The LinkedGo ST802-B is a flush-mounted wall thermostat for fan coil units and floor heating, “Powered by Shelly”. It switches the fan coil’s three fan speeds, the fan coil valve and the floor heating valve itself, and has a built-in room temperature and humidity sensor. TapHome talks to it over the local Shelly RPC API (HTTP on port 80, Wi-Fi) — no cloud connection is needed.
The template reads the room temperature and humidity and sets the target temperature, fan speed, working mode, on/off, anti-freeze and target humidity. This is a community template by Libor Kratochvíl.
Hardware connection
The thermostat is mounted in a 60 mm flush wall box, indoors only (IP20). It is powered from 230 V AC mains; the Shelly knowledge base lists an input range of 90–240 V AC, 50/60 Hz. Maximum load is 1 A inductive or 2 A resistive. Installation and every change of the wiring belong to a qualified electrician, with the terminals disconnected from the mains.
Terminals
| Terminal | Function |
|---|---|
| N, L | power supply, neutral and live |
| H, M, Lo | fan high, medium and low speed — 230 V output, 1 A each |
| NO, NC | fan coil valve — relay with normally open and normally closed contact, 230 V |
| FL | floor heating valve — 230 V output |
| C1, C2 | dry contact (digital output) to switch a heat pump or gas boiler on and off |
| 0-10V, GND | analog output for the speed of a DC fan motor, and common |
| A1/B1, A2/B2 | RS485 — not used by this template |

Wiring per thermostat function (parameter H02)
How the fan and valves are wired depends on the system type, which is set on the thermostat by the installer parameter H02. The LinkedGo technical instruction shows one diagram per H02 value:
| H02 | System | Modes offered |
|---|---|---|
| 0 | 2-pipe AC fan coil — fan on H/M/Lo, fan coil valve on NO/NC | cooling, heating, dry, ventilation |
| 1 | DC fan coil — fan speed from the 0-10V output, fan coil valve on NO/NC | cooling, heating, dry, ventilation |
| 2 | floor heating only — floor heating valve on FL | floor heating |
| 3 | AC fan coil cooling + floor heating | fan coil cooling, floor heating |
| 4 | AC fan coil cooling and heating + floor heating | cooling, heating, floor heating, dry, ventilation |
| 6 | DC fan coil cooling + floor heating | fan coil cooling, floor heating, dry, ventilation |
| 7 | DC fan coil cooling and heating + floor heating | cooling, heating, floor heating, dry, ventilation |
| 17 | 4-pipe AC fan coil — cooling valve on NO/NC, heating valve on FL | cooling, heating, dry, ventilation |

Configuration
Connecting the thermostat to Wi-Fi
The thermostat is added to the network with the free Shelly Smart Control app (App Store, Google Play or AppGallery; a free Shelly account is required). Use a 2.4 GHz Wi-Fi network and turn Bluetooth on in the phone before you start.
- Open the Shelly Smart Control app and tap + in the bottom right corner.
- Select Add via Bluetooth and tap Next; a list of supported devices appears.
- Select the thermostat and tap Next.
- Enter the Wi-Fi name and password and tap Add device. Adding can take a few minutes; a success message appears at the end.
- Give the device a name and picture, pick a room and tap Save.
If the app does not find the thermostat, hold the ON/OFF button on the thermostat for 10 seconds and scan again. Once the thermostat is connected, the Wi-Fi signal icon appears on its display.
Fixed IP address
TapHome reaches the thermostat by its IP address. Give it a fixed address — the simplest way is a DHCP reservation for the thermostat’s MAC address in the router — so the address does not change after a router or thermostat restart. You need this address when importing the template.
Password protection off
Leave password protection of the thermostat turned off in the Shelly app. TapHome does not support the HTTP Digest authentication of Shelly Gen2+ devices; with a password set, the thermostat answers HTTP 401 and every TapHome device shows the error “Thermostat asks for a password (HTTP 401)”.
To check it, open http://<thermostat IP>/rpc/Shelly.GetDeviceInfo in a browser on the same network. If it returns JSON without asking for a login, TapHome can read the thermostat.
Temperature unit in °C
Keep the thermostat’s temperature unit set to degrees Celsius. TapHome reads all temperatures as °C; when the thermostat is set to Fahrenheit, the module shows the warning “Thermostat uses degrees Fahrenheit”. The current setting is visible at http://<thermostat IP>/rpc/Service.GetConfig?id=0 ("temp_unit": "C").
Installer parameters on the thermostat
Set the installer parameters on the thermostat’s keypad before connecting it to TapHome, because they decide which modes and set points the thermostat accepts:
- H02 — system type and the working modes the thermostat offers (table above).
- H05 — 0 heating and cooling, 1 cooling only, 2 heating only.
- H23 / H24 — minimum and maximum set point (default 5 °C and 35 °C).
- A05 / A06 — antifreeze protection on/off and its room temperature point (0–21 °C, default 5 °C).
To enter the installer parameters, hold the Mode button for 5 seconds; the display shows the parameter groups (H, P, F …). Select the group and parameter with the up and down buttons, change the value and save it. The full parameter list is in the LinkedGo technical instruction.
Adding the thermostat in TapHome
In TapHome, add the module from this template under a Packet Parser interface and enter the thermostat’s IP address.
Device capabilities
| Device | What it does |
|---|---|
| Thermostat | room temperature, target temperature (5–35 °C, step 0.5 °C) and room humidity |
| Fan speed | Auto, Low, Medium, High |
| Working mode | Cool, Heat, Dry, Ventilation, Floor heating |
| Thermostat on/off | switches the thermostat’s control function on or off |
| Anti-freeze | frost protection on or off |
| Target humidity | humidity set point for the Dry mode (40–75 %) |
Which working modes the thermostat accepts depends on H02. A unit configured for a 2-pipe AC fan coil (H02 = 0) offers Cool, Dry, Heat and Ventilation. If you pick a mode the thermostat does not offer (for example Floor heating without a floor heating valve), the thermostat refuses it and TapHome shows the mode that stays active. A mode the template does not know is shown as an error on the Working mode device.
Module information and service actions
The module shows the Wi-Fi network, IP address, signal strength, MAC address, the service state, the thermostat mode (cool, heat or auto), the temperature unit and the temperature and humidity calibration offsets. It warns when a firmware update is available, when a restart is required, when the thermostat reports a service error and when it is set to degrees Fahrenheit. Service actions: firmware update and reboot.
Which relay output is switched at the moment (fan speed, fan coil valve, floor heating valve) is not available in the Shelly API, so TapHome cannot show it.
Behaviour worth knowing
- After a TapHome Core restart every device reads its value from the thermostat, so a change made on the thermostat’s keypad while Core was off is kept, never overwritten.
- A value outside the thermostat’s range (for example target humidity 80 %, or a set point outside H23–H24) is refused by the thermostat; TapHome then shows the value that stays set.
- Values are polled every 5–15 seconds; a change on the keypad appears in TapHome within that time.
Troubleshooting
All devices show “HTTP 401”
Password protection is turned on in the thermostat. Turn it off in the Shelly app, then check http://<thermostat IP>/rpc/Shelly.GetDeviceInfo in a browser — it must answer without a login prompt.
Devices show “Thermostat answered HTTP …” or no values
- Check that the thermostat shows the Wi-Fi icon and that its IP address has not changed (fixed address or DHCP reservation).
- Open
http://<thermostat IP>/rpc/Shelly.GetDeviceInfofrom a device in the same network as TapHome Core — if it returns JSON, the thermostat is reachable. - Make sure TapHome Core and the thermostat are in the same network or that routing between them is allowed.
Temperatures look wrong
- Check the temperature unit — the module warns when the thermostat is set to Fahrenheit.
- Check the temperature and humidity calibration offsets shown on the module.
Working mode or fan speed shows an error
The thermostat reported a value the template does not know. The Shelly API lists the fan speeds auto, low, medium and high; the LinkedGo technical instruction lists five speeds for a DC fan coil. Check the H02 setting and the value on the thermostat’s display.
Display shows E03
E03 is the LinkedGo alarm code for a room sensor failure. Errors that the thermostat reports through the Shelly API appear on the module as the warning “Thermostat reports: …”.