SolaX X3-IES three-phase hybrid inverter with battery, connected to TapHome over Modbus RTU (RS-485, COM port pins 11 and 12). The template monitors PV, battery and grid power and energy, the run status and fault codes.

Modbus RTU8 devicesRevision 1.0 Last updated: November 24, 2026

Submitted by eltime

SolaX X3 Hybrid IES

Import into the TapHome appHardware › Modbus › Add from template

Download Template
On this page

Integration guide

The SolaX X3-IES series (X3-IES-4K, 5K, 6K, 8K, 10K, 12K and 15K) is a three-phase residential energy storage system that combines a transformerless hybrid inverter with a T-BAT-SYS high-voltage battery. TapHome communicates with the inverter over Modbus RTU on RS-485, using the dedicated Modbus485 pins of the inverter’s COM port.

The template reads PV production, battery state, grid exchange measured by the inverter’s meter or CT, operating status and fault codes. Additional values are available as service attributes.

Hardware connection

COM port and Modbus485 pins

The COM port of the X3-IES is a communication connector with two RJ45 sockets (P1, P2) for parallel operation and two terminal blocks (P3, P4) for external devices.

SolaX X3-IES COM port connector with P1, P2 (parallel RJ45), P3 and P4 terminal blocks and pin table of P1 and P2.

The TapHome connection uses the P4 terminal block:

SolaX X3-IES COM port pin table: P3 pins 7-8 remote 485A/B for datahub, P4 pins 11 (modbus 485A) and 12 (modbus 485B) for external Modbus devices.
BlockPinDefinitionUse with TapHome
P411modbus 485ARS-485 A
P412modbus 485BRS-485 B
P410GNDGround connection
P4912V_COM12 V supply output — not used
P37, 8remote 485A / remote 485BNot used — reserved for SolaX DataHub, EV charger and other SolaX devices

According to the manufacturer, pins 11 and 12 are intended for data acquisition and external control by professional personnel, and the protocol on these pins is Modbus RTU.

Do not connect TapHome to pins 7 and 8 of the P3 block (remote 485). That port serves SolaX accessories such as the DataHub, EV charger and Adapter Box G2. TapHome must be wired to pins 11 (485A) and 12 (485B) of the P4 block.

Wiring to TapHome Core

  1. Connect pin 11 (modbus 485A) to the A terminal and pin 12 (modbus 485B) to the B terminal of an RS-485 bus of the TapHome Core (or of the RS-485 converter that serves the Core).
  2. Where the TapHome side has a ground terminal, connect it to pin 10 (GND) of the P4 block.
  3. The manufacturer lists a CAT5E network cable (0.2 mm²) as the communication wire.

Wiring of the COM terminal block, as described in the user manual:

  1. Loosen the swivel nut of the communication connector, remove the rubber stopper and pull the terminal block out.
  2. Thread the cable through the swivel nut and the connector and strip the insulation.
  3. Insert the wires into ferrules, crimp them and plug them into the terminal block.
  4. Insert the terminal block back into the connector until it clicks, then tighten the swivel nut.

Configuration

Modbus settings on the inverter display

The Modbus interface of the inverter is set in the LCD menu Menu > Setting > Advance Setting > Modbus. The menu shows two items, Baud Rate and Address:

SolaX X3-IES inverter LCD Modbus menu showing Baud Rate 19200 and Address 1.

Advance Setting is protected by the advance password, which only professional installers receive from the SolaX after-sales team. The user password (default 0000) opens only User Setting.

Communication parameters (manufacturer defaults, also the template’s suggested values):

ParameterValue
Baud rate19200 bps
Modbus address (Slave ID)1
Data bits8
ParityNone
Stop bits1

The same values are readable over Modbus: holding register 0x00AF holds the Modbus RTU address and 0x00B0 the baud rate code (4 = 19200; other codes: 0 = 115200, 1 = 57600, 2 = 56000, 3 = 38400, 5 = 14400, 6 = 9600).

RS-485 port function (485CommFunSelect)

Holding register 0x013E (485CommFunSelect) selects the function of the RS-485 port: 0 = Modbus 485, 1 = EV Charge. It must be 0 for TapHome. With value 1 the port is used for EV charger communication and the inverter does not answer TapHome.

Request timing

The manufacturer’s protocol specifies a minimum interval of 1 second between two requests and a response timeout of 1 second. The template therefore suggests a delay of 1000 ms between requests and a read/write timeout of 1000 ms on the Modbus RTU interface.

In TapHome, the template is imported into a Modbus RTU interface of the Core configured with the parameters above, and the only import parameter is the inverter’s Modbus Slave ID (default 1).

Device capabilities

The template is intended for monitoring. Its read-only devices are described below.

Do not use the control devices yet. The template also contains the devices Work mode control, Night charging and Remote power control and their service actions. They currently write to register addresses that the SolaX Modbus protocol V3.29 does not list as write registers, so do not use control by writing for now. Monitoring is not affected.

PV production

  • Solar PV array — electricity meter (read-only). Current power is the sum of the DC power of MPPT1 (input register 0x000A) and MPPT2 (0x000B). Total energy is the total PV yield (0x0094–0x0095, 0.1 kWh). Polled every 15 s.
  • Solar energy — today — variable with today’s PV yield in kWh (0x0096). Polled every 60 s.

Battery

Battery — electricity meter (read-only). Current power is the battery charge/discharge power (0x0016) and total energy is the total energy output by the battery (0x001D–0x001E, 0.1 kWh). The device shows the battery direction as an information message (Discharging, Charging, Idle) and raises the warning BMS not connected when the BMS connection state (0x0017) is 0.

Service attributes: battery SOC, battery voltage, battery current, battery temperature, max./min. cell voltage, max./min. battery temperature, BMS user SOC, BMS SOH, BMS max. charge current and BMS max. discharge current.

Grid exchange

Grid — power and energy — electricity meter (read-only) based on the inverter’s grid meter or CT. Current power is the feed-in power (0x0046–0x0047): positive values mean export to the grid, negative values import from the grid. Total energy is the total energy exported to the grid (0x0048–0x0049, 0.01 kWh). When the grid status (0x001A) reports off-grid, the device shows the information message Off-grid operation.

Service attributes: total exported energy, total imported energy, energy to grid today and total energy to grid at the inverter AC port, power of phases R, S and T, feed-in power of phases R, S and T, and voltage of phase R.

Inverter status

Inverter status — read-only multi-value switch showing the run mode (input register 0x0009):

ValueState
0Waiting
1Checking
2Normal operation
3Fault
4Permanent fault
5Firmware update
6Off-grid waiting
7Off-grid operation
8Self test
9Idle

Service attributes: heatsink temperature, DC bus voltage, number of MPPT channels, PV1 and PV2 voltage, PV1 and PV2 current.

Module diagnostics and parallel systems

The module decodes fault registers of the inverter and reports them as errors:

  • Inverter faults (bits 0–9 of 0x0040): TZ protect fault, grid lost, grid voltage fault, grid frequency fault, PV voltage fault, DC bus voltage fault, battery voltage fault, AC 10-minute voltage fault, DCI overcurrent and DCV overcurrent.
  • Manager fault (0x0043), reported with its fault code.
  • BMS fault (0x0044), reported with its fault code.

Module service attributes: DSP firmware version, ARM firmware version, inverter Slave ID, number of inverters in the parallel system, and the total AC power of phases R, S and T and total battery power of the parallel system (0x01DD and following registers). According to the manufacturer, up to 3 inverters can run in parallel without an X3-PBOX device and up to 10 with an X3-PBOX-60kW-G2 or X3-PBOX-150kW-G2.

Troubleshooting

The inverter does not respond

  • Check that the cable is on P4 pins 11 (485A) and 12 (485B), not on P3 pins 7 and 8.
  • Check the A/B polarity — swap the two wires if the inverter still does not answer — and the ground on P4 pin 10.
  • Check that 485CommFunSelect (0x013E) is 0 (Modbus 485), not 1 (EV Charge).
  • In Advance Setting > Modbus on the display, compare Address with the Slave ID entered in TapHome and Baud Rate with the interface setting (19200 by default). Over Modbus, the address is in register 0x00AF and the baud rate code in 0x00B0 (4 = 19200).
  • Keep the delay between requests at 1000 ms or more; the manufacturer requires at least 1 second between two requests.

Battery values are zero or missing

  • If the Battery device shows BMS not connected, the BMS connection state (0x0017) is 0 (Disconnected) and the inverter has no data from the battery. Check the communication between the battery and the inverter.

Faults on the module

  • Inverter, manager and BMS faults are shown as module errors. Bit names follow the manufacturer’s inverter error code table; manager and BMS faults are reported as numeric codes, which are listed in the manufacturer’s Modbus protocol.

Available devices 8

These devices appear in TapHome after import.

SolaX X3 Hybrid IES Module
Service Attributes
Verzia DSP FW
Verzia ARM FW
Slave ID striedača
Počet striedačov v paralelnej inštalácii
Celkový výkon AC (R-fáza, paralelné)
Celkový výkon AC (S-fáza, paralelné)
Celkový výkon AC (T-fáza, paralelné)
Celkový výkon batérií (paralelné)

SolaX X3 Hybrid IES

Read (module)
var FaultLSB := MODBUSR(A, 64, UInt16);
var FaultMSB := MODBUSR(A, 65, UInt16);
IF (GETBIT(FaultLSB, 0))
ADDERROR(0, "Chyba ochrany TZ")
END
IF (GETBIT(FaultLSB, 1))
ADDERROR(1, "Strata siete")
END
IF (GETBIT(FaultLSB, 2))
ADDERROR(2, "Chyba napätia siete")
END
IF (GETBIT(FaultLSB, 3))
ADDERROR(3, "Chyba frekvencie siete")
END
IF (GETBIT(FaultLSB, 4))
ADDERROR(4, "Chyba napätia FV")
END
IF (GETBIT(FaultLSB, 5))
ADDERROR(5, "Chyba napätia DC zbernice")
END
IF (GETBIT(FaultLSB, 6))
ADDERROR(6, "Chyba napätia batérie")
END
IF (GETBIT(FaultLSB, 7))
ADDERROR(7, "Chyba AC10min napätia")
END
IF (GETBIT(FaultLSB, 8))
ADDERROR(8, "Pretečenie DCI")
END
IF (GETBIT(FaultLSB, 9))
ADDERROR(9, "Pretečenie DCV")
END
var MgrFault := MODBUSR(A, 67, UInt16);
IF (MgrFault > 0)
ADDERROR(10, "Chyba manažéra (kód " + TOSTRING(MgrFault, "F0") + ")")
END
var BMSFaultLSB := MODBUSR(A, 68, UInt16);
var BMSFaultMSB := MODBUSR(A, 69, UInt16);
IF (BMSFaultLSB > 0)
ADDERROR(11, "Chyba BMS (kód " + TOSTRING(BMSFaultLSB, "F0") + ")")
END
Service Attributes
Verzia DSP FW
TOSTRING(MODBUSR(H, 127, UInt16), "F0") + "." + TOSTRING(MODBUSR(H, 125, UInt16), "F0")
Verzia ARM FW
TOSTRING(MODBUSR(H, 128, UInt16), "F0") + "." + TOSTRING(MODBUSR(H, 131, UInt16), "F0")
Slave ID striedača
TOSTRING(MODBUSR(H, 175, UInt16), "F0")
Počet striedačov v paralelnej inštalácii
TOSTRING(MODBUSR(A, 477, UInt16), "F0")
Celkový výkon AC (R-fáza, paralelné)
TOSTRING(MODBUSR(A, 480, LittleEndianInt32), "F0") + " W"
Celkový výkon AC (S-fáza, paralelné)
TOSTRING(MODBUSR(A, 482, LittleEndianInt32), "F0") + " W"
Celkový výkon AC (T-fáza, paralelné)
TOSTRING(MODBUSR(A, 484, LittleEndianInt32), "F0") + " W"
Celkový výkon batérií (paralelné)
TOSTRING(MODBUSR(A, 506, LittleEndianInt32), "F0") + " W"
Solárne FV pole Electricity Meter

Solárne FV pole

Read total consumption
MODBUSR(A, 148, LittleEndianUint32) / 10
Read demand
MODBUSR(A, 10, UInt16) + MODBUSR(A, 11, UInt16)
Batéria Electricity Meter
Service Attributes
SOC batérie
Napätie batérie
Prúd batérie
Teplota batérie
Max. napätie článku
Min. napätie článku
Max. teplota batérie
Min. teplota batérie
BMS SOC (používateľský)
BMS SOH
Max. nabíjací prúd BMS
Max. vybíjací prúd BMS

Batéria

Read total consumption
MODBUSR(A, 29, LittleEndianUint32) / 10
Read demand
MODBUSR(A, 22, Int16)
Read (module)
var SOC := MODBUSR(A, 28, UInt16);
var BDC := MODBUSR(A, 25, UInt16);
IF (BDC = 0)
ADDINFO(0, "Vybíjanie")
END
IF (BDC = 1)
ADDINFO(1, "Nabíjanie")
END
IF (BDC = 2)
ADDINFO(2, "Nečinná")
END
var BMS := MODBUSR(A, 23, UInt16);
IF (BMS = 0)
ADDWARNING(0, "BMS nie je pripojený")
END
Service Attributes
SOC batérie
TOSTRING(MODBUSR(A, 28, UInt16), "F0") + " %"
Napätie batérie
TOSTRING(MODBUSR(A, 20, Int16) / 10, "F1") + " V"
Prúd batérie
TOSTRING(MODBUSR(A, 21, Int16) / 10, "F1") + " A"
Teplota batérie
TOSTRING(MODBUSR(A, 24, Int16), "F0") + " °C"
Max. napätie článku
TOSTRING(MODBUSR(A, 188, UInt16) / 1000, "F3") + " V"
Min. napätie článku
TOSTRING(MODBUSR(A, 189, UInt16) / 1000, "F3") + " V"
Max. teplota batérie
TOSTRING(MODBUSR(A, 186, Int16) / 10, "F1") + " °C"
Min. teplota batérie
TOSTRING(MODBUSR(A, 187, Int16) / 10, "F1") + " °C"
BMS SOC (používateľský)
TOSTRING(MODBUSR(A, 190, UInt16), "F0") + " %"
BMS SOH
TOSTRING(MODBUSR(A, 191, UInt16), "F0") + " %"
Max. nabíjací prúd BMS
TOSTRING(MODBUSR(A, 36, UInt16) / 10, "F1") + " A"
Max. vybíjací prúd BMS
TOSTRING(MODBUSR(A, 37, UInt16) / 10, "F1") + " A"
Sieť — výkon a energia Electricity Meter
Service Attributes
Celková exportovaná energia (sieť)
Celková importovaná energia (sieť)
Energia do siete dnes (AC port)
Celková energia do siete (AC port)
Výkon R-fázy
Výkon S-fázy
Výkon T-fázy
Feedin R-fáza
Feedin S-fáza
Feedin T-fáza
Napätie R-fázy

Sieť — výkon a energia

Read total consumption
MODBUSR(A, 72, LittleEndianUint32) / 100
Read demand
MODBUSR(A, 70, LittleEndianInt32)
Read (module)
var GridStatus := MODBUSR(A, 26, UInt16);
IF (GridStatus = 1)
ADDINFO(0, "Ostrovná prevádzka (OffGrid)")
END
Service Attributes
Celková exportovaná energia (sieť)
TOSTRING(MODBUSR(A, 72, LittleEndianUint32) / 100, "F2") + " kWh"
Celková importovaná energia (sieť)
TOSTRING(MODBUSR(A, 74, LittleEndianUint32) / 100, "F2") + " kWh"
Energia do siete dnes (AC port)
TOSTRING(MODBUSR(A, 80, UInt16) / 10, "F1") + " kWh"
Celková energia do siete (AC port)
TOSTRING(MODBUSR(A, 82, LittleEndianUint32) / 10, "F1") + " kWh"
Výkon R-fázy
TOSTRING(MODBUSR(A, 108, Int16), "F0") + " W"
Výkon S-fázy
TOSTRING(MODBUSR(A, 112, Int16), "F0") + " W"
Výkon T-fázy
TOSTRING(MODBUSR(A, 116, Int16), "F0") + " W"
Feedin R-fáza
TOSTRING(MODBUSR(A, 130, LittleEndianInt32), "F0") + " W"
Feedin S-fáza
TOSTRING(MODBUSR(A, 132, LittleEndianInt32), "F0") + " W"
Feedin T-fáza
TOSTRING(MODBUSR(A, 134, LittleEndianInt32), "F0") + " W"
Napätie R-fázy
TOSTRING(MODBUSR(A, 106, UInt16) / 10, "F1") + " V"
Solárna energia — dnes Variable

Solárna energia — dnes

Read
MODBUSR(A, 150, UInt16) / 10
Stav striedača Multi-value Switch
Values / States: Čakanie · Kontrola · Normálna prevádzka · Porucha · Trvalá porucha · Aktualizácia FW · Čakanie na ostrov · Ostrovná prevádzka · Vlastný test · Nečinný

Stav striedača

Read switch state
MODBUSR(A, 9, UInt16)
Service Attributes
Teplota chladiča
TOSTRING(MODBUSR(A, 8, Int16), "F0") + " °C"
Napätie DC zbernice
TOSTRING(MODBUSR(A, 102, UInt16) / 10, "F1") + " V"
Počet MPPT kanálov
TOSTRING(MODBUSR(A, 27, UInt16), "F0")
Napätie FV1
TOSTRING(MODBUSR(A, 3, UInt16) / 10, "F1") + " V"
Napätie FV2
TOSTRING(MODBUSR(A, 4, UInt16) / 10, "F1") + " V"
Prúd FV1
TOSTRING(MODBUSR(A, 5, UInt16) / 10, "F1") + " A"
Prúd FV2
TOSTRING(MODBUSR(A, 6, UInt16) / 10, "F1") + " A"
Riadenie pracovného režimu Multi-value Switch
Values / States: Vlastná spotreba (Self use) · Priorita FV do siete · Zálohovanie · Manuálny mód

Riadenie pracovného režimu

Read switch state
MODBUSR(H, 139, UInt16)
Write switch state
MODBUSWNE(SH, 139, UInt16, Mu)
Service Attributes
Manuálny mód
MODBUSR(H, 140, UInt16) = 0 ? "Stop" : (MODBUSR(H, 140, UInt16) = 1 ? "Vynútené nabíjanie" : "Vynútené vybíjanie")
Limit exportu výkonu
TOSTRING(MODBUSR(H, 182, UInt16), "F0") + " W"
Max. SOC nabíjania
TOSTRING(MODBUSR(H, 270, UInt16), "F0") + " %"
Min. SOC vybíjania (SelfUse)
TOSTRING(MODBUSR(H, 147, UInt16) >> 8, "F0") + " %"
Nočné nabíjanie Switch
Values / States: Zapnuté · Vypnuté

Nočné nabíjanie

Read switch state
MODBUSR(H, 147, UInt16) & 0xFF
Write switch state
var r := MODBUSR(H, 147, UInt16);
MODBUSWNE(SH, 147, UInt16, (r & 0xFF00) | St);
Vzdialené riadenie výkonu Multi-value Switch
Values / States: Vzdialené riadenie vypnuté · Riadenie výkonom · Riadenie energiou · Riadenie SOC
Service Actions
Nastaviť cieľový výkon
Nastaviť cieľový SOC
Nastaviť timeout
Vynútiť nabíjanie

Vzdialené riadenie výkonu

Read switch state
MODBUSR(A, 256, UInt16)
Write switch state
MODBUSWNE(SH, 256, UInt16, Mu)
Service Attributes
Cieľový výkon
TOSTRING(MODBUSR(A, 258, LittleEndianInt32), "F0") + " W"
Cieľový SOC
TOSTRING(MODBUSR(A, 283, UInt16), "F0") + " %"
Timeout vzdialeného riadenia
TOSTRING(MODBUSR(A, 286, UInt16), "F0") + " s"
Vynútené nabíjanie
MODBUSR(A, 287, UInt16) = 1 ? "Áno" : "Nie"
Service Actions
Nastaviť cieľový výkon
Parameters: Výkon [W] (-30000–30000 pw)
MODBUSW(SH, 258, LittleEndianInt32, pw);
Nastaviť cieľový SOC
Parameters: SOC [%] (10–100 sc)
MODBUSW(SH, 283, UInt16, sc);
Nastaviť timeout
Parameters: Timeout [s] (4–65535 to)
MODBUSW(SH, 286, UInt16, to);
Vynútiť nabíjanie
Parameters: Akcia
MODBUSW(SH, 287, UInt16, fc);
Connection: Modbus RTU • 19200 baud• 8N1 • Slave ID: $[SlaveId]