title: "Domat UC100 Thermostat"
description: "Domat UC100 Modbus RTU room controller with temperature measurement, fan speed control, heating/cooling mode and CO2 sensor via RS-485."
url: "https://taphome.com/en/compatibility/domat-uc100-thermostat/"
language: en
lastmod: 2026-03-29
generator: hugo
ai:
  topics: ["modbus-rtu","thermostat","rs485","room-controller","hvac","fan-coil","co2-sensor"]
  questions: ["How to integrate Domat UC100 room controller with TapHome?","What does the Domat UC100 TapHome template control?","How to connect Domat UC100 via RS-485 to TapHome?","How to configure the Modbus address on the Domat UC100?","How does the fan speed and heating/cooling mode bitmask work on the UC100?","Does the Domat UC100 template support CO2 monitoring?"]
---

# Domat UC100 Thermostat

Communication: Modbus RTU

- [Domat UC100 Datasheet](https://domat.blob.core.windows.net/cms/ContentItems/299_00299/DEji8x/domat-uc100-en.pdf)
- [Domat Control System Website](https://www.domat.cz)

## Integration guide

The Domat UC100 is a communicative room heating controller from Domat Control System (Czech Republic) that connects to TapHome via Modbus RTU over RS-485. The controller measures room temperature, controls a heating valve output via PWM, provides fan speed and heating/cooling mode selection, and optionally reports CO2 concentration.

The UC100 works either autonomously with its built-in PI controller and weekly scheduler, or as a slave device controlled from TapHome. The TapHome template exposes temperature reading and setpoint, fan speed, heating/cooling mode, a digital output for the valve relay, and a CO2 sensor.

> [!WARNING]
> **Archived product** — The Domat UC100 is no longer in production. The current replacement is the Domat UC102. The TapHome template remains functional for existing UC100 installations.

## Hardware connection

### Terminal connections

![Domat UC100 terminal connections and technical specifications](https://taphome.com/images/compatibility/domat-uc100-thermostat/02_terminals_and_specs_hu_904c55d68c0126e8.jpg)

The UC100 has 9 screw terminals on the bottom part of the housing:

| Terminal | Function |
|----------|----------|
| 1 | NC — not connected |
| 2 | NC — not connected |
| 3 | **DO1** — heating valve output (SSR, max 0.4 A at 24 V AC) |
| 4 | NC — not connected |
| 5 | **G0** — power and output reference point |
| 6 | **G0** — power and output reference point |
| 7 | **G** — power (24 V AC) |
| 8 | **K-** — RS-485 communication (-) |
| 9 | **K+** — RS-485 communication (+) |

### Technical specifications

- **Power supply:** 24 V AC ±10%
- **Consumption:** 600 mVA + peripherals (approx. 5 VA)
- **Measuring range:** -20 to +50 °C
- **Sensor accuracy:** ±1.5 K (with software correction)
- **Output:** 1× solid state relay (SSR), PWM controlled, max 0.4 A at 24 V AC
- **Communication:** Modbus RTU, RS-485, optically isolated
- **Default settings:** 9600 baud, 8 data bits, no parity, 1 stop bit
- **Protection:** IP20

### RS-485 wiring

Connect using a **2-wire RS-485 connection** plus power:

- **K+** (terminal 9) → A+/D+ on TapHome RS-485
- **K-** (terminal 8) → B-/D- on TapHome RS-485
- **G** (terminal 7) → 24 V AC power
- **G0** (terminals 5, 6) → Power and output reference point

![Domat UC100 wiring diagram — power, RS-485 communication and valve connection](https://taphome.com/images/compatibility/domat-uc100-thermostat/06_wiring_diagram_hu_abcfb70449d91b77.jpg)

**Cable specification:**

- Type: LAM DATAPAR 2×0.8 or JYTY 2×1 (2-wire for communication)
- For combined power + communication: 4-core LAM DATAPAR 2×2×0.8 or JYTY 4×1
- Twisted pair recommended for EMC (LAM DATAPAR or Belden 8205)
- Max cable length: approximately **50 m** for 10 controllers (with 15% voltage drop limit)

> [!WARNING]
> **Important — RS-485 bus isolation**
>
> The RS-485 bus on the UC100 is **galvanically isolated**. This means the bus can connect controllers regardless of how they are powered. However, ensure proper termination on the last device using the **BUS END** DIP switch.

## Configuration

### DIP switches

![Domat UC100 DIP switches on back of PCB and installation guidelines](https://taphome.com/images/compatibility/domat-uc100-thermostat/03_dip_switches_and_installation_hu_ec4ef40faa88bfb.jpg)

Three DIP switches are located on the back of the PCB:

| Switch | Function |
|--------|----------|
| **BUS END** | If ON, the bus is terminated with a resistor (set ON for the last device on the line) |
| **USR** | Not used, reserved for future applications |
| **INIT** | Sets the controller to default state — address 1, baud rate 9600 |

### Enabling Modbus communication

Modbus RTU communication is enabled by default on the UC100. The default slave address is **1** and the baud rate is **9600**.

To change the Modbus address or baud rate:

1. Connect the UC100 via RS-485 to a PC running **ModComTool** (free configuration software from Domat)
2. Scan for the controller on the bus
3. Open the controller window in ModComTool
4. Change the slave address in register 4 LSB (range 1–247)
5. Change the baud rate in register 4 MSB if needed (13 = 9600, default)
6. Restart the controller — address and baud rate changes take effect only after restart

**To reset to defaults (INIT procedure):**

1. Connect the device via RS-485 to a PC with ModComTool
2. Set the INIT DIP switch to ON
3. Apply power (use only the connector without bottom part)
4. Find the controller in ModComTool (Scan)
5. Set INIT to OFF
6. Open the controller window and click the Init button
7. Remove and reapply power

### Bus termination

Set the **BUS END** DIP switch to ON on the **last** UC100 on the RS-485 bus. All other controllers should have BUS END set to OFF. TapHome Core has a built-in 100 Ω termination resistor on its BUS terminals.

## Device capabilities

### Temperature control (Thermostat)

The template provides a thermostat device that reads the current room temperature from H:16 and the desired (setpoint) temperature from H:10, both with automatic ÷100 conversion to °C. The setpoint can be written back to H:10 from TapHome.

The UC100's built-in PI controller processes the temperature difference and drives the PWM output accordingly. The controller supports three operation modes — Day (comfort), Night (standby), and Off (depression) — each with separate heating and cooling setpoints.

**Default setpoints:**

| Mode | Heating | Cooling |
|------|---------|---------|
| Day / Comfort | 21 °C | 24 °C |
| Night / Standby | 19 °C | 26 °C |
| Off / Depression | 12 °C | 35 °C |

### Fan mode

The fan speed is read from the low byte of H:20 as a bitmask. The template decodes the bit position into a value 0–4:

| Bit value | Decoded | Meaning |
|-----------|---------|---------|
| 1 (bit 0) | 0 | Speed 0 (off) |
| 2 (bit 1) | 1 | Speed 1 |
| 4 (bit 2) | 2 | Speed 2 |
| 8 (bit 3) | 3 | Speed 3 |
| 16 (bit 4) | 4 | Speed 4 |

Writing is handled by the module writescript, which combines the fan speed and heating/cooling mode into a single H:20 write: `(1 << fan_value) | ((1 << mode_value) << 8)`.

### Heating/Cooling mode

The operating mode is read from the high byte of H:20 using the same bitmask decoding as fan speed. Values 0–4 represent different operating modes.

The fan speed and heating/cooling mode share the same register (H:20) — the module writescript ensures both values are written atomically in a single Modbus transaction.

### Digital output DO1

The template exposes the heating valve relay output at H:6 as an on/off switch. This controls the SSR (solid state relay) on terminal 3, which drives a thermal actuator or heating valve (max 0.4 A at 24 V AC). The write uses a "write-if-changed" strategy to avoid unnecessary bus traffic.

### CO2 sensor

The template reads CO2 concentration from H:199 with a 5-minute poll interval. This register is not documented in the 2012 Modbus register table and is likely a newer firmware extension or an external CO2 sensor module connected to the UC100.

> [!TIP]
> The CO2 sensor reading is only available on UC100 units equipped with the optional CO2 sensor module. If no CO2 sensor is connected, the register may return 0 or an invalid value.

### Module writescript

The module writescript atomically writes both fan speed and heating/cooling mode in a single register:

```taphome
MODBUSW(H, 20, Int16, (1 << Mu3) | ((1 << Mu4) << 8))
```

Where `Mu3` is the fan mode device value and `Mu4` is the heating/cooling mode device value. This ensures both settings are always consistent.

## Important notes

### Register address discrepancy

The TapHome XML template uses register addresses that **do not match** the official 2012 Modbus register table. For example, H:16 in the template reads current temperature, but the 2012 documentation lists register 16 as "Night/Standby heating setpoint". Similarly, H:10 in the template is used for desired temperature, while the 2012 docs describe it as "Manual control".

This discrepancy is most likely due to the template targeting a newer firmware version than the 2012 documentation. The UC100 has been in production for many years and the register layout may have been reorganized in later firmware revisions.

> [!WARNING]
> If the template does not work correctly with your UC100 unit, check the firmware version. The template may require a firmware version newer than 13200 (the version documented in the 2012 Modbus register table).

### Temperature warm-up

After switching the UC100 on, allow approximately **90 minutes** for the internal heat to dissipate before the temperature sensor measures correctly. Do not calibrate the sensor correction immediately after powering on.

### Change-over function

The UC100 supports a change-over function that switches between heating and cooling modes. The change-over signal can be sent via Modbus from TapHome or another master. When change-over is active, cooling setpoints come into effect. This is useful in systems with heat pumps that support heating/cooling change-over.

## Troubleshooting

### No Modbus communication

1. **Check RS-485 cables:**
   - K+ (terminal 9) correctly connected to A+/D+ on TapHome
   - K- (terminal 8) correctly connected to B-/D- on TapHome
2. Verify the Modbus slave address matches TapHome configuration (default is 1)
3. Confirm communication parameters: 9600 baud, 8 data bits, no parity, 1 stop bit
4. Check the BUS END DIP switch — set ON only on the last device on the bus
5. Ensure the UC100 is powered with 24 V AC

### Temperature readings incorrect

1. Allow 90 minutes warm-up after initial power-on
2. Check that the controller is not exposed to direct sunlight, heat sources, or cold draughts
3. Verify the sensor correction value in register 37 (default -1.5 K)
4. If register values appear wrong, check the firmware version — the template may target a different register layout than older firmware

### Fan mode or heating/cooling mode not responding

1. Verify that H:20 is writable on your UC100 firmware version
2. Check the module writescript is correctly combining fan and mode values
3. If using an older firmware, the bitmask encoding at H:20 may not be supported — consult the ModComTool configuration software to verify register assignments

## Available devices 5

These devices appear in TapHome after import.

Domat UC100 Module

Write (module)

```taphome
MODBUSWNE(H, 20, Int16, (1 << Mu3) | ((1 << Mu4) << 8))
```

Thermostat Thermostat Read and write

Room temperature sensor and setpoint control — reads current temperature from H:16 and desired temperature from H:10, both with /100 conversion to °C

Register: H:16 (current temp), H:10 (desired temp) → H:10 Int16 Unit: °C numeric

Read temperature

```taphome
MODBUSR(H, 16, Int16) / 100
```

Read desired temperature

```taphome
MODBUSR(H, 10, Int16) / 100
```

Write desired temperature

```taphome
MODBUSW(H, 10, Int16, Se * 100)
```

Fan Mode Multi-value Switch Read-only

Fan speed selector — reads from H:20 low byte bitmask, values 0–4 decoded from bit position

Register: H:20 (& 0x00FF) Int16 bitmask

Read switch state

```taphome
SWITCH(MODBUSR(H, 20, Int16) & 0x00FF, 1, 0, 2, 1, 4, 2, 8, 3, 16, 4, 0)
```

Heating/Cooling Mode Multi-value Switch Read-only

Operating mode selector — reads from H:20 high byte bitmask, values 0–4 decoded from bit position

Register: H:20 (&gt;&gt; 8) Int16 bitmask

Read switch state

```taphome
SWITCH(MODBUSR(H, 20, Int16) >> 8, 1, 0, 2, 1, 4, 2, 8, 3, 16, 4, 0)
```

Digital Output DO1 Switch Read and write

Heating valve relay output — controls SSR on terminal 3, max 0.4 A at 24 V AC

Register: H:6 → H:6 Bool

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 6, Bool)
```

Write switch state

```taphome
MODBUSWNE(H, 6, Bool, St)
```

CO2 Sensor Variable Read-only

CO2 concentration in ppm — reads H:199 with 5-minute poll interval, requires optional CO2 sensor module

Register: H:199 Int16 Unit: ppm numeric

Read

```taphome
MODBUSR(H, 199, Int16) / 1
```

**Connection:** Modbus RTU • 9600 baud• 8N1 • Slave ID: $\[SlaveId]

Possible improvements (14)

- 21 Actual Temperature — Measured room temperature (value/100 °C) — documented as the actual temperature register; template uses H:16 instead (which docs say is Night heating setpoint)
- 13 Actual Heating Setpoint — Actual heating setpoint including user correction (value/100 °C) — read-only calculated value
- 14 Actual Cooling Setpoint — Actual cooling setpoint including user correction (value/100 °C) — read-only calculated value
- 22 Outside Temperature — Outside temperature R/W (value/100 °C) — can be written for display purposes
- 23 Presence Mode — Set presence mode: bit 0=comfort/day, bit 1=standby/night, bit 2=off, bit 3=auto, bit 4=party; bit 15=write enable
- 25 LSB Actual Control Mode — Current active control mode (comfort/standby/off) — follows presence mode or weekly schedule
- 8 LSB PID Output HEAT — Heating PI controller output 0–100% — useful for monitoring valve modulation
- 8 MSB PID Output COOL — Cooling PI controller output 0–100% — only in change-over mode
- 7 MSB Heating/Cooling Demand — Binary demand flags — bit 2: heating demand (PID &gt; 5%), bit 3: cooling demand (PID &gt; 5%)
- 12 Temperature Correction — User setpoint correction R/W (value/100 °C) — resets at each mode change
- 15 Day/Comfort Heating Setpoint — Day/comfort mode heating setpoint R/W EEPROM (default 21°C)
- 18 Day/Comfort Cooling Setpoint — Day/comfort mode cooling setpoint R/W EEPROM (default 24°C)
- 10 LSB Manual Control / Change-over — Manual control bitmask — bit 1: heat output (1=manual), bit 5: change-over active. NOTE: template uses H:10 for desired temperature — this may be the same register with different firmware interpretation
- 54–137 Weekly Time Schedule — 7 days × 6 events × (time + value) — complete weekly schedule for Day/Night/Off mode switching

## Import parameters

Enter these values when you import the XML.

| Asked in the app | Default       |
|------------------|---------------|
| Slave ID         | `1`           |
| IP address       | `192.168.0.1` |

## Sources

- Domat UC100 Datasheet
  
  [domat.blob.core.windows.net](https://domat.blob.core.windows.net/cms/ContentItems/299_00299/DEji8x/domat-uc100-en.pdf) 2026-03-29
  
  [PDF](https://taphome.com/compatibility/devices/domat-uc100-thermostat/manufacturer/datasheet.pdf)
- UC100 Modbus Register Table
  
  [domat.blob.core.windows.net](https://domat.blob.core.windows.net/cms/UserFiles/wp-content/uploads/modbus/UC100_modbus_en.pdf) 2026-03-29
  
  [PDF](https://taphome.com/compatibility/devices/domat-uc100-thermostat/manufacturer/modbus-table.pdf)

Manufacturer documents are © their respective owners. They are provided as published by the manufacturer, for reference only.

## Related Documentation

- [Modbus Integration](https://taphome.com/en/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/en/docs/integration/modbus/)
- [Simple configuration using templates](https://taphome.com/en/docs/integration/modbus/templates/)
- [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/)
- [Modbus functions](https://taphome.com/en/docs/script/modbus/)
- [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/)