  questions: ["How to integrate the SolaX X3 Hybrid IES inverter with TapHome?","Which COM port pins of the SolaX X3-IES are used for Modbus RTU?","How to set the Modbus address and baud rate on the SolaX X3-IES display?","What does the SolaX X3 Hybrid IES TapHome template monitor?","Why does the SolaX X3-IES not respond to Modbus requests from TapHome?"]
---

# SolaX X3 Hybrid IES

Communication: Modbus RTU

## Integration guide

The SolaX X3-IES series (X3-IES-4K, 5K, 6K, 8K, 10K, 12K and 15K) is a three-phase residential energy storage system that combines a transformerless hybrid inverter with a T-BAT-SYS high-voltage battery. TapHome communicates with the inverter over Modbus RTU on RS-485, using the dedicated Modbus485 pins of the inverter's COM port.

The template reads PV production, battery state, grid exchange measured by the inverter's meter or CT, operating status and fault codes. Additional values are available as service attributes.

## Hardware connection

### COM port and Modbus485 pins

The COM port of the X3-IES is a communication connector with two RJ45 sockets (P1, P2) for parallel operation and two terminal blocks (P3, P4) for external devices.

![SolaX X3-IES COM port connector with P1, P2 (parallel RJ45), P3 and P4 terminal blocks and pin table of P1 and P2.](https://taphome.com/images/compatibility/solax-x3-hybrid-ies/com-port-pinout-p1-p2_hu_67559ea88b8f8b4c.jpg)

The TapHome connection uses the **P4** terminal block:

![SolaX X3-IES COM port pin table: P3 pins 7-8 remote 485A/B for datahub, P4 pins 11 (modbus 485A) and 12 (modbus 485B) for external Modbus devices.](https://taphome.com/images/compatibility/solax-x3-hybrid-ies/com-port-pinout-p3-p4-modbus-485_hu_2c899d9f7632f160.jpg)

| Block | Pin | Definition | Use with TapHome |
|---|---|---|---|
| P4 | **11** | modbus 485A | RS-485 A |
| P4 | **12** | modbus 485B | RS-485 B |
| P4 | 10 | GND | Ground connection |
| P4 | 9 | 12V_COM | 12 V supply output — not used |
| P3 | 7, 8 | remote 485A / remote 485B | Not used — reserved for SolaX DataHub, EV charger and other SolaX devices |

According to the manufacturer, pins 11 and 12 are intended for data acquisition and external control by professional personnel, and the protocol on these pins is Modbus RTU.

> [!WARNING]
> Do not connect TapHome to pins 7 and 8 of the P3 block (remote 485). That port serves SolaX accessories such as the DataHub, EV charger and Adapter Box G2. TapHome must be wired to pins 11 (485A) and 12 (485B) of the P4 block.

### Wiring to TapHome Core

1. Connect **pin 11 (modbus 485A)** to the A terminal and **pin 12 (modbus 485B)** to the B terminal of an RS-485 bus of the TapHome Core (or of the RS-485 converter that serves the Core).
2. Where the TapHome side has a ground terminal, connect it to **pin 10 (GND)** of the P4 block.
3. The manufacturer lists a CAT5E network cable (0.2 mm²) as the communication wire.

Wiring of the COM terminal block, as described in the user manual:

1. Loosen the swivel nut of the communication connector, remove the rubber stopper and pull the terminal block out.
2. Thread the cable through the swivel nut and the connector and strip the insulation.
3. Insert the wires into ferrules, crimp them and plug them into the terminal block.
4. Insert the terminal block back into the connector until it clicks, then tighten the swivel nut.

## Configuration

### Modbus settings on the inverter display

The Modbus interface of the inverter is set in the LCD menu **Menu > Setting > Advance Setting > Modbus**. The menu shows two items, **Baud Rate** and **Address**:

![SolaX X3-IES inverter LCD Modbus menu showing Baud Rate 19200 and Address 1.](https://taphome.com/images/compatibility/solax-x3-hybrid-ies/lcd-modbus-baud-address_hu_82c29bfecd1de9c.jpg)

> [!NOTE]
> Advance Setting is protected by the advance password, which only professional installers receive from the SolaX after-sales team. The user password (default 0000) opens only User Setting.

Communication parameters (manufacturer defaults, also the template's suggested values):

| Parameter | Value |
|---|---|
| Baud rate | 19200 bps |
| Modbus address (Slave ID) | 1 |
| Data bits | 8 |
| Parity | None |
| Stop bits | 1 |

The same values are readable over Modbus: holding register **0x00AF** holds the Modbus RTU address and **0x00B0** the baud rate code (4 = 19200; other codes: 0 = 115200, 1 = 57600, 2 = 56000, 3 = 38400, 5 = 14400, 6 = 9600).

### RS-485 port function (485CommFunSelect)

Holding register **0x013E** (485CommFunSelect) selects the function of the RS-485 port: **0 = Modbus 485**, 1 = EV Charge. It must be **0** for TapHome. With value 1 the port is used for EV charger communication and the inverter does not answer TapHome.

### Request timing

The manufacturer's protocol specifies a minimum interval of **1 second** between two requests and a response timeout of 1 second. The template therefore suggests a delay of 1000 ms between requests and a read/write timeout of 1000 ms on the Modbus RTU interface.

In TapHome, the template is imported into a Modbus RTU interface of the Core configured with the parameters above, and the only import parameter is the inverter's **Modbus Slave ID** (default 1).

## Device capabilities

The template is intended for monitoring. Its read-only devices are described below.

> [!WARNING]
> **Do not use the control devices yet.** The template also contains the devices Work mode control, Night charging and Remote power control and their service actions. They currently write to register addresses that the SolaX Modbus protocol V3.29 does not list as write registers, so do not use control by writing for now. Monitoring is not affected.

### PV production

- **Solar PV array** — electricity meter (read-only). Current power is the sum of the DC power of MPPT1 (input register 0x000A) and MPPT2 (0x000B). Total energy is the total PV yield (0x0094–0x0095, 0.1 kWh). Polled every 15 s.
- **Solar energy — today** — variable with today's PV yield in kWh (0x0096). Polled every 60 s.

### Battery

**Battery** — electricity meter (read-only). Current power is the battery charge/discharge power (0x0016) and total energy is the total energy output by the battery (0x001D–0x001E, 0.1 kWh). The device shows the battery direction as an information message (Discharging, Charging, Idle) and raises the warning **BMS not connected** when the BMS connection state (0x0017) is 0.

Service attributes: battery SOC, battery voltage, battery current, battery temperature, max./min. cell voltage, max./min. battery temperature, BMS user SOC, BMS SOH, BMS max. charge current and BMS max. discharge current.

### Grid exchange

**Grid — power and energy** — electricity meter (read-only) based on the inverter's grid meter or CT. Current power is the feed-in power (0x0046–0x0047): positive values mean export to the grid, negative values import from the grid. Total energy is the total energy exported to the grid (0x0048–0x0049, 0.01 kWh). When the grid status (0x001A) reports off-grid, the device shows the information message **Off-grid operation**.

Service attributes: total exported energy, total imported energy, energy to grid today and total energy to grid at the inverter AC port, power of phases R, S and T, feed-in power of phases R, S and T, and voltage of phase R.

### Inverter status

**Inverter status** — read-only multi-value switch showing the run mode (input register 0x0009):

| Value | State |
|---|---|
| 0 | Waiting |
| 1 | Checking |
| 2 | Normal operation |
| 3 | Fault |
| 4 | Permanent fault |
| 5 | Firmware update |
| 6 | Off-grid waiting |
| 7 | Off-grid operation |
| 8 | Self test |
| 9 | Idle |

Service attributes: heatsink temperature, DC bus voltage, number of MPPT channels, PV1 and PV2 voltage, PV1 and PV2 current.

### Module diagnostics and parallel systems

The module decodes fault registers of the inverter and reports them as errors:

- Inverter faults (bits 0–9 of 0x0040): TZ protect fault, grid lost, grid voltage fault, grid frequency fault, PV voltage fault, DC bus voltage fault, battery voltage fault, AC 10-minute voltage fault, DCI overcurrent and DCV overcurrent.
- Manager fault (0x0043), reported with its fault code.
- BMS fault (0x0044), reported with its fault code.

Module service attributes: DSP firmware version, ARM firmware version, inverter Slave ID, number of inverters in the parallel system, and the total AC power of phases R, S and T and total battery power of the parallel system (0x01DD and following registers). According to the manufacturer, up to 3 inverters can run in parallel without an X3-PBOX device and up to 10 with an X3-PBOX-60kW-G2 or X3-PBOX-150kW-G2.

## Troubleshooting

### The inverter does not respond

- Check that the cable is on **P4 pins 11 (485A) and 12 (485B)**, not on P3 pins 7 and 8.
- Check the A/B polarity — swap the two wires if the inverter still does not answer — and the ground on P4 pin 10.
- Check that 485CommFunSelect (0x013E) is **0 (Modbus 485)**, not 1 (EV Charge).
- In **Advance Setting > Modbus** on the display, compare **Address** with the Slave ID entered in TapHome and **Baud Rate** with the interface setting (19200 by default). Over Modbus, the address is in register 0x00AF and the baud rate code in 0x00B0 (4 = 19200).
- Keep the delay between requests at 1000 ms or more; the manufacturer requires at least 1 second between two requests.

### Battery values are zero or missing

- If the Battery device shows **BMS not connected**, the BMS connection state (0x0017) is 0 (Disconnected) and the inverter has no data from the battery. Check the communication between the battery and the inverter.

### Faults on the module

- Inverter, manager and BMS faults are shown as module errors. Bit names follow the manufacturer's inverter error code table; manager and BMS faults are reported as numeric codes, which are listed in the manufacturer's Modbus protocol.

## Available devices 8

These devices appear in TapHome after import.

SolaX X3 Hybrid IES Module

Service Attributes

|                                          |
|------------------------------------------|
| Verzia DSP FW                            |
| Verzia ARM FW                            |
| Slave ID striedača                       |
| Počet striedačov v paralelnej inštalácii |
| Celkový výkon AC (R-fáza, paralelné)     |
| Celkový výkon AC (S-fáza, paralelné)     |
| Celkový výkon AC (T-fáza, paralelné)     |
| Celkový výkon batérií (paralelné)        |

Read (module)

```taphome
var FaultLSB := MODBUSR(A, 64, UInt16);
var FaultMSB := MODBUSR(A, 65, UInt16);
IF (GETBIT(FaultLSB, 0))
ADDERROR(0, "Chyba ochrany TZ")
END
IF (GETBIT(FaultLSB, 1))
ADDERROR(1, "Strata siete")
END
IF (GETBIT(FaultLSB, 2))
ADDERROR(2, "Chyba napätia siete")
END
IF (GETBIT(FaultLSB, 3))
ADDERROR(3, "Chyba frekvencie siete")
END
IF (GETBIT(FaultLSB, 4))
ADDERROR(4, "Chyba napätia FV")
END
IF (GETBIT(FaultLSB, 5))
ADDERROR(5, "Chyba napätia DC zbernice")
END
IF (GETBIT(FaultLSB, 6))
ADDERROR(6, "Chyba napätia batérie")
END
IF (GETBIT(FaultLSB, 7))
ADDERROR(7, "Chyba AC10min napätia")
END
IF (GETBIT(FaultLSB, 8))
ADDERROR(8, "Pretečenie DCI")
END
IF (GETBIT(FaultLSB, 9))
ADDERROR(9, "Pretečenie DCV")
END
var MgrFault := MODBUSR(A, 67, UInt16);
IF (MgrFault > 0)
ADDERROR(10, "Chyba manažéra (kód " + TOSTRING(MgrFault, "F0") + ")")
END
var BMSFaultLSB := MODBUSR(A, 68, UInt16);
var BMSFaultMSB := MODBUSR(A, 69, UInt16);
IF (BMSFaultLSB > 0)
ADDERROR(11, "Chyba BMS (kód " + TOSTRING(BMSFaultLSB, "F0") + ")")
END
```

Service Attributes

Verzia DSP FW

```taphome
TOSTRING(MODBUSR(H, 127, UInt16), "F0") + "." + TOSTRING(MODBUSR(H, 125, UInt16), "F0")
```

Verzia ARM FW

```taphome
TOSTRING(MODBUSR(H, 128, UInt16), "F0") + "." + TOSTRING(MODBUSR(H, 131, UInt16), "F0")
```

Slave ID striedača

```taphome
TOSTRING(MODBUSR(H, 175, UInt16), "F0")
```

Počet striedačov v paralelnej inštalácii

```taphome
TOSTRING(MODBUSR(A, 477, UInt16), "F0")
```

Celkový výkon AC (R-fáza, paralelné)

```taphome
TOSTRING(MODBUSR(A, 480, LittleEndianInt32), "F0") + " W"
```

Celkový výkon AC (S-fáza, paralelné)

```taphome
TOSTRING(MODBUSR(A, 482, LittleEndianInt32), "F0") + " W"
```

Celkový výkon AC (T-fáza, paralelné)

```taphome
TOSTRING(MODBUSR(A, 484, LittleEndianInt32), "F0") + " W"
```

Celkový výkon batérií (paralelné)

```taphome
TOSTRING(MODBUSR(A, 506, LittleEndianInt32), "F0") + " W"
```

Solárne FV pole Electricity Meter

Read total consumption

```taphome
MODBUSR(A, 148, LittleEndianUint32) / 10
```

Read demand

```taphome
MODBUSR(A, 10, UInt16) + MODBUSR(A, 11, UInt16)
```

Batéria Electricity Meter

Service Attributes

|                         |
|-------------------------|
| SOC batérie             |
| Napätie batérie         |
| Prúd batérie            |
| Teplota batérie         |
| Max. napätie článku     |
| Min. napätie článku     |
| Max. teplota batérie    |
| Min. teplota batérie    |
| BMS SOC (používateľský) |
| BMS SOH                 |
| Max. nabíjací prúd BMS  |
| Max. vybíjací prúd BMS  |

Read total consumption

```taphome
MODBUSR(A, 29, LittleEndianUint32) / 10
```

Read demand

```taphome
MODBUSR(A, 22, Int16)
```

Read (module)

```taphome
var SOC := MODBUSR(A, 28, UInt16);
var BDC := MODBUSR(A, 25, UInt16);
IF (BDC = 0)
ADDINFO(0, "Vybíjanie")
END
IF (BDC = 1)
ADDINFO(1, "Nabíjanie")
END
IF (BDC = 2)
ADDINFO(2, "Nečinná")
END
var BMS := MODBUSR(A, 23, UInt16);
IF (BMS = 0)
ADDWARNING(0, "BMS nie je pripojený")
END
```

Service Attributes

SOC batérie

```taphome
TOSTRING(MODBUSR(A, 28, UInt16), "F0") + " %"
```

Napätie batérie

```taphome
TOSTRING(MODBUSR(A, 20, Int16) / 10, "F1") + " V"
```

Prúd batérie

```taphome
TOSTRING(MODBUSR(A, 21, Int16) / 10, "F1") + " A"
```

Teplota batérie

```taphome
TOSTRING(MODBUSR(A, 24, Int16), "F0") + " °C"
```

Max. napätie článku

```taphome
TOSTRING(MODBUSR(A, 188, UInt16) / 1000, "F3") + " V"
```

Min. napätie článku

```taphome
TOSTRING(MODBUSR(A, 189, UInt16) / 1000, "F3") + " V"
```

Max. teplota batérie

```taphome
TOSTRING(MODBUSR(A, 186, Int16) / 10, "F1") + " °C"
```

Min. teplota batérie

```taphome
TOSTRING(MODBUSR(A, 187, Int16) / 10, "F1") + " °C"
```

BMS SOC (používateľský)

```taphome
TOSTRING(MODBUSR(A, 190, UInt16), "F0") + " %"
```

BMS SOH

```taphome
TOSTRING(MODBUSR(A, 191, UInt16), "F0") + " %"
```

Max. nabíjací prúd BMS

```taphome
TOSTRING(MODBUSR(A, 36, UInt16) / 10, "F1") + " A"
```

Max. vybíjací prúd BMS

```taphome
TOSTRING(MODBUSR(A, 37, UInt16) / 10, "F1") + " A"
```

Sieť — výkon a energia Electricity Meter

Service Attributes

|                                    |
|------------------------------------|
| Celková exportovaná energia (sieť) |
| Celková importovaná energia (sieť) |
| Energia do siete dnes (AC port)    |
| Celková energia do siete (AC port) |
| Výkon R-fázy                       |
| Výkon S-fázy                       |
| Výkon T-fázy                       |
| Feedin R-fáza                      |
| Feedin S-fáza                      |
| Feedin T-fáza                      |
| Napätie R-fázy                     |

Read total consumption

```taphome
MODBUSR(A, 72, LittleEndianUint32) / 100
```

Read demand

```taphome
MODBUSR(A, 70, LittleEndianInt32)
```

Read (module)

```taphome
var GridStatus := MODBUSR(A, 26, UInt16);
IF (GridStatus = 1)
ADDINFO(0, "Ostrovná prevádzka (OffGrid)")
END
```

Service Attributes

Celková exportovaná energia (sieť)

```taphome
TOSTRING(MODBUSR(A, 72, LittleEndianUint32) / 100, "F2") + " kWh"
```

Celková importovaná energia (sieť)

```taphome
TOSTRING(MODBUSR(A, 74, LittleEndianUint32) / 100, "F2") + " kWh"
```

Energia do siete dnes (AC port)

```taphome
TOSTRING(MODBUSR(A, 80, UInt16) / 10, "F1") + " kWh"
```

Celková energia do siete (AC port)

```taphome
TOSTRING(MODBUSR(A, 82, LittleEndianUint32) / 10, "F1") + " kWh"
```

Výkon R-fázy

```taphome
TOSTRING(MODBUSR(A, 108, Int16), "F0") + " W"
```

Výkon S-fázy

```taphome
TOSTRING(MODBUSR(A, 112, Int16), "F0") + " W"
```

Výkon T-fázy

```taphome
TOSTRING(MODBUSR(A, 116, Int16), "F0") + " W"
```

Feedin R-fáza

```taphome
TOSTRING(MODBUSR(A, 130, LittleEndianInt32), "F0") + " W"
```

Feedin S-fáza

```taphome
TOSTRING(MODBUSR(A, 132, LittleEndianInt32), "F0") + " W"
```

Feedin T-fáza

```taphome
TOSTRING(MODBUSR(A, 134, LittleEndianInt32), "F0") + " W"
```

Napätie R-fázy

```taphome
TOSTRING(MODBUSR(A, 106, UInt16) / 10, "F1") + " V"
```

Solárna energia — dnes Variable

Read

```taphome
MODBUSR(A, 150, UInt16) / 10
```

Stav striedača Multi-value Switch

Values / States: Čakanie · Kontrola · Normálna prevádzka · Porucha · Trvalá porucha · Aktualizácia FW · Čakanie na ostrov · Ostrovná prevádzka · Vlastný test · Nečinný

Read switch state

```taphome
MODBUSR(A, 9, UInt16)
```

Service Attributes

Teplota chladiča

```taphome
TOSTRING(MODBUSR(A, 8, Int16), "F0") + " °C"
```

Napätie DC zbernice

```taphome
TOSTRING(MODBUSR(A, 102, UInt16) / 10, "F1") + " V"
```

Počet MPPT kanálov

```taphome
TOSTRING(MODBUSR(A, 27, UInt16), "F0")
```

Napätie FV1

```taphome
TOSTRING(MODBUSR(A, 3, UInt16) / 10, "F1") + " V"
```

Napätie FV2

```taphome
TOSTRING(MODBUSR(A, 4, UInt16) / 10, "F1") + " V"
```

Prúd FV1

```taphome
TOSTRING(MODBUSR(A, 5, UInt16) / 10, "F1") + " A"
```

Prúd FV2

```taphome
TOSTRING(MODBUSR(A, 6, UInt16) / 10, "F1") + " A"
```

Riadenie pracovného režimu Multi-value Switch

Values / States: Vlastná spotreba (Self use) · Priorita FV do siete · Zálohovanie · Manuálny mód

Read switch state

```taphome
MODBUSR(H, 139, UInt16)
```

Write switch state

```taphome
MODBUSWNE(SH, 139, UInt16, Mu)
```

Service Attributes

Manuálny mód

```taphome
MODBUSR(H, 140, UInt16) = 0 ? "Stop" : (MODBUSR(H, 140, UInt16) = 1 ? "Vynútené nabíjanie" : "Vynútené vybíjanie")
```

Limit exportu výkonu

```taphome
TOSTRING(MODBUSR(H, 182, UInt16), "F0") + " W"
```

Max. SOC nabíjania

```taphome
TOSTRING(MODBUSR(H, 270, UInt16), "F0") + " %"
```

Min. SOC vybíjania (SelfUse)

```taphome
TOSTRING(MODBUSR(H, 147, UInt16) >> 8, "F0") + " %"
```

Nočné nabíjanie Switch

Values / States: Zapnuté · Vypnuté

Read switch state

```taphome
MODBUSR(H, 147, UInt16) & 0xFF
```

Write switch state

```taphome
var r := MODBUSR(H, 147, UInt16);
MODBUSWNE(SH, 147, UInt16, (r & 0xFF00) | St);
```

Vzdialené riadenie výkonu Multi-value Switch

Values / States: Vzdialené riadenie vypnuté · Riadenie výkonom · Riadenie energiou · Riadenie SOC

Service Actions

|                        |
|------------------------|
| Nastaviť cieľový výkon |
| Nastaviť cieľový SOC   |
| Nastaviť timeout       |
| Vynútiť nabíjanie      |

Read switch state

```taphome
MODBUSR(A, 256, UInt16)
```

Write switch state

```taphome
MODBUSWNE(SH, 256, UInt16, Mu)
```

Service Attributes

Cieľový výkon

```taphome
TOSTRING(MODBUSR(A, 258, LittleEndianInt32), "F0") + " W"
```

Cieľový SOC

```taphome
TOSTRING(MODBUSR(A, 283, UInt16), "F0") + " %"
```

Timeout vzdialeného riadenia

```taphome
TOSTRING(MODBUSR(A, 286, UInt16), "F0") + " s"
```

Vynútené nabíjanie

```taphome
MODBUSR(A, 287, UInt16) = 1 ? "Áno" : "Nie"
```

Service Actions

Nastaviť cieľový výkon

Parameters: Výkon \[W] (-30000–30000 pw)

```taphome
MODBUSW(SH, 258, LittleEndianInt32, pw);
```

Nastaviť cieľový SOC

Parameters: SOC \[%] (10–100 sc)

```taphome
MODBUSW(SH, 283, UInt16, sc);
```

Nastaviť timeout

Parameters: Timeout \[s] (4–65535 to)

```taphome
MODBUSW(SH, 286, UInt16, to);
```

Vynútiť nabíjanie

Parameters: Akcia

```taphome
MODBUSW(SH, 287, UInt16, fc);
```

**Connection:** Modbus RTU • 19200 baud• 8N1 • Slave ID: $\[SlaveId]

## Import parameters

Enter these values when you import the XML.

| Asked in the app | Default |
|------------------|---------|
| Modbus Slave ID  | `1`     |

## Related Documentation

- [Modbus Integration](https://taphome.com/en/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/en/docs/integration/modbus/)
- [Simple configuration using templates](https://taphome.com/en/docs/integration/modbus/templates/)
- [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/)
- [Modbus functions](https://taphome.com/en/docs/script/modbus/)
- [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/)