  questions: ["How to integrate Samsung air conditioning indoor units with TapHome?","What does the Samsung MIM-B19N IU TapHome template control?","How to connect Samsung MIM-B19N via RS-485 to TapHome for AC control?","How to configure multi-unit addressing for Samsung indoor units via MIM-B19N?","What is the difference between the Samsung MIM-B19N IU and EHS templates?","How to control Samsung 360 cassette airflow direction via TapHome?","How to enable Samsung Wind-Free mode via TapHome Modbus?"]
---

# Samsung MIM-B19N (IU)

Communication: Modbus RTU

- [Samsung MIM-B19N Product Page](https://www.samsung.com/global/dvms/products/accessory/mim-b19n/)
- [ZimKev MIM-B19N Modbus Repository](https://github.com/ZimKev/MIM-B19n_Modbus)

The Samsung MIM-B19N is a Modbus RTU gateway that connects Samsung air conditioning indoor units -- cassettes, wall units and 360 cassettes -- to TapHome via RS-485. This template is specifically designed for **indoor AC units (IU)**, not heat pumps. For Samsung EHS/HE/HT heat pump units, use the [Samsung MIM-B19N (EHS)](https://taphome.com/en/compatibility/samsung-mim-b19n-ehs/) template. For gateway-level outdoor unit monitoring, see the [Samsung MIM-B19N (GW)](https://taphome.com/en/compatibility/samsung-mim-b19n-gw/) template.

The gateway translates between the Samsung R1/R2 internal bus protocol and standard Modbus RTU, exposing room temperature control, fan speed, operation modes, airflow direction and the Wind-Free function as holding registers. Each MIM-B19N can manage up to 48 indoor units. The gateway address is set using a combination of DIP switches and a rotary switch (range 1--247).

## Hardware connection

### Specifications

- **Power supply:** DC 12 V from CN12 on outdoor unit main board
- **Operating temperature:** -10 °C to +50 °C
- **Protocol:** Modbus RTU Slave, RS-485
- **Baud rate:** 9600, even parity, 1 stop bit, 8 data bits
- **Max units:** 48 indoor units per gateway
- **Max bus length:** 1000 m (RS-485)

### RS-485 wiring

Connect the MIM-B19N to TapHome using a **2-wire RS-485 connection**:

- **A (R1)** --> A+/D+ on TapHome RS-485
- **B (R2)** --> B-/D- on TapHome RS-485

The MIM-B19N draws power from the outdoor unit via the DC 12 V connector (CN12). The Samsung internal communication uses the F1-F2 bus to reach indoor and outdoor units.

> [!WARNING]
> **Important -- RS-485 polarity**
>
> Match the RS-485 polarity between the MIM-B19N and TapHome. Swapped A/B wires will prevent communication. The RED LED on the module blinks when Modbus communication is active -- if it stays off, check the wiring.

### Wiring topology

```text
Outdoor unit ---- F1/F2 ---- MIM-B19N ---- RS-485 (A/B) ---- TapHome Core
  |                              |
  +-- 12V/GND (CN12) -----------+
  |
  +-- F1/F2 ---- Indoor units (cassette, wall, 360)
```

## Configuration

### DIP and rotary switch addressing

The MIM-B19N address is calculated as the **sum of DIP switch values plus the rotary switch value**.

| Switch | Location | ON value |
|--------|----------|----------|
| SW4-1 | DIP | 128 |
| SW4-2 | DIP | 64 |
| SW5-1 | DIP | 32 |
| SW5-2 | DIP | 16 |
| SW1 | Rotary | 0--15 (hex) |

**Recommended:** Address 1 for a single gateway (all DIP switches OFF, rotary switch set to 1). Address 0 is invalid. Valid range is 1--247.

### Indoor unit prerequisite

Before the MIM-B19N can control indoor units, the **"Use of central control" (SEG5)** setting on each indoor unit must be set to **"Use (1)"**. Without this setting, the gateway can read status but cannot send control commands.

### Multi-unit addressing (IU variable)

For systems with multiple indoor units, register addresses shift by 50 per unit using the **IU variable** formula: `base = 50 + IU * 50`.

| Indoor unit | IU value | Base register | Power register |
|-------------|----------|---------------|----------------|
| Unit 0 (first) | 0 | 50 | H:52 |
| Unit 1 | 1 | 100 | H:102 |
| Unit 2 | 2 | 150 | H:152 |

The TapHome template is configured for the first indoor unit (IU=0). For additional units, duplicate the template and adjust the IU variable value in the module scripts.

## Device capabilities

### Room temperature control

- **Room Temperature** (H:base+9 read / H:base+8 write) -- current room temperature and setpoint control with °C x 10 conversion. Setpoint ranges: Cooling 18--30 °C, Heating 16--30 °C

### Unit power and operation mode

- **Power ON/OFF** (H:base+2) -- turns the indoor unit on or off
- **Operation Mode** (H:base+3) -- selects Auto, Cool, Dry, Fan, or Heat mode
- **Fan Speed** (H:base+4) -- selects Auto, Low, Medium, or High

### Airflow control

- **Vertical Air Flow** (H:base+5) -- enables or disables the vertical vane swing
- **360 Air Flow Direction** (H:base+31) -- controls the 360 cassette vane position: Off, Spot, Mid, Wide, Swing, or Individual Control. Only applicable to Samsung 360 cassette units

### Wind-Free function

- **Wind Free** (H:base+30) -- enables Samsung Wind-Free cooling mode, which disperses air through micro-holes instead of direct airflow. Values: 0=Off, 9=WindFree. Only available on Wind-Free compatible indoor units

### Service diagnostics

The module exposes three service attributes for system monitoring:

- **Communication Status** (H:base+0) -- bitfield showing: Exist, Type OK, Ready, Communication error
- **Remote Control Restriction** (H:base+14) -- shows whether the remote controller is locked
- **Wind-Free Function Status** (H:base+30) -- shows whether Wind-Free is active (None, WindFree, Ignored)

One service action is available:

- **Clear Filter Alarm** (H:base+6) -- resets the filter cleaning reminder

The module ReadScript monitors the filter alarm register (H:base+6) and the indoor unit error code (H:base+13), reporting them as warnings and errors in TapHome.

### Additional capabilities

The MIM-B19N register map also exposes per-unit registers for discharge temperature (H:base+10), quiet mode control (H:base+28), away function (H:base+29), and remote control restriction write (H:base+14). These can be added in a future template update.

> [!TIP]
> This template covers **air conditioning indoor units** only. If you have Samsung EHS, HE, or HT heat pump units connected to the same MIM-B19N gateway, use the separate [Samsung MIM-B19N (EHS)](https://taphome.com/en/compatibility/samsung-mim-b19n-ehs/) template for those units.

## LED and 7-segment indicators

| Indicator | Function |
|-----------|----------|
| Y-GRN LED | Blinks during MIM-B19N to outdoor unit communication |
| RED LED | Blinks during Modbus RS-485 communication with BMS/TapHome |

**7-segment error codes:**

| Display | Condition |
|---------|-----------|
| E6 / 16 | All indoor/outdoor communication stopped for >3 minutes |
| E6 / 15 | Specific indoor unit communication stopped for >3 minutes |
| E6 / 04 | Tracking not completed within 10 minutes after power on |
| E6 / 54 | EEPROM error |
| E6 / 34 | Address error |

## Troubleshooting

### No Modbus communication (RED LED not blinking)

1. **Check RS-485 cables:**
   - A wire correctly connected to A+/D+ on TapHome
   - B wire correctly connected to B-/D- on TapHome
   - Verify polarity is not swapped
2. Verify the gateway address using DIP and rotary switches
3. Confirm TapHome is set to: 9600 baud, **even parity**, 1 stop bit, 8 data bits
4. Check that the RS-485 bus length does not exceed 1000 m

### Unit not tracked (Communication Status bits 0--2 not all = 1)

1. Verify indoor unit is powered on and connected to the Samsung F1/F2 bus
2. Check that **"Use of central control" (SEG5)** is set to "Use (1)" on the indoor unit
3. Wait up to 10 minutes for tracking to complete after power-on
4. If 7-segment shows E6/04, reset the MIM-B19N module

### Control commands not taking effect

1. Confirm Communication Status register (H:base+0) shows bits 0--2 all set to 1 (Exist + Type OK + Ready)
2. Check that Remote Control Restriction is not active (H:base+14 = 0x0000)
3. Verify the indoor unit IU address is within range (0--47)
4. Allow at least 10 ms between consecutive Modbus read/write commands

### 360 Air Flow Direction not responding

1. Confirm the indoor unit is a Samsung 360 cassette model -- this register is only available on 360 cassettes
2. Verify the multi-value values match the installed unit's capabilities
3. Check the template is using the correct IU variable for the target unit

## Available devices

Samsung MIM-B19N Module

Service Attributes

|                            |                                                                                           |
|----------------------------|-------------------------------------------------------------------------------------------|
| Communication Status       | reads H:base+0 (UInt16); bitfield: b0=Exist, b1=Type OK, b2=Ready, b3=Communication error |
| Remote Control Restriction | reads H:base+14 (UInt16); 0x0000=No restriction, other=Restriction active                 |
| Wind-Free Function Status  | reads H:base+30 (UInt16); 0=None, 9=WindFree, other=Ignored                               |

Service Actions

|                    |                                                |
|--------------------|------------------------------------------------|
| Clear Filter Alarm | writes H:base+6 (UInt16); 1=Clear filter alarm |

360 Air Flow Direction Multi-value Switch

Controls the 360 cassette vane position — only applicable to Samsung 360 cassette units

Register: H:base+31 Int16 mapped

Values / States: Spot · Mid · Wide · Swing · Individual Control

Fan Speed Multi-value Switch

Controls the indoor unit fan speed

Register: H:base+4 UInt16 numeric

Values / States: Auto · Low · Medium · High

Operation Mode Multi-value Switch

Selects the AC operation mode

Register: H:base+3 UInt16 numeric

Values / States: Auto · Cool · Dry · Fan · Heat

Power ON/OFF Switch

Turns the indoor AC unit on or off

Register: H:base+2 Bool

Values / States: ON · OFF

Room Temperature Thermostat

Current room temperature and setpoint control

Register: H:base+9 → H:base+8 Int16 Unit: °C numeric

Vertical Air Flow Switch

Enables or disables the vertical vane swing

Register: H:base+5 Bool

Values / States: ON · OFF

Wind Free Switch

Samsung Wind-Free cooling mode — disperses air through micro-holes instead of direct airflow

Register: H:base+30 UInt16 numeric

Values / States: ON · OFF

**Connection:** Modbus RTU • 9600 baud• 8E1 • Slave ID: $\[SlaveId]

Possible improvements (6)

- H:base+6 Filter-Cleaning Reminder — 0=No alarm, 1=Filter alarm present. Read via module readscript (ADDWARNING) but not exposed as device. Indoor/ERV/FCU only
- H:base+10 Discharge Temperature — Discharge temperature °C × 10. Available for Indoor units. Read-only
- H:base+13 Indoor Unit Error Code — 0=No error, 100–999=Error code. Read via module readscript (ADDERROR) but not exposed as device
- H:base+14 Remote Control Restriction (write) — Write: 0x0000=No restriction, 0x6363=Restriction. Read exposed as service attribute but write not exposed as service action
- H:base+28 Quiet Control — 0=Silence Off, 1=Silence On. Available for Indoor units but not implemented in template
- H:base+29 Away Function — 0=Outing Off, 1=Outing On. Available for Indoor units but not implemented in template

## Sources

- MIM-B19N Installation Manual — Modbus register table, wiring, DIP switch addressing
  
  [midsummerwholesale.co.uk](https://midsummerwholesale.co.uk/pdfs/mim-b19n-manual.pdf)
- Extended register map with MessageSet IDs for outdoor/indoor hidden registers
  
  [github.com](https://github.com/ZimKev/MIM-B19n_Modbus)
- Samsung Modbus community integration reference
  
  [github.com](https://github.com/glynhudson)

## Related Documentation

- [Modbus Integration](https://taphome.com/en/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/en/docs/integration/modbus/)
- [Simple configuration using templates](https://taphome.com/en/docs/integration/modbus/templates/)
- [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/)
- [Modbus functions](https://taphome.com/en/docs/script/modbus/)
- [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/)