The Midea M-Thermal A Series Split (R32) is an inverter heat pump system consisting of an outdoor unit and a hydronic box. The system communicates with TapHome via Modbus RTU over RS-485 at 9600 baud, exposing holding registers for control and monitoring. The template provides heating and DHW on/off control, forced water heating and forced backup heater switches, operating mode selection, DHW and zone 1 thermostats, temperature sensors, defrost and backup-heater status contacts, fault code and alarm readback, a calculated maximum outlet water temperature, cumulative energy counters, compressor diagnostics and refrigerant pressure monitoring.
The same Modbus register map is used by OEM clones including Hyundai, Concept, Hajdu, Immergas and Clivet Swan heat pumps. The template is compatible with these units when using the same wired controller and hydronic box hardware.
The Modbus register map for this device is community-sourced (Home Assistant community). Register addresses have been verified by multiple users but are not officially documented by Midea.
Hardware connection
RS-485 wiring
The RS-485 Modbus connection is provided through ports H1 and H2 on the wired controller PCB. The wired controller must be connected to the hydraulic module for full Modbus data access.
Connect the RS-485 signal lines:
| Signal | Direction | Port |
|---|---|---|
| BUS1 (A+) | <-> | H2 |
| BUS2 (B-) | <-> | H1 |
Important — Wired controller required
The wired controller must be connected to the hydronic box for Modbus communication to work. Without the wired controller, registers will not be accessible over RS-485.
Technical specifications
- Protocol: Modbus RTU Slave, RS-485
- Baud rate: 9600, no parity, 1 stop bit, 8 data bits
- Default Slave ID: 1 (rotary switch S3 position 0)
- Models: MHA-V4W to MHA-V16W (4-16 kW), D2N8-B and D2RN8-B variants
- Hydronic box: HB-A60/A100/A160/CGN8-B
Configuration
Slave address (S3 rotary switch)
The Modbus slave address is set by rotary switch S3 on the hydronic box main PCB. Position 0 corresponds to slave address 1.

Key components on the hydronic box PCB:
- S3 (label 2) — Rotary dip switch for Modbus slave address
- CN14 (label 21) — Communication with the wired controller
- CN19 (label 20) — Communication between indoor and outdoor unit
- CN30 (label 22) — Communication with wired controller and internal machine parallel
- DIS1 (label 3) — Digital display for error codes
Enabling Modbus communication
- Remove all power from the heat pump system
- Remove the wired controller backplate
- Connect the RS-485 lines to the wired controller: BUS1 (A+) to H2 and BUS2 (B-) to H1
- Access the hydronic box PCB
- Ensure the rotary switch S3 is set to the desired position (position 0 = slave address 1)
- Turn on the heat pump system
When configuring the TapHome module, use Modbus RTU with 9600 baud, no parity, 1 stop bit, 8 data bits. The default slave ID is 1 (S3 position 0). If using a Modbus TCP-to-RTU gateway (such as WaveShare), configure the gateway port to 502 and set the slave ID to match the S3 switch position.
Static IP recommendation
If connecting through a Modbus TCP-to-RTU gateway, assign a static IP address or DHCP reservation to the gateway to prevent connectivity issues when the IP address changes.
Device capabilities
Heating and DHW control
The template uses register H:0 as a bit field to control individual functions:
- Heating (Heat Pump) (H:0 bit 1) — enables or disables heat-pump space heating
- DHW (H:0 bit 2) — enables or disables the domestic hot water function
Each function is controlled independently using GETBIT/SETBIT operations, allowing heating and DHW to be toggled without affecting each other.
Disinfection Status reads H:5 bit 4 as a read-only contact and shows whether the DHW tank disinfection cycle is running.
Forced operation
Two switches start forced functions of the heat pump. Switching on writes 1 to the register, switching off writes 2; the switch shows on while the register holds 1.
- Forced Water Heating (H:7) — forced heating of the domestic hot water tank
- Force IBH (H:9) — forced operation of the internal backup heater (IBH1)
Status contacts
Four read-only contacts expose bits of the heat pump status words:
- Defrosting (H:128 bit 1) — the outdoor unit is running a defrost cycle
- IBH1 Immersion Heater (3 kW) (H:129 bit 0) — the internal 3 kW backup immersion heater is energised
- SV1 3-Way Valve (H:129 bit 4) — the SV1 valve diverts heating water to the DHW tank coil
- TC Alarm (H:129 bit 12) — shows Alarm or Ok
Error Code (H:124) shows the number of the current fault code of the heat pump.
Operating mode
Heat Pump Mode (H:1) selects the operating mode: Auto (1), Cooling (2) or Heating (3). The template presents this as a multi-value switch; the other values of the register are not offered.
DHW thermostat
DHW Temperature reads the current DHW tank temperature from H:115 (T5 sensor) and writes the target temperature to H:4, in the range 20–60 °C. This functions as a thermostat — the current temperature is displayed alongside the setpoint.
Zone 1 thermostat
Zone 1 Target Water Temperature writes the target water temperature of the zone 1 heating circuit (5–65 °C; 5–25 °C in cooling and 25–65 °C in heating) to the low byte of H:2. The register packs two values into one word, so the template writes the low byte with SETBYTE and leaves the high byte untouched. The setpoint is read back from the low byte of H:2, and the current value is the outlet water temperature from H:105.
Temperature monitoring
The template provides seven temperature sensors:
- Calculated Water Temperature (H:110) — final water outlet temperature (T1 sensor)
- Weather-Compensated Target Temperature (H:136) — equithermic curve target temperature calculated by the heat pump controller
- Inlet Water Temperature (H:104) — water entering the heat exchanger (Tw_in sensor)
- Outlet Water Temperature (H:105) — water leaving the heat exchanger (Tw_out sensor)
- Outdoor Temperature (H:107) — outdoor ambient temperature (T4 sensor), polled every 15 seconds
- Heat Exchanger Temperature T3 (H:106) — refrigerant outlet temperature of the air-side heat exchanger in the outdoor unit (T3 sensor)
- DHW Temperature Sensor (H:115) — domestic hot water tank temperature (T5 probe) as a plain read-only sensor, the same probe the DHW thermostat reads
Maximum outlet water temperature
Max Temperature is calculated by the template, not read from the heat pump. It takes the current outdoor temperature (T4, limited to −25 … 43 °C) and looks up the maximum outlet water temperature for it in a table stored in the module — for example 45 °C at −25 °C, 60 °C between −15 and 0 °C, 65 °C between 5 and 19 °C and 55 °C from 35 °C. A smart rule can use it, for example, to keep the DHW setpoint in summer at or below this value, so that the internal backup heater (IBH) is not needed to reach it.
Compressor and performance diagnostics
- Compressor Frequency (H:100) — current inverter compressor speed in Hz
- Compressor Operating Time (H:122) — cumulative compressor run time in hours
- Fan Speed (H:102) — outdoor unit fan speed in RPM (12 speed steps, 200-730 RPM depending on model)
- Capacity (H:140) — current heat pump capacity output (raw value / 100)
- Water Flow (H:138) — water flow rate through the hydronic circuit in m³/h (raw value / 100)
Energy counters
- Total Electricity Consumption (H:143–H:144) — cumulative electricity consumed by the heat pump in kWh, with the current power calculated as outdoor unit current × voltage (H:118 × H:119 / 1000, kW)
- Heat Production (H:145–H:146) — cumulative heat energy delivered by the heat pump in kWh
Both counters are read as 32-bit values spanning two registers.
Electrical monitoring
- Outdoor Unit Voltage (H:119) — supply voltage (protection: single phase >=265 V or <=172 V, error code H7)
- Outdoor Unit Current (H:118) — compressor current draw (protection limits vary by model: 18 A for 4-6 kW, 30 A for 12-16 kW)
- DC Bus Voltage (H:134) — inverter DC bus voltage (raw value x 10)
- DC Bus Current (H:133) — inverter DC bus current
Refrigerant pressure
- Outdoor Unit High Pressure (H:116) — refrigerant high-side pressure in kPa (protection triggers at >4.3 MPa, error code P1)
- Outdoor Unit Low Pressure (H:117) — refrigerant low-side pressure in kPa (protection triggers at <0.14 MPa, error code P0)
Service diagnostics
The module exposes these service attributes:
- Software Version (H:130) — heat pump firmware version number
- T4 0 to T4 35 — part of the maximum outlet water temperature table used by Max Temperature, as fixed values
Additional capabilities
The Midea M-Thermal system also exposes registers for heating curve selection, forced tank booster heater (TBH) control, Smart Grid maximum setpoint, and additional temperature sensors including T1S (final water outlet), Tp (discharge pipe), Th (suction pipe), T1, T2 (liquid pipe) and T2B (gas pipe). Target compressor frequency and the remaining bits of the status words (H:128, H:129) are also available. IBH1, IBH2 and TBH power settings can be configured. These can be added in a future template update.
Troubleshooting
No Modbus communication
- Verify the wired controller is connected to the hydronic box — without it, Modbus registers are not accessible
- Check RS-485 signal connections: BUS1 to H2, BUS2 to H1
- Confirm TapHome is set to: 9600 baud, no parity, 1 stop bit, 8 data bits
- Verify the slave address: check the S3 rotary switch position on the hydronic box PCB (position 0 = address 1)
- If using a TCP-to-RTU gateway, verify the gateway is reachable and the serial port settings match
Communication error (H0 error code)
Error code H0 indicates a communication error between the outdoor unit and the hydronic box. Possible causes:
- Power supply abnormal — check transformer input (220 V AC) and output (13.5 V AC)
- Electromagnetic interference from nearby high-frequency devices — relocate or shield
- Communication wires P, Q, E between outdoor unit and hydraulic module are loose or damaged — reconnect
Temperature sensor errors (E3–E9, H2, H3, Ed, HA, EA codes)
Error codes E3, E4, H2, H3, Ed, HA, E5, E6, E9, EA indicate temperature sensor failures:
- Check the sensor connection on the corresponding PCB port (see PCB layout diagram)
- Measure sensor resistance — if too low, the sensor is short-circuited; if inconsistent with the resistance table, the sensor has failed
- If connections are correct and sensor is functional, the PCB may need replacement
Pressure protection errors
- P0 (low pressure) — suction pressure below 0.14 MPa. Check refrigerant charge, expansion valve operation
- P1 (high pressure) — discharge pressure above 4.3 MPa. Check condenser airflow, fan operation, refrigerant overcharge
- P4 (high discharge temperature) — discharge pipe temperature above 115 °C. Check compressor operation, refrigerant levels
