title: "Deye SUN-xK-SG04LP3-EU / SG05LP3-EU"
description: "Deye SG04LP3 hybrid inverter over Modbus RTU: PV, load, grid and battery energy flow, SoC, faults, work mode and Time of Use schedule. RJ45 Modbus port."
url: "https://taphome.com/en/compatibility/deye-sg04lp3-hybrid-inverter/"
language: en
lastmod: 2026-11-10
generator: hugo
ai:
  topics: ["modbus-rtu","rs485","inverter","hybrid-inverter","solar","battery-storage","3-phase","energy-monitoring","time-of-use"]
  questions: ["How to integrate a Deye SUN-xK-SG04LP3-EU hybrid inverter with TapHome?","What does the Deye SG04LP3 TapHome template measure and control?","How to connect the Deye SG04LP3 inverter to TapHome via Modbus RTU?","Where do I set the Modbus address on a Deye SG04LP3 inverter?","Which RJ45 port of the Deye SG04LP3 is used for Modbus and what is its pinout?","Why does the Deye SG04LP3 not answer on the Modbus port?","Can TapHome control the Time of Use schedule of a Deye hybrid inverter?"]
---

# Deye SUN-xK-SG04LP3-EU / SG05LP3-EU

Communication: Modbus RTU

## Integration guide

The Deye SUN-xK-SG04LP3-EU is a three-phase (230 V / 400 V) low-voltage hybrid inverter with a battery input and two MPPT inputs for the PV array; the manufacturer's manual covers the SUN-5K, 6K, 8K, 10K and 12K-SG04LP3-EU models. TapHome talks to the inverter over **Modbus RTU** on RS-485 (9600 baud, 8N1), using the RJ45 port labelled **Modbus** on the inverter's communication board.

The template reads PV production, load, grid import and export, battery charge and discharge and battery state of charge, and provides the seven devices of the TapHome energy flow. It also reads battery, grid, PV string and inverter output values, decodes the inverter's running state, warnings and fault codes into TapHome notifications, and writes the energy management mode, grid charging, battery current limits, generator port use and the six-window Time of Use (TOU) schedule.

## Hardware connection

> [!WARNING]
> Only qualified personnel may install and wire the inverter. The communication ports sit inside the wiring compartment behind the metal cover; the AC and DC circuits must be disconnected separately before work starts, as described in the manufacturer's manual.

### Communication ports

The RJ45 communication ports are on the right side of the communication board: **Parallel_A**, **Parallel_B**, **Meter-485**, **Modbus**, **BMS** and **DRM**.

![Deye SG04LP3-EU communication ports: Parallel_A, Parallel_B, Meter-485, Modbus, BMS and DRM RJ45 connectors with their roles.](https://taphome.com/images/compatibility/deye-sg04lp3-hybrid-inverter/ports-layout_hu_aeac3891ac9c016.jpg)

| Port | Role according to the manufacturer |
|------|-----------------------------------|
| Parallel_A, Parallel_B | Parallel communication between inverters (CAN interface) |
| Meter-485 | Communication with the external energy meter (for example CHNT DTSU666 or Eastron SDM630) |
| Modbus | Labelled "Reserved"; the pinout appendix describes it as the port for remote monitoring |
| BMS | Battery communication (CAN / RS-485) |
| DRM | External digital input signals |
| WIFI/RS232 (separate 9-pin port) | Wi-Fi datalogger |

TapHome connects to the **Modbus** port. Do not use the Meter-485 port (it serves the energy meter) or the BMS port (it serves the battery).

> [!WARNING]
> The manufacturer marks the Modbus port as **"Reserved"** and notes that **for some hardware versions, this port is useless**. Before running the cable, check that the Modbus port on the specific inverter answers; if it does not, the template cannot communicate through it.

### Modbus port pinout

![RJ45 pin definitions of the BMS, Meter-485 and Modbus ports of the Deye SG04LP3-EU inverter; Modbus port uses pins 1/8 as 485_B, 2/7 as 485_A, 3/6 as GND_485.](https://taphome.com/images/compatibility/deye-sg04lp3-hybrid-inverter/wiring-rs485-pinout_hu_6afed0daae2db4b4.jpg)

| RJ45 pin (Modbus port) | Signal | TapHome RS-485 bus |
|------------------------|--------|--------------------|
| 1, 8 | 485_B | B |
| 2, 7 | 485_A | A |
| 3, 6 | GND_485 | GND |
| 4, 5 | Not used | — |

Crimp an RJ45 plug on a twisted-pair cable and connect 485_A to the A terminal and 485_B to the B terminal of the TapHome RS-485 bus. A common GND connection (GND_485) is recommended for longer cable runs.

> [!NOTE]
> Only one Modbus master may poll the inverter on the RS-485 line connected to the Modbus port. If another Modbus monitoring device is wired to the same line, disconnect it or use an RS-485 splitter or hub. The manufacturer's Wi-Fi datalogger uses its own WIFI/RS232 port.

## Configuration

### Setting the Modbus address

The Modbus address is the **Modbus SN** field on the inverter display:

1. On the main screen, press the **System Setup** icon.
2. Open **Advanced Function** and go to the page with **Parallel**, **Modbus SN** and **EX_Meter For CT** (Paral. Set3).
3. Set **Modbus SN** and confirm with the tick button.

The template's import parameter **Modbus Slave ID** (default **1**) must match the Modbus SN. The manual's screenshot of a single inverter shows `00`; set a non-zero value, because Modbus address 0 is reserved for broadcast. In a parallel system the manual gives every inverter its own Modbus SN (01, 02, 03), so each inverter needs its own template import with its own Slave ID.

### Communication parameters

| Parameter | Value |
|-----------|-------|
| Baud rate | 9600 |
| Data bits | 8 |
| Parity | None |
| Stop bits | 1 |
| Function codes | 0x03 (read), 0x10 (write multiple registers) |
| Modbus Slave ID | 1 (must match Modbus SN) |

Write operations use function code 0x10; the inverter does not support function code 0x06 (write single register).

In TapHome, add a Modbus RTU interface with these parameters on the RS-485 bus the inverter is wired to and import the template with the matching Modbus Slave ID.

> [!WARNING]
> Never write to registers 80, 81, 91 and 92 (inverter on/off, factory reset, EEPROM) or to the battery type and protection registers (98–103, 111). The template exposes only user-configurable registers.

## Device capabilities

### Energy flow

The template provides the seven devices TapHome uses for a complete solar energy flow:

- **PV Production** — sum of the PV input powers (registers 672–675) in kW, total energy from the 32-bit counter at registers 534–535.
- **Load** — total load power (register 653) and total consumption (registers 527–528).
- **From Grid** and **To Grid** — the signed grid power (register 625) is split: positive values feed From Grid, negative values (as positive numbers) feed To Grid. Total energy from registers 522–523 (from grid) and 524–525 (to grid).
- **From Battery** and **To Battery** — the signed battery power (register 590) is split the same way. Total energy from registers 518–519 (discharge) and 516–517 (charge).
- **Battery (SOC)** — battery state of charge, register 588, 0–100 %.

> [!TIP]
> For the Energy Manager smart rule, select the meter **Grid - power balance**. It reports the signed grid power (register 625): positive when importing from the grid, negative when exporting surplus. From Grid and To Grid are always non-negative and must not be used as the Energy Manager meter.

### Battery

- **Battery - temperature** — register 586, formula `(raw − 1000) / 10`.
- **Battery - voltage** — register 587; battery current (register 591) and battery power (register 590) as service attributes.
- **Battery - charge today** — register 514; energy discharged today (register 515) as a service attribute.

### Grid

- **Grid - power balance** — signed total grid power (register 625); grid power on L1, L2 and L3 (registers 622–624) and energy bought and sold today (registers 520 and 521) as service attributes.
- **Grid - voltage L1** — register 598; grid voltage L2 and L3 (registers 599 and 600) and grid frequency (register 609) as service attributes.

### PV and load

- **PV1 - voltage** and **PV2 - voltage** — registers 676 and 678; the string current (registers 677 and 679) and string power (registers 672 and 673) as service attributes.
- **PV - production today** — register 529.
- **Load - consumption today** — register 526; load power on L1, L2 and L3 (registers 650–652) as service attributes.

### Inverter

- **Inverter - output power total** — register 636; output power per phase (registers 633–635), output voltage per phase (registers 627–629) and output frequency (register 638) as service attributes.
- **Backup - output power** — register 643.
- **Generator port - power** — register 667.
- **DC transformer temperature** (register 540) and **Heat sink temperature** (register 541).

### State, warnings and faults

The module shows the **Running state** (register 500: Standby, Self-check, Normal, Alarm, Fault, Activating), the device type (register 0) and the rated power (registers 20–21) as service attributes. Running state Alarm raises a warning and Fault raises an error.

The warning words (registers 553–554) are decoded into named warnings: fan warning, wrong grid phase sequence, meter communication failure, lithium battery lost and parallel communication quality. The fault words (registers 555–558) are decoded into named errors for fault codes F07, F10, F13, F18, F20, F22–F24, F26, F29, F35, F41, F42, F46–F49, F56, F58 and F62–F64; the meaning of each code and the manufacturer's remedy are in the fault table of the inverter manual.

### Operating settings

- **Settings - energy management mode** — Selling first, Zero export to load or Zero export to CT (register 142). According to the manual, Zero export to CT needs the external current transformers on the CT-L1, CT-L2 and CT-L3 inputs.
- **Settings - solar sell** — allows surplus PV energy to be sold to the grid in the zero export modes (register 145).
- **Settings - max sell power** (register 143) and **Settings - max solar sell power** (register 340).
- **Settings - grid charging** — grid charging of the battery on or off (register 130) and **Settings - grid charge current** (register 128).
- **Settings - max battery charge current** (register 108) and **Settings - max battery discharge current** (register 109). The manual gives the allowed range per model: 0–120 A (5 kW), 0–150 A (6 kW), 0–190 A (8 kW), 0–210 A (10 kW) and 0–240 A (12 kW).
- **Settings - generator port use** — Generator input, Smart load output or Micro-inverter input (register 133).

### Time of Use schedule

The inverter's Time of Use schedule has six windows. The template exposes for each window W1–W6:

- **TOU W1–W6 - start time** — HHMM value (for example 1430 = 14:30), registers 148–153.
- **TOU W1–W6 - target SoC** — battery target state of charge as a 0–100 % slider, registers 166–171.
- **TOU W1–W6 - grid charging** — grid charging during the window on or off; the template changes only bit 0 of registers 172–177 and keeps the other bits.

**TOU - enable** switches the whole schedule on or off through bit 0 of register 146 and keeps the day-of-week selection (bits 1–7).

> [!NOTE]
> According to the manual, the inverter interprets the battery value of each window as a voltage or as a state of charge depending on the **Use Batt V** / **Use Batt %** choice in the Battery Setting menu. The target SoC devices are percentages, so the inverter should be set to Use Batt %. When the grid is present, the battery discharges only if Time of Use is ticked.

## Troubleshooting

**No data / communication failure**

- Check that the cable is in the **Modbus** port, not in Meter-485 or BMS.
- Check the A/B polarity (pins 2/7 = 485_A, pins 1/8 = 485_B) and the GND connection.
- Check that the template's Modbus Slave ID matches the **Modbus SN** in Advanced Function and that the Modbus SN is not 0.
- Check that no other Modbus master is active on the same RS-485 line.
- The manufacturer states that on some hardware versions the Modbus port is useless. If wiring and address are correct and the inverter still does not answer, the port on that hardware version may not be usable.

**Values look 1000× off or nonsensical**

Confirm that the inverter is a low-voltage (LV) SG04LP3 or SG05LP3 variant. The high-voltage SG01HP3 family uses different scaling for battery voltage, battery power and PV input power; the template targets LV scaling only.

**Battery (SOC) stuck at 0 %**

Register 588 returns 0 during some self-check states. Wait until the Running state reaches Normal; the state of charge updates within the next poll interval.

**Time of Use settings not applied**

Make sure **TOU - enable** is on and that at least one window has a non-zero start time. Check that the inverter is set to Use Batt % if the target SoC values seem to be ignored.

**Meter communication failure warning**

The warning is reported by the inverter itself (warning word, register 553) and does not mean that the TapHome connection failed. The energy meter is connected to the Meter-485 port; check its wiring and, when an external meter is used with EX_Meter For CT, the **Meter Select** setting (CHNT or Eastron) in Advanced Function.

## Available devices 49

These devices appear in TapHome after import.

Deye SUN-xK-SG04LP3-EU Module

Service Attributes

|               |
|---------------|
| Running state |
| Device type   |
| Rated power   |

Read (module)

```taphome
VAR state := MODBUSR(H, 500, UInt16);
IF(state = 3, ADDWARNING(64, "Inverter alarm (running state 3)"));
IF(state = 4, ADDERROR(65, "Inverter fault (running state 4)"));

VAR w1 := MODBUSR(H, 553, UInt16);
IF(GETBIT(w1, 1), ADDWARNING(1, "Fan warning"));
IF(GETBIT(w1, 2), ADDWARNING(2, "Grid phase sequence wrong"));
IF(GETBIT(w1, 3), ADDWARNING(3, "Meter communication failure"));

VAR w2 := MODBUSR(H, 554, UInt16);
IF(GETBIT(w2, 14), ADDWARNING(14, "Lithium battery lost"));
IF(GETBIT(w2, 15), ADDWARNING(15, "Parallel communication quality"));

VAR f1 := MODBUSR(H, 555, UInt16);
IF(GETBIT(f1, 6), ADDERROR(6, "F07 DC/DC soft-start fault"));
IF(GETBIT(f1, 9), ADDERROR(9, "F10 Auxiliary power supply fault"));
IF(GETBIT(f1, 12), ADDERROR(12, "F13 Working mode changed"));

VAR f2 := MODBUSR(H, 556, UInt16);
IF(GETBIT(f2, 1), ADDERROR(17, "F18 AC over-current"));
IF(GETBIT(f2, 3), ADDERROR(19, "F20 DC over-current"));
IF(GETBIT(f2, 5), ADDERROR(21, "F22 Emergency stop - inverter locked"));
IF(GETBIT(f2, 6), ADDERROR(22, "F23 Leakage current fault"));
IF(GETBIT(f2, 7), ADDERROR(23, "F24 PV insulation resistance fault"));
IF(GETBIT(f2, 9), ADDERROR(25, "F26 DC bus unbalanced"));
IF(GETBIT(f2, 12), ADDERROR(28, "F29 Parallel CAN bus fault"));

VAR f3 := MODBUSR(H, 557, UInt16);
IF(GETBIT(f3, 2), ADDERROR(34, "F35 No AC grid"));
IF(GETBIT(f3, 8), ADDERROR(40, "F41 Parallel system stop"));
IF(GETBIT(f3, 9), ADDERROR(41, "F42 AC line low voltage"));
IF(GETBIT(f3, 13), ADDERROR(45, "F46 Backup battery fault"));
IF(GETBIT(f3, 14), ADDERROR(46, "F47 AC over-frequency"));
IF(GETBIT(f3, 15), ADDERROR(47, "F48 AC under-frequency"));

VAR f4 := MODBUSR(H, 558, UInt16);
IF(GETBIT(f4, 0), ADDERROR(48, "F49 Backup battery fault"));
IF(GETBIT(f4, 7), ADDERROR(55, "F56 DC bus voltage too low"));
IF(GETBIT(f4, 9), ADDERROR(57, "F58 BMS communication fault"));
IF(GETBIT(f4, 13), ADDERROR(61, "F62 DRM stop"));
IF(GETBIT(f4, 14), ADDERROR(62, "F63 Arc fault"));
IF(GETBIT(f4, 15), ADDERROR(63, "F64 Heat sink temperature too high"));
```

Service Attributes

Running state

```taphome
IF(MODBUSR(H, 500, UInt16) = 0, "Standby", IF(MODBUSR(H, 500, UInt16) = 1, "Self-check", IF(MODBUSR(H, 500, UInt16) = 2, "Normal", IF(MODBUSR(H, 500, UInt16) = 3, "Alarm", IF(MODBUSR(H, 500, UInt16) = 4, "Fault", "Activating")))))
```

Device type

```taphome
TOSTRING(MODBUSR(H, 0, UInt16))
```

Rated power

```taphome
TOSTRING(MODBUSR(H, 20, LittleEndianUint32) / 10, "F1") + " W"
```

${deviceType\_PVProduction} Electricity Meter

Read total consumption

```taphome
MODBUSR(H, 534, LittleEndianUint32) / 10
```

Read demand

```taphome
(MODBUSR(H, 672, UInt16) + MODBUSR(H, 673, UInt16) + MODBUSR(H, 674, UInt16) + MODBUSR(H, 675, UInt16)) / 1000
```

${deviceType\_PVLoad} Electricity Meter

Read total consumption

```taphome
MODBUSR(H, 527, LittleEndianUint32) / 10
```

Read demand

```taphome
MODBUSR(H, 653, Int16) / 1000
```

${deviceType\_PVFromGrid} Electricity Meter

Read total consumption

```taphome
MODBUSR(H, 522, LittleEndianUint32) / 10
```

Read demand

```taphome
MAX(MODBUSR(H, 625, Int16), 0) / 1000
```

${deviceType\_PVToGrid} Electricity Meter

Read total consumption

```taphome
MODBUSR(H, 524, LittleEndianUint32) / 10
```

Read demand

```taphome
MAX(-MODBUSR(H, 625, Int16), 0) / 1000
```

${deviceType\_PVFromBattery} Electricity Meter

Read total consumption

```taphome
MODBUSR(H, 518, LittleEndianUint32) / 10
```

Read demand

```taphome
MAX(MODBUSR(H, 590, Int16), 0) / 1000
```

${deviceType\_PVToBattery} Electricity Meter

Read total consumption

```taphome
MODBUSR(H, 516, LittleEndianUint32) / 10
```

Read demand

```taphome
MAX(-MODBUSR(H, 590, Int16), 0) / 1000
```

${deviceType\_BatterySOC} Analog Input

Read input level

```taphome
MODBUSR(H, 588, UInt16) / 100
```

Battery - temperature Temperature Sensor

Read temperature

```taphome
(MODBUSR(H, 586, UInt16) - 1000) / 10
```

Battery - voltage Variable

Service Attributes

|                 |
|-----------------|
| Battery current |
| Battery power   |

Read

```taphome
MODBUSR(H, 587, UInt16) / 100
```

Service Attributes

Battery current

```taphome
TOSTRING(MODBUSR(H, 591, Int16) / 100, "F2") + " A"
```

Battery power

```taphome
TOSTRING(MODBUSR(H, 590, Int16), "F0") + " W"
```

Battery - charge today Variable

Service Attributes

|                         |
|-------------------------|
| Battery discharge today |

Read

```taphome
MODBUSR(H, 514, UInt16) / 10
```

Service Attributes

Battery discharge today

```taphome
TOSTRING(MODBUSR(H, 515, UInt16) / 10, "F1") + " kWh"
```

Grid - voltage L1 Variable

Service Attributes

|                 |
|-----------------|
| Grid voltage L2 |
| Grid voltage L3 |
| Grid frequency  |

Read

```taphome
MODBUSR(H, 598, UInt16) / 10
```

Service Attributes

Grid voltage L2

```taphome
TOSTRING(MODBUSR(H, 599, UInt16) / 10, "F1") + " V"
```

Grid voltage L3

```taphome
TOSTRING(MODBUSR(H, 600, UInt16) / 10, "F1") + " V"
```

Grid frequency

```taphome
TOSTRING(MODBUSR(H, 609, UInt16) / 100, "F2") + " Hz"
```

Grid - power balance Electricity Meter

Service Attributes

|                          |
|--------------------------|
| Grid power L1            |
| Grid power L2            |
| Grid power L3            |
| Grid energy bought today |
| Grid energy sold today   |

Read demand

```taphome
MODBUSR(H, 625, Int16) / 1000
```

Service Attributes

Grid power L1

```taphome
TOSTRING(MODBUSR(H, 622, Int16)) + " W"
```

Grid power L2

```taphome
TOSTRING(MODBUSR(H, 623, Int16)) + " W"
```

Grid power L3

```taphome
TOSTRING(MODBUSR(H, 624, Int16)) + " W"
```

Grid energy bought today

```taphome
TOSTRING(MODBUSR(H, 520, UInt16) / 10, "F1") + " kWh"
```

Grid energy sold today

```taphome
TOSTRING(MODBUSR(H, 521, UInt16) / 10, "F1") + " kWh"
```

PV1 - voltage Variable

Service Attributes

|             |
|-------------|
| PV1 current |
| PV1 power   |

Read

```taphome
MODBUSR(H, 676, UInt16) / 10
```

Service Attributes

PV1 current

```taphome
TOSTRING(MODBUSR(H, 677, UInt16) / 10, "F1") + " A"
```

PV1 power

```taphome
TOSTRING(MODBUSR(H, 672, UInt16)) + " W"
```

PV2 - voltage Variable

Service Attributes

|             |
|-------------|
| PV2 current |
| PV2 power   |

Read

```taphome
MODBUSR(H, 678, UInt16) / 10
```

Service Attributes

PV2 current

```taphome
TOSTRING(MODBUSR(H, 679, UInt16) / 10, "F1") + " A"
```

PV2 power

```taphome
TOSTRING(MODBUSR(H, 673, UInt16)) + " W"
```

PV - production today Variable

Read

```taphome
MODBUSR(H, 529, UInt16) / 10
```

Load - consumption today Variable

Service Attributes

|               |
|---------------|
| Load power L1 |
| Load power L2 |
| Load power L3 |

Read

```taphome
MODBUSR(H, 526, UInt16) / 10
```

Service Attributes

Load power L1

```taphome
TOSTRING(MODBUSR(H, 650, Int16)) + " W"
```

Load power L2

```taphome
TOSTRING(MODBUSR(H, 651, Int16)) + " W"
```

Load power L3

```taphome
TOSTRING(MODBUSR(H, 652, Int16)) + " W"
```

Inverter - output power total Variable

Service Attributes

|                     |
|---------------------|
| Inverter output L1  |
| Inverter output L2  |
| Inverter output L3  |
| Inverter voltage L1 |
| Inverter voltage L2 |
| Inverter voltage L3 |
| Inverter frequency  |

Read

```taphome
MODBUSR(H, 636, Int16)
```

Service Attributes

Inverter output L1

```taphome
TOSTRING(MODBUSR(H, 633, Int16)) + " W"
```

Inverter output L2

```taphome
TOSTRING(MODBUSR(H, 634, Int16)) + " W"
```

Inverter output L3

```taphome
TOSTRING(MODBUSR(H, 635, Int16)) + " W"
```

Inverter voltage L1

```taphome
TOSTRING(MODBUSR(H, 627, UInt16) / 10, "F1") + " V"
```

Inverter voltage L2

```taphome
TOSTRING(MODBUSR(H, 628, UInt16) / 10, "F1") + " V"
```

Inverter voltage L3

```taphome
TOSTRING(MODBUSR(H, 629, UInt16) / 10, "F1") + " V"
```

Inverter frequency

```taphome
TOSTRING(MODBUSR(H, 638, UInt16) / 100, "F2") + " Hz"
```

Backup - output power Variable

Read

```taphome
MODBUSR(H, 643, UInt16)
```

Generator port - power Variable

Read

```taphome
MODBUSR(H, 667, Int16)
```

DC transformer temperature Temperature Sensor

Read temperature

```taphome
(MODBUSR(H, 540, UInt16) - 1000) / 10
```

Heat sink temperature Temperature Sensor

Read temperature

```taphome
(MODBUSR(H, 541, UInt16) - 1000) / 10
```

Settings - energy management mode Multi-value Switch

Values / States: Selling first · Zero export to load · Zero export to CT

Read switch state

```taphome
MODBUSR(H, 142, UInt16)
```

Write switch state

```taphome
MODBUSWNE(H, 142, UInt16, Mu)
```

Settings - solar sell Switch

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 145, UInt16)
```

Write switch state

```taphome
MODBUSWNE(H, 145, UInt16, St)
```

Settings - max sell power Variable

Read

```taphome
MODBUSR(H, 143, UInt16)
```

Write

```taphome
MODBUSWNE(H, 143, UInt16, Va)
```

Settings - max solar sell power Variable

Read

```taphome
MODBUSR(H, 340, UInt16)
```

Write

```taphome
MODBUSWNE(H, 340, UInt16, Va)
```

Settings - grid charging Switch

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 130, UInt16)
```

Write switch state

```taphome
MODBUSWNE(H, 130, UInt16, St)
```

Settings - grid charge current Variable

Read

```taphome
MODBUSR(H, 128, UInt16)
```

Write

```taphome
MODBUSWNE(H, 128, UInt16, Va)
```

Settings - max battery charge current Variable

Read

```taphome
MODBUSR(H, 108, UInt16)
```

Write

```taphome
MODBUSWNE(H, 108, UInt16, Va)
```

Settings - max battery discharge current Variable

Read

```taphome
MODBUSR(H, 109, UInt16)
```

Write

```taphome
MODBUSWNE(H, 109, UInt16, Va)
```

Settings - generator port use Multi-value Switch

Values / States: Generator input · Smart load output · Micro-inverter input

Read switch state

```taphome
MODBUSR(H, 133, UInt16)
```

Write switch state

```taphome
MODBUSWNE(H, 133, UInt16, Mu)
```

TOU - enable Switch

Values / States: ON · OFF

Read switch state

```taphome
GETBIT(MODBUSR(H, 146, UInt16), 0)
```

Write switch state

```taphome
VAR reg := MODBUSR(H, 146, UInt16);
reg := SETBIT(reg, 0, St);
MODBUSWNE(H, 146, UInt16, reg)
```

TOU W1 - start time Variable

Read

```taphome
MODBUSR(H, 148, UInt16)
```

Write

```taphome
MODBUSWNE(H, 148, UInt16, Va)
```

TOU W1 - target SoC Dimmer

Read level

```taphome
LINEAR(MODBUSR(H, 166, UInt16), 0, 0, 100, 1)
```

Write level

```taphome
MODBUSWNE(H, 166, UInt16, LINEAR(Le, 0, 0, 1, 100))
```

TOU W1 - grid charging Switch

Values / States: ON · OFF

Read switch state

```taphome
GETBIT(MODBUSR(H, 172, UInt16), 0)
```

Write switch state

```taphome
VAR reg := MODBUSR(H, 172, UInt16);
reg := SETBIT(reg, 0, St);
MODBUSWNE(H, 172, UInt16, reg)
```

TOU W2 - start time Variable

Read

```taphome
MODBUSR(H, 149, UInt16)
```

Write

```taphome
MODBUSWNE(H, 149, UInt16, Va)
```

TOU W2 - target SoC Dimmer

Read level

```taphome
LINEAR(MODBUSR(H, 167, UInt16), 0, 0, 100, 1)
```

Write level

```taphome
MODBUSWNE(H, 167, UInt16, LINEAR(Le, 0, 0, 1, 100))
```

TOU W2 - grid charging Switch

Values / States: ON · OFF

Read switch state

```taphome
GETBIT(MODBUSR(H, 173, UInt16), 0)
```

Write switch state

```taphome
VAR reg := MODBUSR(H, 173, UInt16);
reg := SETBIT(reg, 0, St);
MODBUSWNE(H, 173, UInt16, reg)
```

TOU W3 - start time Variable

Read

```taphome
MODBUSR(H, 150, UInt16)
```

Write

```taphome
MODBUSWNE(H, 150, UInt16, Va)
```

TOU W3 - target SoC Dimmer

Read level

```taphome
LINEAR(MODBUSR(H, 168, UInt16), 0, 0, 100, 1)
```

Write level

```taphome
MODBUSWNE(H, 168, UInt16, LINEAR(Le, 0, 0, 1, 100))
```

TOU W3 - grid charging Switch

Values / States: ON · OFF

Read switch state

```taphome
GETBIT(MODBUSR(H, 174, UInt16), 0)
```

Write switch state

```taphome
VAR reg := MODBUSR(H, 174, UInt16);
reg := SETBIT(reg, 0, St);
MODBUSWNE(H, 174, UInt16, reg)
```

TOU W4 - start time Variable

Read

```taphome
MODBUSR(H, 151, UInt16)
```

Write

```taphome
MODBUSWNE(H, 151, UInt16, Va)
```

TOU W4 - target SoC Dimmer

Read level

```taphome
LINEAR(MODBUSR(H, 169, UInt16), 0, 0, 100, 1)
```

Write level

```taphome
MODBUSWNE(H, 169, UInt16, LINEAR(Le, 0, 0, 1, 100))
```

TOU W4 - grid charging Switch

Values / States: ON · OFF

Read switch state

```taphome
GETBIT(MODBUSR(H, 175, UInt16), 0)
```

Write switch state

```taphome
VAR reg := MODBUSR(H, 175, UInt16);
reg := SETBIT(reg, 0, St);
MODBUSWNE(H, 175, UInt16, reg)
```

TOU W5 - start time Variable

Read

```taphome
MODBUSR(H, 152, UInt16)
```

Write

```taphome
MODBUSWNE(H, 152, UInt16, Va)
```

TOU W5 - target SoC Dimmer

Read level

```taphome
LINEAR(MODBUSR(H, 170, UInt16), 0, 0, 100, 1)
```

Write level

```taphome
MODBUSWNE(H, 170, UInt16, LINEAR(Le, 0, 0, 1, 100))
```

TOU W5 - grid charging Switch

Values / States: ON · OFF

Read switch state

```taphome
GETBIT(MODBUSR(H, 176, UInt16), 0)
```

Write switch state

```taphome
VAR reg := MODBUSR(H, 176, UInt16);
reg := SETBIT(reg, 0, St);
MODBUSWNE(H, 176, UInt16, reg)
```

TOU W6 - start time Variable

Read

```taphome
MODBUSR(H, 153, UInt16)
```

Write

```taphome
MODBUSWNE(H, 153, UInt16, Va)
```

TOU W6 - target SoC Dimmer

Read level

```taphome
LINEAR(MODBUSR(H, 171, UInt16), 0, 0, 100, 1)
```

Write level

```taphome
MODBUSWNE(H, 171, UInt16, LINEAR(Le, 0, 0, 1, 100))
```

TOU W6 - grid charging Switch

Values / States: ON · OFF

Read switch state

```taphome
GETBIT(MODBUSR(H, 177, UInt16), 0)
```

Write switch state

```taphome
VAR reg := MODBUSR(H, 177, UInt16);
reg := SETBIT(reg, 0, St);
MODBUSWNE(H, 177, UInt16, reg)
```

**Connection:** Modbus RTU • 9600 baud• 8N1 • Slave ID: $\[SlaveId]

## Import parameters

Enter these values when you import the XML.

| Asked in the app | Default |
|------------------|---------|
| Modbus Slave ID  | `1`     |

## Related Documentation

- [Modbus Integration](https://taphome.com/en/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/en/docs/integration/modbus/)
- [Simple configuration using templates](https://taphome.com/en/docs/integration/modbus/templates/)
- [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/)
- [Modbus functions](https://taphome.com/en/docs/script/modbus/)
- [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/)