanja sklopke

```taphome
MODBUSR(H, 10705, Int16)
```

Zapis stanja sklopke

```taphome
MODBUSWNE(H, 10709, Int16, Mu)
```

Vanjska temperatura zraka (T-ODA) Senzor temperature Samo za čitanje

Vanjska temperatura zraka — vrijednost iz ugrađenog senzora ili iz BMS-a

Registar: I:10211 Int16 Jedinica: °C numeric (value / 10 = °C, negative: (value − 65536) / 10)

Servisni atributi

|                 |
|-----------------|
| Izvor za T-ODA  |
| Položaj senzora |

Servisne radnje

|                       |
|-----------------------|
| Odaberi izvor         |
| Položaj senzora T-ODA |

Čitanje temperature

```taphome
MODBUSR(A, 10211, Int16) / 10
```

Servisni atributi

Source for T-ODA

```taphome
var source := MODBUSR(C, 10510, Bool);
IF(source = 1, "Data from BMS", "Built-in sensor")
```

Sensor Position

```taphome
SWITCH(MODBUSR(H,10508, Uint16), 0, "Internal", 1, "External", "Unknown");
```

Servisne radnje

Choose Source

Parametri: Source

```taphome
MODBUSW(C, 10510, Bool, So)
```

T-ODA Sensor Position

Parametri: Position

```taphome
MODBUSW(H,10508, Uint16, pos)
```

Temperatura odsisnog zraka (T-ETA) Senzor temperature Samo za čitanje

Registar: I:10213 Int16 Jedinica: °C numeric (value / 10 = °C)

Čitanje temperature

```taphome
MODBUSR(A, 10213, Int16) / 10
```

Ventilacija Dimer Čitanje i pisanje

Upravljanje snagom ventilatora — podešava intenzitet ventilacije uz praćenje motora M1/M2

Registar: H:10704 (read power), H:10708 (write power) Int16 Jedinica: % numeric (0=Off, 12–100 = power %)

Servisni atributi

|                                   |
|-----------------------------------|
| M1                                |
| M2                                |
| Regulacija M1 / M2                |
| Interval ventilacije (automatski) |

Servisne radnje

|                                   |
|-----------------------------------|
| Regulacija M1/M2                  |
| Interval ventilacije (automatski) |

Čitanje razine

```taphome
MODBUSR(H, 10704, Int16) / 100
```

Zapis razine

```taphome
MODBUSWNE(H, 10708, Int16, Le * 100)
```

Servisni atributi

M1

```taphome
MODBUSR(H, 10200, Int16)/100 + "%"
```

M2

```taphome
MODBUSR(H, 10201, Int16)/100 + "%"
```

Regulation M1 / M2

```taphome
SWITCH(MODBUSR(H, 10510, Uint16), 0, "Direct", 1, "Constant flow", 2, "Constant Pressure", 3, "IN1 + IN2", "Unknown" );
```

Ventilation Interval (Auto)

```taphome
MODBUSR(H, 10502, Uint16) +" min";
```

Servisne radnje

Regulation M1/M2

Parametri: Regulation

```taphome
MODBUSW(H, 10510, Uint16, Reg);
```

Ventilation Interval (Auto)

Parametri: Interval (0–60 Inter)

```taphome
MODBUSW(H, 10502, Uint16, Inter);
```

**Povezivanje:** Modbus TCP • Slave ID: $\[SlaveId]

Moguća poboljšanja (19)

- I:10214 Exhaust Air Temperature (T-EHA) — Int16, value / 10 = °C, read-only — air temperature after heat recovery (exhaust side)
- H:10706 Required Temperature (read) — Int16, value / 10 = °C — currently set temperature target, read-only
- H:10704 Required Power (read) — Int16, 0–100% — currently set fan power, read-only
- H:10712 Forced Mode Status — Int16, 0–32 — shows if unit is in a forced mode (startup, rundown, defrost, D1–D4, etc.)
- I:11401 Current Season — 0=Heating Season, 1=Non-Heating Season
- H:11401 Season Control — R/W, 0=HS, 1=NHS, 2=T-ODA, 3=T-ODA+ — manual or automatic season switching
- I:11600 Required Supply Volume Flow — 0–15000 m3/h
- I:11601 Current Supply Volume Flow — 0–15000 m3/h
- I:11602 Required Extract Volume Flow — 0–15000 m3/h
- I:11603 Current Extract Volume Flow — 0–15000 m3/h
- H:10910 Filter Replacement Period — R/W, 0–365 days
- C:10005 Alarm Reset — Write 1 to reset all resetable alarms
- C:10007 Filter Reset — Write 1 to reset filter change interval counter
- H:10700 Power Control Routine — R/W, 0=Manual, 1=Schedule, 2=Temporary — BMS should use Manual (0)
- H:10701 Mode Control Routine — R/W, 0=Manual, 1=Schedule, 2=Temporary
- H:10702 Temperature Control Routine — R/W, 0=Manual, 1=Schedule, 2=Temporary
- H:10703 Zone Control Routine — R/W, 0=Manual, 1=Schedule, 2=Temporary
- H:10707 Required Zone — R/W, 0=Both, 1=Zone 1, 2=Zone 2 — requires SZ1/SZ2 function enabled
- I:11420 Average Outdoor Temperature — Int16, averaged T-ODA over configurable time window

## Parametri uvoza

Ove vrijednosti unosite pri uvozu XML-a.

| Pitanje u aplikaciji | Zadano        |
|----------------------|---------------|
| Slave ID             | `1`           |
| IP adresa            | `192.168.1.0` |

## Izvori

- Index Table for Modbus TCP — RD5 Control System
  
  [atrea.eu](https://atrea.eu/en/documents/) 2026-03-15
  
  [PDF](https://taphome.com/compatibility/devices/atrea-rd5-air-recovery/manufacturer/RD5_parameters_EN.pdf)
- pyatrea — Python Library for Atrea Ventilation Units
  
  [github.com](https://github.com/JurajNyiri/pyatrea) 2026-03-15
- Atrea Ventilation — HA Custom Component (Community Thread)
  
  [community.home-assistant.io](https://community.home-assistant.io/t/atrea-ventilation-custom-component/108905) 2026-03-15

Dokumenti proizvođača zaštićeni su autorskim pravom (©) svojih vlasnika. Dostupni su onako kako ih je proizvođač objavio, samo za informaciju.

## Povezana dokumentacija

- [Modbus Integration](https://taphome.com/hr/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/hr/docs/integration/modbus/)
- [Jednostavna konfiguracija pomoću predložaka](https://taphome.com/hr/docs/integration/modbus/templates/)
- [Skripte Modbus i prefetch](https://taphome.com/hr/docs/script/modbus-scripts/)
- [Funkcije Modbus](https://taphome.com/hr/docs/script/modbus/)
- [Tipovi podataka Modbus](https://taphome.com/hr/docs/script/modbus-data-types/)