The SolaX X3-IES series (X3-IES-4K, 5K, 6K, 8K, 10K, 12K and 15K) is a three-phase residential energy storage system that combines a transformerless hybrid inverter with a T-BAT-SYS high-voltage battery. TapHome communicates with the inverter over Modbus RTU on RS-485, using the dedicated Modbus485 pins of the inverter’s COM port.
The template reads PV production, battery state, grid exchange measured by the inverter’s meter or CT, operating status and fault codes. Additional values are available as service attributes.
Hardware connection
COM port and Modbus485 pins
The COM port of the X3-IES is a communication connector with two RJ45 sockets (P1, P2) for parallel operation and two terminal blocks (P3, P4) for external devices.

The TapHome connection uses the P4 terminal block:

| Block | Pin | Definition | Use with TapHome |
|---|---|---|---|
| P4 | 11 | modbus 485A | RS-485 A |
| P4 | 12 | modbus 485B | RS-485 B |
| P4 | 10 | GND | Ground connection |
| P4 | 9 | 12V_COM | 12 V supply output — not used |
| P3 | 7, 8 | remote 485A / remote 485B | Not used — reserved for SolaX DataHub, EV charger and other SolaX devices |
According to the manufacturer, pins 11 and 12 are intended for data acquisition and external control by professional personnel, and the protocol on these pins is Modbus RTU.
Do not connect TapHome to pins 7 and 8 of the P3 block (remote 485). That port serves SolaX accessories such as the DataHub, EV charger and Adapter Box G2. TapHome must be wired to pins 11 (485A) and 12 (485B) of the P4 block.
Wiring to TapHome Core
- Connect pin 11 (modbus 485A) to the A terminal and pin 12 (modbus 485B) to the B terminal of an RS-485 bus of the TapHome Core (or of the RS-485 converter that serves the Core).
- Where the TapHome side has a ground terminal, connect it to pin 10 (GND) of the P4 block.
- The manufacturer lists a CAT5E network cable (0.2 mm²) as the communication wire.
Wiring of the COM terminal block, as described in the user manual:
- Loosen the swivel nut of the communication connector, remove the rubber stopper and pull the terminal block out.
- Thread the cable through the swivel nut and the connector and strip the insulation.
- Insert the wires into ferrules, crimp them and plug them into the terminal block.
- Insert the terminal block back into the connector until it clicks, then tighten the swivel nut.
Configuration
Modbus settings on the inverter display
The Modbus interface of the inverter is set in the LCD menu Menu > Setting > Advance Setting > Modbus. The menu shows two items, Baud Rate and Address:

Advance Setting is protected by the advance password, which only professional installers receive from the SolaX after-sales team. The user password (default 0000) opens only User Setting.
Communication parameters (manufacturer defaults, also the template’s suggested values):
| Parameter | Value |
|---|---|
| Baud rate | 19200 bps |
| Modbus address (Slave ID) | 1 |
| Data bits | 8 |
| Parity | None |
| Stop bits | 1 |
The same values are readable over Modbus: holding register 0x00AF holds the Modbus RTU address and 0x00B0 the baud rate code (4 = 19200; other codes: 0 = 115200, 1 = 57600, 2 = 56000, 3 = 38400, 5 = 14400, 6 = 9600).
RS-485 port function (485CommFunSelect)
Holding register 0x013E (485CommFunSelect) selects the function of the RS-485 port: 0 = Modbus 485, 1 = EV Charge. It must be 0 for TapHome. With value 1 the port is used for EV charger communication and the inverter does not answer TapHome.
Request timing
The manufacturer’s protocol specifies a minimum interval of 1 second between two requests and a response timeout of 1 second. The template therefore suggests a delay of 1000 ms between requests and a read/write timeout of 1000 ms on the Modbus RTU interface.
In TapHome, the template is imported into a Modbus RTU interface of the Core configured with the parameters above, and the only import parameter is the inverter’s Modbus Slave ID (default 1).
Device capabilities
The template is intended for monitoring. Its read-only devices are described below.
Do not use the control devices yet. The template also contains the devices Work mode control, Night charging and Remote power control and their service actions. They currently write to register addresses that the SolaX Modbus protocol V3.29 does not list as write registers, so do not use control by writing for now. Monitoring is not affected.
PV production
- Solar PV array — electricity meter (read-only). Current power is the sum of the DC power of MPPT1 (input register 0x000A) and MPPT2 (0x000B). Total energy is the total PV yield (0x0094–0x0095, 0.1 kWh). Polled every 15 s.
- Solar energy — today — variable with today’s PV yield in kWh (0x0096). Polled every 60 s.
Battery
Battery — electricity meter (read-only). Current power is the battery charge/discharge power (0x0016) and total energy is the total energy output by the battery (0x001D–0x001E, 0.1 kWh). The device shows the battery direction as an information message (Discharging, Charging, Idle) and raises the warning BMS not connected when the BMS connection state (0x0017) is 0.
Service attributes: battery SOC, battery voltage, battery current, battery temperature, max./min. cell voltage, max./min. battery temperature, BMS user SOC, BMS SOH, BMS max. charge current and BMS max. discharge current.
Grid exchange
Grid — power and energy — electricity meter (read-only) based on the inverter’s grid meter or CT. Current power is the feed-in power (0x0046–0x0047): positive values mean export to the grid, negative values import from the grid. Total energy is the total energy exported to the grid (0x0048–0x0049, 0.01 kWh). When the grid status (0x001A) reports off-grid, the device shows the information message Off-grid operation.
Service attributes: total exported energy, total imported energy, energy to grid today and total energy to grid at the inverter AC port, power of phases R, S and T, feed-in power of phases R, S and T, and voltage of phase R.
Inverter status
Inverter status — read-only multi-value switch showing the run mode (input register 0x0009):
| Value | State |
|---|---|
| 0 | Waiting |
| 1 | Checking |
| 2 | Normal operation |
| 3 | Fault |
| 4 | Permanent fault |
| 5 | Firmware update |
| 6 | Off-grid waiting |
| 7 | Off-grid operation |
| 8 | Self test |
| 9 | Idle |
Service attributes: heatsink temperature, DC bus voltage, number of MPPT channels, PV1 and PV2 voltage, PV1 and PV2 current.
Module diagnostics and parallel systems
The module decodes fault registers of the inverter and reports them as errors:
- Inverter faults (bits 0–9 of 0x0040): TZ protect fault, grid lost, grid voltage fault, grid frequency fault, PV voltage fault, DC bus voltage fault, battery voltage fault, AC 10-minute voltage fault, DCI overcurrent and DCV overcurrent.
- Manager fault (0x0043), reported with its fault code.
- BMS fault (0x0044), reported with its fault code.
Module service attributes: DSP firmware version, ARM firmware version, inverter Slave ID, number of inverters in the parallel system, and the total AC power of phases R, S and T and total battery power of the parallel system (0x01DD and following registers). According to the manufacturer, up to 3 inverters can run in parallel without an X3-PBOX device and up to 10 with an X3-PBOX-60kW-G2 or X3-PBOX-150kW-G2.
Troubleshooting
The inverter does not respond
- Check that the cable is on P4 pins 11 (485A) and 12 (485B), not on P3 pins 7 and 8.
- Check the A/B polarity — swap the two wires if the inverter still does not answer — and the ground on P4 pin 10.
- Check that 485CommFunSelect (0x013E) is 0 (Modbus 485), not 1 (EV Charge).
- In Advance Setting > Modbus on the display, compare Address with the Slave ID entered in TapHome and Baud Rate with the interface setting (19200 by default). Over Modbus, the address is in register 0x00AF and the baud rate code in 0x00B0 (4 = 19200).
- Keep the delay between requests at 1000 ms or more; the manufacturer requires at least 1 second between two requests.
Battery values are zero or missing
- If the Battery device shows BMS not connected, the BMS connection state (0x0017) is 0 (Disconnected) and the inverter has no data from the battery. Check the communication between the battery and the inverter.
Faults on the module
- Inverter, manager and BMS faults are shown as module errors. Bit names follow the manufacturer’s inverter error code table; manager and BMS faults are reported as numeric codes, which are listed in the manufacturer’s Modbus protocol.