title: "Daikin RTD-NET FBA-A(9)"
description: "Daikin RTD-NET Modbus RTU interface adapter for centralized control of VRV, Sky Air, VAM and VKM indoor units via RS-485."
url: "https://taphome.com/en/compatibility/daikin-rtd-net-fba-a9/"
language: en
lastmod: 2026-03-24
generator: hugo
ai:
  topics: ["modbus-rtu","air-conditioning","rs485","dip-switch","vrv","p1p2-bus","vam"]
  questions: ["How to integrate Daikin RTD-NET with TapHome?","What does the Daikin RTD-NET TapHome template control?","How to connect Daikin RTD-NET via RS-485 to TapHome?","How to configure the DIP switch address on the Daikin RTD-NET?","What is the difference between RTD-NET and RTD-10?","How to control VAM/VKM ventilation units through the RTD-NET?"]
---

# Daikin RTD-NET FBA-A(9)

Communication: Modbus RTU

- [Daikin Official Website](https://www.daikin.com)

## Integration guide

The Daikin RTD-NET FBA-A(9) is a Modbus RTU interface PCB for centralized monitoring and control of Daikin VRV, Sky Air, VAM and VKM units. It connects to the indoor units via the Daikin P1/P2 remote controller network and exposes control and monitoring registers over RS-485. A single RTD-NET can manage up to 16 indoor units as one group.

The RTD-10 uses the same Modbus register layout and is fully compatible with this template.

## Hardware connection

### PCB overview

![Daikin RTD-NET PCB layout showing power connector, P1/P2 REMCON terminals, RS-485 D-BUS terminals, DIP switch SW1 and status LEDs](https://taphome.com/images/compatibility/daikin-rtd-net-fba-a9/pcb-overview_hu_b59023ccc8c7cb06.jpg)

**Key components on the PCB:**

- **POWER (0V / +V)** — 15–24 V DC power input
- **REMCON (P1 / P2)** — connection to the Daikin P1/P2 remote controller network
- **RS485 D-BUS (DB / DA / GND)** — Modbus RTU communication with TapHome
- **SW1** — 8-position DIP switch for Modbus address and timeout configuration
- **LED1 / LED2** — status indicators (green / red)
- **LED3 / LED4** — P1/P2 and Modbus communication activity

### Power supply wiring

![Daikin RTD-NET power supply wiring from indoor unit PCB (X18A/X35A VRV, X35A Skyair)](https://taphome.com/images/compatibility/daikin-rtd-net-fba-a9/power-wiring_hu_5b0a78c6572b9dbc.jpg)

### DIP switch addressing

![Daikin RTD-NET DIP switch address configuration and RS-485 D-BUS pin mapping (DB+, DA-, GND)](https://taphome.com/images/compatibility/daikin-rtd-net-fba-a9/dip-switch-addressing_hu_b36c29fe62509432.jpg)

### P1/P2 daisy-chain topology

![Daikin RTD-NET P1/P2 daisy-chain connection between indoor units and wired remote controller](https://taphome.com/images/compatibility/daikin-rtd-net-fba-a9/p1p2-daisy-chain_hu_fd6919f27796c9f1.jpg)

**Power supply:** The RTD-NET is powered from the indoor unit PCB — connect to X18A or X35A on VRV units, X35A on Sky Air units, or X11A on VAM/VKM units. A 1 m cable with connector is supplied.

**RS-485 wiring (3-wire connection):**

- **DB(+)** → A+/D+ on TapHome RS-485
- **DA(-)** → B-/D- on TapHome RS-485
- **GND** → GND on TapHome power supply (**mandatory**)

**Cable specification:**

- Type: 24 AWG twisted pair, shielded or unshielded
- Standard: CAT3, CAT4 or CAT5
- Max length: **500 m**
- Topology: daisy-chain only (star and ring connections are not supported)

> [!WARNING]
> The GND wire **must** be connected between all devices on the RS-485 bus. If shielded cable is used, the shield can serve as the GND connection. Connect GND to local earth at one point only (single-point grounding).

**P1/P2 network:** Connect P1 and P2 terminals to the Daikin P1/P2 network. Up to 16 indoor units and one remote controller can be connected. Maximum P1/P2 cable length is 500 m.

> [!NOTE]
> BRC infra-red receivers must be set to **SUB (S)** mode when the RTD-NET operates as MAIN (M).

## Configuration

### DIP switch addressing (SW1)

The Modbus RTU slave address is set using DIP switch SW1, positions 1–6 (binary encoding, range 0–63).

**Address examples:**

| Address | SW1 (1) | SW1 (2) | SW1 (3) | SW1 (4) | SW1 (5) | SW1 (6) |
|---------|---------|---------|---------|---------|---------|---------|
| **0** | OFF | OFF | OFF | OFF | OFF | OFF |
| **1** | ON | OFF | OFF | OFF | OFF | OFF |
| **2** | OFF | ON | OFF | OFF | OFF | OFF |
| **3** | ON | ON | OFF | OFF | OFF | OFF |
| **10** | OFF | ON | OFF | ON | OFF | OFF |

**Recommended:** Address 1 for the first adapter (SW1-1 = ON, all others OFF).

### Modbus master timeout (SW1 positions 7–8)

| SW1 (7) | SW1 (8) | Behavior |
|---------|---------|----------|
| OFF | OFF | No timeout |
| ON | OFF | After 120 s without a holding register write: all units ON with current settings, remote controllers **unlocked** |
| OFF | ON | After 120 s without a holding register write: all units ON with current settings, remote controller lock state **unchanged** |

### Communication parameters

| Parameter | Value |
|-----------|-------|
| Baud rate | 9600 (configurable) |
| Parity | None (configurable) |
| Stop bits | 1 |
| Data bits | 8 |
| Register base | 0 |

## Device capabilities

### Unit power and operation mode

- **ON/OFF** (H:5) — turns all indoor units on or off
- **Operation Mode** (H:3) — selects Auto, Heat, Fan, Cool, or Dry mode
- **Fan Speed** (H:2) — selects Off, Low, Medium, or High. The available speeds depend on the indoor unit model
- **Louvre Direction** (H:4) — controls the vane position: Stop, Swing, 0°, 20°, 45°, 70°, or 90°

### Temperature monitoring

- **Remote Controller Temperature** (A:50) — room temperature reading from the wired remote controller, with automatic °C x 100 conversion. Only available when exactly one indoor unit is connected and the remote controller is in Sub mode

The temperature sensor also exposes service attributes for return air temperatures across all connected units: **Return Air Average** (A:23), **Return Air Min** (A:25), and **Return Air Max** (A:26), as well as the **RC Operation Mode** (A:51) showing whether the system is idle, heating, cooling, or in combined heat & cool mode.

### VAM/VKM ventilation control

The Fan Speed device includes two service attributes for VAM and VKM ventilation units:

- **Damper Control** (H:30) — sets the ventilation mode: Auto, Cross Flow / Heat Recovery, or Bypass
- **VAM Fan Speed** (H:31) — sets the ventilation rate: Low or High

### Update modes and control limiting

The module exposes a comprehensive set of service attributes for managing how control values are pushed to indoor units:

**Update mode registers** (H:10–H:15) determine the behavior for each control parameter (Global, Setpoint, Fanspeed, Mode, Louvre, Power):

| Update mode | Remote controller | Behavior |
|-------------|-------------------|----------|
| **LastTouch** (default) | Unlocked | Updates on every write, even if value unchanged |
| **Central** | Locked | Remote controller buttons locked, value repeatedly written |
| **Local** | Unlocked | No updates sent to unit |
| **OnChange** | Unlocked | Updates only when value changes |

The **Control Update** service action allows setting all six update mode parameters at once.

**Control limiting registers** restrict what end users can adjust from the remote controller:

- **SetPoint** (H:1) — current temperature setpoint value
- **SetPoint Min / Max** (H:20, H:21) — limit the allowable setpoint range (0 = no limit)
- **Fanspeed Inhibit** (H:23) — bitmask to disable specific fan speeds
- **Mode Inhibit** (H:24) — bitmask to disable specific operation modes
- **Louvre Inhibit** (H:24) — bitmask to disable specific louvre positions

### Service diagnostics

The module ReadScript monitors three status registers and reports them as errors or warnings in TapHome:

- **Unit fault** (A:21) — if any indoor unit reports a fault, an error is raised with the fault code from A:22
- **Defrost** (A:35) — if any unit is in defrost cycle, a warning is displayed
- **Filter alarm** (A:24) — if any unit has a filter alarm, an error is raised

The **Unit Count** service attribute (A:20) shows how many indoor units are detected on the P1/P2 network, and **Summary of Unit Operation** (A:30) reports the group thermal activity (Idle/Fan, Heating, Cooling, or Heat & Cool).

### Additional capabilities

The RTD-NET also exposes per-unit input registers for individual monitoring of up to 16 indoor units, including per-unit return air temperature, fault status, fault codes, filter alarms, coil inlet/outlet temperatures, and thermal state. Smart Grid control (H:55), available on the related EKMBPP1 adapter, is not included in this template. These can be added in a future template update.

## LED status indicators

| LED state | Meaning |
|-----------|---------|
| LED1 + LED2 alternating | P1/P2 search mode (power-up, unit configuration) |
| LED1 steady ON, LED2 OFF | Normal operation, no fault |
| LED1 ON, LED2 flashing | At least one indoor unit in fault |
| LED1 flashing, LED2 OFF | Device configuration error |
| LED1 OFF, LED2 flashing slow | AC unit missing (U5 fault) |
| LED1 flashing, LED2 flashing | RS-485 communication timeout |

## Troubleshooting

### No Modbus communication (LED activity absent)

1. **Check RS-485 cables:**
   - DB(+) correctly connected to A+/D+ on TapHome
   - DA(-) correctly connected to B-/D- on TapHome
   - **GND connected** — most common issue
2. Verify the Modbus slave address on DIP switch SW1 (positions 1–6)
3. Confirm TapHome is set to: 9600 baud, no parity, 1 stop bit
4. Check cable topology — daisy-chain only, no star or ring connections
5. Verify maximum cable length does not exceed 500 m

### Indoor unit not found (LED1 OFF, LED2 flashing slow)

1. Check P1/P2 cables between the RTD-NET and the indoor unit
2. Verify the indoor unit is powered on
3. Wait at least 1 minute after power-up for P1/P2 communication to establish
4. Restart the adapter by disconnecting and reconnecting power

### RC Temperature reads zero or is unavailable

The remote controller temperature (A:50) is only available when exactly one indoor unit is connected and the remote controller is configured as MAIN. With multiple units or the RTD-NET in MAIN mode, this register returns no data.

### Timeout warning (LED1 + LED2 both flashing)

If DIP switch positions 7–8 are configured for timeout and TapHome stops writing holding registers for more than 120 seconds, the RTD-NET will switch all units ON with current settings and indicate a timeout on the LEDs. Ensure TapHome is regularly polling and writing registers.

## Available devices 5

These devices appear in TapHome after import.

Daikin RTD-NET FBA-A(9) Module

Service Attributes

|                           |                                                                               |
|---------------------------|-------------------------------------------------------------------------------|
| Summary of Unit Operation | Group thermal activity — Idle/Fan, Heating, Cooling, Heat & Cool              |
| Global Update             | Update mode for all control parameters — Last Touch, Central, Local, OnChange |
| Setpoint Update           |                                                                               |
| Fanspeed Update           |                                                                               |
| Mode Update               |                                                                               |
| Louvre Update             |                                                                               |
| Power Update              |                                                                               |
| SetPoint                  | Current temperature setpoint value in °C                                      |
| SetPoint Min              | Minimum allowed setpoint — 0 means no limit                                   |
| Setpoint Max              | Maximum allowed setpoint — 0 means no limit                                   |
| Fanspeed Inhibit          | Bitmask restricting available fan speeds — 0 means no restriction             |
| Mode Inhibit              | Bitmask restricting available operation modes — 0 means no restriction        |
| Louvre Inhibit            | Bitmask restricting available louvre positions — 0 means no restriction       |
| Unit Count                | Number of indoor units detected on the P1/P2 network                          |

Service Actions

|                |                                                             |
|----------------|-------------------------------------------------------------|
| Control Update | Sets the update mode for all six control parameters at once |

Read (module)

```taphome
IF(MODBUSR(A, 21, Uint16) = 1, ADDERROR("At least one unit in fault", MODBUSR(A, 22, Uint16)));
IF(MODBUSR(A, 35, Uint16) = 1, ADDWARNING("At least one unit in defrost"));
IF(MODBUSR(A, 24, Uint16) = 1, ADDERROR("At least one unit in filter alarm"));
```

Service Attributes

Summary of unit operation

```taphome
Switch(MODBUSR(A, 30, Uint16), 0, "Idle/Fan", 1, "Heating", 2, "Cooling", 3, "Heat & Cool", "Unknown");
```

Global Update

```taphome
var gu := MODBUSR(H, 10, Uint16);
SWITCH(gu, 0, "Last Touch", 1, "Central", 2, "Local", 3,"OnChange", "Unknown")
```

Setpoint Update

```taphome
var se := MODBUSR(H, 11, Uint16);
SWITCH(se, 0, "Last Touch", 1, "Central", 2, "Local", 3,"OnChange", "Unknown")
```

Fanspeed Update

```taphome
var fe := MODBUSR(H, 12, Uint16);
SWITCH(fe, 0, "Last Touch", 1, "Central", 2, "Local", 3,"OnChange", "Unknown")
```

Mode Update

```taphome
var mu := MODBUSR(H, 13, Uint16);
SWITCH(mu, 0, "Last Touch", 1, "Central", 2, "Local", 3,"OnChange", "Unknown")
```

Louvre Update

```taphome
var se := MODBUSR(H, 14, Uint16);
SWITCH(se, 0, "Last Touch", 1, "Central", 2, "Local", 3,"OnChange", "Unknown")
```

Power Update

```taphome
var pow := MODBUSR(H, 15, Uint16);
SWITCH(pow, 0, "Last Touch", 1, "Central", 2, "Local", 3,"OnChange", "Unknown")
```

SetPoint

```taphome
MODBUSR(H, 1, Uint16);
```

SetPoint Min

```taphome
var sm := MODBUSR(H, 20, Uint16);
IF(sm = 0,"No limit", sm);
```

Setpoint Max

```taphome
var sm := MODBUSR(H, 21, Uint16);
IF(sm = 0,"No limit", sm);
```

Fanspeed Inhibit

```taphome
var sm := MODBUSR(H, 23, Uint16);
IF(sm = 0,"No limit", sm);
```

Mode Inhibit

```taphome
var sm := MODBUSR(H, 24, Uint16);
IF(sm = 0,"No limit", sm);
```

Louvre Inhibit

```taphome
var sm := MODBUSR(H, 24, Uint16);
IF(sm = 0,"No limit", sm);
```

Unit Count

```taphome
var uc := MODBUSR(A, 20, Uint16);
uc + " unit" + IF(uc != 1, "s", "");
```

Service Actions

Control Update

Parameters: Global Update, Setpoint Update, Fanspeed Update, Mode Update, Louvre Update, Power Update

```taphome
MODBUSW(H, 10, Uint16, gu);
MODBUSW(H, 11, Uint16, su);
MODBUSW(H, 12, Uint16, fu);
MODBUSW(H, 13, Uint16, mu);
MODBUSW(H, 14, Uint16, lu);
MODBUSW(H, 15, Uint16, pu);
```

Fan Speed Multi-value Switch Read and write

Fan speed control — Off, Low, Medium, High

Register: H:2 UInt16 numeric

Values / States: Low · Medium · High

Read switch state

```taphome
MODBUSR(H, 2, UInt16)
```

Write switch state

```taphome
MODBUSW(H, 2, UInt16, Mu)
```

Service Attributes

Damper Control

```taphome
Switch(MODBUSR(H, 30, Uint16), 0, "Auto", 1, "Cross Flow / Heat Recovery", 2, "Bypass", "Unknown");
```

VAM Fanspeed

```taphome
Switch(MODBUSR(H, 31, Uint16),1, "Low", 2, "High", "Unknown");
```

Louvre Direction Multi-value Switch Read and write

Airflow vane position — Stop, Swing, 0°, 20°, 45°, 70°, 90°

Register: H:4 Int16 numeric

Values / States: Swing · 0° · 20° · 45° · 70° · 90°

Read switch state

```taphome
MODBUSR(H, 4, Int16)
```

Write switch state

```taphome
MODBUSW(H, 4, Int16, Mu)
```

ON/OFF Switch Read and write

Register: H:5 UInt16

Values / States: ON · OFF

Read switch state

```taphome
MODBUSR(H, 5, Uint16)
```

Write switch state

```taphome
MODBUSW(H, 5, Uint16, St)
```

Remote Controller Temperature Temperature Sensor Read-only

Room temperature from the wired remote controller (°C) — available only with a single indoor unit in Sub mode

Register: A:50 UInt16 Unit: °C numeric

Service Attributes

|                    |                                                                       |
|--------------------|-----------------------------------------------------------------------|
| RC Operation Mode  | Remote controller operation — Idle/Fan, Heating, Cooling, Heat & Cool |
| Return Air Min     | Minimum return air temperature across all indoor units (°C)           |
| Return Air Max     | Maximum return air temperature across all indoor units (°C)           |
| Return Air Average | Group average return air temperature across all indoor units (°C)     |

Read temperature

```taphome
MODBUSR(A, 50, Uint16) / 100
```

Service Attributes

RC Operation Mode

```taphome
var om := MODBUSR(A, 51, UInt16);
Switch(om, 0, "Idle/Fan", 1, "Heating", 2, "Cooling", 3, "Heat & Cool", "Unknown");
```

Return Air Min

```taphome
MODBUSR(A, 25, Uint16)/100 + "°C"
```

Return Air Max

```taphome
MODBUSR(A, 26, Uint16)/100 + "°C"
```

Return Air Average

```taphome
MODBUSR(A, 23, Uint16)/100 + "°C"
```

Operation Mode Multi-value Switch Read and write

HVAC operation mode — Auto, Heat, Fan, Cool, Dry

Register: H:3 Int16 numeric

Values / States: Auto · Heat · Fan · Cool · Dry

Read switch state

```taphome
MODBUSR(H, 3, Int16)
```

Write switch state

```taphome
MODBUSW(H, 3, Int16, Mu)
```

**Connection:** Modbus RTU • 9600 baud• 8N1 • Slave ID: $\[SlaveId]

Possible improvements (4)

- H:22 Fan Speed Inhibit — Bitmask — inhibit specific fan speeds (template uses H:23 for Fanspeed Inhibit which may be a register error; H:22 is the documented fan speed inhibit register)
- H:25 Louvre Inhibit (correct register) — Template reads H:24 for both Mode Inhibit and Louvre Inhibit — likely a copy-paste error; the actual louvre inhibit register should be H:25
- A:22 Error Code (group) — Read by module readscript as ADDERROR parameter, but not exposed as a standalone service attribute
- H:55 Smart Grid — 0=Free running, 1=Forced off, 2=Recommended on, 3=Forced on. Present in EKMBPP1 template but absent from RTD-NET template

## Import parameters

Enter these values when you import the XML.

| Asked in the app | Default       |
|------------------|---------------|
| Slave ID         | `1`           |
| IP address       | `192.168.1.0` |

## Sources

- RTD-NET Installation Instructions (18870-1.06)
  
  [www.daikin.eu](https://www.daikin.eu/content/dam/document-library/installation-manuals/ctrl/RTD-NET%20installation%20instructions_18870-1.06%20EN_Installation%20manuals_English.pdf) 2026-03-24
  
  [PDF](https://taphome.com/compatibility/devices/daikin-rtd-net-fba-a9/manufacturer/rtd-net-installation-instructions.pdf)
- Daikin RTD-NET Application Note (NorthBT)
  
  [www.northbt.com](https://www.northbt.com/doc/driver/Daikin%20RTD-NET%20Application%20Note.pdf) 2026-03-24
  
  [PDF](https://taphome.com/compatibility/devices/daikin-rtd-net-fba-a9/manufacturer/rtd-net-application-note.pdf)

Manufacturer documents are © their respective owners. They are provided as published by the manufacturer, for reference only.

## Related Documentation

- [Modbus Integration](https://taphome.com/en/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/en/docs/integration/modbus/)
- [Simple configuration using templates](https://taphome.com/en/docs/integration/modbus/templates/)
- [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/)
- [Modbus functions](https://taphome.com/en/docs/script/modbus/)
- [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/)