The Vaillant aroTHERM plus template connects TapHome to a Vaillant aroTHERM plus air-to-water heat pump and its system controller sensoCOMFORT VRC 720 or multiMATIC VRC 700 through an eBUS Adapter Shield or Stick C6 from ebusd.eu. The adapter sits on the eBUS of the controller and runs micro-ebusd, which decodes the Vaillant messages and offers them over a local HTTP JSON API. TapHome talks only to the adapter, in the local network; no cloud is used.
The template reads the outdoor, room, flow and hot water temperatures, the water pressure, the power and energy of the heat pump and the errors of the controller. It sets the room setpoint of zone 1, the hot water setpoint, the operating modes of zone 1 and the hot water and starts a one-time hot water charge. It also reads the flow, return and air inlet temperatures, the compressor modulation and the activity of the heat pump, and sets the heating curve, the lowest heating and cooling flow temperatures, the cooling mode of zone 1 and the hot water charge hysteresis.
Community template. The template was generated in the TapHome portal from the micro-ebusd documentation and the ebusd message definitions for the VRC 720, the VRC 700 and the aroTHERM plus; feedback from the field is welcome. Download the XML on this page, or get it from the TapHome portal: Vaillant aroTHERM plus + VRC 720 / VRC 700 — community template, and import it as a new module.
The template complements the official TapHome template eBUS Adapter Shield C6 Stick, which shows the health of the adapter itself (bus signal, daemon, temperature) over MQTT; the two can run side by side. It is not related to the community template for the Vaillant aroVAIR fan coil, which uses Modbus RTU.
What you need
- Vaillant aroTHERM plus with the controller sensoCOMFORT VRC 720 or multiMATIC VRC 700 on the eBUS.
- eBUS Adapter Shield C6 or Stick C6 (adapter.ebusd.eu) with the latest firmware and micro-ebusd activated. micro-ebusd is a paid function of the adapter, unlocked with a token; each adapter gets one 30-day trial.
- The adapter and the TapHome Core in the same local network.
Hardware connection
The adapter connects to the two eBUS terminals of the controller (VRC 720 or VRC 700); eBUS is polarity-independent. The aroTHERM plus talks to the controller over the same bus, so no wire to the outdoor unit is needed. Disconnect the mains power before working on the controller terminals.
Connect the adapter to the local network as described in the adapter documentation and reserve its IP address in the router, so that TapHome can always reach it.
Configuration
Activating micro-ebusd
- Update the adapter to the latest firmware (adapter.ebusd.eu).
- Get a micro-ebusd token at token.ebusd.eu (one 30-day trial per adapter, then paid) and enter it in the web interface of the adapter.
- After the activation the HTTP JSON API answers at
http://<adapter-ip>/api/v1/ebus.
Finding the circuit names
micro-ebusd addresses each value by circuit and message name. Open http://<adapter-ip>/api/v1/ebus/list in a browser: it lists the circuits and messages the adapter found on the bus. The controller sensoCOMFORT VRC 720 appears as ctlv2, ctlv3 or 720 depending on its version, the multiMATIC VRC 700 as 700, the outdoor unit of the aroTHERM plus as hmu. The template supports both controllers; for the VRC 700 enter 700 as the controller circuit.
Import parameters
| Parameter | Default | Description |
|---|---|---|
ADAPTER_IP | (empty) | IP address of the eBUS adapter |
CONTROLLER_CIRCUIT | ctlv2 | Circuit name of the controller from /api/v1/ebus/list, for example ctlv2 for the VRC 720 or 700 for the VRC 700 |
HEAT_SOURCE_CIRCUIT | hmu | Circuit name of the aroTHERM plus outdoor unit |
The import creates two modules on the same adapter: Controller (sensoCOMFORT VRC 720 / multiMATIC VRC 700) with thirteen devices and aroTHERM plus (hmu) with six devices of the heat pump.
Device capabilities
Temperatures and pressure
- Outdoor Temperature — outdoor temperature as shown by the controller.
- Flow Temperature — system flow temperature (heating supply).
- Water Pressure — water pressure of the heating system in bar (read only).
Zone 1
- Zone 1 Thermostat — room temperature and the setpoint the controller really uses. A setpoint set in TapHome (5–30 °C) is sent as quick veto: a temporary change for 3 hours (the device variable
QuickVetoHours, 0.5–12 h); then the time programme of the controller applies again. After the write the template reads the value again from the bus. - Zone 1 Operating Mode — Off, Auto (time programme), Manual / Day and Night. The template takes the names from the definition the adapter reports:
off,auto,manualwith micro-ebusd firmware from April 2026,off,auto,day,nightwith older firmware. Night exists only with the older names; the VRC 720 itself has Manual, Auto and Off. - Zone 1 Cooling Mode — Off, Auto and Manual for cooling of zone 1. On the VRC 720 it needs micro-ebusd firmware from 2026-04-22 and cooling enabled for heating circuit 1; with older firmware the device stays without a value. On the VRC 700 the template uses the cooling mode of the VRC 700 and writes Manual as
day.
Heating and cooling flow water
- Heating Curve — heating curve of heating circuit 1, from 0.1 to 4.0.
- Heating Minimum Flow Temperature — lowest flow water temperature in heating, from 15 to 80 °C. The controller heats to the higher of its heating curve and this value, so with a low heating curve the value written here sets the flow water temperature; the maximum flow temperature of the controller still caps it. A smart rule such as Equithermic regulation can write the flow water temperature it calculates into this device. The value is rounded to a whole degree and written only when it changes. The controller keeps it in its permanent memory: as a precaution, let the smart rule change it at most about once every 10 minutes.
- Cooling Minimum Flow Temperature — lowest flow water temperature in cooling, from 7 to 24 °C; the dew point monitoring of the controller can raise it. On the VRC 720 with micro-ebusd firmware from 2026-04-22 it is offered only when cooling is enabled for heating circuit 1.
Hot water
- Hot Water Thermostat — temperature of the hot water storage tank and the hot water setpoint, adjustable from 35 to 75 °C.
- Hot Water Operating Mode — Off, Auto, Manual / Day or Night (Night only with older firmware, see above).
- Hot Water Boost — one-time hot water charge. Switching it on starts the charge; the controller returns to auto by itself when the tank is charged, and the switch then shows off again.
- Hot Water Charge Hysteresis — hysteresis of the hot water charge in K. The controller rejects a value outside its range; TapHome then shows the value the controller kept.
Heat pump electricity
The module aroTHERM plus (hmu) carries six devices. Heat Pump Electricity is an electricity meter of the outdoor unit:
- Demand — current electrical power of the heat pump in kW.
- Total consumption — total electricity consumption of the heat pump in kWh. The counter is a 16-bit number (at most 65535 kWh), so on a unit that has run for many years it can have started from zero again.
It also shows three service attributes:
| Service attribute | Description |
|---|---|
| COP (heating) | Coefficient of performance of the heat pump in heating |
| Total thermal yield [kWh] | Total heat yield of the heat pump — thermal energy, not electricity |
| Operational state | State reported by the outdoor unit: ready, heating, cooling, heating_water or error |
Heat pump operation
- Heat Pump Flow Temperature, Heat Pump Return Temperature and Air Inlet Temperature — temperatures measured by the outdoor unit.
- Compressor Modulation — compressor modulation in %, with the compressor speed, the compressor inlet and outlet temperatures and the high pressure as service attributes.
- Heat Pump Activity — what the heat pump is doing, from its status code: 0 standby, 1 heating, 2 cooling, 3 hot water, 4 defrost, 5 other (for example protection or fault). The service attribute Status code shows the status code itself.
Controller errors
The module Controller (sensoCOMFORT VRC 720 / multiMATIC VRC 700) reads the current errors of the controller every cycle. For each of its five error fields that is not zero, the module shows an error with the error number, for example Controller error code: 1025.
How the template talks to the adapter
Each value is one message of the ebusd definition. The template reads it with GET /api/v1/ebus/{circuit}/{message}/get?from=1, which answers from the cache of the adapter or asks the bus, and takes data.fields.value from the answer. A write is PUT /api/v1/ebus/{circuit}/{message}/set with the body {"fields":{"value":…}}, followed by a read with from=2, which always asks the bus. The modules and all devices read every 60 s. micro-ebusd firmware from 2026-04-22 uses newer message names (OutsideTemp, Z1TempDesired, CurrentError); the template reads the newer name first and falls back to the older one.
None of the devices writes anything when the TapHome Core starts: they take their state from the adapter, not from the last value in TapHome.
Some VRC 720 firmware versions confirm a write and do not apply it. Because the template reads the value back from the bus after each write, TapHome then shows the value the controller really uses, not the one you set.
The multiMATIC VRC 700 has fewer messages than the VRC 720. It has no lowest flow temperature for cooling, so Cooling Minimum Flow Temperature stays without a value. It has no quick veto duration: Zone 1 Thermostat writes only the quick veto temperature, and
QuickVetoHoursdoes not apply. The setpoint of zone 1 and the outdoor temperature come from the older messagesZ1ActualRoomTempDesiredandDisplayedOutsideTemp.
What the template does not do
- Other installer parameters (maximum flow temperature and the rest of the installer settings) are left out on purpose — of the installer settings the template changes only the heating curve, the lowest heating and cooling flow temperatures and the hot water charge hysteresis.
- The cooling setpoint of zone 1, zones 2 and 3, and the weekly time programme are not part of the template.
- The current heat output of the outdoor unit is available on the bus but not read.
Troubleshooting
No values at all
Check that micro-ebusd is activated and the token has not expired: without micro-ebusd the adapter does not answer on /api/v1/ebus. Check that http://<adapter-ip>/api/v1/ebus/list opens in a browser.
The controller devices show no value
The circuit name does not match. Open http://<adapter-ip>/api/v1/ebus/list, find the name of the controller (ctlv2, ctlv3 or 720 for the VRC 720, 700 for the VRC 700) and of the outdoor unit (hmu) and import the template again with these names.
A setpoint or mode returns to the old value
The controller did not apply the write; TapHome shows the value read back from the bus. Check the operating mode of the zone and the firmware of the controller. A setpoint from TapHome also returns to the time programme when the quick veto ends (QuickVetoHours).
Module error Controller error code: …
The controller reports an error with this number. Look it up in the documentation of the controller or the heat pump; the module error goes away when the controller clears it.