title: "Power Limiting with PWM Groups"
description: "Limit the total power of PWM outputs on TapHome 12 DO and 16 DO modules: groups, total resources, output power and priority."
url: "https://taphome.com/en/docs/configuration/power-limiting-pwm-groups/"
language: en
lastmod: 2026-11-01
generator: hugo
ai:
  topics: ["power-limiting","pwm-groups","electric-heating","taphome-bus-modules"]
  questions: ["How do I limit the total power of electric heating on a 12 DO module?","Is power limiting available on the 16 DO module as on the 12 DO?","What does Total resources mean in a PWM group?","Why does a heating output get less power than requested?"]
---

# Power Limiting with PWM Groups

PWM groups on TapHome Bus output modules (12 DO, 16 DO and others) keep the total power of electric heating outputs within a set limit by staggering their PWM cycles.

Last updated: 2026-11-01

Power limiting keeps the total power of several electric heating circuits within a limit, for example the capacity of the main circuit breaker. The outputs share one group: the module staggers their pulse-width modulation (PWM) so that the outputs switched on at the same time never exceed the group's limit. It applies only to outputs set to **Pulse-width modulation** and added to a group; an ordinary switched digital output is never limited.

## Which modules support it

PWM groups are available on TapHome Bus modules with digital or universal outputs that support PWM: the 16 DO, 4 LED OC, 6 LED OC modules and the Core from their first firmware, and other modules, including the 12 DO, from firmware 27. A module has as many groups as outputs minus two, at least 1 and at most 7, so both the 12 DO and the 16 DO have 7 groups.

## Setting up a group

1. **Settings** → **Hardware** → TapHome Bus → tap the module.
2. Set each heating output to **Pulse-width modulation**.
3. In the **Power limiting** section, tap **Add new group** and then the new group.
4. Save the module page; the group is saved with it.

The group page shows its labels in English in every language of the app:

- **Total resources** — the limit of the group, a number without a unit. Use any unit (W, A), but the same one for the outputs.
- **Pulse width (interval)** — the common PWM period of the group, 600 to 7200 seconds for digital outputs, 0.5 to 7200 seconds for universal outputs.
- **Outputs** → **Add new output** — offers the module's outputs set to PWM that are not in another group. Tap an added output to enter its power; a value larger than Total resources is rejected with the message "Resource can't be more than total resources!".
- The order of the outputs is their priority: the top output gets power first. Drag the rows to change it.

## How the module limits the power

The module runs the limit itself, without the Core. All outputs of a group start their PWM cycle together. During the cycle, an output is on while it still has on-time left and the outputs already on, plus its own power, stay within Total resources; the outputs with higher priority are served first. An output that does not fit waits, and on-time it has not used by the end of the cycle is lost. A heating circuit can therefore get less power than its thermostat requests when the whole group needs more than the limit; the app does not report it.

**See also** — [Heating and Cooling](https://taphome.com/en/docs/functional-areas/heating-cooling/), [Energy Manager](https://taphome.com/en/docs/energy-manager/).