Daikin FCBAG plug-in Modbus RTU module for Daikin FWT-HT and FWT-HTV fan coil units, connected to TapHome over RS-485. Switches the unit on and off, sets the operation mode, set temperature, louver position and fan speed, and reads the room temperature, Daikin error codes and room sensor fault. Modbus is enabled on the mainboard DIP switch, the slave address on the module.

Modbus RTU5 devicesRevision 1.0 Last updated: November 12, 2026

Submitted by Architechnik Kft.

Daikin FCBAG Modbus RTU

Import into the TapHome appHardware › Modbus › Add from template

Download Template
On this page

Integration guide

The Daikin FCBAG is an optional plug-in Modbus RTU module for Daikin FWT-HT and FWT-HTV wall-mounted chilled water fan coil units. It sits in a dedicated slot in the control box of the indoor unit, connects to the unit’s mainboard with a short wire harness and exposes the unit on an RS-485 bus. The template connects TapHome directly to this bus — no other gateway is needed — and covers switching the unit on and off, the operation mode, the room temperature and set temperature, the louver position, the fan speed and the unit’s error codes.

The device names in the template are in Hungarian. Below, each device is named exactly as it appears after the import, followed by its English meaning, for example Klíma (unit on/off).

Hardware connection

Installation must be done by a qualified person. Switch the unit off and disconnect all power supplies before opening the control box.

FCBAG module

Daikin FCBAG module PCB layout: TB_RS485 terminal, CN_MODBUS_MODULAR_1 connector, DIP_RS485 switch, TX and RX LEDs
ItemFunction
TB_RS485RS-485 terminal (A, B) for the Modbus master and other FCBAG modules
CN_MODBUS_MODULAR_1Connector for the harness to CN_MODBUS_MODULAR on the unit’s mainboard
DIP_RS485Slave address of the unit
TX_LED (yellow)Data transmission in progress
RX_LED (red)Data reception in progress

The box contains the module, a 10-wire harness (100 mm) to the mainboard and the manual. According to Daikin, the module can only be used with fan coil units produced by Daikin Manufacturing.

Installing the module in the unit

  1. Switch the unit off and remove the metal cover of the control box.
  2. Insert the FCBAG module into the dedicated slot and push it fully into the hook.
  3. Connect the harness from CN_MODBUS_MODULAR_1 on the module to CN_MODBUS_MODULAR on the mainboard (the connector labelled “Accessory: Modbus (FCBAG)” in the unit’s installation manual).
  4. Route the RS-485 cable as shown in the module manual.
  5. Set the DIP switches (see Configuration below) and close the control box with the metal cover.

RS-485 wiring

Connect A and B of TB_RS485 to A and B of the TapHome RS-485 bus. Several units are chained from one TB_RS485 to the next — the module manual shows up to 15 units on one bus behind the Modbus master.

ConnectionCableMax. length
FCBAG module to Modbus master (TapHome)24 AWG shielded twisted pair, 100 Ω characteristic impedance1000 m
FCBAG module to mainboard10-wire harness (supplied)100 mm

Configuration

The communication settings are set on two DIP switches: DIP_Config on the unit’s mainboard and DIP_RS485 on the FCBAG module. Modbus is off until pin 1 of DIP_Config is switched ON.

Daikin FCBAG configuration table: DIP_Config pins for Modbus enable, baud rate, stop bit and parity, and DIP_RS485 slave address pins

DIP_Config on the mainboard

PinFunctionOFFONFor this template
1ModbusDisableEnableON
2Baud rate9600 bps19200 bpsOFF (9600)
3Stop bit1 (with parity)2 (no parity)OFF
4Parity (only when pin 3 is OFF)EvenOddOFF (Even)
5Reserved in the module manual——see note

The unit’s installation manual uses DIP_Config pin 5 to enable the dry-contact on/off input (TB_ON/OFF). It is not part of the Modbus settings — leave it as that function requires.

Slave address (DIP_RS485 on the module)

Pins 1–4 of DIP_RS485 set the slave address in binary: pin 1 = 1, pin 2 = 2, pin 3 = 4, pin 4 = 8 (the address is the sum of the pins switched ON). Addresses 1–15 are valid; 0 (all OFF) disables Modbus communication. Pin 5 is reserved. Each unit on the bus needs its own address, and the template covers one unit — with several units it is imported once per unit with that unit’s address.

The template’s default Slave ID is 2 — only pin 2 ON. The module manual (page “Unit configuration”) shows the switch positions for all addresses 1–15.

Communication parameters

ParameterValue
Baud rate9600
ParityEven
Data bits8
Stop bits1
Slave ID2 (import parameter Modbus Slave ID)

In TapHome, the template is imported on a Modbus RTU interface of this RS-485 bus with the parameters above, and the import parameter Modbus Slave ID is set to the address from DIP_RS485.

Device capabilities

Register numbers below follow the module manual: input registers 3xxxx are read, holding registers 4xxxx are written. Commands that change one part of register 42001 read it first and write it back with only that part changed, so on/off, louver and fan speed do not overwrite each other.

On/off

Klíma (unit on/off) — reads bit 0 of input register 32001 and writes bit 0 of holding register 42001. Its service attributes show the current fan speed (Ventilátor sebesség) and the louver position (Légirány (swing)). The louver attribute reads only bits 8–9, so it shows positions 4, 5 and Swing as other values — the Lamella állás device shows the full value.

Operation mode

Üzemmód (operation mode) — reads input register 32002 and writes holding register 42002:

ValueState in TapHomeMeaning
0VentilátorFan
1FűtésHeat
2HűtésCool
3AutoAuto
7SzárazDry

Temperature

Hőmérséklet (thermostat):

  • room temperature from input register 32005, divided by 10,
  • set temperature read from input register 32003 (divided by 10) and written to holding register 42003 (multiplied by 10),
  • set temperature range in TapHome 16–32 °C.

The thermostat also reports two errors:

  • Meghibásodás (unit fault) — when bit 9 of input register 32004 (error code) is set. The text shows the Daikin error code: a letter from bits 8–12 (1 = A, 2 = C, 3 = E, 4 = H, 5 = F, 6 = J, 7 = L, 8 = P, 9 = U) followed by the number from bits 0–3.
  • Szobahőmérséklet-érzékelő hiba (room temperature sensor fault) — when bit 8 of input register 32006 is set.

Louver and fan

  • Lamella állás (louver position) — bits 8–10 of 32001, written to bits 8–10 of 42001: Megáll (stop), 1. pozíció … 5. pozíció (positions 1–5) and Swing.
  • Ventilátor sebesség (fan speed) — bits 12–14 of 32001, written to bits 12–14 of 42001: Alacsony (low), Közép-alacsony (medium-low), Közepes (medium), Közép-magas (medium-high), Magas (high) and Auto.

The module manual also lists Disable Handset Control (42010), Force Compressor / Valve Off (42011), the indoor coil temperature (32201), the module and connection status (30001, 30002) and the set temperature limits of the unit (31002, 31003). They are not included in this template.

Troubleshooting

The LEDs on the module show the state of the bus: RX_LED (red) for reception, TX_LED (yellow) for transmission.

  • No communication, RX_LED lit steadily but not blinking, TX_LED not blinking: A and B on TB_RS485 are swapped, or one of them is not connected. Check the wiring at TB_RS485.
  • No communication, RX_LED blinking, TX_LED not blinking: the DIP_Config setting on the mainboard is wrong — pin 1 (Modbus) must be ON. Also check that DIP_RS485 is not set to 0 and matches the Modbus Slave ID of the template.
  • Values are read but the unit does not react to commands (both LEDs blinking): DIP_Config does not match the communication settings of the TapHome interface. With pin 2 ON the module runs at 19200 Bd, with pin 3 ON it uses 2 stop bits without parity, with pin 4 ON odd parity.

Available devices 5

These devices appear in TapHome after import.

Daikin FCBAG modul Module
Klíma Switch
Values / States: ON · OFF

Klíma

Read switch state
GETBIT(MODBUSR(A, 2000, UInt16), 0)
Write switch state
VAR reg := MODBUSR(H, 2000, UInt16);
reg := SETBIT(reg, 0, St);
MODBUSWNE(H, 2000, UInt16, reg);
Service Attributes
Ventilátor sebesség
SWITCH(GETBITS(MODBUSR(A, 2000, UInt16), 12, 3), 1, "Alacsony", 2, "Közép-alacsony", 3, "Közepes", 4, "Közép-magas", 5, "Magas", 7, "Auto", "Ismeretlen")
Légirány (swing)
SWITCH(GETBITS(MODBUSR(A, 2000, UInt16), 8, 2), 0, "Megáll", 1, "1. pozíció", 2, "2. pozíció", 3, "3. pozíció", 4, "4. pozíció", 5, "5. pozíció", 7, "Swing", "Ismeretlen")
Üzemmód Multi-value Switch
Values / States: Ventilátor · Fűtés · Hűtés · Auto · Száraz

Üzemmód

Read switch state
MODBUSR(A, 2001, UInt16)
Write switch state
MODBUSWNE(H, 2001, UInt16, Mu)
Hőmérséklet Thermostat

Hőmérséklet

Read temperature
MODBUSR(A, 2004, Int16)/10
Read desired temperature
MODBUSR(A, 2002, Int16)/10
Write desired temperature
MODBUSWNE(H, 2002, Int16, Se*10)
Read (module)
VAR errorReg := MODBUSR(A, 2003, UInt16);
IF(GETBIT(errorReg, 9))
  VAR upper := GETBITS(errorReg, 8, 5);
  VAR lower := GETBITS(errorReg, 0, 4);
  VAR letter := SWITCH(upper, 1, "A", 2, "C", 3, "E", 4, "H", 5, "F", 6, "J", 7, "L", 8, "P", 9, "U", "?");
  ADDERROR(1, "Meghibásodás: " + letter + TOSTRING(lower, "F0"));
END
VAR sensorReg := MODBUSR(A, 2005, UInt16);
IF(GETBIT(sensorReg, 8))
  ADDERROR(2, "Szobahőmérséklet-érzékelő hiba");
END
Lamella állás Multi-value Switch
Values / States: Megáll · 1. pozíció · 2. pozíció · 3. pozíció · 4. pozíció · 5. pozíció · Swing

Lamella állás

Read switch state
GETBITS(MODBUSR(A, 2000, UInt16), 8, 3)
Write switch state
VAR reg := MODBUSR(H, 2000, UInt16);
reg := SETBITS(reg, 8, 3, Mu);
MODBUSW(H, 2000, UInt16, reg);
Ventilátor sebesség Multi-value Switch
Values / States: Alacsony · Közép-alacsony · Közepes · Közép-magas · Magas · Auto

Ventilátor sebesség

Read switch state
GETBITS(MODBUSR(A, 2000, UInt16), 12, 3)
Write switch state
VAR reg := MODBUSR(H, 2000, UInt16);
reg := SETBITS(reg, 12, 3, Mu);
MODBUSW(H, 2000, UInt16, reg);
Connection: Modbus RTU • 9600 baud• 8E1 • Slave ID: $[SlaveId]

Import parameters

Enter these values when you import the XML.

Asked in the appDefault
Modbus Slave ID2

Found a problem with this device template?

Tell us what's wrong, what's missing, or how the template should behave. We rely on your feedback to keep the catalog accurate.

Template · TapHome portal Daikin FCBAG Modbus RTU Open this template in the Customer Portal to apply it to one of your homes, or to draft a refinement and submit it back to the catalog. Modbus RTU View in TapHome portal