title: "De Dietrich HPI S 11 TR"
description: "De Dietrich HPI S 11 TR heat pump connected to TapHome via Modbus RTU through BDR Thermea GTW-08 gateway."
url: "https://taphome.com/en/compatibility/de-dietrich-hpi-s-11-tr/"
language: en
lastmod: 2026-03-20
generator: hugo
ai:
  topics: ["modbus-rtu","heat-pump","rs485","gateway","zone-control","thermostat","hot-water"]
  questions: ["How to integrate De Dietrich HPI S 11 TR with TapHome?","What does the De Dietrich HPI TapHome template control?","How to connect De Dietrich heat pump via GTW-08 gateway to TapHome?","How to configure the GTW-08 Modbus address for TapHome?","What heating zones does the De Dietrich HPI template support?","How to monitor water pressure and temperatures on De Dietrich HPI via TapHome?"]
---

# De Dietrich HPI S 11 TR

Communication: Modbus RTU

- [GTW-08 Configuration Manual (PDF)](https://tools.remeha.nl/wp-content/uploads/sites/11/2024/07/configuratiehandleiding-GTW-08.pdf)
- [De Dietrich Official Website](https://www.dedietrich-heating.com)

The De Dietrich HPI S 11 TR is an air/water heat pump that connects to TapHome via Modbus RTU through the BDR Thermea GTW-08 gateway. The GTW-08 is a communication module installed inside the heat pump's control PCB that bridges the appliance's internal L-Bus to an external RS-485 Modbus RTU interface.

The TapHome template provides zone thermostat control for up to 7 heating zones, flow and return temperature monitoring, outdoor temperature, water pressure and system power readout. The same GTW-08 gateway and register map is shared across all BDR Thermea group appliances (De Dietrich, Remeha, Baxi).

## Hardware connection

### System overview

![GTW-08 Modbus gateway system overview — BMS to appliance connection via L-Bus](https://taphome.com/images/compatibility/de-dietrich-hpi-s-11-tr/gtw-08-overview-p004-004_hu_38cb3b7eae0b7644.jpg)

The GTW-08 gateway sits between the BMS (TapHome) and the heating/cooling appliance. TapHome communicates with the gateway over RS-485, and the gateway communicates with the heat pump over the internal L-Bus.

**Key components on the GTW-08 PCB:**

- **1** — L-Bus connectors (connection to the appliance's main CU or EHC PCB)
- **2** — DIP switches (baud rate and parity configuration)
- **3** — Modbus connectors / X6 terminal (RS-485 to TapHome)
- **4** — Communication status LEDs
- **5** — Status LED (two-colour: green/red/orange)
- **6** — Rotary knob (Modbus slave address)

### RS-485 wiring

Connect TapHome to the GTW-08 gateway's **X6 Modbus connector** using a standard RS-485 cable:

1. Power off the heat pump
2. Access the control PCB unit inside the appliance
3. Connect the Modbus cable from TapHome to the GTW-08 X6 connector
4. Ensure the L-Bus cable is connected between the GTW-08 and the appliance's main CU or EHC PCB
5. Connect the L-Bus termination connector on the GTW-08

> [!WARNING]
> **Important — Installation**
>
> The GTW-08 must be installed by a qualified professional. Always power off the appliance before accessing the control PCB. Follow all safety instructions in the appliance's installation manual.

## Enabling Modbus communication

### Gateway address (rotary knob)

![GTW-08 DIP switch configuration and LED status indications](https://taphome.com/images/compatibility/de-dietrich-hpi-s-11-tr/gtw-08-installation-p005-005_hu_a3049e7e88652a89.jpg)

The rotary knob on the GTW-08 sets the Modbus slave address. The default position **0** corresponds to address **100**.

| Position | Address |
|----------|---------|
| **0** | **100** (default) |
| 1 | 101 |
| 2 | 102 |
| 3–9 | 103–109 |
| A–F | 110–115 |

**For TapHome:** Use the default address **100** (rotary knob position 0). Set the same slave address in the TapHome Modbus module configuration.

### DIP switch configuration

The GTW-08 has 4 DIP switches for baud rate (switches 1–2) and parity (switches 3–4):

**Baud rate (DIP 1–2):**

| DIP 1 | DIP 2 | Baud rate |
|-------|-------|-----------|
| OFF | OFF | **9600** (default) |
| ON | OFF | 19200 |
| OFF | ON | 38400 |
| ON | ON | 57600 |

**Parity (DIP 3–4):**

| DIP 3 | DIP 4 | Parity |
|-------|-------|--------|
| OFF | OFF | **None** (default) |
| ON | OFF | Odd |
| OFF | ON | Even |
| ON | ON | None |

**For TapHome:** Use the default settings — **9600 baud, no parity, 1 stop bit**. All DIP switches OFF.

### LED status indications

| Colour | State | Meaning |
|--------|-------|---------|
| OFF | — | No power or defect |
| Green | Continuous | Normal operation |
| Green | Fast blinking (100 ms) | GTW-08 start-up phase |
| Red | Fixed | No Modbus communication |
| Orange | Fixed | No communication on L-Bus |
| Orange | Slow blinking (500 ms) | GTW-08 Modbus error |

**Normal state:** Green LED steady — the gateway is communicating on both L-Bus and Modbus.

## Device capabilities

### Temperature monitoring

The template provides three temperature sensors reading from holding registers with automatic conversion:

- **Outdoor Temperature** (H:384) — instantaneous outside temperature, with a service attribute showing the heating upper limit temperature (H:386)
- **HP Flow Temperature** (H:403) — heat pump circuit flow temperature
- **HP Return Temperature** (H:404) — heat pump circuit return temperature

These three sensors use INT16 with 0.01 °C resolution (value / 100). Zone thermostat temperatures use a different conversion — see the zone section below.

### System monitoring

- **Current System Power** (H:272) — actual power output of the system as a percentage (0–100%) from the consumer manager
- **Water Pressure** (H:409) — primary circuit water pressure in bar (value / 10, range 0–3.0 bar)

### Zone thermostat control

The template supports **7 independent heating zones**, each with its own thermostat device. Each zone thermostat reads the current zone temperature and allows setting the desired room temperature:

- **Zone N Thermostat** — reads current zone temperature and writes room temperature setpoint
- Each thermostat has 4 service attributes: zone short name, zone request type, zone function, and zone pump status

Zone registers are calculated using a 512-register offset per zone:

| Zone | Operating mode register | Setpoint register | Temperature register |
|------|------------------------|-------------------|---------------------|
| 1 | H:649 | H:664 | H:1105 |
| 2 | H:1161 | H:1176 | H:1612 |
| 3 | H:1673 | H:1688 | H:2129 |
| 4 | H:2185 | H:2200 | H:2636 |
| 5 | H:2697 | H:2712 | H:3148 |
| 6 | H:3209 | H:3224 | H:3660 |
| 7 | H:3721 | H:3736 | H:4172 |

### Zone operating mode

Each zone has a separate operating mode control with three options:

- **Scheduling** (0) — follows the appliance's built-in time program
- **Manual** (1) — uses the manually set room temperature setpoint
- **Off** (2) — zone is turned off

### Service diagnostics

The module exposes 8 service attributes for system monitoring:

- **Cascade Number** (H:7000) — shows whether the appliance is Master (1), Slave, or Not a Member (255) in a cascade setup
- **Zone Count** (H:189) — number of zones detected in the system
- **Deactivated Zone Count** (H:190) — number of deactivated zones
- **Heating Zone Count** (H:191) — heating-only zones
- **Heating+Cooling Zone Count** (H:192) — zones with heating and cooling
- **DHW Zone Count** (H:193) — domestic hot water zones
- **Process Heating Zone Count** (H:194) — process heating zones
- **Pool Zone Count** (H:195) — pool zones

### Additional capabilities

The GTW-08 gateway exposes many additional registers not included in the current template, including BMS power and temperature request control (H:256–259), system flow/return temperatures (H:400–401), exhaust gas temperature (H:402), DHW flow setpoint (H:408), main and sub status codes (H:411–412), actual relative power (H:413), pump speed (H:459), actual power in kW (H:460), instantaneous COP (H:9230), and comprehensive energy counters for CH, DHW and cooling consumption and delivery (H:433–451). Cascade management registers (H:7000+) are also available for multi-appliance setups.

> [!TIP]
> The BMS control registers (H:256–259) allow direct power and temperature demand control. To use them, add custom Modbus devices in TapHome: set Algorithm Type (H:258) to select control mode, then write Power Request (H:256) or Temperature Request (H:257) along with Heat Demand Type (H:259).

## Troubleshooting

### No Modbus communication (LED red)

1. **Check RS-485 cables** between TapHome and the GTW-08 X6 connector
2. Verify the rotary knob address matches the slave address configured in TapHome (default: 100)
3. Confirm TapHome is set to: **9600 baud, no parity, 1 stop bit**
4. Check DIP switch positions on the GTW-08 — all should be OFF for default settings
5. Power cycle the heat pump to restart the gateway

### No L-Bus communication (LED orange)

1. Check the L-Bus cable between the GTW-08 and the appliance's main CU or EHC PCB
2. Verify the L-Bus termination connector is installed on the GTW-08
3. Ensure the appliance is powered on and the control board is operational

### Zone not responding

1. Check the Zone Count service attribute — verify the zone is detected by the system
2. Verify the zone is not in the Deactivated Zone Count
3. Check the Zone Function service attribute — ensure the zone type matches the expected configuration (CH, DHW, Pool, etc.)
4. Try setting the zone operating mode to Manual and writing a temperature setpoint

### Gateway error (LED orange blinking)

1. Read register H:277 for error codes — 0 means no errors
2. Check registers H:531–547 for per-board error codes
3. Consult the appliance's service manual for specific error code meanings
4. If error code is 0xFFFE — the device board is not available

## Available devices

De Dietrich HPI S 11 TR Module

Service Attributes

|                            |                                                                        |
|----------------------------|------------------------------------------------------------------------|
| Cascade Number             | reads H:7000 (UInt16); SWITCH: 1=Master, 255=Not a Member, other=Slave |
| Zone Count                 | reads H:189 (UInt16); number of zones detected in the system           |
| Deactivated Zone Count     | reads H:190 (UInt16); number of deactivated zones present              |
| Heating Zone Count         | reads H:191 (UInt16); number of heating-only zones present             |
| Heating+Cooling Zone Count | reads H:192 (UInt16); number of heating+cooling zones present          |
| DHW Zone Count             | reads H:193 (UInt16); number of domestic hot water zones present       |
| Process Heating Zone Count | reads H:194 (UInt16); number of process heating zones present          |
| Pool Zone Count            | reads H:195 (UInt16); number of pool zones present                     |

Current System Power Variable Read-only

Actual power output of the system as percentage from consumer manager (0–100%)

Register: H:272 Int16 Unit: % numeric

HP Flow Temperature Temperature Sensor Read-only

Heat pump circuit flow temperature

Register: H:403 Int16 Unit: C numeric

Zone 1 Operating Mode Multi-value Switch

Zone 1 operating mode — Scheduling, Manual, or Off

Register: H:0\*512+649 UInt16 numeric

Values / States: Ruční · Ochrana proti zamrznutí

Zone 2 Operating Mode Multi-value Switch

Zone 2 operating mode — Scheduling, Manual, or Off

Register: H:1\*512+649 UInt16 numeric

Values / States: Ruční · Ochrana proti zamrznutí

Zone 3 Operating Mode Multi-value Switch

Zone 3 operating mode — Scheduling, Manual, or Off

Register: H:2\*512+649 UInt16 numeric

Values / States: Ruční · Ochrana proti zamrznutí

Zone 4 Operating Mode Multi-value Switch

Zone 4 operating mode — Scheduling, Manual, or Off

Register: H:3\*512+649 UInt16 numeric

Values / States: Ruční · Ochrana proti zamrznutí

Zone 5 Operating Mode Multi-value Switch

Zone 5 operating mode — Scheduling, Manual, or Off

Register: H:4\*512+649 UInt16 numeric

Values / States: Neaktivní · Ruční · Ochrana proti zamrznutí

Zone 6 Operating Mode Multi-value Switch

Zone 6 operating mode — Scheduling, Manual, or Off

Register: H:5\*512+649 UInt16 numeric

Values / States: Neaktivní · Ruční · Ochrana proti zamrznutí

Zone 7 Operating Mode Multi-value Switch

Zone 7 operating mode — Scheduling, Manual, or Off

Register: H:6\*512+649 UInt16 numeric

Values / States: Neaktivní · Ruční · Ochrana proti zamrznutí

Zone 1 Thermostat Thermostat

Zone 1 room thermostat — reads current temperature and sets desired temperature

Register: H:0\*512+1105 → H:0\*512+664 UInt16 Unit: C numeric

Zone 2 Thermostat Thermostat

Zone 2 room thermostat — reads current temperature and sets desired temperature

Register: H:1\*512+1100 → H:1\*512+664 Int16 Unit: C numeric

Zone 3 Thermostat Thermostat

Zone 3 room thermostat — reads current temperature and sets desired temperature

Register: H:2\*512+1105 → H:2\*512+664 UInt16 Unit: C numeric

Zone 4 Thermostat Thermostat

Zone 4 room thermostat — reads current temperature and sets desired temperature

Register: H:3\*512+1100 → H:3\*512+664 Int16 Unit: C numeric

Zone 5 Thermostat Thermostat

Zone 5 room thermostat — reads current temperature and sets desired temperature

Register: H:4\*512+1100 → H:4\*512+664 UInt16 Unit: C numeric

Zone 6 Thermostat Thermostat

Zone 6 room thermostat — reads current temperature and sets desired temperature

Register: H:5\*512+1100 → H:5\*512+664 Int16 Unit: C numeric

Zone 7 Thermostat Thermostat

Zone 7 room thermostat — reads current temperature and sets desired temperature

Register: H:6\*512+1100 → H:6\*512+664 UInt16 Unit: C numeric

Water Pressure Variable Read-only

Primary circuit water pressure (0–3.0 bar)

Register: H:409 Int16 Unit: bar numeric

Outdoor Temperature Temperature Sensor Read-only

Instantaneous outside temperature

Register: H:384 Int16 Unit: C numeric

Service Attributes

|                     |
|---------------------|
| Heating Upper Limit |

HP Return Temperature Temperature Sensor Read-only

Heat pump circuit return temperature

Register: H:404 Int16 Unit: C numeric

**Connection:** Modbus RTU • 9600 baud• 8N1 • Slave ID: $\[SlaveId]

Possible improvements (24)

- H:256 Power Request — Power request 0–100% (UINT8, R/W). Key BMS control register — sets heat demand power level
- H:257 Temperature Request — Temperature request (UINT16, 0.01C, R/W). Sets desired flow temperature for heat demand
- H:258 Algorithm Type — 0=Remote management (temp+power), 1=Power, 2=Temperature, 3=Monitoring only. Determines BMS control level
- H:259 Heat Demand Type — 0=Standby, 7=Heating, 8=Cooling. Activates/deactivates heat production
- H:275 Heat Demand Bitfield — Bitfield: zones allowed, cooling, DHW, heat engine active. Useful for diagnostics
- H:277 Error List — List of errors for all connected devices (UINT16, 0–65535)
- H:279 Output Status 2 (byte 1) — Bitfield: flame on, HP on, backup 1/2 on, DHW backup, service required, power down, water pressure low
- H:280 Output Status 2 (byte 2) — Bitfield: pump, 3-way valve open/close, DHW active, CH active, cooling active
- H:385 Seasonal Mode — ENUM8: 0=Winter, 1=Frost protection, 2=Summer neutral, 3=Summer
- H:400 System Flow Temperature — System flow temperature (INT16, 0.01C, display code AM016). Different from HP flow (403)
- H:401 System Return Temperature — Return temperature of water entering appliance (INT16, 0.01C, display code AM018)
- H:402 Exhaust Gas Temperature — Temperature of exhaust gas leaving appliance (INT16, 0.01C, -20..120, display code AM036)
- H:408 DHW Flow Setpoint — Flow temperature setpoint for domestic hot water (UINT16, 0.01C, display code DM004)
- H:411 Main Status — ENUM8: 0=Standby, 1=Heat demand, 3=Generator CH, 4=Generator DHW, 7=Cooling, 9=Blocking, 10=Locking, 16=Frost protection, etc.
- H:412 Sub Status — ENUM8: detailed sub-status (60+ values) — anti-cycling, defrost, compressor states, backup control
- H:413 Actual Relative Power — Actual relative power of appliance (UINT16, %, 0–100, display code AM024)
- H:459 Pump Speed — Current pump speed (UINT16, 0.1%, R/W, display code AM010)
- H:460 Actual Power kW — Actual power of appliance (UINT32, 0.01 kW, display code AM047)
- H:9230 Instantaneous COP — Calculated instantaneous COP (UINT16, 0.001, display code HM031). Key efficiency metric
- H:433 Energy Consumed CH — UINT32 (2 registers), energy consumed for central heating in kWh
- H:435 Energy Consumed DHW — UINT32 (2 registers), energy consumed for domestic hot water in kWh
- H:443 Total Thermal Energy Delivered — UINT32 (2 registers), total thermal energy delivered in kWh
- H:445 Thermal Energy CH — UINT32 (2 registers), thermal energy delivered for central heating in kWh
- H:447 Thermal Energy DHW — UINT32 (2 registers), thermal energy delivered for domestic hot water in kWh

## Sources

- GTW-08 Modbus Configuration Manual
  
  [tools.remeha.nl](https://tools.remeha.nl/wp-content/uploads/sites/11/2024/07/configuratiehandleiding-GTW-08.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/de-dietrich-hpi-s-11-tr/manufacturer/gtw-08-configuration-manual.pdf)
- De Dietrich / BDR Thermea GTW-08 Registers (EVCC)
  
  [github.com](https://github.com/evcc-io/evcc/issues/25470) 2026-03-20

## Related Documentation

- [Modbus Integration](https://taphome.com/en/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/en/docs/integration/modbus/)
- [Simple configuration using templates](https://taphome.com/en/docs/integration/modbus/templates/)
- [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/)
- [Modbus functions](https://taphome.com/en/docs/script/modbus/)
- [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/)