title: "Shelly Pro 3EM"
description: "Connect the Shelly Pro 3EM to TapHome over the local HTTP RPC API: per-phase current, voltage, power factor and grid import/export energy, no cloud."
url: "https://taphome.com/en/compatibility/shelly-pro-3-em/"
language: en
lastmod: 2026-10-08
generator: hugo
ai:
  topics: ["http","electric-meter","3-phase","wifi","energy-metering","mdns","bidirectional"]
  questions: ["How to integrate Shelly Pro 3EM with TapHome?","What does the Shelly Pro 3EM TapHome template measure?","How to connect Shelly Pro 3EM via HTTP to TapHome?","Can TapHome monitor grid consumption and feed-in separately with Shelly Pro 3EM?","What is the difference between Shelly Pro 3EM and 3EM Gen3 in TapHome?","How to use mDNS hostname for Shelly Pro 3EM in TapHome?"]
---

# Shelly Pro 3EM

Communication: Packet Parser → HTTP

- [Shelly Pro 3EM Product Page](https://www.shelly.com/en/products/shop/shelly-pro-3-em)

> Network address
> 
> TapHome reaches this device at the address entered on import. Give the device a fixed address — an IP reservation in the router, or its mDNS name if it supports one — otherwise the integration stops working when the router changes the address.
> 
> [Network Preparation](https://taphome.com/en/docs/setup/network-preparation/)

## Integration guide

The Shelly Pro 3EM is a professional DIN-rail three-phase energy meter designed for use with external current transformers. It is available in three variants — the Pro 3EM (120A CTs), Pro 3EM-400 (400A CTs), and Pro 3EM-3CT63 (integrated 63A CTs). The device connects to the local network over Wi-Fi or Ethernet (RJ45) and exposes real-time measurements via the Gen2+ HTTP RPC API. TapHome polls the device over HTTP on port 80 — no cloud connection is required.

The template provides eleven devices organized into bidirectional energy metering: per-phase current sensors (L1, L2, L3), per-phase From Grid and To Grid energy meters, and total From Grid and To Grid energy meters. The From Grid devices track energy consumed from the grid, while the To Grid devices track energy fed back (e.g., from solar panels), with the demand value inverted to show feed-in as a positive number.

## Hardware connection

The Shelly Pro 3EM mounts on a standard DIN rail (94 x 19 x 69 mm). It requires four voltage inputs (three phase conductors + neutral) via screw terminals and four external CT inputs (three phase + neutral). The device is powered between any phase and neutral (100-260 V AC, 50/60 Hz).

Key wiring considerations:

- **Voltage inputs:** LA, LB, LC (one per phase) + N (neutral)
- **CT inputs:** Three phase CTs + one neutral CT, connected to the respective CT input jacks
- **Ethernet:** One RJ45 connector for LAN connection (disconnect power before plugging/unplugging the LAN cable)
- **Conductor cross section:** 0.5-2.5 mm² (20-14 AWG), stripped length 6-7 mm, max torque 0.4 Nm

> [!WARNING]
> External protection should be rated at 16 A max with characteristic B or C and a 6 kA minimum interrupting capacity. The operating voltage range is 100-260 V per phase.

## Configuration

The Shelly Pro 3EM connects over Wi-Fi or Ethernet. During TapHome template import, enter the device's IP address (default placeholder `192.168.0.1`).

### Authentication

TapHome does not support HTTP Digest Authentication. Make sure authentication is **disabled** on the Shelly device before adding it to TapHome. This can be configured in the Shelly web UI under Settings → Authentication.

### CT type selection

After connecting the current transformers, configure the CT type via the Shelly web UI or by calling `EM.SetConfig` with the appropriate `ct_type` value. Use `EM.GetCTTypes` to list supported types (typically `120A` and `400A`). If the CT type is not set, the device reports a `ct_type_not_set` error and measurements will not be available.

### Phase-to-phase calibration

The Pro 3EM supports channel-to-channel calibration to improve measurement accuracy between phases. Calibration requires a minimum load of 500 W per channel and takes approximately 5 seconds. Use `EM.PhaseToPhaseCalib` to calibrate and `EM.PhaseToPhaseCalibReset` to revert to factory defaults.

### ECO mode

If ECO mode is enabled on the Shelly device, it may cause communication timeouts due to the 3-second module poll interval used by TapHome. Disable ECO mode for reliable operation.

## Device capabilities

### Per-phase current monitoring

Three current sensor devices (L1 Current, L2 Current, L3 Current) report the instantaneous current in Amps for each phase, read directly from `EM.GetStatus` fields `a_current`, `b_current`, and `c_current`. These are simple sensor values with no unit conversion.

### Per-phase bidirectional energy metering

Each phase has two energy meter devices — From Grid and To Grid:

- **L1/L2/L3 From Grid** — active power consumed from the grid (W, converted to kW) and cumulative energy consumed (Wh, converted to kWh). Each From Grid device also exposes four service attributes: Power Factor, Current [A], Voltage [V], and Total Returned Energy [kWh].
- **L1/L2/L3 To Grid** — active power fed to the grid (W, divided by -1000 to show feed-in as positive kW) and cumulative returned energy (Wh, converted to kWh). The To Grid devices have no service attributes.

The service attributes on From Grid devices provide a complete per-phase picture: real-time current and voltage, power factor for power quality assessment, and a returned energy counter for tracking cumulative feed-in alongside the From Grid consumption counter.

### Total bidirectional energy metering

Two aggregate devices summarize all three phases:

- **Total From Grid** — combined 3-phase active power (kW) and total cumulative energy consumed from the grid (kWh)
- **Total To Grid** — combined 3-phase returned power (kW, inverted) and total cumulative energy fed to the grid (kWh)

All devices use a 3-second poll interval matching the module read cycle.

### Additional capabilities

The Shelly Pro 3EM also natively exposes apparent power per phase and total, neutral current measurement (unique to the Pro model — not available on the 3EM Gen3), grid frequency per phase, total current across all phases, and module diagnostics (WiFi SSID, IP address, signal strength, MAC address). Firmware update and reboot actions are also available via the RPC API. Phase sequence error detection and up to 60 days of 1-minute resolution data logging with CSV/JSON export are supported natively. These capabilities can be added in a future template update.

## Troubleshooting

### Device not responding

1. Verify the Shelly is connected to Wi-Fi or LAN and has a valid IP address
2. Try using the mDNS hostname (`ShellyPro3EM-XXXXXXXXXXXX.local`) instead of the IP address — the IP may have changed after a DHCP renewal
3. Open `http://{device-ip}/rpc/Shelly.GetDeviceInfo` in a browser — if it responds with JSON, the device is reachable
4. Check that TapHome Core and Shelly are on the same network / VLAN

### ct_type_not_set error

If the EM or EMData component reports a `ct_type_not_set` error, the current transformer type has not been configured. Set the CT type via the Shelly web UI or by calling `EM.SetConfig` with the appropriate `ct_type` value. Use `EM.GetCTTypes` to list supported types.

### Phase sequence error

If the `phase_sequence` error appears in `EM.GetStatus`, the phases are connected in reverse order (A-C-B instead of A-B-C). Either rewire the phases in the correct sequence or disable `monitor_phase_sequence` in the EM configuration to suppress the error if the reversed order is intentional.

### Negative or zero values on To Grid devices

The To Grid devices use an inverted conversion (division by -1000) to represent grid feed-in as a positive number. If there is no feed-in (the system is only consuming), the To Grid demand value will show as zero or negative. This is expected behavior — the From Grid device tracks consumption, while To Grid tracks export.

> [!NOTE]
> Gen2+/Gen3 Shelly devices support up to **6 concurrent HTTP connections**. Each polling system (TapHome, Home Assistant, etc.) consumes connections. Avoid running too many integrations on the same device simultaneously.

## How to install in TapHome

### Prerequisites

- Shelly device installed and powered on
- Local Wi-Fi network (2.4 GHz)
- TapHome CCU on the same network

### Step 1 — Connect Shelly to Wi-Fi

**Option A — Shelly app (recommended):**

1. Download the [Shelly app](https://www.shelly.com/en/support/shelly-app) (iOS / Android)
2. Tap **+** → **Add Device** and follow the Bluetooth pairing wizard
3. Enter your Wi-Fi credentials when prompted

**Option B — AP mode (no app):**

1. On first power-up the device creates a hotspot: `ShellyXXX-AABBCCDDEE`
2. Connect your phone/PC to that hotspot
3. Open `http://192.168.33.1` → **Internet & Security** → **Wi-Fi Mode - Client**
4. Enter SSID and password → **Save**

> [!NOTE]
> Shelly only supports **2.4 GHz** networks. 5 GHz networks will not appear in the scan.

### Step 2 — Find the device address

Shelly Gen1 devices support **mDNS** (Zeroconf). You can reach the device using a hostname instead of an IP address:

```
shelly<model>-<MAC>.local
```

For example: `shelly1pm-AABBCCDDEE.local` (MAC address in uppercase hex, no colons).

> [!TIP]
> **Recommended: use the TapHome IP Scanner.** Open the TapHome app and use the **IP Scanner** (Settings → Network → Scan). The scanner will discover devices on your network and show both the IP address and the mDNS hostname. Use the **hostname** instead of the IP address for a more reliable connection — it stays the same even if the device's IP changes after a router reboot.

**Alternative methods** to find the IP address:

- **Shelly app:** Device detail → **Device info** → IP address
- **Shelly web UI:** Connect to the device AP before Wi-Fi setup — the IP is shown after saving
- **Router DHCP table:** Look for a hostname like `shelly1pm-AABBCCDDEE`

### Step 3 — Configure in TapHome

1. In TapHome, add a new **Packet Parser (HTTP)** module
2. **Address:** enter the mDNS hostname (e.g., `shelly1pm-AABBCCDDEE.local`) or IP address from Step 2
3. **Port:** `80` (default, no change needed)
4. Import the template — TapHome will poll `/status` to read device state

> [!NOTE]
> HTTP authentication is disabled by default on Shelly devices. If you have enabled login protection, TapHome does not support HTTP Basic Auth at this time — keep auth disabled for TapHome integration.

## Available devices 11

These devices appear in TapHome after import.

Shelly Pro 3 EM Module

Custom Variables

Read (module)

```taphome
VAR response := SENDHTTPREQUEST("/rpc/EM.GetStatus?id=0");
IF response.IsSuccess
    EMStatus := response.Content;
END;

response := SENDHTTPREQUEST("/rpc/EMData.GetStatus?id=0");
IF response.IsSuccess
    EMDataStatus := response.Content;
END
```

L1 Current Variable Read-only

numeric Unit: A json\_path

Read

```taphome
todouble(PARSEjson(EMStatus, "a_current"))
```

L1 From Grid Electricity Meter Read-only

Phase A active power (kW) and cumulative energy consumed from grid (kWh), with voltage, current, power factor, and returned energy

numeric Unit: kW / kWh json\_path

Service Attributes

|                       |                                                     |
|-----------------------|-----------------------------------------------------|
| Power Factor          |                                                     |
| Current               |                                                     |
| Voltage               |                                                     |
| Total Returned Energy | Phase A cumulative returned (feed-in) energy in kWh |

Read total consumption

```taphome
todouble(PARSEjson(EMDataStatus, "a_total_act_energy"))/1000
```

Read demand

```taphome
todouble(PARSEjson(EMStatus, "a_act_power"))/1000
```

Service Attributes

power factor

```taphome
RETURN(todouble(PARSEjson(EMStatus, "a_pf")));
```

Current \[A]

```taphome
RETURN(todouble(PARSEjson(EMStatus, "a_current")));
```

voltage \[V]

```taphome
RETURN(todouble(PARSEjson(EMStatus, "a_voltage")));
```

Total returned energy \[kWh]

```taphome
RETURN(todouble(PARSEjson(EMDataStatus, "a_total_act_ret_energy"))/1000);
```

L1 To Grid Electricity Meter Read-only

Phase A returned power (kW, inverted) and cumulative energy fed to grid (kWh)

numeric Unit: kW / kWh json\_path

Read total consumption

```taphome
todouble(PARSEjson(EMDataStatus, "a_total_act_ret_energy"))/1000
```

Read demand

```taphome
todouble(PARSEjson(EMStatus, "a_act_power"))/-1000
```

L2 Current Variable Read-only

numeric Unit: A json\_path

Read

```taphome
todouble(PARSEjson(EMStatus, "b_current"))
```

L2 From Grid Electricity Meter Read-only

Phase B active power (kW) and cumulative energy consumed from grid (kWh), with voltage, current, power factor, and returned energy

numeric Unit: kW / kWh json\_path

Service Attributes

|                       |                                                     |
|-----------------------|-----------------------------------------------------|
| Power Factor          |                                                     |
| Current               |                                                     |
| Voltage               |                                                     |
| Total Returned Energy | Phase B cumulative returned (feed-in) energy in kWh |

Read total consumption

```taphome
todouble(PARSEjson(EMDataStatus, "b_total_act_energy"))/1000
```

Read demand

```taphome
todouble(PARSEjson(EMStatus, "b_act_power"))/1000
```

Service Attributes

power factor

```taphome
RETURN(todouble(PARSEjson(EMStatus, "b_pf")));
```

current [A[

```taphome
RETURN(todouble(PARSEjson(EMStatus, "b_current")));
```

voltage \[V]

```taphome
RETURN(todouble(PARSEjson(EMStatus, "b_voltage")));
```

total returned energy \[kWh]

```taphome
RETURN(todouble(PARSEjson(EMDataStatus, "b_total_act_ret_energy"))/1000);
```

L2 To Grid Electricity Meter Read-only

Phase B returned power (kW, inverted) and cumulative energy fed to grid (kWh)

numeric Unit: kW / kWh json\_path

Read total consumption

```taphome
todouble(PARSEjson(EMDataStatus, "b_total_act_ret_energy"))/1000
```

Read demand

```taphome
todouble(PARSEjson(EMStatus, "b_act_power"))/-1000
```

L3 Current Variable Read-only

numeric Unit: A json\_path

Read

```taphome
todouble(PARSEjson(EMStatus, "c_current"))
```

L3 From Grid Electricity Meter Read-only

Phase C active power (kW) and cumulative energy consumed from grid (kWh), with voltage, current, power factor, and returned energy

numeric Unit: kW / kWh json\_path

Service Attributes

|                       |                                                     |
|-----------------------|-----------------------------------------------------|
| Power Factor          |                                                     |
| Current               |                                                     |
| Voltage               |                                                     |
| Total Returned Energy | Phase C cumulative returned (feed-in) energy in kWh |

Read total consumption

```taphome
todouble(PARSEjson(EMDataStatus, "c_total_act_energy"))/1000
```

Read demand

```taphome
todouble(PARSEjson(EMStatus, "c_act_power"))/1000
```

Service Attributes

power factor

```taphome
RETURN(todouble(PARSEjson(EMStatus, "c_pf")));
```

current \[A]

```taphome
RETURN(todouble(PARSEjson(EMStatus, "c_current")));
```

voltage \[V]

```taphome
RETURN(todouble(PARSEjson(EMStatus, "c_voltage")));
```

Total returned energy \[kWh]

```taphome
RETURN(todouble(PARSEjson(EMDataStatus, "c_total_act_ret_energy"))/1000);
```

L3 To Grid Electricity Meter Read-only

Phase C returned power (kW, inverted) and cumulative energy fed to grid (kWh)

numeric Unit: kW / kWh json\_path

Read total consumption

```taphome
todouble(PARSEjson(EMDataStatus, "c_total_act_ret_energy"))/1000
```

Read demand

```taphome
todouble(PARSEjson(EMStatus, "c_act_power"))/-1000
```

Total From Grid Electricity Meter Read-only

Combined 3-phase active power (kW) and total cumulative energy consumed from grid (kWh)

numeric Unit: kW / kWh json\_path

Read total consumption

```taphome
todouble(PARSEjson(EMDataStatus, "total_act"))/1000
```

Read demand

```taphome
todouble(PARSEjson(EMStatus, "total_act_power"))/1000
```

Total To Grid Electricity Meter Read-only

Combined 3-phase returned power (kW, inverted) and total cumulative energy fed to grid (kWh)

numeric Unit: kW / kWh json\_path

Read total consumption

```taphome
todouble(PARSEjson(EMDataStatus, "total_act_ret"))/1000
```

Read demand

```taphome
todouble(PARSEjson(EMStatus, "total_act_power"))/-1000
```

**Connection:** Packet Parser → HTTP • Hostname: `ShellyPro3EM-{MAC}.local`

Possible improvements (14)

- Phase A Apparent Power — Apparent power in VA, available per phase — could complement active power
- Total Apparent Power — Sum of apparent power on all phases \[VA]
- Neutral Current — Current on neutral conductor \[A] — Pro 3EM supports this (unlike 3EM Gen3)
- Grid Frequency — Network frequency in Hz, available per phase — not exposed as device or SA
- Total Current — Sum of current on all three phases \[A]
- MAC Address — No module-level service attributes in this template (unlike 3EM Gen3)
- WiFi SSID — No module-level service attributes in this template (unlike 3EM Gen3)
- Signal Strength — WiFi RSSI in dBm — not polled by module readscript
- Firmware Update — No module-level service actions in this template (unlike 3EM Gen3)
- Reboot — No module-level service actions in this template (unlike 3EM Gen3)
- Uptime — Seconds since last reboot
- Free RAM — Available RAM in bytes
- Total Returned Energy (dedicated) — Already implemented as Total To Grid device (readtotalconsumption), listed for completeness
- Phase Sequence Monitoring — Enable/disable phase sequence error detection via EM.SetConfig

## Import parameters

Enter these values when you import the XML.

| Asked in the app | Default       |
|------------------|---------------|
| IP address       | `192.168.0.1` |

## Sources

- Shelly Gen2+ RPC API Reference
  
  [shelly-api-docs.shelly.cloud](https://shelly-api-docs.shelly.cloud/gen2/) 2026-03-28
- Shelly Gen2+ Sys Component API
  
  [shelly-api-docs.shelly.cloud](https://shelly-api-docs.shelly.cloud/gen2/ComponentsAndServices/Sys/) 2026-03-28
- Shelly Gen2+ WiFi Component API
  
  [shelly-api-docs.shelly.cloud](https://shelly-api-docs.shelly.cloud/gen2/ComponentsAndServices/WiFi/) 2026-03-28
- Home Assistant Shelly Integration (Gen2+)
  
  [www.home-assistant.io](https://www.home-assistant.io/integrations/shelly/) 2026-03-28
- Shelly Pro 3EM Knowledge Base
  
  [kb.shelly.cloud](https://kb.shelly.cloud/knowledge-base/shelly-pro-3em) 2026-03-28
- Shelly Gen2+ EM Component API
  
  [shelly-api-docs.shelly.cloud](https://shelly-api-docs.shelly.cloud/gen2/ComponentsAndServices/EM/) 2026-03-28
- Shelly Gen2+ EMData Component API
  
  [shelly-api-docs.shelly.cloud](https://shelly-api-docs.shelly.cloud/gen2/ComponentsAndServices/EMData/) 2026-03-28

## Related Documentation

- [Packet Parser Integration](https://taphome.com/en/compatibility/packet-parser-guide/)
- [Packet Parser (HTTP, TCP, UDP, FTP, MQTT)](https://taphome.com/en/docs/integration/packet-parser/)
- [Packet parser functions](https://taphome.com/en/docs/script/packet-parser/)
- [Parsing functions](https://taphome.com/en/docs/script/parsing-functions/)