  questions: ["How do I read a Modbus register in a TapHome script?","How do I write a value to a Modbus register?","What is the difference between MODBUSW and MODBUSWNE?","How do I read many Modbus registers in one transaction?","What do the register types H, C, D and A mean?","What are the SH and SC register types?","How do I read a text string from Modbus registers?"]
---

# Modbus functions

TapHome script Modbus functions — MODBUSR, MODBUSW, MODBUSWNE and the block functions MODBUSRBLOCK, MODBUSWBLOCK, MODBUSWBLOCKNE — and the Modbus register types C, D, H and A.

Last updated: 2026-11-06

Modbus functions read and write the coils and registers of the Modbus device that a script belongs to. They work only in the [scripts of a Modbus module or device](https://taphome.com/en/docs/script/modbus-scripts/); anywhere else the script stops with *ModbusFunction - unknown modbus device to work with*. The data type names (`Uint16`, `BigEndianFloat`, …) are on [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/). Setting up the module and templates is described in [Modbus integration](https://taphome.com/en/docs/integration/modbus/).

## Register types

The first argument of every Modbus function is the register type.

| Type | Modbus object | Function codes | Access |
|---|---|---|---|
| `C` | Coil | FC01 read, FC05 / FC15 write | read and write |
| `D` | Discrete input | FC02 | read only |
| `H` | Holding register | FC03 read, FC06 / FC16 write | read and write |
| `A` | Input register | FC04 | read only |

`SC` and `SH` are older values that scripts still accept. They address the same coils and holding registers as `C` and `H`, but the module reads them from the device on every call instead of from the cache and writes them one register per request (FC05 / FC06). Use `C` and `H` in new scripts. This behaviour is taken from the engine code and was not verified on a device.

## MODBUSR

`MODBUSR` reads one value from a coil, a discrete input or one or more registers and converts it to the given data type.

```text
MODBUSR(registerType, register, dataType)
MODBUSR(registerType, register, String, numberOfRegisters)
```

| Name | Type | Description |
|---|---|---|
| `registerType` | `C`, `D`, `H`, `A` | See [Register types](https://taphome.com/en/docs/script/modbus/#register-types). |
| `register` | number | Register address 0 – 65535, decimal or hexadecimal (`0x14`). It is sent to the device unchanged and counts from 0. Manuals that write addresses as 4xxxx or 3xxxx count from 1 and put the register type in the first digit: 40021 is `H, 20`, 30001 is `A, 0`. |
| `dataType` | Modbus data type | Decides how many registers are read: 1, 2 or 4. |
| `numberOfRegisters` | number | Required for `String`, 0 – 123. One register holds 2 characters. |

**Returns** — a number for the 16- and 32-bit types, `Float` and `Double`; `bool` for `Bool`; `int64` or `uint64` for `Int64` and `UInt64`; a string for `String`, ending at the first zero byte.

**Remarks** — A multi-register value is read in one request, so all its registers come from the same moment.

**Example**

```taphome
MODBUSR(H, 20, Int16) / 100;   # signed register, divided by 100
# Result: the register as a signed number, divided by 100
MODBUSR(A, 0x0040, Uint32);   # 32-bit value from two input registers
MODBUSR(H, 14, String, 4);   # text from 4 registers
# Result: text of up to 8 characters
```

**Errors** — *Invalid register number: X*; *String data type must have specified length - number of registers to read*.

## MODBUSW

`MODBUSW` writes one value, or up to 101 values to consecutive registers, and returns `TRUE`.

```text
MODBUSW(registerType, register, dataType, value [, value2, …])
```

**Remarks**

- With several values the register address moves by the size of the data type — 1, 2 or 4 registers per value.
- A coil (`C`) accepts only the `Bool` data type; `D` and `A` cannot be written.
- How values are rounded and checked is described in [Writing values](https://taphome.com/en/docs/script/modbus-data-types/#writing-values).

**Example**

```taphome
MODBUSW(H, 20, Int16, Te * 100);
MODBUSW(H, 100, Uint16, 1, 2, 3);
# Result: TRUE — registers 100, 101 and 102 are written
MODBUSW(C, 5, Bool, St);
```

**Errors** — *WriteInt16: Cannot write Int16 to coils* (and the same for other types); *Invalid register number: X*.

## MODBUSWNE

`MODBUSWNE` ("write if not equal") writes one value like `MODBUSW`, but only when it differs from the value the register holds, which saves bus traffic and the EEPROM write cycles of the device.

```text
MODBUSWNE(registerType, register, dataType, value)
```

**Remarks**

- The value is compared with the module's register cache. With [prefetch](https://taphome.com/en/docs/script/modbus-scripts/#prefetch) on, that is the value read by the last prefetch (the register is added to the prefetch); a register not read yet is read first. With **No prefetch** the register is read from the device right before the comparison.
- It is never compared with the value written last time: a write does not change the cached value until the register is read again.
- A multi-register value is compared and written as a whole.

**Example — configuration in the initialize script**

```taphome
MODBUSWNE(H, 27, Uint16, 0);
```

## MODBUSRBLOCK

`MODBUSRBLOCK` reads a block of consecutive registers or coils in one Modbus transaction and returns them as a collection.

```text
MODBUSRBLOCK(registerType, register, count)
```

| Register type | Returns | Maximum `count` |
|---|---|---|
| `H`, `A` | `collection<uint16>` | 123 (FC03 / FC04) |
| `C`, `D` | `collection<bool>` | 2000 (FC01 / FC02) |

**Remarks** — With prefetch on, registers already in the cache are not read again; the missing ones are read in one request. Read typed values from the block with [UNPACKVALUE](https://taphome.com/en/docs/script/binary-data/#unpackvalue). One block read replaces many single reads.

**Example**

```taphome
collection<uint16> data := MODBUSRBLOCK(H, 100, 4);
UNPACKVALUE(data, 0, BigEndianFloat);
# Result: the float in registers 100 and 101
```

**Errors** — *MODBUSRBLOCK: count must be between 1 and 123 for 16-bit registers (H)*; *MODBUSRBLOCK: invalid register range X..Y*.

**Available** — TapHome Next 2026.1.39016+. The same holds for `MODBUSWBLOCK` and `MODBUSWBLOCKNE`.

## MODBUSWBLOCK

`MODBUSWBLOCK` writes a whole collection to consecutive holding registers or coils in one Modbus transaction and returns `TRUE`. A block longer than the [prefetch](https://taphome.com/en/docs/integration/modbus/#prefetch) group size of the module (100 by default) is split into several consecutive requests.

```text
MODBUSWBLOCK(registerType, register, collection)
```

| Register type | Collection | Maximum length |
|---|---|---|
| `H` | `collection<uint16>` | 123 (FC16) |
| `C` | `collection<bool>` | 1968 (FC15) |

**Example — set coils 0 and 3, clear coils 1, 2 and 4 to 7**

```taphome
collection<bool> coils := BOOLCOLLECTION(8);
SETAT(coils, 0, TRUE);
SETAT(coils, 3, TRUE);
MODBUSWBLOCK(C, 0, coils);
```

**Errors** — *MODBUSWBLOCK: cannot write to read-only registers (D)*; *MODBUSWBLOCK: register type C expects Collection&lt;Bool&gt;, got Collection&lt;UInt16&gt;*.

## MODBUSWBLOCKNE

`MODBUSWBLOCKNE` writes a collection like `MODBUSWBLOCK`, but only when at least one value differs from the current contents of the registers; a changed block is written the same way, split by the same group size.

```text
MODBUSWBLOCKNE(registerType, register, collection)
```

**Remarks** — The current contents are read the same way as for [MODBUSWNE](https://taphome.com/en/docs/script/modbus/#modbuswne).

**Example — change one register of a block with minimal bus traffic**

```taphome
collection<uint16> c := MODBUSRBLOCK(H, 100, 4);
PACKVALUE(c, 1, Uint16, 9);
MODBUSWBLOCKNE(H, 100, c);
```

**See also** — [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/), [Binary data](https://taphome.com/en/docs/script/binary-data/), [Bit operations](https://taphome.com/en/docs/script/bit-operations/).