TapHome

Helios easyControls 3.0

Modbus RTU
Submitted by
Last updated: 03. 2026

The Helios easyControls 3.0 is a building control system interface for Helios KWL ventilation units with heat recovery. It communicates with TapHome via Modbus RTU over RS-485, providing access to CO2 and humidity sensor readings, fan speed monitoring and configuration, ventilation mode switching (Home, Away, Boost, Fireplace), and timer management.

The system uses holding registers in the range H:4353 to H:21772. Temperature values are transmitted in centiKelvin (cK), where 0 degrees C equals 27315 cK.

Hardware connection

RS-485 wiring

The Helios KWL unit exposes an RS-485 Modbus RTU interface on its PCB terminal block. Multiple units can be daisy-chained on the same bus with a 120 ohm termination resistor on the last unit.

Helios easyControls Modbus RTU RS-485 wiring diagram showing master-slave daisy chain with 120 ohm termination

Connect using a 3-wire RS-485 connection to the KWL unit’s terminal block:

  • MB_A (Data+) to A+/D+ on TapHome RS-485
  • MB_B (Data-) to B-/D- on TapHome RS-485
  • GND to GND on TapHome power supply

The last unit on the bus requires a 120 ohm termination resistor between MB_A and MB_B.

Important – Grounding

The GND wire must be connected between the Helios unit and the TapHome power supply. Without proper grounding, communication errors may occur.

Configuration

Enabling Modbus communication

The Modbus RTU default settings can be changed via the KWL-BE Touch panel or via the unit’s internal web server.

Helios easyControls 3.0 Modbus settings screen showing address, baud rate, parity and stop bit configuration

Default Modbus parameters:

ParameterDefault value
Address1
Baud rate19200
ParityEven
Stop bit1

Configure TapHome to match: Set the RS-485 bus to 19200 baud, even parity, 1 stop bit. Use Slave ID 1 (or the address configured on the unit).

Profile priority

If more than one profile is active simultaneously, the profile with higher priority overrides the lower-priority profile. The priority order (highest to lowest) is:

  1. Timer configurable input (assigned to digital inputs)
  2. Fireplace function
  3. Boost ventilation
  4. Home/Away

For example, if both the fireplace function and boost ventilation profiles are active at the same time, the fireplace function overrides the boost ventilation due to its higher priority.

Device capabilities

CO2 monitoring

CO2 Value (H:4364) reads the highest CO2 measurement across all connected CO2 sensors in PPM. If no CO2 sensor is connected, the value reads 0 and a warning is generated in TapHome.

The device exposes seven service attributes:

  • CO2 Sensor 0 through CO2 Sensor 5 (H:4379 to H:4384) – individual sensor readings in PPM. A value of 65535 indicates no sensor connected at that position.
  • CO2 Threshold (H:20491) – the current CO2 control threshold (range 500 to 2000 PPM).

A service action CO2 Threshold allows setting the CO2 threshold value for automatic ventilation adjustment.

Fan speed monitoring and profiles

Fan Speed (H:4353) displays the current fan speed as a percentage (0 to 100%). This represents the actual running speed of the ventilation unit.

Service attributes expose the configured fan speeds for each profile:

  • Away Fan Speed (H:20501) – fan speed in Away profile
  • Home Fan Speed (H:20507) – fan speed in Home profile
  • Boost Fan Speed (H:20513) – fan speed in Boost profile
  • Boost Air Target Temperature (H:20514) – supply air target temperature in Boost profile (centiKelvin to degrees C conversion)
  • Boost CO2 Control and Boost RH Control (H:20512, H:20511) – enable/disable CO2 and humidity-based automatic adjustment in Boost mode

Two service actions allow configuring fan parameters:

  • Fan Speed Setup – sets fan speed percentages for Home, Away and Boost profiles simultaneously
  • Boost Set Up – configures the Boost profile including fan speed, supply air target temperature, and CO2/RH control toggles
Internal sensor (temperature and humidity)

Internal Sensor (H:4369/H:4370) reads temperature and relative humidity from the built-in multisensor. The temperature uses 12-bit internal encoding and the humidity is divided by 100 to get the percentage value.

This device exposes extensive service attributes for monitoring the ventilation system:

Air temperatures (all in centiKelvin, converted to degrees C):

  • Extract Air Temperature (H:4354) – air entering the heat recovery cell from indoors
  • Exhaust Air Temperature (H:4355) – air leaving the heat recovery cell to outdoors
  • Outdoor Air Temperature (H:4356) – fresh air entering the unit from outside
  • Supply Air Temperature (H:4358) – conditioned air delivered to rooms after the heater

Humidity sensors:

  • RH Sensor 0 through RH Sensor 5 (H:4373 to H:4378) – individual relative humidity readings in percent. A value of 65535 indicates no sensor connected.
  • RH Basic Level (H:20490) – the calculated or manually set RH basic level (65535 if not yet calculated)
  • RH Level Mode (H:20543) – 0 for Automatic Level Update, 1 for Manual

System status:

  • Cell State (H:4616) – heat recovery cell operation: 0 = Heat Recovery, 1 = Cool Recovery, 2 = Bypass, 3 = Defrosting
  • Filter Change Date (H:20546 to H:20548) – last filter change date (day, month, year)
  • Filter Change Interval (H:20537) – interval in days for the filter change indicator (30 to 365)

Service actions on the Internal Sensor device:

  • Filter Change Date – records a new filter change date
  • RH Basic Level – sets the humidity reference level (0 to 100%)
  • RH Level Mode – selects automatic or manual humidity level control
Ventilation mode control

Mode (H:4609) is a multi-value switch controlling the ventilation profile with four states:

ValueModeDescription
0HomeNormal ventilation with home profile settings
1AwayReduced ventilation for unoccupied periods
2BoostIntensive ventilation (timer-based via H:21766)
3FireplacePositive-pressure mode for homes with a fireplace (timer-based via H:21767)

The Mode device exposes twelve service attributes showing per-profile configuration:

  • Away settings: fan speed, supply air target, RH control, CO2 control
  • Home settings: fan speed, supply air target, RH control, CO2 control
  • Fireplace fan speeds: separate extract and supply fan speed percentages
  • Weekly Timer state (enabled/disabled) and WeekDay (1 = Monday through 7 = Sunday)

Five service actions allow full profile configuration:

  • Away Set Up / Home Set Up – configures fan speed, supply air target temperature, RH and CO2 control for each profile
  • Fan Speed Set Up – sets Home, Away, and Boost fan speed percentages simultaneously
  • Fireplace Set Up – configures extract and supply fan speeds for fireplace mode
  • Weekly Timer – enables or disables the weekly timer program
Module-level service diagnostics

The module exposes nine service attributes for system monitoring:

  • Date and Time – current unit clock (day, month, year, hours, minutes)
  • Fireplace Timer and Fireplace Time – fireplace mode timer state and duration in minutes
  • Boost Timer and Boost Time – boost ventilation timer state and duration in minutes
  • Extra Timer – configurable digital input timer state
  • Weekly Timer – weekly program state (enabled/disabled)
  • Filter Change Date – last filter change date

Four module-level service actions:

  • Set Date and Time – sets the unit clock (year, month, day, hour, minute)
  • Timers Control – toggles boost, fireplace, and extra timers on/off
  • Timers Set Up – configures boost and fireplace timer durations (1 to 1440 minutes)
  • Filter Change – records a filter change date
Additional capabilities

The Helios easyControls 3.0 also exposes registers for four individual air temperatures (outdoor, extract, exhaust, supply) as standalone sensor devices, a separate RH aggregate value, an optional external temperature sensor (H:4389), and boost/fireplace timer remaining time counters. These are currently available as service attributes on the Internal Sensor and Mode devices. They can be added as standalone TapHome devices in a future template update.

The four air temperature sensors (outdoor, extract, exhaust, supply) are accessible as service attributes on the Internal Sensor device. If standalone temperature devices are needed, they can be added as custom Modbus devices in TapHome using the corresponding register addresses with centiKelvin-to-Celsius conversion (subtract 27315, divide by 100).

Troubleshooting

No Modbus communication
  1. Check RS-485 cables:
    • MB_A correctly connected to A+/D+ on TapHome
    • MB_B correctly connected to B-/D- on TapHome
    • GND connected to TapHome power supply ground – most common issue
  2. Verify the Modbus Slave address matches the unit configuration (default: 1)
  3. Check the 120 ohm termination resistor on the last unit
  4. Confirm TapHome is set to: 19200 baud, even parity, 1 stop bit
  5. Measure voltage between MB_A and MB_B – should be 1.5 to 5 V at idle
CO2 or RH sensor warnings

If TapHome shows “No CO2 sensor” or “No RH sensor” warnings:

  1. Verify the external CO2/RH sensors are physically connected to the KWL unit
  2. Check individual sensor readings in the service attributes (CO2 Sensor 0 through 5, RH Sensor 0 through 5) – a value of 65535 indicates no sensor at that position
  3. If all sensors show 65535, check the sensor wiring at the KWL terminal block
Temperature readings incorrect

Temperature values are transmitted in centiKelvin. If readings appear as large numbers (e.g., 29315 instead of 20 degrees C):

  1. Verify TapHome is applying the conversion correctly
  2. The correct formula is: Temperature in degrees C = (cK value - 27315) / 100
  3. Valid range for temperature registers is 21000 to 33224 cK (approximately -63 degrees C to +59 degrees C)
easyControls 2.0 compatibility

The easyControls 2.0 system uses a non-standard Modbus TCP/IP protocol with ASCII-encoded variable names. It is not compatible with this template or with standard TapHome Modbus integration. Only easyControls 3.0 units with Modbus RTU support can use this template.

Available devices

Helios easyControls 3.0 Module
Service Attributes
Date
Time
Fireplace Timer
Fireplace TimeFireplace timer duration in minutes
Boost Timer
Boost TimeBoost ventilation timer duration in minutes
Extra TimerConfigurable digital input timer state
Weekly Timer
Filter Change Date
Service Actions
Set Date and Time
Timers ControlToggles boost, fireplace and extra timers on or off
Timers Set UpConfigures boost and fireplace timer durations (1 to 1440 minutes)
Filter ChangeRecords the date of a filter replacement

Helios

Service Attributes
Date
ModbusR(H, 4851, Uint16) 
+ "." + ModbusR(H, 4852, Uint16) 
+ " 20" + ModbusR(H, 4853, Uint16)
Time
var min := ModbusR(H, 4849, Uint16);

ModbusR(H, 4850, Uint16) + ":" + IF(min < 10, "0", "") + min
Fireplace Timer
IF(MODBUSR(H, 21767, Uint16) > 0, "ON", "OFF")
Fireplace Time
MODBUSR(H, 20545, Uint16) + " min";
Boost Timer
IF(MODBUSR(H, 21766, Uint16) > 0, "ON", "OFF")
Boost Time
MODBUSR(H, 20544, Uint16) + " min";
Extra Timer
IF(MODBUSR(H, 21772, Uint16) > 0, "ON", "OFF")
Weekly Timer
IF(MODBUSR(H, 4615, Uint16) > 0, "Enabled", "Disabled")
Filter Change Date
ModbusR(H, 20546, Uint16) 
+ "." + ModbusR(H, 20547, Uint16) 
+ " 20" + ModbusR(H, 20548, Uint16)
Service Actions
Set Date and Time
Parameters: Year 20__ (1–99 Y), Month (1–12 Mo), Day (1–31 Da), Hours (0–23 Ho), Minutes (0–59 Min)
ModbusW(H, 4849, Uint16, Min);
ModbusW(H, 4850, Uint16, Ho);
ModbusW(H, 4851, Uint16, Da);
ModbusW(H, 4852, Uint16, Mo);
ModbusW(H, 4853, Uint16, Y);
Timers Control
Parameters: Boost Timer (On / Off), Fireplace Timer (On / Off), Extra Timer (On / Off)
ModbusWNE(H, 21766, Uint16, bt);
ModbusWNE(H, 21767, Uint16, ft);
ModbusWNE(H, 21772, Uint16, et);
Timers Set Up
Parameters: Boost Time (1–1440 btt), Fireplace Time (1–1440 ftt)
MODBUSWNE(H, 20544, Uint16, btt);
MODBUSWNE(H, 20545, Uint16, ftt);
Filter Change
Parameters: Day (1–31 Da), Month (1–12 Mo), Year (1–99 Y)
ModbusW(H, 20546, Uint16, Da);
ModbusW(H, 20547, Uint16, Mo);
ModbusW(H, 20548, Uint16, Y);
CO2 Value Dimmer Read-only

Highest CO2 measurement across all connected sensors in PPM — warns if no sensor is connected

Register: H:4364 UInt16 Unit: PPM numeric
Service Attributes
CO2 Sensor 0
CO2 Sensor 1
CO2 Sensor 2
CO2 Sensor 3
CO2 Sensor 4
CO2 Sensor 5
CO2 ThresholdCO2 control threshold for automatic ventilation adjustment (500 to 2000 PPM)
Service Actions
CO2 ThresholdSets the CO2 threshold for automatic ventilation control

CO2 Value

Read (module)
IF(MODBUSR(H, 4364, Uint16)=0, ADDWARNING("No CO2 sensor"));
Read level
MODBUSR(H, 4364, Uint16) / 1000000
Service Attributes
CO2 Sensor 0
var press := MODBUSR(H, 4379, Uint16);
IF(press=65535, "No sensor", press/1000000);
CO2 Sensor 1
var press := MODBUSR(H, 4380, Uint16);
IF(press=65535, "No sensor", press/1000000);
CO2 Sensor 2
var press := MODBUSR(H, 4381, Uint16);
IF(press=65535, "No sensor", press/1000000);
CO2 Sensor 3
var press := MODBUSR(H, 4382, Uint16);
IF(press=65535, "No sensor", press/1000000);
CO2 Sensor 4
var press := MODBUSR(H, 4383, Uint16);
IF(press=65535, "No sensor", press/1000000);
CO2 Sensor 5
var press := MODBUSR(H, 4384, Uint16);
IF(press=65535, "No sensor", press/1000000);
Co2 Threshold
MODBUSR(H, 20491, Uint16) + " PPM"
Service Actions
CO2 Threshold
Parameters: Threshold (500–2000 co)
MODBUSW(H, 20491, Uint16, (co))
Fan Speed Dimmer Read-only

Current ventilation fan speed as percentage (0 to 100%)

Register: H:4353 UInt16 Unit: % numeric
Service Attributes
Away Fan Speed
Home Fan Speed
Boost Fan Speed
Boost Air Target TemperatureSupply air target temperature in Boost profile
Boost CO2 Control
Boost RH Control
Service Actions
Boost Set UpConfigures Boost profile — fan speed, supply air target, RH and CO2 control
Fan Speed SetupSets fan speed percentages for Home, Away and Boost profiles

Fan Speed

Read level
MODBUSR(H, 4353, Int16) / 100
Service Attributes
Away Fan Speed
MODBUSR(H, 20501, Uint16) + "%";
Home Fan Speed
MODBUSR(H, 20507, Uint16) + "%";
Boost Fan Speed
MODBUSR(H, 20513, Uint16) + "%";
Boost Air Target Temperature
(MODBUSR(H, 20514, UInt16) - 27315)/100 + "°C"
Boost CO2 Control
IF(MODBUSR(H, 20512, Uint16) > 0, "Enabled", "Disabled")
Boost RH Control
IF(MODBUSR(H, 20511, Uint16) > 0, "Enabled", "Disabled")
Service Actions
Boost Set Up
Parameters: Fan Speed [%] (1–100 fsb), Supply Air [5-25°C] (5–25 sab), RH Control (Enabled / Disabled), CO2 Control (Enabled / Disabled)
MODBUSWNE(H, 20511,Uint16,rhb);
MODBUSWNE(H, 20512, Uint16, cob);
MODBUSWNE(H,20513, Uint16, fsb);
MODBUSWNE(H, 20514, UInt16, (sab*100) + 27315);
Fan Speed Setup
Parameters: Home (0–100 ho), Away (0–100 aw), Boost (0–100 bo)
MODBUSW(H, 20501, Uint16, aw);
MODBUSW(H, 20507, Uint16, ho);
MODBUSW(H, 20513, Uint16, bo);
Internal Sensor Temperature Sensor Read-only

Built-in temperature and humidity multisensor with air quality monitoring, filter status and heat recovery cell state

Register: H:4369 Int16 Unit: °C numeric
Service Attributes
Filter Change Date
Filter Change IntervalDays between filter change reminders (30 to 365)
Cell StateHeat recovery cell operation — Heat Recovery, Cool Recovery, Bypass, or Defrosting
Exhaust Air TemperatureAir leaving the heat recovery cell to outdoors
Extract Air TemperatureAir entering the heat recovery cell from indoors
Outdoor Air TemperatureFresh air entering the unit from outside
Supply Air TemperatureConditioned air delivered to rooms after the heater
RH Sensor 0
RH Sensor 1
RH Sensor 2
RH Sensor 3
RH Sensor 4
RH Sensor 5
RH Basic LevelHumidity reference level for automatic ventilation control
RH Level ModeAutomatic or manual humidity level control
Service Actions
Filter Change DateRecords the date of a filter replacement
RH Basic LevelSets the humidity reference level (0 to 100%)
RH Level Mode

Internal Sensor

Read humidity
MODBUSR(H, 4370, Int16) / 100
Read (module)
IF(MODBUSR(H, 4363, Uint16)=0, ADDWARNING("No RH sensor"));
Read temperature
MODBUSR(H, 4369, Int16)
Service Attributes
Filter Change Date
MODBUSR(H, 20546, Uint16) + "." + MODBUSR(H, 20547, Uint16) + ".20" + MODBUSR(H, 20548, Uint16)
Filter Change Interval
MODBUSR(H, 20537, Uint16) + " days";
Cell State
SWITCH(MODBUSR(H, 4616, Uint16), 0, "Heat Recovery", 1, "Cool Recovery", 2, "Bypass", 3, "Defrosting", "Unknown") 
Exhaust Air Temperature
(MODBUSR(H, 4355, UInt16) - 27315)/100 + " °C"
Extract Air Temperature
(MODBUSR(H, 4354, UInt16) - 27315)/100 + " °C"
Outdoor Air Temperature
(MODBUSR(H, 4356, UInt16) - 27315)/100 + " °C"
Supply Air Temperature
(MODBUSR(H, 4358, UInt16) - 27315)/100 + " °C"
RH Sensor 0
var temp := MODBUSR(H, 4373, Uint16);
IF(temp=65535, "No sensor", temp);
RH Sensor 1
var temp := MODBUSR(H, 4374, Uint16);
IF(temp=65535, "No sensor", temp);
RH Sensor 2
var temp := MODBUSR(H, 4375, Uint16);
IF(temp=65535, "No sensor", temp);
RH Sensor 3
var temp := MODBUSR(H, 4376, Uint16);
IF(temp=65535, "No sensor", temp);
RH Sensor 4
var temp := MODBUSR(H, 4377, Uint16);
IF(temp=65535, "No sensor", temp);
RH Sensor 5
var temp := MODBUSR(H, 4378, Uint16);
IF(temp=65535, "No sensor", temp);
RH Basic Level
var rh := MODBUSR(H, 20490, Uint16);
IF(rh = 65535, "Not Calculated", rh + "%")
RH Level Mode
IF(MODBUSR(H, 20543, Uint16) > 0, "Manual", "Automatic Level Update");
Service Actions
Filter Change Date
Parameters: Day (1–31 day), Month (1–12 mon), Year (2000–2099 ye)
MODBUSWNE(H, 20546, Uint16, day);
MODBUSWNE(H, 20547, Uint16, mon);
MODBUSWNE(H, 20548, Uint16, ye);
RH Basic Level
Parameters: Basic Level [%] (0–100 bl)
MODBUSW(H, 20490, Uint16, bl);
RH Level Mode
Parameters: Mode (Manual / Automatic Level Update)
MODBUSW(H, 20543, Uint16, mo);
Mode Multi-value Switch

Ventilation profile selector — Home, Away, Boost, or Fireplace mode with per-profile fan speed and air quality settings

Register: H:4609 UInt16 multi-register
Values / States: Home · Away · Boost · Fireplace
Service Actions
Weekly TimerEnables or disables the weekly timer program
Away Set UpConfigures Away profile — fan speed, supply air target, RH and CO2 control
Home Set UpConfigures Home profile — fan speed, supply air target, RH and CO2 control
Fan Speed Set UpSets fan speed percentages for Home, Away and Boost profiles
Fireplace Set UpConfigures extract and supply fan speeds for Fireplace mode

Mode

Read switch state
if(MODBUSR(H, 4609, Uint16) = 1, return(1));
if(MODBUSR(H, 21767, Uint16) = 1, return(3));
if(MODBUSR(H, 21772, Uint16) = 1, return(2));
return(0);
Write switch state
IF Mu = 0
MODBUSWNE(H, 21767, Uint16, 0);
MODBUSWNE(H, 21772, Uint16, 0);
MODBUSWNE(H, 4609, Uint16, 0);
END
IF Mu = 1
MODBUSWNE(H, 21767, Uint16, 0);
MODBUSWNE(H, 21772, Uint16, 0);
MODBUSWNE(H, 4609, Uint16, 1);
END
IF Mu = 2
MODBUSWNE(H, 21767, Uint16, 0);
MODBUSWNE(H, 21772, Uint16, 1);
MODBUSWNE(H, 4609, Uint16, 0);
END
IF Mu = 3
MODBUSWNE(H, 21767, Uint16, 1);
MODBUSWNE(H, 21772, Uint16, 0);
MODBUSWNE(H, 4609, Uint16, 0);
END
Service Attributes
WeekDay
SWITCH(MODBUSR(H, 4854, Uint16), 1,"Monday",2,"Tuesday",3,"Wednesday",4,"Thursday",5,"Friday",6,"Saturday",7,"Sunday","Unknown")
Weekly Timer
IF(MODBUSR(H, 4615, Uint16) = 1, "ON", "OFF")
Away Fan Speed
MODBUSR(H, 20501, Uint16) + "%"
Away Supply Air
(MODBUSR(H, 20502, UInt16) - 27315)/100 + "°C"
Away RH Control
IF(MODBUSR(H, 20499, Uint16) > 0, "Enabled", "Disabled")
Away CO2 Control
IF(MODBUSR(H, 20500, Uint16) > 0, "Enabled", "Disabled")
Home Fan Speed
MODBUSR(H, 20507, Uint16) + "%"
Home Supply Air
(MODBUSR(H, 20508, UInt16) - 27315)/100 + "°C"
Home RH Control
IF(MODBUSR(H, 20505, Uint16) > 0, "Enabled", "Disabled")
Home CO2 Control
IF(MODBUSR(H, 20506, Uint16) > 0, "Enabled", "Disabled")
Fireplace Extract Fan Speed
MODBUSR(H, 20487, Uint16) + " %"
Fireplace Supply Fan Speed
MODBUSR(H, 20487, Uint16) + " %"
Service Actions
Weekly Timer
Parameters: Tmer (ON / OFF)
MODBUSWNE(H, 4615, Uint16, tim);
Away Set Up
Parameters: Fan Speed [%] (0–100 fsa), Supply Air [5-25°C] (5–25 sata), RH Control (Enabled / Disabled), CO2 Control (Disabled / Enabled)
MODBUSWNE(H, 20499,Uint16,rha);
MODBUSWNE(H, 20500, Uint16, coa);
MODBUSWNE(H,20501, Uint16, fsa);
MODBUSWNE(H, 20502, UInt16, (sata*100) + 27315);
Home Set Up
Parameters: Fan Speed[%] (0–100 fsh), Supply Air [5-25°C] (5–25 sath), RH Control (Enabled / Disabled), CO2 Control (Enabled / Disabled)
MODBUSWNE(H, 20505,Uint16,rhh);
MODBUSWNE(H, 20506, Uint16, coh);
MODBUSWNE(H,20507, Uint16, fsh);
MODBUSWNE(H, 20508, UInt16, (sath*100) + 27315);
Fan Speed Set Up
Parameters: Home [%] (0–100 ho), Away [%] (0–100 aw), Boost [%] (0–100 bo)
MODBUSW(H, 20501, Uint16, aw);
MODBUSW(H, 20507, Uint16, ho);
MODBUSW(H, 20513, Uint16, bo);
Fireplace Set Up
Parameters: Exctract Speed [%] (0–100 ex), Supply Speed [%] (0–100 sup)
MODBUSW(H, 20487, Uint16, ex);
MODBUSW(H, 20488, Uint16, sup);
Connection: Modbus RTU • 19200 baud• 8E1 • Slave ID: $[SlaveId]
Possible improvements (8)
  • H:4356 Outdoor Air Temperature (as device) — TEMP_OUTDOOR_AIR — exposed only as service attribute on Internal Sensor, not as standalone temperature device
  • H:4354 Extract Air Temperature (as device) — TEMP_EXTRACT_AIR — exposed only as service attribute on Internal Sensor, not as standalone temperature device
  • H:4355 Exhaust Air Temperature (as device) — TEMP_EXHAUST_AIR — exposed only as service attribute on Internal Sensor, not as standalone temperature device
  • H:4358 Supply Air Temperature (as device) — TEMP_SUPPLY_AIR — exposed only as service attribute on Internal Sensor, not as standalone temperature device
  • H:4363 RH Value (as device) — RH_VALUE — highest RH measurement across sensors. Only used for warning check in readscript, not as standalone humidity device
  • H:4389 Optional External Temperature Sensor — TEMP_OPTIONAL in centiKelvin — not used in template
  • H:4612 Boost Timer Remaining Time — Remaining minutes for boost ventilation timer (65535=duration active). Not exposed as sensor device
  • H:4613 Fireplace Timer Remaining Time — Remaining minutes for fireplace mode timer (65535=duration active). Not exposed as sensor device

Sources

  • https://www.heliosventilatoren.de/en/products/ventilation-with-heat-recovery/domestic-units-for-wall-ceiling-installation/helios-kwl-r-with-easycontrols-3-0