External sensor not communicating after replacement

Replaced external sensor (temperature, humidity, CO2) still not communicating with the module

  • Service You need the Service permission (typically your installation partner).

How you recognise it

After replacing a faulty external sensor (temperature + humidity, CO2, or other EXT sensor), the new sensor still doesn’t communicate with the IO module. The sensor shows no values or remains in an error state.

Cause

There are three common causes:

  • Module cache - The IO module remembers the old sensor and doesn’t automatically detect the new one
  • Power cycle needed - The module needs a restart to reinitialize the sensor port
  • Upside down connection - The sensor connector is plugged in upside down (the connector has no locking mechanism to prevent incorrect orientation)

Solution

Step 1: Find new devices

Service installation partner
  1. Go to Settings → Hardware
  2. Select the IO module where the sensor is connected
  3. Run Find new devices
  4. The module will scan for and register the new sensor

Step 2: Power Cycle the Module

Service installation partner

If Find new devices doesn’t help:

  1. Disconnect power from the IO module
  2. Wait 10 seconds
  3. Reconnect power
  4. The module will reinitialize and detect the new sensor

Step 3: Check Connector Orientation

Service installation partner

If the sensor still doesn’t work:

  1. Unplug the sensor connector from the EXT port
  2. Try plugging it in upside down (rotated 180°)
  3. The connector has no locking mechanism, so it can be inserted incorrectly