title: "Jablotron Futura L+"
description: "Control ventilation modes, monitor temperature, humidity and filter wear, and trigger boost/circulation/overpressure timers via Modbus TCP."
url: "https://taphome.com/en/compatibility/jablotron-futura-l/"
language: en
lastmod: 2026-10-08
generator: hugo
ai:
  topics: ["modbus-tcp","air-recovery","heat-recovery-ventilation","ethernet","zone-ventilation"]
  questions: ["How to integrate Jablotron Futura L+ with TapHome?","What does the Jablotron Futura L+ TapHome template measure and control?","How to connect Jablotron Futura L+ via Modbus TCP to TapHome?","What is the difference between the Futura L+ and Futura L/M/S register maps?","How to activate boost or overpressure ventilation on Jablotron Futura L+ via TapHome?","Why are my Modbus writes to the Jablotron Futura L+ being rejected?","How to use TapHome CO2 sensors for Jablotron Futura L+ zone ventilation?","Why do Jablotron Futura L+ zone sensor values show 0 in TapHome?"]
---

# Jablotron Futura L+

Communication: Modbus TCP

- [Jablotron Futura Product Page](https://www.jablotron.com/en/products-and-services/other-products-and-services/energy-recovery-ventilation-of-houses)

> Network address
> 
> TapHome reaches this device at the address entered on import. Give the device a fixed address — an IP reservation in the router, or its mDNS name if it supports one — otherwise the integration stops working when the router changes the address.
> 
> [Network Preparation](https://taphome.com/en/docs/setup/network-preparation/)

## Integration guide

The Jablotron Futura L+ is a heat-recovery ventilation unit (MVHR) with an enthalpy counter-current exchanger, built by JABLOTRON LIVING TECHNOLOGY CZ for residential buildings. TapHome connects directly to the unit via **Modbus TCP over Ethernet** — no gateway or accessory module is required.

The template exposes ventilation mode selection, timed boost/circulation/overpressure functions, filter wear, supply/exhaust/outdoor temperature and humidity, heat-recovery and power metrics, feature enable switches (bypass, heating, cooling, anti-radon, auto-circulation), a temperature setpoint and read/write access to the 8 external-sensor and 8 external-button zones.

> [!WARNING]
> The **Futura L+** has a condensed register address space that differs from the **Futura L/M/S**. A separate TapHome template (`Jablotron Futura L, M, S`) exists for the older models. Importing the wrong template will produce `ILLEGAL_DATA_ADDRESS` errors or silently read junk. Verify the unit model before import.

## Hardware connection

The Futura unit has a single RJ45 Ethernet connector on the main control board (**X1** — LAN). Connect it to the same local network as TapHome Core using a standard Ethernet cable — no additional gateway, converter or accessory is required for TapHome integration.

Only the **LAN connector (X1)** is relevant for TapHome. The RS-485 buses (X2, X3) and AA bus (X6) are reserved for Jablotron's own accessories (Alfa control panels, wall sensors, CoolBreeze, VarioBreeze) and are not exposed for external BMS use.

### Control board connectors

![Jablotron Futura control board connector layout (X1-X6 and T1 button)](https://taphome.com/images/compatibility/jablotron-futura-l/pcb-connectors_hu_3cbf1801a8cb78df.jpg)

| Connector | Type | Function |
|-----------|------|----------|
| **X1** | RJ45 | LAN — Modbus TCP to TapHome, MyJABLOTRON cloud |
| **X2** | Phoenix Contact 3-pin | RS-485 bus — reserved / unused |
| **X3** | Phoenix Contact 4-pin | RS-485 bus for Alfa panels, CO2 sensors, CoolBreeze |
| **X4** | Phoenix Contact 2-pin | NTC 10 kΩ outdoor-temperature sensor |
| **X5** | Phoenix Contact 5-pin | IN/OUT: LED, BST (boost), IN2, IN1 (0–10 V or contact), GND |
| **X6** | Phoenix Contact 2-pin | AA bus (legacy single-panel bus) |
| **T1** | PCB button | Short press = filter init, long press = Bluetooth service mode |

> [!NOTE]
> Analog inputs **IN1/IN2** on X5 (0–10 V or potential-free contact) are an optional parallel BMS channel. Per the installation manual, analog control is superior to CO2 sensors (overrides them) — useful when Modbus TCP is not feasible, but TapHome integration uses only the LAN port.

## Configuration

No activation, DIP switch or service menu is required to enable Modbus TCP on the Futura L+. The TCP server is active by default once the unit is powered and connected to the LAN.

When importing the template in TapHome, provide:

- **IP Address** — the unit's IP on the local network
- **Device address (Unit ID)** — Modbus slave address (fixed value: `1`)

Connection parameters:

| Parameter | Value |
|-----------|-------|
| Protocol | Modbus TCP |
| Port | 502 |
| Device address | 1 |
| Available sockets | 1 (single concurrent client) |
| Firmware minimum | FLA.P.01.06 |
| Register range | IR:0–IR:26, HR:0–HR:273 |

> [!WARNING]
> The Futura L+ accepts **only one Modbus TCP client at a time**. If another system (Home Assistant, custom Modbus client, second TapHome Core) is already connected, TapHome will be unable to open the socket. Disconnect other Modbus TCP clients before importing the template. The MyJABLOTRON cloud link uses outbound HTTPS and does not occupy the Modbus socket.

> [!NOTE]
> Composite registers (uint32, int32) must be read and written in a single Modbus operation — partial reads return `ILLEGAL_DATA_ADDRESS`. The TapHome template batches reads correctly; this error during normal operation typically indicates the wrong template variant (L/M/S vs L+) was imported.

### Optional password protection

Holding register **HR:920** (`user_password`) is **65535 = disabled** by default, meaning Modbus writes are accepted without authentication. If an installer has enabled password protection via the MyJABLOTRON / MyCOMPANY app, Modbus writes will silently fail until the access code is written to HR:900 within the password timeout (default 300 s, HR:922). For typical TapHome installations, leave the password disabled.

## Device capabilities

The template exposes 84 devices covering unit-wide metrics, timed functions, feature toggles, the temperature setpoint and the 8 external-sensor and 8 external-button zones.

### Ventilation mode

- **Ventilation Mode** — selector for fan power via holding register HR:0. Exposed values: Off (0), manual Level 1–5 (1–5), Automatic (6). The template additionally exposes numeric values 7–9 that have no documented meaning in the register map and should be treated as reserved.

### Timed functions

Three timed functions are exposed as multi-value switches with 10 preset durations (Off, 30 s, 60 s, 5 min, 10 min, 15 min, 30 min, 1 h, 1.5 h, 2 h). Each function also exposes a **Remaining Time [s]** service attribute and a service action accepting a custom countdown value (1–7200 s):

- **Boost Function** (HR:1) — maximum ventilation for the selected period
- **Circulation Function** (HR:2) — air recirculation (internal loop) without heat recovery
- **Overpressure Function** (HR:3) — supply > exhaust, useful during fireplace ignition

Reading the register returns the remaining countdown in seconds; writing arms the function.

### Air path sensors

Three of the unit's air-path sensor positions are exposed, each combining temperature and humidity from separate input registers, plus the optional external NTC probe:

| Device | Temperature | Humidity | Description |
|--------|-------------|----------|-------------|
| Outdoor Air | IR:12 | IR:16 | Ambient air before heat recovery |
| Supply Air | IR:13 | IR:17 | Fresh air delivered into the building |
| Exhaust Air | IR:15 | IR:19 | Waste air leaving the building |
| External NTC Sensor | IR:20 | — | Optional NTC 10 kΩ outdoor probe on X4 |

Temperatures are stored as 0.1 °C (`int16`) and scaled to °C in the template; humidity values are scaled to fractions (0–1) from the raw 0.1 % reading.

> [!NOTE]
> The **External NTC Sensor** reports `-99` when no probe is connected to the X4 connector. The template maps this sentinel to NaN so the value does not appear as a valid temperature in TapHome.

### Performance monitoring

- **Heat Recovery** (IR:23) — instantaneous heat recovered from exhaust into supply, in W
- **Power Consumption** (IR:22) — total electrical power draw of the unit, in W
- **Heating Power** (IR:24) — current draw of the internal 350 W electric post-heater, in W
- **Air Flow** (IR:25) — combined supply + exhaust volumetric flow, in m³/h
- **Filter Wear Level** (IR:21) — filter contamination level: 0 % = clean, 100 % = replacement needed. Exposed as a dimmer-style level (0.0–1.0).

### Temperature setpoint

- **Preferred Temperature** (HR:4) — indoor temperature setpoint for the unit's internal control loop, in °C. Reads and writes are scaled ×10 (0.1 °C resolution).

### Feature enable switches

Binary on/off switches controlling unit behavior:

- **Bypass Enable** (HR:7) — automatic bypass of the heat exchanger when free cooling is useful
- **Cooling Enable** (HR:9) — enables the CoolBreeze cooling module (requires accessory)
- **Heating Enable** (HR:15) — enables the internal 350 W electric post-heater
- **Anti-Radon Protection Enable** (HR:6) — reduced recirculation to prevent radon accumulation
- **Auto Circulation** (HR:10) — automatic air-recirculation function
- **Time Program** (HR:5) — weekly time-program scheduling

### External zone sensors (zones 1–8)

The Futura L+ accepts values of up to 8 external CO2/temperature/humidity sensors, one per zone. These are inputs of the Futura: TapHome writes the values into them, it does not read Jablotron sensors from them (see **Using TapHome sensors for zone ventilation** below). For each of the 8 zones the template exposes:

- **Sensor Present** — enables the sensor input for the zone
- **Temperature** — external temperature value (−20 °C to 100 °C, 0.1 °C resolution)
- **Humidity** — relative humidity (0–100 %)
- **CO2** — CO2 level (0–10 000 ppm)

Zone sensor holding-register blocks are at HR:100–175 (10 registers per zone, stride 10).

The measured CO2, temperature and humidity of zones 1–8 (IR:100–173) are available in the L+ Modbus map but not in the template. They can be added as Modbus variables.

### External zone buttons (zones 1–8)

The Futura L+ also supports 8 external wall buttons for quick boost or kitchen-hood activation. Per zone:

- **Button Present** — enables the button input
- **Button Mode** — selects between Boost (0) and Kitchen Hood / Digestoř (1)
- **Button Timer** — countdown (0–10 800 s)
- **Button Activation** — triggers the button action (3-hour time limit)

Zone button holding-register blocks are at HR:200–273 (10 registers per zone, stride 10).

### Module service attributes

Two diagnostic attributes are exposed at module level:

- **MAC Address** (IR:2–IR:4) — the unit's Ethernet MAC, assembled from three 16-bit registers and formatted as a hex string
- **Firmware Version** (IR:0) — the L+ firmware revision (`uint32`)

## Using TapHome sensors for zone ventilation

With VarioBreeze room-by-room ventilation, the Futura pairs the components of a zone by the same DIP switch setting (zone 1–8). Over Modbus it also provides an external sensor input for each of the 8 zones, so TapHome sensors — for example a wall switch with a built-in CO2 sensor — can supply the zone values. The direction is **TapHome → Futura**.

For each room:

1. **Zone number** — the DIP switch setting on the valve of that room (1–8). Use the zone devices with the same number.
2. Turn on **Zone N – Sensor Present** (in the app: *Zona N - Přítomnost externích čidel*).
3. Add a Smart Rule **Formula** for each zone value:
   - **Zone N – CO2** (*Zona N - CO2*) = room CO2 sensor, in ppm
   - **Zone N – Temperature** (*Zona N - Teplota*) = room temperature, in °C
   - **Zone N – Humidity** (*Zona N - vlhkost*) = room humidity **× 100**
4. Set **Ventilation Mode** (*Výkon větrání*) to **Automatic** — levels 1–5 are manual fan levels.

> [!WARNING]
> TapHome stores humidity as a fraction (0–1), the Futura expects percent (0–100). Without **× 100** in the formula, a humidity of 0.45 is written as 0 %.

> [!NOTE]
> Fill all three values of every zone with **Sensor Present** turned on. A zone device without a rule keeps the value 0 and TapHome writes it to the Futura — the zone then reports 0 °C and 0 %.

## Troubleshooting

### Zone sensor values are 0

TapHome writes the current value of each zone device to the Futura on every poll. A zone device without a Smart Rule keeps the value 0, so the Futura receives 0 ppm, 0 °C or 0 %. Add a rule for every value of an active zone and keep **Sensor Present** off for zones that are not used. If only the humidity is 0, the formula is missing the **× 100**.

### The Futura does not react to zone sensors

1. **Ventilation Mode** is set to **Automatic** — levels 1–5 are manual
2. **Zone N – Sensor Present** is turned on for that zone
3. The zone number used in TapHome matches the DIP switch setting on the zone's valve

### No Modbus communication

1. Verify the Ethernet cable is connected to **X1 (LAN)** on the main board — not to any Phoenix Contact terminal
2. Confirm the unit's IP address via the router's DHCP lease table or the MyJABLOTRON app; ensure TapHome Core and the Futura are on the same subnet
3. Check that no firewall is blocking TCP port 502 between TapHome and the unit
4. Ensure no other Modbus TCP client (Home Assistant, diagnostic tool, second TapHome Core) is holding the single available socket — disconnect any such client and retry
5. Verify firmware is **FLA.P.01.06** or newer (visible in MyJABLOTRON)

### ILLEGAL_DATA_ADDRESS errors

Composite registers (uint32 bitmaps, int32 timestamps) must be read in a single Modbus operation. In practice this error during normal TapHome polling indicates the **wrong template variant was imported**. The L/M/S template addresses registers at IR:30–52 / HR:0–17 which do not exist in the L+ map (L+ starts at IR:0 and HR:0 with a condensed layout). Re-import the correct `Jablotron Futura L+` template.

### Modbus writes have no effect

If the unit responds to reads but ignores writes (mode changes, timer starts, enable toggles), the installer may have enabled the user password in MyJABLOTRON. Either disable the password (write 65535 to HR:920 while logged in) or write the access code to HR:900 again within the HR:922 timeout window. For typical TapHome installations the password should remain disabled.

### Temperature or humidity values look wrong

The Futura L+ uses 0.1 °C and 0.1 % encoding for temperatures and humidity. The TapHome template already applies the correct scaling (÷10 for temperature, ÷1000 for humidity in the supply/exhaust/outdoor devices). If values appear 10× or 1000× off, the wrong template (L/M/S) was imported — the scaling factors differ between variants.

## Available devices 84

These devices appear in TapHome after import.

Jablotron Futura L+ Module

Service Attributes

|                  |
|------------------|
| MAC Address      |
| Firmware Version |

Read (module)

```taphome
var Code := MODBUSR(A,6, UInt32);
IF (GETBIT(Code,0), ADDINFO(0,"Aktivní funkce Boost"));
IF (GETBIT(Code,1), ADDINFO(1,"Aktivní funkce Cirkulace"));
IF (GETBIT(Code,2), ADDINFO(2,"Aktivní časový program"));
IF (GETBIT(Code,3), ADDINFO(3,"Aktivní funkce Přetlak"));
IF (GETBIT(Code,4), ADDINFO(4,"Aktivní funkce Dovolená"));
IF (GETBIT(Code,5), ADDINFO(5,"Aktivní funkce Párty"));
IF (GETBIT(Code,6), ADDINFO(6,"Aktivní funkce Noční režim"));
IF (GETBIT(Code,7), ADDINFO(7,"Aktivní funkce Protiradonová ochrana"));
IF (GETBIT(Code,8), ADDINFO(8,"Zařízení je zapnuto, není v režimu snížené spotřeby"));
IF (GETBIT(Code,9), ADDINFO(9,"Probíhá kontrola filtrů"));
IF (GETBIT(Code,10), ADDINFO(10,"Probíhá vysoušení"));
IF (GETBIT(Code,11), ADDINFO(11,"Otevřený Bypass"));
IF (GETBIT(Code,12), ADDINFO(12,"Nízká venkovní teplota, omezená funkce větrání"));
IF (GETBIT(Code,13), ADDINFO(13,"Odstavení po chybě"));
IF (GETBIT(Code,14), ADDINFO(14,"Zařízení se spouští"));
IF (GETBIT(Code,15), ADDINFO(15,"Aktivní servisní režim"));
IF (GETBIT(Code,16), ADDINFO(16,"Teplota odpadního vzduchu < -3°C (splněna podmínka ochrany před zamrznutím)"));
IF (GETBIT(Code,17), ADDINFO(17,"Nouzové vypnutí"));
IF (GETBIT(Code,18), ADDINFO(18,"Nouzové vypnutí"));
IF (GETBIT(Code,19), ADDINFO(19,"Odměřování tlakové ztráty"));
IF (GETBIT(Code,20), ADDINFO(20,"Stand-by"));
IF (GETBIT(Code,21), ADDINFO(21,"Zónový boost"));
IF (GETBIT(Code,22), ADDINFO(22,"Odměřování tlakové ztráty zón"));

Code := MODBUSR(A,8, UInt32);
IF (GETBIT(Code,0), ADDERROR(0,"Chyba senzoru ambient"));
IF (GETBIT(Code,1), ADDERROR(1,"Chyba senzoru indoor"));
IF (GETBIT(Code,2), ADDERROR(2,"Chyba senzoru fresh"));
IF (GETBIT(Code,3), ADDERROR(3,"Chyba senzoru waste"));
IF (GETBIT(Code,4), ADDERROR(4,"Chyba přívodního ventilátoru"));
IF (GETBIT(Code,5), ADDERROR(5,"Chyba odtahového ventilátoru"));
IF (GETBIT(Code,6), ADDERROR(6,"Chyba komunikace s výměníkem"));
IF (GETBIT(Code,7), ADDERROR(7,"Chyba polohy klapek výměníku"));
IF (GETBIT(Code,8), ADDERROR(8,"Chyba komunikace s IO deskou"));
IF (GETBIT(Code,9), ADDERROR(9,"Zablokovaný přívodní ventilátor"));
IF (GETBIT(Code,10), ADDERROR(10,"Zablokovaný odtahový ventilátor"));
IF (GETBIT(Code,11), ADDERROR(11,"Chyba komunikace s Coolbreeze"));
IF (GETBIT(Code,12), ADDERROR(12,"Chyba venkovní jednotky Coolbreeze"));

Code := MODBUSR(A,10, UInt32);
IF (GETBIT(Code,0), ADDWARNING(0,"Neinicializovaný filtr"));
IF (GETBIT(Code,1), ADDWARNING(1,"Filtr je příliš zanesený"));
IF (GETBIT(Code,2), ADDWARNING(2,"Filtr se používá příliš dlouho"));
IF (GETBIT(Code,3), ADDWARNING(3,"Nízké napětí RTC baterie"));
IF (GETBIT(Code,4), ADDWARNING(4,"Příliš vysoké otáčky přívodního ventilátoru"));
IF (GETBIT(Code,5), ADDWARNING(5,"Příliš vysoké otáčky odtahového ventilátoru"));
IF (GETBIT(Code,8), ADDWARNING(8,"Příliš nízká venkovní teplota, omezená funkce větrání"));
IF (GETBIT(Code,9), ADDWARNING(9,"Nesprávná konfigurace zónového větrání - přívod"));
IF (GETBIT(Code,10), ADDWARNING(10,"Nesprávná konfigurace zónového větrání - odtah"));
IF (GETBIT(Code,11), ADDWARNING(11,"Nouzové vypnutí"));
IF (GETBIT(Code,12), ADDWARNING(12,"Chyba komunikace se SuperBreeze"));
IF (GETBIT(Code,13), ADDWARNING(13,"Obecná chyba SuperBreeze"));
```

Service Attributes

MAC adresa

```taphome
var macA := MODBUSR(A, 2, Uint16);
var macB := MODBUSR(A, 3, Uint16);
var macC := MODBUSR(A, 4, Uint16);
TOSTRING(GETBYTE(macA, 0), "X2") + ":" +
TOSTRING(GETBYTE(macA, 1), "X2") + ":" +
TOSTRING(GETBYTE(macB, 0), "X2") + ":" +
TOSTRING(GETBYTE(macB, 1), "X2") + ":" +
TOSTRING(GETBYTE(macC, 0), "X2") + ":" +
TOSTRING(GETBYTE(macC, 1), "X2");
```

Verze firmware

```taphome
MODBUSR(A, 0, Uint32)
```

Heat Recovery Variable Read-only

Instantaneous heat recovered from exhaust air into the supply stream, in watts

Register: IR:23 UInt16 Unit: W

Read

```taphome
MODBUSR(A, 23, Uint16)
```

Power Consumption Variable Read-only

Instantaneous electrical power draw of the unit (fans + electronics + post-heater), in watts

Register: IR:22 UInt16 Unit: W

Read

```taphome
MODBUSR(A, 22, Uint16)
```

Air Flow Variable Read-only

Combined supply and exhaust air flow volume, in m³/h

Register: IR:25 UInt16 Unit: m3/h

Read

```taphome
MODBUSR(A, 25, Uint16)
```

Auto Circulation Switch Read and write

Enables automatic air recirculation (internal loop) when conditions require it

Register: HR:10 Bool boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 10, Bool)
```

Write switch state

```taphome
MODBUSW(H, 10, Bool, St)
```

Time Program Switch Read and write

Enables the weekly time-program schedule configured on the unit

Register: HR:5 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 5, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 5, Uint16, St)
```

Supply Air Temperature Sensor Read-only

Fresh air temperature and humidity delivered into the building (after heat recovery)

Register: IR:13 Int16 Unit: °C direct, /10

Read humidity

```taphome
MODBUSR(A, 17, Int16) / 1000
```

Read temperature

```taphome
MODBUSR(A, 13, Int16) / 10
```

External NTC Sensor Temperature Sensor Read-only

Optional external NTC 10 kΩ outdoor-temperature probe on connector X4; reads -99 when disconnected

Register: IR:20 Int16 Unit: °C direct, /10

Read temperature

```taphome
var x:= MODBUSR(A, 20, Int16) / 10;
if (x = -99, NaN, x)
```

Boost Function Multi-value Switch Read and write

Timed maximum ventilation — select a preset duration; reading returns the remaining countdown

Register: HR:1 UInt16 Unit: s numeric

Values / States: Off · 30 s · 60 s · 5 min · 10 min · 15 min · 30 min · 1 h · 1.5 h · 2 h

Service Actions

|                |
|----------------|
| Boost Function |

Read switch state

```taphome
var x := MODBUSR(H, 1, Uint16);
IF(x = 0, RETURN(0));
IF(x > 5400, RETURN(9));
IF(x > 3600, RETURN(8));
IF(x > 1800, RETURN(7));
IF(x > 900, RETURN(6));
IF(x > 600, RETURN(5));
IF(x > 300, RETURN(4));
IF(x > 60, RETURN(3));
IF(x > 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Write switch state

```taphome
IF(Mu = 0, MODBUSW(H, 1, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 1, Uint16, 30));
IF(Mu = 2, MODBUSW(H, 1, Uint16, 60));
IF(Mu = 3, MODBUSW(H, 1, Uint16, 300));
IF(Mu = 4, MODBUSW(H, 1, Uint16, 600));
IF(Mu = 5, MODBUSW(H, 1, Uint16, 900));
IF(Mu = 6, MODBUSW(H, 1, Uint16, 1800));
IF(Mu = 7, MODBUSW(H, 1, Uint16, 3600));
IF(Mu = 8, MODBUSW(H, 1, Uint16, 5400));
IF(Mu = 9, MODBUSW(H, 1, Uint16, 7200));
```

Service Attributes

Zbývající čas \[s]

```taphome
MODBUSR(H, 1, Uint16)
```

Service Actions

Funkce Boost

Parameters: Čas (1–7200 sec)

```taphome
MODBUSW(H, 1, Uint16, sec)
```

Circulation Function Multi-value Switch Read and write

Timed air recirculation (internal loop, no heat recovery); reading returns the remaining countdown

Register: HR:2 UInt16 Unit: s numeric

Values / States: Off · 30 s · 60 s · 5 min · 10 min · 15 min · 30 min · 1 h · 1.5 h · 2 h

Service Actions

|                      |
|----------------------|
| Circulation Function |

Read switch state

```taphome
var x := MODBUSR(H, 2, Uint16);
IF(x = 0, RETURN(0));
IF(x > 5400, RETURN(9));
IF(x > 3600, RETURN(8));
IF(x > 1800, RETURN(7));
IF(x > 900, RETURN(6));
IF(x > 600, RETURN(5));
IF(x > 300, RETURN(4));
IF(x > 60, RETURN(3));
IF(x > 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Write switch state

```taphome
IF(Mu = 0, MODBUSW(H, 2, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 2, Uint16, 30));
IF(Mu = 2, MODBUSW(H, 2, Uint16, 60));
IF(Mu = 3, MODBUSW(H, 2, Uint16, 300));
IF(Mu = 4, MODBUSW(H, 2, Uint16, 600));
IF(Mu = 5, MODBUSW(H, 2, Uint16, 900));
IF(Mu = 6, MODBUSW(H, 2, Uint16, 1800));
IF(Mu = 7, MODBUSW(H, 2, Uint16, 3600));
IF(Mu = 8, MODBUSW(H, 2, Uint16, 5400));
IF(Mu = 9, MODBUSW(H, 2, Uint16, 7200));
```

Service Attributes

Zbývající čas \[s]

```taphome
MODBUSR(H, 2, Uint16)
```

Service Actions

Funkce Cirkulace

Parameters: Čas (1–7200 sec)

```taphome
MODBUSW(H, 2, Uint16, sec)
```

Overpressure Function Multi-value Switch Read and write

Timed overpressure mode (supply &gt; exhaust) — useful during fireplace ignition; reading returns the remaining countdown

Register: HR:3 UInt16 Unit: s numeric

Values / States: Off · 30 s · 60 s · 5 min · 10 min · 15 min · 30 min · 1 h · 1.5 h · 2 h

Service Actions

|                       |
|-----------------------|
| Overpressure Function |

Read switch state

```taphome
var x := MODBUSR(H, 3, Uint16);
IF(x = 0, RETURN(0));
IF(x > 5400, RETURN(9));
IF(x > 3600, RETURN(8));
IF(x > 1800, RETURN(7));
IF(x > 900, RETURN(6));
IF(x > 600, RETURN(5));
IF(x > 300, RETURN(4));
IF(x > 60, RETURN(3));
IF(x > 30, RETURN(2));
IF(x > 0, RETURN(1));
```

Write switch state

```taphome
IF(Mu = 0, MODBUSW(H, 3, Uint16, 0));
IF(Mu = 1, MODBUSW(H, 3, Uint16, 30));
IF(Mu = 2, MODBUSW(H, 3, Uint16, 60));
IF(Mu = 3, MODBUSW(H, 3, Uint16, 300));
IF(Mu = 4, MODBUSW(H, 3, Uint16, 600));
IF(Mu = 5, MODBUSW(H, 3, Uint16, 900));
IF(Mu = 6, MODBUSW(H, 3, Uint16, 1800));
IF(Mu = 7, MODBUSW(H, 3, Uint16, 3600));
IF(Mu = 8, MODBUSW(H, 3, Uint16, 5400));
IF(Mu = 9, MODBUSW(H, 3, Uint16, 7200));
```

Service Attributes

Zbývající čas \[s]

```taphome
MODBUSR(H, 3, Uint16)
```

Service Actions

Funkce Přetlak

Parameters: Čas (1–7200 sec)

```taphome
MODBUSW(H, 3, Uint16, sec)
```

Filter Wear Level Dimmer Read-only

Filter contamination level — 0 % = clean, 100 % = replacement needed

Register: IR:21 UInt16 Unit: % numeric, /100

Read level

```taphome
MODBUSR(A, 21, Uint16) / 100
```

Exhaust Air Temperature Sensor Read-only

Waste air temperature and humidity leaving the building (before the heat exchanger)

Register: IR:15 Int16 Unit: °C direct, /10

Read humidity

```taphome
MODBUSR(A, 19, Int16) / 1000
```

Read temperature

```taphome
MODBUSR(A, 15, Int16) / 10
```

Bypass Enable Switch Read and write

Enables automatic bypass of the heat exchanger when free cooling is useful

Register: HR:7 UInt16 boolean

Values / States: Povoleno · Zakázáno

Read switch state

```taphome
MODBUSR(H, 7, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 7, Uint16, St)
```

Cooling Enable Switch Read and write

Enables the CoolBreeze active cooling module (requires accessory)

Register: HR:9 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 9, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 9, Uint16, St)
```

Anti-Radon Protection Enable Switch Read and write

Enables anti-radon protection — reduced recirculation to prevent radon accumulation

Register: HR:6 UInt16 boolean

Values / States: Povoleno · Zakázáno

Read switch state

```taphome
MODBUSR(H, 6, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 6, Uint16, St)
```

Heating Enable Switch Read and write

Enables the internal 350 W electric post-heater for supply air temperature control

Register: HR:15 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 15, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 15, Uint16, St)
```

Preferred Temperature Thermostat Read and write

Indoor temperature setpoint for the unit's internal control loop

Register: HR:4 UInt16 Unit: °C direct, /10

Read desired temperature

```taphome
MODBUSR(H, 4, Uint16) / 10
```

Write desired temperature

```taphome
MODBUSW(H, 4, Uint16, Se * 10)
```

Outdoor Air Temperature Sensor Read-only

Outdoor/ambient air temperature and humidity (before heat recovery)

Register: IR:12 Int16 Unit: °C direct, /10

Read humidity

```taphome
MODBUSR(A, 16, Int16) / 1000
```

Read temperature

```taphome
MODBUSR(A, 12, Int16) / 10
```

Heating Power Variable Read-only

Current power drawn by the internal 350 W electric post-heater, in watts

Register: IR:24 UInt16 Unit: W

Read

```taphome
MODBUSR(A, 24, Uint16)
```

Ventilation Mode Multi-value Switch Read and write

Fan power selector — Off, manual Level 1–5, or Automatic (CO2/humidity controlled)

Register: HR:0 UInt16 numeric

Values / States: Off · Level 1 · Level 2 · Level 3 · Level 4 · Level 5 · Automatic

Read switch state

```taphome
MODBUSR(H, 0, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 0, Uint16, Mu)
```

Zone 1 — CO2 Variable Read and write

Register: HR:104 UInt16 Unit: ppm

Read

```taphome
MODBUSR(H, 104, Uint16)
```

Write

```taphome
MODBUSW(H, 104, Uint16, round(Va))
```

Zone 1 — Sensor Present Switch Read and write

Register: HR:100 Bool boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 100, Bool)
```

Write switch state

```taphome
MODBUSW(H, 100, Bool, St)
```

Zone 1 — Temperature Variable Read and write

Register: HR:102 Int16 Unit: °C direct, /10

Read

```taphome
MODBUSR(H, 102, Int16) / 10
```

Write

```taphome
MODBUSW(H, 102, Int16, round(Va * 10))
```

Zone 1 — Humidity Variable Read and write

Register: HR:103 UInt16 Unit: %

Read

```taphome
MODBUSR(H, 103, Uint16)
```

Write

```taphome
MODBUSW(H, 103, Uint16, round(Va))
```

Zone 2 — CO2 Variable Read and write

Register: HR:114 UInt16 Unit: ppm

Read

```taphome
MODBUSR(H, 114, Uint16)
```

Write

```taphome
MODBUSW(H, 114, Uint16, round(Va))
```

Zone 2 — Sensor Present Switch Read and write

Register: HR:110 Bool boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 110, Bool)
```

Write switch state

```taphome
MODBUSW(H, 110, Bool, St)
```

Zone 2 — Temperature Variable Read and write

Register: HR:112 Int16 Unit: °C direct, /10

Read

```taphome
MODBUSR(H, 112, Int16) / 10
```

Write

```taphome
MODBUSW(H, 112, Int16, round(Va * 10))
```

Zone 2 — Humidity Variable Read and write

Register: HR:113 UInt16 Unit: %

Read

```taphome
MODBUSR(H, 113, Uint16)
```

Write

```taphome
MODBUSW(H, 113, Uint16, round(Va))
```

Zone 3 — CO2 Variable Read and write

Register: HR:124 UInt16 Unit: ppm

Read

```taphome
MODBUSR(H, 124, Uint16)
```

Write

```taphome
MODBUSW(H, 124, Uint16, round(Va))
```

Zone 3 — Sensor Present Switch Read and write

Register: HR:120 Bool boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 120, Bool)
```

Write switch state

```taphome
MODBUSW(H, 120, Bool, St)
```

Zone 3 — Temperature Variable Read and write

Register: HR:122 Int16 Unit: °C direct, /10

Read

```taphome
MODBUSR(H, 122, Int16) / 10
```

Write

```taphome
MODBUSW(H, 122, Int16, round(Va * 10))
```

Zone 3 — Humidity Variable Read and write

Register: HR:123 UInt16 Unit: %

Read

```taphome
MODBUSR(H, 123, Uint16)
```

Write

```taphome
MODBUSW(H, 123, Uint16, round(Va))
```

Zone 4 — CO2 Variable Read and write

Register: HR:134 UInt16 Unit: ppm

Read

```taphome
MODBUSR(H, 134, Uint16)
```

Write

```taphome
MODBUSW(H, 134, Uint16, round(Va))
```

Zone 4 — Sensor Present Switch Read and write

Register: HR:130 Bool boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 130, Bool)
```

Write switch state

```taphome
MODBUSW(H, 130, Bool, St)
```

Zone 4 — Temperature Variable Read and write

Register: HR:132 Int16 Unit: °C direct, /10

Read

```taphome
MODBUSR(H, 132, Int16) / 10
```

Write

```taphome
MODBUSW(H, 132, Int16, round(Va * 10))
```

Zone 4 — Humidity Variable Read and write

Register: HR:133 UInt16 Unit: %

Read

```taphome
MODBUSR(H, 133, Uint16)
```

Write

```taphome
MODBUSW(H, 133, Uint16, round(Va))
```

Zone 5 — CO2 Variable Read and write

Register: HR:144 UInt16 Unit: ppm

Read

```taphome
MODBUSR(H, 144, Uint16)
```

Write

```taphome
MODBUSW(H, 144, Uint16, round(Va))
```

Zone 5 — Sensor Present Switch Read and write

Register: HR:140 Bool boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 140, Bool)
```

Write switch state

```taphome
MODBUSW(H, 140, Bool, St)
```

Zone 5 — Temperature Variable Read and write

Register: HR:142 Int16 Unit: °C direct, /10

Read

```taphome
MODBUSR(H, 142, Int16) / 10
```

Write

```taphome
MODBUSW(H, 142, Int16, round(Va * 10))
```

Zone 5 — Humidity Variable Read and write

Register: HR:143 UInt16 Unit: %

Read

```taphome
MODBUSR(H, 143, Uint16)
```

Write

```taphome
MODBUSW(H, 143, Uint16, round(Va))
```

Zone 6 — CO2 Variable Read and write

Register: HR:154 UInt16 Unit: ppm

Read

```taphome
MODBUSR(H, 154, Uint16)
```

Write

```taphome
MODBUSW(H, 154, Uint16, round(Va))
```

Zone 6 — Sensor Present Switch Read and write

Register: HR:150 Bool boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 150, Bool)
```

Write switch state

```taphome
MODBUSW(H, 150, Bool, St)
```

Zone 6 — Temperature Variable Read and write

Register: HR:152 Int16 Unit: °C direct, /10

Read

```taphome
MODBUSR(H, 152, Int16) / 10
```

Write

```taphome
MODBUSW(H, 152, Int16, round(Va * 10))
```

Zone 6 — Humidity Variable Read and write

Register: HR:153 UInt16 Unit: %

Read

```taphome
MODBUSR(H, 153, Uint16)
```

Write

```taphome
MODBUSW(H, 153, Uint16, round(Va))
```

Zone 7 — CO2 Variable Read and write

Register: HR:164 UInt16 Unit: ppm

Read

```taphome
MODBUSR(H, 164, Uint16)
```

Write

```taphome
MODBUSW(H, 164, Uint16, round(Va))
```

Zone 7 — Sensor Present Switch Read and write

Register: HR:160 Bool boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 160, Bool)
```

Write switch state

```taphome
MODBUSW(H, 160, Bool, St)
```

Zone 7 — Temperature Variable Read and write

Register: HR:162 Int16 Unit: °C direct, /10

Read

```taphome
MODBUSR(H, 162, Int16) / 10
```

Write

```taphome
MODBUSW(H, 162, Int16, round(Va * 10))
```

Zone 7 — Humidity Variable Read and write

Register: HR:163 UInt16 Unit: %

Read

```taphome
MODBUSR(H, 163, Uint16)
```

Write

```taphome
MODBUSW(H, 163, Uint16, round(Va))
```

Zone 8 — CO2 Variable Read and write

Register: HR:174 UInt16 Unit: ppm

Read

```taphome
MODBUSR(H, 174, Uint16)
```

Write

```taphome
MODBUSW(H, 174, Uint16, round(Va))
```

Zone 8 — Sensor Present Switch Read and write

Register: HR:170 Bool boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 170, Bool)
```

Write switch state

```taphome
MODBUSW(H, 170, Bool, St)
```

Zone 8 — Temperature Variable Read and write

Register: HR:172 Int16 Unit: °C direct, /10

Read

```taphome
MODBUSR(H, 172, Int16) / 10
```

Write

```taphome
MODBUSW(H, 172, Int16, round(Va * 10))
```

Zone 8 — Humidity Variable Read and write

Register: HR:173 UInt16 Unit: %

Read

```taphome
MODBUSR(H, 173, Uint16)
```

Write

```taphome
MODBUSW(H, 173, Uint16, round(Va))
```

Zone 1 — Button Activation Switch Read and write

Register: HR:203 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 203, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 203, Uint16, St)
```

Zone 1 — Button Timer Variable Read and write

Register: HR:202 UInt16 Unit: s

Read

```taphome
MODBUSR(H, 202, Uint16)
```

Write

```taphome
MODBUSW(H, 202, Uint16, Va)
```

Zone 1 — Button Present Switch Read and write

Register: HR:200 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 200, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 200, Uint16, St)
```

Zone 1 — Button Mode Switch Read and write

Register: HR:201 UInt16 boolean

Values / States: Digestoř · Boost

Read switch state

```taphome
MODBUSR(H, 201, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 201, Uint16, St)
```

Zone 2 — Button Activation Switch Read and write

Register: HR:213 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 213, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 213, Uint16, St)
```

Zone 2 — Button Timer Variable Read and write

Register: HR:212 UInt16 Unit: s

Read

```taphome
MODBUSR(H, 212, Uint16)
```

Write

```taphome
MODBUSW(H, 212, Uint16, Va)
```

Zone 2 — Button Present Switch Read and write

Register: HR:210 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 210, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 210, Uint16, St)
```

Zone 2 — Button Mode Switch Read and write

Register: HR:211 UInt16 boolean

Values / States: Digestoř · Boost

Read switch state

```taphome
MODBUSR(H, 211, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 211, Uint16, St)
```

Zone 3 — Button Activation Switch Read and write

Register: HR:223 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 223, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 223, Uint16, St)
```

Zone 3 — Button Timer Variable Read and write

Register: HR:222 UInt16 Unit: s

Read

```taphome
MODBUSR(H, 222, Uint16)
```

Write

```taphome
MODBUSW(H, 222, Uint16, Va)
```

Zone 3 — Button Present Switch Read and write

Register: HR:220 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 220, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 220, Uint16, St)
```

Zone 3 — Button Mode Switch Read and write

Register: HR:221 UInt16 boolean

Values / States: Digestoř · Boost

Read switch state

```taphome
MODBUSR(H, 221, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 221, Uint16, St)
```

Zone 4 — Button Activation Switch Read and write

Register: HR:233 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 233, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 233, Uint16, St)
```

Zone 4 — Button Timer Variable Read and write

Register: HR:232 UInt16 Unit: s

Read

```taphome
MODBUSR(H, 232, Uint16)
```

Write

```taphome
MODBUSW(H, 232, Uint16, Va)
```

Zone 4 — Button Present Switch Read and write

Register: HR:230 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 230, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 230, Uint16, St)
```

Zone 4 — Button Mode Switch Read and write

Register: HR:231 UInt16 boolean

Values / States: Digestoř · Boost

Read switch state

```taphome
MODBUSR(H, 231, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 231, Uint16, St)
```

Zone 5 — Button Activation Switch Read and write

Register: HR:243 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 243, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 243, Uint16, St)
```

Zone 5 — Button Timer Variable Read and write

Register: HR:242 UInt16 Unit: s

Read

```taphome
MODBUSR(H, 242, Uint16)
```

Write

```taphome
MODBUSW(H, 242, Uint16, Va)
```

Zone 5 — Button Present Switch Read and write

Register: HR:240 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 240, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 240, Uint16, St)
```

Zone 5 — Button Mode Switch Read and write

Register: HR:241 UInt16 boolean

Values / States: Digestoř · Boost

Read switch state

```taphome
MODBUSR(H, 241, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 241, Uint16, St)
```

Zone 6 — Button Activation Switch Read and write

Register: HR:253 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 253, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 253, Uint16, St)
```

Zone 6 — Button Timer Variable Read and write

Register: HR:252 UInt16 Unit: s

Read

```taphome
MODBUSR(H, 252, Uint16)
```

Write

```taphome
MODBUSW(H, 252, Uint16, Va)
```

Zone 6 — Button Present Switch Read and write

Register: HR:250 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 250, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 250, Uint16, St)
```

Zone 6 — Button Mode Switch Read and write

Register: HR:251 UInt16 boolean

Values / States: Digestoř · Boost

Read switch state

```taphome
MODBUSR(H, 251, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 251, Uint16, St)
```

Zone 7 — Button Activation Switch Read and write

Register: HR:263 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 263, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 263, Uint16, St)
```

Zone 7 — Button Timer Variable Read and write

Register: HR:262 UInt16 Unit: s

Read

```taphome
MODBUSR(H, 262, Uint16)
```

Write

```taphome
MODBUSW(H, 262, Uint16, Va)
```

Zone 7 — Button Present Switch Read and write

Register: HR:260 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 260, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 260, Uint16, St)
```

Zone 7 — Button Mode Switch Read and write

Register: HR:261 UInt16 boolean

Values / States: Digestoř · Boost

Read switch state

```taphome
MODBUSR(H, 261, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 261, Uint16, St)
```

Zone 8 — Button Activation Switch Read and write

Register: HR:273 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 273, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 273, Uint16, St)
```

Zone 8 — Button Timer Variable Read and write

Register: HR:272 UInt16 Unit: s

Read

```taphome
MODBUSR(H, 272, Uint16)
```

Write

```taphome
MODBUSW(H, 272, Uint16, Va)
```

Zone 8 — Button Present Switch Read and write

Register: HR:270 UInt16 boolean

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 270, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 270, Uint16, St)
```

Zone 8 — Button Mode Switch Read and write

Register: HR:271 UInt16 boolean

Values / States: Digestoř · Boost

Read switch state

```taphome
MODBUSR(H, 271, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 271, Uint16, St)
```

**Connection:** Modbus TCP • Slave ID: $\[SlaveId]

Possible improvements (12)

- IR:6-7 Operation Mode Bitmap (fut\_mode) — UInt32, bitmap of 24 active mode/status bits — template parses this in readscript for info/error/warning ADDINFO calls but does not expose a dedicated device
- IR:8-9 Error Bitmap (fut\_error) — UInt32, 22 error bits (sensor errors, fan errors, exchanger errors) — parsed in readscript as ADDERROR, not exposed as device
- IR:10-11 Warning Bitmap (fut\_warning) — UInt32, 18 warning bits (filter, battery, zone config) — parsed in readscript as ADDWARNING, not exposed as device
- IR:14 Indoor Air Temperature (fut\_temp\_indoor) — Int16, 0.1°C — indoor/extract air temperature upstream of the exchanger
- IR:18 Indoor Air Humidity (fut\_humi\_indoor) — Int16, 0.1% — indoor/extract air humidity
- IR:26 Heating/Cooling Status (fut\_heat\_cool\_status) — UInt16, bitmask: inner heating, CoolBreeze heating/cooling active; L+ only
- HR:8 Heating Enable (cfg\_heating\_enable, per register map) — UInt16, 0/1 — register map documents L+ cfg\_heating\_enable at HR:8. Template uses HR:15 instead (see Inconsistency Report)
- HR:101, 111, …, 171 External Sensor Invalidate (ext\_sens\_invalidate\[1–8]) — UInt16 bitmask per zone — bit0=temp, bit1=humidity, bit2=CO2, bit3=floor temp invalidation flags
- HR:105, 115, …, 175 External Floor Temperature (ext\_sens\_t\_floor\[1–8]) — Int16, 0.1°C per zone — floor temperature sensor channel, R/W
- HR:900 Access Code — UInt16 — write to unlock service registers after user\_password is set
- HR:920 User Password — UInt16, 65535 = disabled — gates Modbus writes when enabled by installer
- HR:922 Password Timeout — UInt16, default 300 s — auto-logout after inactivity

## Import parameters

Enter these values when you import the XML.

| Asked in the app | Default       |
|------------------|---------------|
| Slave ID         | `1`           |
| IP address       | `192.168.1.0` |

## Sources

- Jablotron Futura Modbus TCP Register Map
  
  2026-04-22
  
  [PDF](https://taphome.com/compatibility/devices/jablotron-futura-l/manufacturer/FU_TCP_TXT_EN.pdf)
- Jablotron Futura Installation Manual (EN, v6.2)
  
  [www.jablotron.com](https://www.jablotron.com/file/edee/ke-stazeni/_jlt/_en/fu_doc_im_en62.pdf) 2026-04-22
  
  [PDF](https://taphome.com/compatibility/devices/jablotron-futura-l/manufacturer/futura-installation-manual.pdf)
- Home Assistant Jablotron Futura Integration
  
  [github.com](https://github.com/tomas-kulhanek/ha-jablotron-futura) 2026-04-22

Manufacturer documents are © their respective owners. They are provided as published by the manufacturer, for reference only.

## Related Documentation

- [Modbus Integration](https://taphome.com/en/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/en/docs/integration/modbus/)
- [Simple configuration using templates](https://taphome.com/en/docs/integration/modbus/templates/)
- [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/)
- [Modbus functions](https://taphome.com/en/docs/script/modbus/)
- [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/)