  questions: ["How to integrate Victron Energy GX with TapHome?","What does the Victron GX Line Inverter TapHome template monitor and control?","How to connect Victron Cerbo GX via Modbus TCP to TapHome?","How to set ESS power setpoints on Victron via TapHome?","What is Slave ID 227 on Victron GX?","Why does the Victron GX template show incorrect power readings?"]
---

# Victron Energy GX Line Inverter

Communication: Modbus TCP

- [Victron Energy Official Website](https://www.victronenergy.com/)

> Network address
> 
> TapHome reaches this device at the address entered on import. Give the device a fixed address — an IP reservation in the router, or its mDNS name if it supports one — otherwise the integration stops working when the router changes the address.
> 
> [Network Preparation](https://taphome.com/en/docs/setup/network-preparation/)

## Integration guide

The Victron GX device family (Cerbo GX, Cerbo GX MK2, Venus GX, CCGX) are communication and monitoring platforms that provide Modbus TCP access to connected Victron VE.Bus inverter/chargers (MultiPlus, Quattro). The GX device itself is not an inverter — it acts as a Modbus TCP gateway to the VE.Bus system.

TapHome connects to the GX device over Ethernet via Modbus TCP. The template exposes battery SOC monitoring, 3-phase AC input and output metering, ESS (Energy Storage System) power setpoint control, inverter mode switching, PV inverter management and comprehensive alarm monitoring.

## Network connection

The GX device connects to the local network via its Ethernet port. TapHome Core and the GX device must be on the same subnet.

- **Protocol:** Modbus TCP
- **Port:** 502
- **Default Slave ID:** 227 (Cerbo GX VE.Bus port)
- **Function codes:** 3 (ReadHoldingRegisters), 6 (WriteSingleRegister), 16 (WriteMultipleRegisters)

> [!NOTE]
> The default slave ID 227 applies to the Cerbo GX VE.Bus port. Other GX devices use different IDs: 246 for CCGX, 242 for Venus GX, 228 for EasySolar-II GX. Unit IDs have been dynamically assigned since Venus OS 2.60 — verify the actual ID on the GX device via Settings → Services → Modbus/TCP → Available services.

## Configuration

### Enabling Modbus TCP

Modbus TCP is **disabled by default** on all GX devices. To enable it:

1. Navigate to **Settings → Services** on the GX device
2. Enable **Modbus-TCP**

Once enabled, the GX device listens on TCP port 502.

### TapHome template import

When importing the template in TapHome, provide:

- **IP Address** — the GX device's IP on the local network
- **Slave ID** — VE.Bus unit ID (default: 227 for Cerbo GX)

> [!TIP]
> Assign a static IP address to the GX device in the router's DHCP settings, or configure a static IP directly on the GX device via Settings → Ethernet, to prevent the address from changing after a reboot.

## Device capabilities

The template exposes 10 devices organized into battery monitoring, AC metering, mode control and protection switches.

### Battery monitoring

- **Battery** — reads the VE.Bus state of charge (SOC) from register H:30 as a dimmer level. Service attributes show battery voltage (H:26), battery current with direction indicator (H:27), battery temperature (H:61), VE.Bus charge state (Off, Low Power, Fault, Bulk, Absorption, Float, Storage, Equalize, Passthru, Inverting, Power Assist, Power Supply) and BMS charge/discharge permissions (H:57–59). The readscript monitors H:32 for VE.Bus error codes (1–26) and H:60 for BMS errors. A VE.Bus Reset action (H:62) is available for system recovery.

### AC input metering

Three electricity meter devices monitor AC input power per phase:

- **Input Power L1** — AC input power phase 1 from H:12, with service attributes for voltage (H:3), current (H:6), frequency (H:9) and ESS power setpoint (H:37). The ESS setpoint is writable via a service action.
- **Input Power L2** — AC input power phase 2 from H:13, with corresponding L2 service attributes and ESS setpoint L2 (H:40).
- **Input Power L3** — AC input power phase 3 from H:14, with corresponding L3 service attributes and ESS setpoint L3 (H:41).

Each input power device includes an ESS power setpoint service action for its respective phase, allowing TapHome to control the ESS charge/discharge behaviour per phase.

### AC output metering

Three electricity meter devices monitor AC output power per phase:

- **Output Power L1** — AC output from H:18, with service attributes for voltage (H:15), current (H:18) and frequency (H:21). The readscript monitors per-phase alarms for temperature (H:44), low battery (H:45), overload (H:46) and ripple (H:47).
- **Output Power L2** — AC output from H:24, with L2 voltage (H:16), current (H:19) and frequency (H:21). Monitors L2 alarms (H:48–51).
- **Output Power L3** — AC output from H:25, with L3 voltage (H:17), current (H:20) and frequency (H:21). Monitors L3 alarms (H:52–55).

### Current limit control

- **Active Input Current Limit** — reads and writes the active input current limit (H:22) in amps. The "Set Limit" service action accepts a float value (0–100 A).

### Protection switches

- **Feed DC Overvoltage into Grid** — toggle switch (H:65) to control whether excess power from DC-coupled PV (which raises the DC voltage) is fed into the grid. Service attributes show maximum overvoltage feed-in power per phase (H:66–68) and AC input ignored status (H:69–70). A service action allows setting the maximum feed-in power per phase.
- **PV Inverter** — toggle switch (H:56) to enable or disable PV inverter frequency shifting on AC-out. When enabled (switch OFF), the AC-out PV inverter operates normally; when disabled (switch ON), frequency shifting limits the PV output.

### Module-level service attributes and actions

The module itself exposes several service attributes accessible from the gateway device in TapHome:

| Attribute | Register | Description |
|-----------|----------|-------------|
| Phase Count | H:28 | Number of AC phases in the VE.Bus system |
| Switch Position | H:33 | Inverter mode — Charger Only, Inverter Only, On, Off |
| Active Input | H:29 | Active AC input source — AC Input 1, AC Input 2, Disconnected |
| ESS Disable Charge | H:38 | Charge flag — Charge enabled / Charge disabled |
| ESS Disable Feed-in | H:39 | Feed-in flag — Feed in enabled / Feed in disabled |
| ESS Power Setpoint L1–L3 | H:37, H:40, H:41 | Per-phase ESS power setpoint in watts |

Module-level service actions allow switching the inverter mode (Charger Only, Inverter Only, On, Off), toggling the ESS charge flag and toggling the ESS feed-in flag.

### System alarm monitoring

The module readscript monitors 7 system-level alarms:

| Register | Alarm | Levels |
|----------|-------|--------|
| H:34 | Temperature alarm | 0=Ok, 1=Warning, 2=Alarm |
| H:35 | Low battery alarm | 0=Ok, 1=Warning, 2=Alarm |
| H:36 | Overload alarm | 0=Ok, 1=Warning, 2=Alarm |
| H:42 | Temperature sensor alarm | 0=Ok, 1=Warning, 2=Alarm |
| H:43 | Voltage sensor alarm | 0=Ok, 1=Warning, 2=Alarm |
| H:63 | Phase rotation warning | 0=Ok, 1=Warning |
| H:64 | Grid lost alarm | 0=Ok, 1=Alarm |

### Additional capabilities

The VE.Bus register set (H:3–H:231) provides additional registers beyond what the template currently implements. These include energy counters for AC-in/out/battery flows (H:74–92, volatile — reset on reboot), charge state enumeration (H:95), 32-bit ESS power setpoints for larger systems (H:96–100), advanced ESS settings like Prefer Renewable Energy (H:102), PowerAssist configuration (H:106–108), UPS function control (H:109) and microgrid/droop mode registers (H:200–231). These can be added to the TapHome template in a future update.

## Troubleshooting

### No Modbus communication

1. Verify that Modbus TCP is enabled on the GX device (Settings → Services → Modbus-TCP)
2. Confirm the GX device's IP address — check the router's DHCP lease table or the GX device's network settings
3. Ensure TapHome Core and the GX device are on the same subnet
4. Check that no firewall is blocking TCP port 502
5. Verify the correct unit ID — the default 227 applies to Cerbo GX; other GX models use different IDs

### Incorrect power readings

The template uses a `/100` scale factor for power registers (H:12–14, H:23–25), while Victron documentation specifies a scale factor of 0.1 (meaning raw value × 10 = actual watts). This may result in power readings that are lower than expected. If power values appear incorrect, this is a known template scale factor difference — the relative measurements remain proportionally correct.

### VE.Bus error codes

The Battery device readscript checks register H:32 for VE.Bus error codes. Common errors include:

| Code | Description |
|------|-------------|
| 1 | Device switched off because another phase switched off |
| 5 | Overvoltage on AC-out |
| 10 | System time synchronisation problem |
| 14 | Device cannot transmit data |
| 16 | Dongle missing |
| 17 | A device assumed master status because the original master failed |
| 25 | Firmware incompatibility between connected devices |
| 26 | Internal error |

If persistent VE.Bus errors appear, the VE.Bus Reset action (available on the Battery device) can be used to attempt recovery.

### Unit ID changed after Venus OS update

Since Venus OS 2.60, unit IDs are dynamically assigned. After a firmware update, the unit ID may change. Navigate to Settings → Services → Modbus/TCP → Available services on the GX device to verify the current VE.Bus unit ID, then update the TapHome template's slave ID accordingly.

## Available devices 10

These devices appear in TapHome after import.

Victron GX Line Inverter Module

Service Attributes

|                               |                                                                |
|-------------------------------|----------------------------------------------------------------|
| Phase Count                   |                                                                |
| Switch Position               | Inverter operating mode — Charger Only, Inverter Only, On, Off |
| Active Input                  | Active AC input source — AC Input 1, AC Input 2, Disconnected  |
| ESS Disable Charge flag phase | ESS charge permission — Charge enabled or Charge disabled      |
| ESS Disable Feed-in           | ESS feed-in permission — Feed in enabled or Feed in disabled   |
| ESS power setpoint phase 1    |                                                                |
| ESS power setpoint phase 2    |                                                                |
| ESS power setpoint phase 3    |                                                                |

Service Actions

|                   |                                                          |
|-------------------|----------------------------------------------------------|
| Switch Position   | Set inverter mode — Charger Only, Inverter Only, On, Off |
| Charge flag phase | Enable or disable ESS battery charging                   |
| ESS Feed-in Flag  | Enable or disable ESS grid feed-in                       |

Read (module)

```taphome
var temp := MODBUSR(H, 34, Uint16);
IF(temp = 1, ADDWARNING("Temperature alarm"));
IF(temp = 2, ADDERROR("Temperature alarm"));
var low := MODBUSR(H, 35, Uint16);
IF(low = 1, ADDWARNING("Low Battery alarm"));
IF(low = 2, ADDERROR("Low Battery alarm"));
var over := MODBUSR(H, 36, Uint16);
IF(over = 1, ADDWARNING("Overload alarm"));
IF(over = 2, ADDERROR("Overload alarm"));
var seb := MODBUSR(H, 42, Uint16);
IF(seb = 1, ADDWARNING("Temperature sensor alarm"));
IF(seb = 2, ADDERROR("Temperature sensor alarm"));
var vol := MODBUSR(H, 43, Uint16);
IF(vol = 1, ADDWARNING("Voltage sensor alarm"));
IF(vol = 2, ADDERROR("Voltage sensor alarm"));
IF(MODBUSR(H, 63, Uint16) = 1, ADDWARNING("Phase Rotation Warning"));
IF(MODBUSR(H, 64, Uint16) = 1, ADDERROR("Grid Lost Alarm"));
```

Service Attributes

Phase Count

```taphome
MODBUSR(H, 28, Uint16);
```

Switch Position

```taphome
var reg := MODBUSR(H, 33, Uint16);
Switch(reg, 1, "Charger Only", 2, "Inverter Only", 3 ,"On", 4, "Off", "Unknown");
```

Active Input

```taphome
var reg := MODBUSR(H, 29, Uint16);
switch(reg, 0, "AC Input 1", 1, "AC Input 2", 240, "Disconnected", "Unknown");
```

ESS Disable Charge flag phase

```taphome
IF(MODBUSR(H, 38, Uint16) = 1, "Charge disabled", "Charge enabled")
```

ESS Disable Charge feedback phase

```taphome
IF(MODBUSR(H, 39, Uint16) = 1, "Feed disabled");
IF(MODBUSR(H, 39, Uint16) = 0, "Feed in enabled", "Not set");
```

ESS power setpoint phase 1

```taphome
MODBUSR(H, 37, Uint16) + " W";
```

ESS power setpoint phase 2

```taphome
MODBUSR(H, 40, Uint16) + " W";
```

ESS power setpoint phase 3

```taphome
MODBUSR(H, 41, Uint16) + " W";
```

Service Actions

Switch Position

Parameters: Switch Position

```taphome
MODBUSWNE(H, 33, uint16, pos);
```

Charge flag phase

Parameters: Charge flag phase

```taphome
MODBUSWNE(H, 38, Uint16, chfp);
```

Feedback flag phase

Parameters: Feedback flag phase

```taphome
MODBUSWNE(H, 39, Uint16, ffp);
```

Active Input Current Limit Variable Read and write

AC input current limit in amps — adjustable via Set Limit action (0–100 A)

Register: H:22 Int16 Unit: A numeric

Service Actions

|           |
|-----------|
| Set Limit |

Read

```taphome
MODBUSR(H, 22, int16)/10
```

Service Actions

Set Limit

Parameters: Active Input Current Limit \[A] (0–100 aic)

```taphome
MODBUSWNE(H, 22, Int16, aic*10)
```

Battery Dimmer Read and write

Battery state of charge with voltage, current, temperature, VE.Bus charge state and BMS permissions

Register: H:30 UInt16 Unit: % numeric

Service Attributes

|                                            |                                                                                                                                          |
|--------------------------------------------|------------------------------------------------------------------------------------------------------------------------------------------|
| Battery Voltage                            |                                                                                                                                          |
| Battery Current                            |                                                                                                                                          |
| Flow                                       | Current direction — DC system to Multi, Multi to DC system, or idle                                                                      |
| Battery Temperature                        |                                                                                                                                          |
| State                                      | VE.Bus charge state — Off, Low Power, Fault, Bulk, Absorption, Float, Storage, Equalize, Passthru, Inverting, Power Assist, Power Supply |
| VE.Bus BMS allows battery to be charged    |                                                                                                                                          |
| VE.Bus BMS allows battery to be discharged |                                                                                                                                          |
| VE.Bus BMS is expected                     |                                                                                                                                          |

Service Actions

|              |
|--------------|
| VE.Bus Reset |

Read (module)

```taphome
var reg := MODBUSR(H, 32, Uint16);
SWITCH(reg, 1, ADDERROR("VE.Bus Error 1: Device is switched off because one of the other phases in the system has switched of"), 2, "VE.Bus Error 2: New and old types MK2 are mixed in the system", 3, "VE.Bus Error 3: Not all- or more than- the expected devices were found in the system", 4, "VE.Bus Error 4: No other device whatsoever detected", 5, "VE.Bus Error 5: Overvoltage on AC-out", 6, "VE.Bus Error 6: Error in DDC Program", 7, "VE.Bus BMS connected- which requires an Assistant- but no assistant found", 10, "VE.Bus Error 10: System time synchronisation problem occurred", 14, "VE.Bus Error 14: Device cannot transmit data", 16, "VE.Bus Error 16: Dongle missing", 17, "VE.Bus Error 17: One of the devices assumed master status because the original master failed",18, "VE.Bus Error 18: AC Overvoltage on the output of a slave has occurred while already switched off", 22, "VE.Bus Error 22: This device cannot function as slave", 24, "VE.Bus Error 24: Switch-over system protection initiated", 25, "VE.Bus Error 25: Firmware incompatibility. The firmware of one of the connected device is not sufficiently up to date to operate in conjunction with this device", 26, "VE.Bus Error 26: Internal error", "No error");
IF(MODBUSR(H, 60, Uint16) = 1, ADDERROR("VE.Bus BMS error"));
```

Read level

```taphome
MODBUSR(H, 30, UInt16) / 1000
```

Service Attributes

Battery Voltage

```taphome
MODBUSR(H, 26, Uint16)/100 + " V";
```

Battery Current

```taphome
ABS(MODBUSR(H, 27, int16)/10) + " A";
```

Flow

```taphome
var reg := MODBUSR(H, 27, int16);
IF(reg = 0, "-");
IF(reg < 0, "DC system to Multi", "Multi to DC system");
```

Battery Temperature

```taphome
var tempt := MODBUSR(H, 61, Int16)/10; 
IF(tempt = 0, "Unknown", tempt + " °C")
```

State

```taphome
var reg := MODBUSR(H, 31, Uint16);
SWITCH(reg, 0, "Off",
 1, "Low Power",
 2, "Fault",
 3, "Bulk",
 4, "Absorbtion",
 5, "Float", 
 6, "Storage", 
 7, "Equalize", 
 8, "Passtru", 
 9, "Inverting", 
 10, "Power Assist", 
 11, "Power Supply", 
 252, "Bulk protection",
 "Unknown" );
```

VE.Bus BMS allows battery to be charged

```taphome
SWITCH(MODBUSR(H, 57, Uint16), 0, "No", 1, "Yes", "Unknown");
```

VE.Bus BMS allows battery to be discharged

```taphome
SWITCH(MODBUSR(H, 58, Uint16), 0, "No", 1, "Yes", "Unknown");
```

VE.Bus BMS is expected

```taphome
SWITCH(MODBUSR(H, 59, Uint16), 0, "No", 1, "Yes", "Unknown");
```

Service Actions

VE.Bus Reset

Parameters: Reset

```taphome
MODBUSW(H, 62, Uint16, res);
```

Feed DC Overvoltage into Grid Switch Read and write

Toggle DC overvoltage grid feed-in with per-phase maximum power limits

Register: H:65 UInt16 numeric

Values / States: Feed in overvoltage · Don't feed in overvoltage

Service Actions

|                                   |                                                                 |
|-----------------------------------|-----------------------------------------------------------------|
| Maximum overvoltage feed-in power | Set maximum DC overvoltage feed-in power per phase (L1, L2, L3) |

Read switch state

```taphome
MODBUSR(H, 65, Uint16);
```

Write switch state

```taphome
MODBUSW(H, 65, Uint16, St);
```

Service Attributes

Maximum overvoltage feed-in power L1

```taphome
MODBUSR(H, 66, Uint16)/ 0.01 + " W";
```

Maximum overvoltage feed-in power L2

```taphome
MODBUSR(H, 67, Uint16)/ 0.01 + " W";
```

Maximum overvoltage feed-in power L3

```taphome
MODBUSR(H, 68, Uint16)/ 0.01 + " W";
```

AC input 1

```taphome
SWITCH(MODBUSR(H, 69, Uint16), 0, "not ignored", 1, "ignored", "Unknown");
```

AC input 2

```taphome
SWITCH(MODBUSR(H, 70, Uint16), 0, "not ignored", 1, "ignored", "Unknown");
```

Service Actions

Maximum overvoltage feed-in power

Parameters: L1\[W] (0–6.5535e+06 L1), L2\[W] (0–6.5535e+06 L2), L3\[W] (0–65535 L3)

```taphome
MODBUSWNE(H, 66, Uint16, L1)/100;
MODBUSWNE(H, 67, Uint16, L2)/100;
MODBUSWNE(H, 68, Uint16, L2)/100;
```

Input Power L1 Electricity Meter Read and write

AC input power phase 1 with voltage, current, frequency and ESS power setpoint

Register: H:12 Int16 Unit: W numeric

Service Attributes

|                            |
|----------------------------|
| Input Voltage L1           |
| Input Current L1           |
| Input Frequency 1          |
| ESS power setpoint phase 1 |

Service Actions

|                            |
|----------------------------|
| ESS power setpoint phase 1 |

Read demand

```taphome
MODBUSR(H, 12, Int16) / 100
```

Service Attributes

Input Voltage L1

```taphome
MODBUSR(H, 3, Uint16)/10  + " V"
```

Input Current L1

```taphome
MODBUSR(H, 6, Int16)/10  + " A";
```

Input Frequency 1

```taphome
MODBUSR(H, 9, Int16)/100  + " Hz";
```

ESS power setpoint phase 1

```taphome
MODBUSR(H, 37, int16) + " W";
```

Service Actions

ESS power setpoint phase 1

Parameters: Power setpoint L1 \[W] (-32768–32768 L1)

```taphome
MODBUSW(H, 37, int16, L1);
```

Input Power L2 Electricity Meter Read and write

AC input power phase 2 with voltage, current, frequency and ESS power setpoint

Register: H:13 Int16 Unit: W numeric

Service Attributes

|                            |
|----------------------------|
| Input Voltage L2           |
| Input Current L2           |
| Input Frequency 2          |
| ESS power setpoint phase 2 |

Service Actions

|                            |
|----------------------------|
| ESS power setpoint phase 2 |

Read demand

```taphome
MODBUSR(H, 13, Int16) / 100
```

Service Attributes

Input Voltage L2

```taphome
MODBUSR(H, 4, Uint16)/10  + " V"
```

Input Current L2

```taphome
MODBUSR(H, 7, Int16)/10  + " A";
```

Input Frequency 2

```taphome
MODBUSR(H, 10, Int16)/100  + " Hz";
```

ESS power setpoint phase 2

```taphome
MODBUSR(H, 40, int16) + " W";
```

Service Actions

ESS power setpoint phase 2

Parameters: ESS Power setpoint L2 \[W] (-32768–32768 L2)

```taphome
MODBUSW(H, 40, Int16, L2)
```

Input Power L3 Electricity Meter Read and write

AC input power phase 3 with voltage, current, frequency and ESS power setpoint

Register: H:14 Int16 Unit: W numeric

Service Attributes

|                            |
|----------------------------|
| Input Voltage L3           |
| Input Current L3           |
| Input Frequency 3          |
| ESS power setpoint phase 3 |

Service Actions

|                            |
|----------------------------|
| ESS power setpoint phase 3 |

Read demand

```taphome
MODBUSR(H, 14, Int16) / 100
```

Service Attributes

Input Voltage L3

```taphome
MODBUSR(H, 5, Uint16)/10  + " V"
```

Input Current L3

```taphome
MODBUSR(H, 8, Int16)/10  + " A";
```

Input Frequency 3

```taphome
MODBUSR(H, 11, Int16)/100  + " Hz";
```

ESS power setpoint phase 3

```taphome
MODBUSR(H, 41, int16) + " W";
```

Service Actions

ESS power setpoint phase 3

Parameters: ESS power setpoint L3 \[W] (-32768–32768 L3)

```taphome
MODBUSW(H, 41, Int16, L3)
```

Output Power L1 Electricity Meter Read-only

AC output phase 1 with voltage, current, frequency and per-phase alarm monitoring

Register: H:18 Int16 Unit: W numeric

Service Attributes

|                   |
|-------------------|
| Output Voltage L1 |
| Output Current L1 |
| Output Frequency  |

Read demand

```taphome
MODBUSR(H, 18, Int16) / 100
```

Read (module)

```taphome
var tem := MODBUSR(H, 44, Uint16);
SWITCH(tem,1, ADDWARNING("Temperature Alarm L1"), 2, ADDERROR("Temperature Alarm L1"),"");
var bat := MODBUSR(H, 45, Uint16);
SWITCH(bat,1, ADDWARNING("Low Battery Alarm L1"), 2, ADDERROR("Low Battery Alarm L1"),"");
var ove := MODBUSR(H, 46, Uint16);
SWITCH(ove,1, ADDWARNING("Overload Alarm L1"), 2, ADDERROR("Overload Alarm L1"),"");
var rip := MODBUSR(H, 47, Uint16);
SWITCH(rip,1, ADDWARNING("Ripple Alarm L1"), 2, ADDERROR("Ripple Alarm L1"),"");
```

Service Attributes

Output Voltage L1

```taphome
MODBUSR(H, 15, UInt16)/10  + " V";
```

Output Current L1

```taphome
MODBUSR(H, 18, Int16)/10  + " A";
```

Output Frequency

```taphome
MODBUSR(H, 21, Int16)/100 + " Hz";
```

Output Power L2 Electricity Meter Read-only

AC output phase 2 with voltage, current, frequency and per-phase alarm monitoring

Register: H:24 Int16 Unit: W numeric

Service Attributes

|                   |
|-------------------|
| Output voltage L2 |
| Output Current L2 |
| Output Frequency  |

Read demand

```taphome
MODBUSR(H, 24, Int16) / 100
```

Read (module)

```taphome
var tem := MODBUSR(H, 48, Uint16);
SWITCH(tem,1, ADDWARNING("Temperature Alarm L2"), 2, ADDERROR("Temperature Alarm L2"),"");
var bat := MODBUSR(H, 49, Uint16);
SWITCH(bat,1, ADDWARNING("Low Battery Alarm L2"), 2, ADDERROR("Low Battery Alarm L2"),"");
var ove := MODBUSR(H, 50, Uint16);
SWITCH(ove,1, ADDWARNING("Overload Alarm L2"), 2, ADDERROR("Overload Alarm L2"),"");
var rip := MODBUSR(H, 51, Uint16);
SWITCH(rip,1, ADDWARNING("Ripple Alarm L2"), 2, ADDERROR("Ripple Alarm L2"),"");
```

Service Attributes

Output voltage L2

```taphome
MODBUSR(H, 16, UInt16)/10  + " V";
```

Output Current L2

```taphome
MODBUSR(H, 19, Int16)/10  + " A";
```

Output Frequency

```taphome
MODBUSR(H, 21, Int16)/100 + " Hz";
```

Output Power L3 Electricity Meter Read-only

AC output phase 3 with voltage, current, frequency and per-phase alarm monitoring

Register: H:25 Int16 Unit: W numeric

Service Attributes

|                   |
|-------------------|
| Output Voltage L3 |
| Output Current L3 |
| Output Frequency  |

Read demand

```taphome
MODBUSR(H, 25, Int16) / 100
```

Read (module)

```taphome
var tem := MODBUSR(H, 52, Uint16);
SWITCH(tem,1, ADDWARNING("Temperature Alarm L3"), 2, ADDERROR("Temperature Alarm L3"),"");
var bat := MODBUSR(H, 53, Uint16);
SWITCH(bat,1, ADDWARNING("Low Battery Alarm L3"), 2, ADDERROR("Low Battery Alarm L3"),"");
var ove := MODBUSR(H, 54, Uint16);
SWITCH(ove,1, ADDWARNING("Overload Alarm L3"), 2, ADDERROR("Overload Alarm L3"),"");
var rip := MODBUSR(H, 55, Uint16);
SWITCH(rip,1, ADDWARNING("Ripple Alarm L3"), 2, ADDERROR("Ripple Alarm L3"),"");
```

Service Attributes

Output Voltage L3

```taphome
MODBUSR(H, 17, UInt16)/10  + " V";
```

Output Current L3

```taphome
MODBUSR(H, 20, Int16)/10  + " A";
```

Output Frequency

```taphome
MODBUSR(H, 21, Int16)/100 + " Hz";
```

PV Inverter Switch Read and write

PV inverter frequency shifting control — enable or disable PV output on AC-out

Register: H:56 UInt16 numeric

Values / States: PV disabled · PV enabled

Read switch state

```taphome
MODBUSR(H, 56, Uint16)
```

Write switch state

```taphome
MODBUSWNE(H, 56, Uint16, St);
```

**Connection:** Modbus TCP • Slave ID: $\[SlaveId]

Possible improvements (16)

- H:23 Output Power L1 — Int16, ×10, W — actual output power L1 register; template uses H:18 (current) for Output Power 1 readdemand instead
- H:71 AcPowerSetpoint acts as feed-in limit — UInt16, 0=Normal, 1=OvervoltageFeedIn limit
- H:72 Solar offset voltage — UInt16, 0=1V offset, 1=0.1V offset
- H:73 Sustain active — UInt16, 0=Inactive, 1=Active
- H:74-92 Energy Counters (10 × UInt32) — /100, kWh — AC-In/Out/Battery energy flow counters; volatile (reset on Multi/GX reboot)
- H:94 BMS Pre-Alarm (Low cell voltage imminent) — UInt16, 0=Ok, 1=Warning, 2=Alarm
- H:95 Charge State — UInt16, enum: 0=Initialising, 1=Bulk, 2=Absorption, 3=Float, 4=Storage, 5=Absorb repeat, 6=Forced absorb, 7=Equalise, 8=Bulk stopped, 9=Unknown
- H:96-100 ESS 32-bit Power Setpoints (L1-L3) — Int32, W — 32-bit complement of H:37/40/41 for larger systems
- H:102 Prefer Renewable Energy — UInt16, 0=No, 1=Yes; Venus 3.30+
- H:103-104 Remote Generator Selected — UInt16, select/status; Venus 3.30+
- H:105 Redetect VE.Bus system — Write 1 to redetect
- H:106 Power Assist boost factor — UInt16, /100; Venus 3.30+
- H:107 Configured output voltage — UInt16, /100, V AC; Venus 3.30+
- H:108 PowerAssist enabled — UInt16, 0=Disabled, 1=Enabled; Venus 3.30+
- H:109 UPS function enabled — UInt16, 0=Enabled, 1=Disabled (inverted); Venus 3.30+
- H:200-231 Microgrid Registers — Grid-forming / grid-following / droop mode control; most RW, some unsupported in current firmware

## Import parameters

Enter these values when you import the XML.

| Asked in the app | Default       |
|------------------|---------------|
| Slave ID         | `227`         |
| IP address       | `192.168.1.0` |

## Sources

- GX Modbus-TCP Manual
  
  [www.victronenergy.com](https://www.victronenergy.com/live/ccgx:modbustcp_faq) 2026-03-28
- CCGX Modbus TCP Register List v3.70
  
  [www.victronenergy.com](https://www.victronenergy.com/upload/documents/CCGX-Modbus-TCP-register-list-3.70.xlsx) 2026-03-28
- hass-victron — Home Assistant Integration
  
  [github.com](https://github.com/sfstar/hass-victron) 2026-03-28

## Related Documentation

- [Modbus Integration](https://taphome.com/en/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/en/docs/integration/modbus/)
- [Simple configuration using templates](https://taphome.com/en/docs/integration/modbus/templates/)
- [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/)
- [Modbus functions](https://taphome.com/en/docs/script/modbus/)
- [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/)