  questions: ["How to integrate Xvent Xcont Central with TapHome?","What does the Xvent Xcont Central TapHome template control?","How to connect Xvent Xcont Central via RS-485 to TapHome?","How to configure the Modbus slave address on the Xcont Central?","What fan speed levels are available in the Xvent Xcont Central template?","How to set CO2 and humidity thresholds for automatic ventilation via TapHome?"]
---

# Xvent Xcont Central

Communication: Modbus RTU

- [Xvent Official Website](https://www.xvent.cz)

The Xvent Xcont Central is a Modbus RTU controller for Xvent Xhouse (XH) and Xflat (XF) central heat recovery units. It connects to TapHome via RS-485 using an RJ45 connector through the XCONT-HUB. The template provides fan speed control, room temperature and humidity monitoring, frost protection temperature, airflow measurement, CO2 and humidity activation thresholds, and operating modes including boost and summer mode.

Firmware version 100 or higher is required for Modbus communication.

## Hardware connection

### RS-485 wiring via RJ45

The Xcont Central uses an **RJ45 connector** for RS-485 communication through the XCONT-HUB. The bus operates in half-duplex mode.

![Xvent Xcont Central RJ45 connector pinout for RS-485 connection to XCONT-HUB](https://taphome.com/images/compatibility/xvent-xcont-central/rj45-wiring-p005_hu_613d95aff9f294d.jpg)

**RJ45 pin assignment:**

| Pin | Function |
|-----|----------|
| 1 | Unconnected |
| 2 | Unconnected |
| 3 | RS-485 bus data wire A |
| 4 | RS-485 bus data wire A |
| 5 | RS-485 bus data wire B |
| 6 | RS-485 bus data wire B |
| 7 | Unconnected |
| 8 | Unconnected |

Connect wires A (pins 3, 4) to TapHome RS-485 A+/D+ and wires B (pins 5, 6) to TapHome RS-485 B-/D-. Pins 1, 2, 7, and 8 must be left unconnected.

> [!WARNING]
> The bus operates in half-duplex mode. The unit requires a minimum pause of 4 ms between Modbus frames for correct frame detection. The typical response time is approximately 4 ms.

### Technical specifications

- **Protocol:** Modbus RTU Slave, RS-485
- **Baud rate:** 19200 (also supports 4800 and 9600)
- **Parity:** Even (also supports no parity)
- **Data bits:** 8
- **Stop bit:** 1
- **Slave address range:** 1–247

## Configuration

### Enabling Modbus communication

The Modbus slave address and communication parameters are configured via the DCFG retention register at address 0x9C50. The default settings are:

- **Baud rate:** 19200 (bits 5–6 = 3)
- **Parity:** Even (bit 7 = 0)
- **Slave address:** Configured in bits 8–15 (range 1–247)

To change the Modbus settings, write to register H:40016 using Modbus function 0x10:

| Bits | Function | Values |
|------|----------|--------|
| 5–6 | Baud rate | 0=Disabled, 1=4800, 2=9600, 3=19200 |
| 7 | Parity | 0=Even, 1=No parity |
| 8–15 | Slave address | 1–247 |

> [!WARNING]
> Changes to baud rate, parity, and slave address take effect immediately. The unit will stop communicating until the Modbus master is reconfigured to match the new parameters.

### TapHome configuration

When adding the device in TapHome, configure the Modbus RTU connection with these settings:

- **Slave ID:** Match the address configured in the unit (default depends on unit)
- **Baud rate:** 19200
- **Parity:** Even
- **Stop bits:** 1
- **Data bits:** 8

## Device capabilities

### Power and operating modes

- **Power** (H:40000 bit 0) — main power ON/OFF switch for the recovery unit
- **Fan Mode** (H:40000 bit 1) — switches between Automatic (AQS-driven based on CO2/humidity sensors) and Manual fan control
- **Summer Mode** (H:40000 bit 2) — activates summer mode bypass with configurable duration (default 8 hours)
- **Boost Mode** (H:40000 bit 4) — activates boost mode with higher fan speed for a configurable duration (default 60 seconds)
- **Touch Button Lock** (H:40000 bit 5) — child lock for the front panel touch buttons

All these controls share a single retention register (H:40000) and use individual bit manipulation — toggling one function does not affect the others.

### Fan speed control

- **Fan Speed Level** (H:40000 bits 6–9) — selects from 8 fan speed levels (0–7), where each level corresponds to a specific voltage output that varies by unit model (XF1-015, XH1-030, XF1-020, XH2-030). The multi-value switch also shows a Boost option (level 8), but it is recommended to use the Boost Mode switch instead

- **Fan Status** (A:30001 bits 8–11) — read-only multi-value indicator showing the current fan operating state: Unit OFF, OFF - cooling process, Fan 1 Error, Fan 2 Error, Normal Mode, Antifreeze Mode, Inactive fans in normal mode, Inactive fans in antifreeze mode, Summer Mode, or Boost Mode. A service attribute shows the previous fan status before the current transition

### Temperature and humidity monitoring

- **Room Temperature & Humidity** (A:30016 / A:30014) — reads room temperature with 0.1°C resolution and relative humidity with 0.1% RH resolution. A sensor status service attribute reports whether the sensor is OK, disconnected, or shorted
- **Frost Protection Temperature** (A:30015) — reads the exhaust-side frost protection temperature sensor with 0.1°C resolution. A sensor status service attribute monitors the sensor connection state
- **Desired Temperature** (A:30012) — reads the currently configured room temperature setpoint with 0.1°C resolution. This value is read-only in the template — the temperature level is set via the front panel register

### Fan voltage monitoring

- **Fan 1 Voltage** (A:30018) — reads the actual output voltage of fan 1 with 0.01 V resolution. Service attributes report the tacho input status and motor start confirmation
- **Fan 2 Voltage** (A:30020) — reads the actual output voltage of fan 2 with 0.01 V resolution. Same service attributes as Fan 1

### Air quality thresholds

- **CO2 Activation Threshold** (H:40001) — configurable CO2 concentration level (600–1000 ppm, default 800 ppm) at which the fans automatically activate when in AQS automatic mode. Adjustable via a "Set Value" service action
- **RH Activation Threshold** (H:40002) — configurable relative humidity level (50–75%, default 65%) at which the fans automatically activate when in AQS automatic mode. Adjustable via a "Set Value" service action

### Airflow measurement

- **Airflow** (A:30015) — reads the current airflow rate from the flow sensor with 0.1 m³/h resolution

### Service diagnostics

The module exposes three service attributes for monitoring:

- **Firmware Version** (A:30000) — current firmware version of the unit
- **UI State** (A:30001 bits 0–3) — current user interface state with 14 possible values including Unit off, Fan errors, Sensor errors, Lock states, Normal operation, Service menu, and User menu
- **Attribute** (H:40000 bits 10–15) — temperature level setting for E-type units

The module ReadScript also monitors CO2 and RH sensor errors from status register A:30003, reporting them as errors in TapHome.

### Additional capabilities

The Xcont Central also exposes registers for CO2 sensor readings (A:30013), AQS air quality state and required fan speed, preheat and reheat status monitoring, filter elapsed time tracking (A:30028), relay status for preheat and reheat, room temperature correction offset, and various timer registers. Configuration options include filter lifetime setting, boost mode fan speed and duration, summer mode duration, and a permanent minimum fan speed flag. These can be added in a future template update.

> [!TIP]
> The CO2 sensor value register (A:30013) and filter elapsed time (A:30028) are not included in the current template. To monitor CO2 levels directly, the CO2 sensor can be added as a custom Modbus device in TapHome using input register A:30013 (function 0x04, address 0x753D).

## Troubleshooting

### No Modbus communication

1. **Check the RJ45 cable connection** — ensure the cable is properly seated in both the XCONT-HUB and the RS-485 adapter
2. **Verify pin wiring** — pins 3/4 (wire A) and 5/6 (wire B) must be correctly mapped to TapHome RS-485 A+/B-
3. **Confirm communication parameters** — TapHome must be set to 19200 baud, even parity, 1 stop bit, 8 data bits (matching the unit defaults)
4. **Check the slave address** — verify the configured address matches what is set in TapHome
5. **Observe frame timing** — ensure at least 4 ms pause between Modbus frames

### Sensor errors reported in TapHome

1. **CO2 sensor error** — check the physical connection of the CO2 sensor to the unit. The module ReadScript reads bit 0 of register A:30003
2. **RH sensor error** — check the physical connection of the humidity sensor. The module ReadScript reads bit 1 of register A:30003
3. **Room sensor disconnected/shorted** — check the service attribute on the Room Temperature & Humidity device. Status values: 0=OK, 1=Disconnected, 2=Shorted

### Fan errors

1. Check the Fan Status device — values 2 and 3 indicate Fan 1 or Fan 2 error respectively
2. Verify the tacho input status service attribute on the Fan Voltage devices (OK/NG)
3. Check the motor start flag service attribute — NG indicates the motor failed to start

### Register address format

The Xcont Central uses high Modbus addresses. Input registers start at 0x7530 (decimal 30000) and retention registers at 0x9C40 (decimal 40000). When configuring custom devices in TapHome, use the decimal register addresses (e.g., 30016 for room temperature, 40000 for front panel control).

## Available devices

Xvent Xcont Central Module

Service Attributes

|                  |
|------------------|
| Firmware Version |
| UI State         |
| Attribute        |

Fan 1 Voltage Variable Read-only

Actual output voltage of supply fan — indicates current fan speed

Register: A:30018 Int16 Unit: V numeric

Service Attributes

|                    |
|--------------------|
| Tacho Input Status |
| Motor Start Flag   |

Fan 2 Voltage Variable Read-only

Actual output voltage of exhaust fan — indicates current fan speed

Register: A:30020 Int16 Unit: V numeric

Service Attributes

|                    |
|--------------------|
| Tacho Input Status |
| Motor Start Flag   |

Boost Mode Switch

Activates temporary high-speed ventilation for rapid air exchange

Register: H:40000 UInt16 bit

Values / States: Aktivní · Neaktivní

Frost Protection Temperature Temperature Sensor Read-only

Exhaust-side temperature sensor for frost protection — triggers fan reduction when temperature drops

Register: A:30015 Int16 Unit: °C numeric

Service Attributes

|               |
|---------------|
| Sensor Status |

CO2 Activation Threshold Variable

CO2 concentration level (600–1000 ppm) at which fans activate automatically in AQS mode

Register: H:40001 UInt16 Unit: ppm numeric

Service Actions

|           |
|-----------|
| Set Value |

RH Activation Threshold Variable

Relative humidity level (50–75%) at which fans activate automatically in AQS mode

Register: H:40002 UInt16 Unit: % RH numeric

Service Actions

|           |
|-----------|
| Set Value |

Summer Mode Switch

Activates summer bypass mode — runs for a configurable duration (default 8 hours)

Register: H:40000 UInt16 bit

Values / States: Aktivní · Neaktivní

Power Switch

Register: H:40000 UInt16 bit

Values / States: ON · OFF

Desired Temperature Variable Read-only

Currently configured room temperature setpoint — read-only, set via front panel

Register: A:30012 Int16 Unit: °C numeric

Airflow Variable Read-only

Current airflow rate from the flow sensor in m³/h

Register: A:30015 UInt16 Unit: m³/h numeric

Fan Mode Switch

Automatic (AQS-driven based on CO2/humidity) or Manual fan control

Register: H:40000 UInt16 bit

Values / States: Automatický · Manuální

Fan Status Multi-value Switch Read-only

Current fan operating state — Unit OFF, Active normal, Antifreeze, Summer mode, Boost mode, or error states

Register: A:30001 UInt16 multi-value

Values / States: Vypnutá jednotka · OFF - proces dochlazování · Chyba ventilátoru 1 · Chyba ventilátoru 2 · Běžný režim · Antifreeze Režim · Neaktivní ventilátory v běžném režimu · Neaktivní ventilátory v antifreeze režimu · Letní režim · Boost režim

Fan Speed Level Multi-value Switch

Fan speed level 0–7 — voltage per level varies by unit model

Register: H:40000 UInt16 multi-value

Values / States: Boost

Room Temperature & Humidity Temperature Sensor Read-only

Room temperature and relative humidity from the combined sensor

Register: A:30016 Int16 Unit: °C numeric

Service Attributes

|               |
|---------------|
| Sensor Status |

Touch Button Lock Switch

Child lock for front panel touch buttons — prevents accidental changes

Register: H:40000 UInt16 bit

Values / States: Zamčeno · Odomčeno

**Connection:** Modbus RTU • 19200 baud• 8E1 • Slave ID: $\[SlaveId]

Possible improvements (14)

- A:30002 Status Register 2 (Preheat/Reheat) — Preheat status (bit 0–3), previous preheat (bit 4–7), last preheat with active fans (bit 8–11), fan modification stage (bit 12–15)
- A:30003 Status Register 3 (Reheat/Filter) — Reheat status, filter status, various change flags. Module readscript checks bits 0–1 for CO2/RH sensor errors only
- A:30004 AQS State — Air quality sensor status: CO2/RH sensor errors, AQS ventilation request, active CO2/RH levels, required fan speed. Partially covered by module readscript error checks
- A:30005 AQS Required Flow — Required flow value according to AQS values (0.1 m3/h)
- A:30006 Required Fan Flow — Required fan flow combining user and AQS settings (0.1 m3/h)
- A:30011 Required Fan Speed — Required fan voltage combining user and AQS settings (0.01 V)
- A:30013 CO2 Sensor Value — Current CO2 sensor reading (1 ppm). Key air quality measurement — surprisingly missing from template
- A:30028 Filter Elapsed Time — Filter active time (1 h). Useful for filter replacement tracking
- A:30033 Relay Status — Relay status: bit 0 = preheat relay, bit 1 = reheat relay
- H:40016 DCFG Configuration — System configuration: auto shutdown flag, permanent min fan speed, Modbus baud rate/parity/address settings. WARNING: writing baud/parity/address takes effect immediately
- H:40017 Room Temperature Correction — Room temperature sensor offset correction (0.1 degC, range -10.0 to +10.0°C)
- H:40018 Summer Mode Duration — Duration of summer mode (1 s, range 3600–32400, default 28800 = 8 h)
- H:40021 Boost Mode Duration — Duration of boost mode (1 s, range 30–3600, default 60)
- H:40023 Filter Lifetime — Filter lifetime setting (1 h, range 2200–8800, default 4400)

## Sources

- User Manual XCONT-CENTRAL-Modbus Communication (V2)
  
  [www.xvent.cz](https://www.xvent.cz/images/Produkty/Rekupera%C4%8Dn%C3%AD%20jednotky/Xhouse/D-502-275-V002-GBR-MN-CENTRAL-MODBUS.pdf) 2026-03-21
  
  [PDF](https://taphome.com/compatibility/devices/xvent-xcont-central/manufacturer/xcont-central-modbus-manual-v2.pdf)

## Related Documentation

- [Modbus Integration](https://taphome.com/en/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/en/docs/integration/modbus/)
- [Simple configuration using templates](https://taphome.com/en/docs/integration/modbus/templates/)
- [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/)
- [Modbus functions](https://taphome.com/en/docs/script/modbus/)
- [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/)