TapHome
Official · TapHome HVAC integration

Daikin Altherma 3 Heat Pump

Daikin Altherma 3 heat pump integration via DCOM-LT/MB Modbus RTU gateway. TapHome template with 20 devices for temperature monitoring, space heating/cooling control, DHW management, weather-dependent setpoints and compressor diagnostics.

DaikinModbus RTU22 devicesRevision 1.4 Last updated: November 17, 2026
Works on Core TapHome 2025.2.32396, Core 2026.1.41766 (Next channel)
iWe imported this template into this Core in the TapHome lab and every device was added without an error.
Daikin Altherma 3 Heat Pump

Import into the TapHome appHardware › Modbus › Add from template

Download Template
On this page

Requires external gateway

Daikin DCOM-LT/MB — product page

Integration guide

The Daikin Altherma 3 is an air-to-water heat pump series covering Altherma 3 R, Altherma 3 H MT and Altherma 3 H HT models. TapHome connects to the heat pump through the DCOM-LT/MB Modbus RTU gateway, which interfaces with the Altherma via the P1P2 bus and exposes registers over RS-485.

This TapHome template provides 22 devices covering temperature monitoring, space heating/cooling control, DHW management, quiet mode, defrost status and weather-dependent setpoints. For an advanced template with service attributes, service actions and module-level error handling, see the DCOM-RW variant.

Hardware connection

DCOM-LT/MB gateway overview

DCOM-LT/MB gateway component layout showing terminals, LEDs and DIP switches

The DCOM-LT/MB gateway (model S34-001) mounts on a DIN rail and has the following connections:

  • Terminals 1–2 (A) — Power supply: 15–24 VDC regulated, minimum 100 mA
  • Terminals 3–5 (B) — RS-485: + (terminal 3), - (terminal 4), C/common (terminal 5)
  • Terminals 10–11 (E) — P1P2 bus connection to Altherma indoor unit
  • SW1 (J) — 8-position DIP switch for Modbus address and operating mode
  • LEDs (P, Q, R) — Status, ACNET (P1P2), RS485 indicators

RS-485 wiring

Connect using a 3-wire RS-485 connection between DCOM-LT/MB and TapHome:

  • Terminal 3 (+) → A+/D+ on TapHome RS-485
  • Terminal 4 (-) → B-/D- on TapHome RS-485
  • Terminal 5 (C) → GND/Common on TapHome

Cable specification:

  • Type: screened twisted pair (Belden 8761 or equivalent)
  • Minimum cross-section: 0.33 mm²
  • Resistance: ≤ 60 Ω/km
  • Max bus length: 1000 m
  • Max devices on bus: 32 (including Modbus master)

The common wire (terminal 5/C) must be connected between DCOM-LT/MB and TapHome. Without a proper common connection, communication errors will occur. Shield should be earthed at one location only.

Termination is not required at 9600 baud for network lengths up to 1000 m. The DCOM-LT/MB has internal failsafe biasing, so no external bias resistors are needed. If termination is used, a failsafe biasing circuit must be added as well.

P1P2 connection

Connect the P1P2 terminals (10, 11) to a compatible Altherma LT Master Remote Controller (e.g., MM4 or equivalent).

Altherma 2 compatibility: The DCOM-LT/MB can only be used with Altherma 2 via the Remcon/LT LAN adaptor. Do NOT connect DCOM directly to Altherma 2 (EKRUCBL / EKRUEHBL) units.

Configuration

DIP switch addressing

DCOM-LT/MB wiring detail and DIP switch address reference table

The 8-position DIP switch SW1 configures the Modbus slave address and operating mode:

SwitchFunction
SW1.1 + SW1.2Smart Grid / operating mode select
SW1.3 + SW1.4Modbus slave address (1–4)
SW1.5Smart Grid function (with SW1.1, SW1.2)
SW1.6–SW1.8Reserved

Modbus address selection (SW1.3 and SW1.4):

SW1.3SW1.4Address
OFFOFF1 (default)
OFFON2
ONOFF3
ONON4

Communication parameters

ParameterValue
ProtocolModbus RTU
Baud rate9600
Data bits8
ParityNone
Stop bits1

Synchronization

After power-up, the DCOM-LT/MB synchronizes with the Altherma Master unit. This process can take up to 8 minutes. During synchronization, register reads return the special value 32765 (“Wait for value”).

Special return values:

ValueMeaning
32765Waiting for value — synchronization in progress
32766Register unavailable in current configuration
32767Register not supported by connected unit

After initial power-up or restart, allow up to 8 minutes for DCOM to fully synchronize before troubleshooting missing register values. The Status LED changes from yellow (synchronizing) to solid green when ready.

Device capabilities

The two templates share a common set of registers but differ in scope. The main template provides comprehensive monitoring and control with 22 devices including defrost status, quiet mode, DHW reheat control and additional temperature sensors. The DCOM-RW template adds module-level error handling, service attributes for system status, and service actions for advanced setpoint management with parameter validation.

Temperature monitoring

All temperature sensors use the comp14 format (signed 16-bit value divided by 100 for °C). The templates handle this conversion automatically.

  • Outside Air Temperature (A:44) — outdoor ambient temperature
  • DHW Temperature (A:43) — domestic hot water tank temperature, shown as the current temperature of the DHW Setpoint device
  • Return Water Temperature (A:42) — heating circuit return water temperature
  • Leaving Water Temp pre PHE (A:40) — leaving water temperature before plate heat exchanger
  • Leaving Water Temp pre BUH (A:41) — leaving water temperature before backup heater
  • Liquid Refrigerant Temperature (A:45) — refrigerant liquid line temperature
  • Flow Rate (A:49) — water flow rate in l/min (main template) or m³/h (DCOM-RW)

Space heating and cooling control

  • Space Heating/Cooling On/Off (H:4) — master switch that turns space heating and cooling on and off
  • Heat Pump Mode (H:3) — operation mode: Auto, Heating, or Cooling
  • Weather Dependent Mode (H:53) — selects between Fixed, Weather Dependent, Fixed+Scheduled, or Weather Dependent+Scheduled setpoint modes
  • Weather Curve Setpoint (H:1) — leaving water main heating setpoint, range 25–55°C, shown with the measured leaving water temperature (A:41) as the current temperature
  • Leaving Water Cooling Setpoint (H:2) — leaving water main cooling setpoint, range 5–22°C, shown with the measured leaving water temperature (A:41) as the current temperature
  • Weather Curve Offset (H:54) — weather dependent setpoint offset, range -10 to +10°C
  • Weather Curve Offset Cooling (H:55) — weather dependent cooling setpoint offset, range -10 to +10°C

Instead of the unit’s own weather-dependent curve, TapHome can write the required leaving water temperature directly — for example from the smart rule Equithermic regulation. The leaving water setpoints (H:1, H:2) and the cooling offset (H:55) are limited to their range, rounded to whole °C and written only when they change.

The absolute leaving water setpoints (H:1 heating, H:2 cooling) apply only when Weather Dependent Mode (H:53) is set to Fixed (0). In weather-dependent mode, the unit uses an offset of its curve instead — Weather Curve Offset (H:54) for heating, Weather Curve Offset Cooling (H:55) for cooling.

The DCOM-RW template extends the Operation Mode device with 4 service attributes reading current setpoints (leaving water heating/cooling, room thermostat heating/cooling) and 4 service actions for writing individual setpoints with defined ranges.

DHW (Domestic Hot Water) control

  • DHW Setpoint (H:10) — reheat setpoint temperature, range 30–65°C. The DHW temperature limit set in the heat pump takes precedence — the heat pump clamps a higher written value to its own limit.
  • DHW Reheat On/Off (H:12) — triggers DHW reheat cycle
  • DHW Booster Mode (H:13) — enables auxiliary/booster heater for DHW (DCOM-RW only)

The DCOM-RW template adds a service attribute on DHW Reheat showing the current setpoint and a service action for setting the DHW reheat temperature (30–65°C).

System status monitoring

  • Unit Error (A:21) — error status: No Error, Fault, or Warning
  • Compressor Run (A:31) — compressor running status (ON/OFF)
  • Circulation Pump (A:30) — circulation pump running status (ON/OFF)
  • Disinfection Operation (A:33) — legionella disinfection cycle status (ON/OFF)
  • 3-Way Valve Position (A:37) — valve position: Space Heating or DHW
  • Defrost/Startup (A:35) — defrost or startup cycle status
  • Quiet Mode (H:9) — quiet mode operation switch

The DCOM-RW template exposes additional module-level service attributes: Booster Heater Run (A:32), Hot Start (A:36), actual Operation Mode (A:38), and two additional temperature readings (Leaving Water Temp pre PHE and pre BUH).

Additional capabilities

The DCOM-LT/MB also exposes registers for room thermostat heating/cooling setpoints (H:6/H:7), unit error code decoding (A:22 text14 format + A:23 sub-code), and room temperature reading (A:50). Some of these are available through service actions in the DCOM-RW template; the rest can be added in a future template update.

The DCOM-RW template provides additional control capabilities. The room thermostat setpoints are accessible via service actions on the Operation Mode device, even though they are not standalone devices.

LED status indicators

The DCOM-LT/MB has three LED indicators:

LEDNormalError
StatusSolid green — synchronized, no faultSolid red — unit fault; slow red blink — timeout
ACNETGreen flash — normal P1P2 communicationRed flash/solid — P1P2 errors
RS485Green flash — normal Modbus communicationRed flash/solid — RS-485 errors

At power-up, all LEDs change from red to green, then the Status LED begins flashing yellow while waiting for Altherma Master synchronization.

Troubleshooting

Status LED yellow (waiting for Master)

  1. Check P1P2 cable connections between DCOM-LT/MB and the Altherma indoor unit
  2. Verify the Altherma unit is powered on and operational
  3. Allow up to 8 minutes for initial synchronization — if the Status LED remains yellow for more than 10 minutes, the DCOM will retry automatically
  4. If Status LED flashes red (timeout), verify P1P2 wiring and restart the DCOM

RS-485 LED red (communication errors)

  1. Check RS-485 wiring: + (terminal 3) to A+/D+, - (terminal 4) to B-/D-, C (terminal 5) to common
  2. Verify the Modbus slave address on DIP switches SW1.3 and SW1.4 matches TapHome configuration
  3. Confirm communication parameters: 9600 baud, 8 data bits, no parity, 1 stop bit
  4. For long cable runs, verify cable impedance and consider adding termination

Registers returning 32765

This indicates the DCOM is still synchronizing with the Altherma Master. Wait up to 8 minutes after power-up. If the value persists, check the Status LED — it should be solid green when synchronization is complete. Until then, the temperature sensors and the setpoint and offset devices show no value instead of a false temperature reading — the same applies to 32766 and 32767.

Register H:9 behavior (Quiet Mode vs DHW Reheat)

Register H:9 has dual functionality depending on the DCOM operating mode: in Normal Mode, official documentation defines it as “DHW Reheat On/Off”; in Sequencer Mode, it functions as “Quiet Mode Operation”. The TapHome templates use it as Quiet Mode based on community verification. Actual behavior may vary depending on firmware version and DCOM configuration.

Unit error code decoding

When Unit Error (A:21) reports a fault, the error code is available in register A:22 as a 16-bit value encoding two ASCII characters. To decode: extract LSB (value mod 256) and MSB ((value - LSB) / 256), then convert both to ASCII characters. For example, value 21816 decodes to “U8” (MSB=85=‘U’, LSB=56=‘8’).

Available devices 22

These devices appear in TapHome after import.

Daikin Altherma 3 Module
Disinfection Operation Reed Contact Read-only
Register: A:33 Int16 numeric

Disinfection Operation

Read
MODBUSR(A, 33, int16)
Weather Curve Setpoint Thermostat Read and write

Leaving water main heating setpoint — adjustable range 25–55°C

Register: H:1 Int16 Unit: °C numeric

Weather Curve Setpoint

Read temperature
var reg := MODBUSR(A, 41, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg / 100)
Read desired temperature
var reg := MODBUSR(H, 1, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg)
Write desired temperature
# Požadovaná výstupná teplota pri kúrení, holding 1, celé °C, 25 až 55 °C.
# Absolútna hodnota platí len pri holding 53 = 0 (Pevne kurenie).
# V režime podľa počasia (holding 53 = 1 alebo 3) sa nastavuje posun krivky v holding 54 (Equitermika - Posun).
# Zapisuje sa len zmena (MODBUSWNE), periodický zápis je vypnutý.
IF(ISNAN(Se), NaN, MODBUSWNE(H, 1, Int16, MAX(25, MIN(55, ROUND(Se)))))
Weather Curve Offset Thermostat Read and write

Weather dependent setpoint offset — adjustable range -10 to +10°C

Register: H:54 Int16 Unit: °C numeric

Weather Curve Offset

Read temperature
var reg := MODBUSR(H, 54, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg)
Read desired temperature
var reg := MODBUSR(H, 54, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg)
Write desired temperature
MODBUSW(H, 54, Int16, Se)
Compressor Run Thermostat Read-only
Register: A:31 Int16 numeric

Compressor Run

Read temperature
var reg := MODBUSR(H, 55, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg)
Read desired temperature
var reg := MODBUSR(H, 55, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg)
Write desired temperature
# Posun požadovanej výstupnej teploty pri chladení v režime podľa počasia, holding 55, celé °C, -10 až 10 °C.
# Platí len pri holding 53 = 1 alebo 3 (podľa počasia), pri pevnej teplote sa nastavuje holding 2.
IF(ISNAN(Se), NaN, MODBUSWNE(H, 55, Int16, MAX(-10, MIN(10, ROUND(Se)))))
Space Heating/Cooling On/Off Reed Contact Read and write

Master switch for space heating and cooling operation

Register: H:4 Int16

Space Heating/Cooling On/Off

Read
MODBUSR(A, 31, int16)
Heat Pump Mode Switch Read and write

Operation mode selector — Auto, Heating, or Cooling

Register: H:3 Int16 numeric
Values / States: Povolené · Blokované

Heat Pump Mode

Read switch state
MODBUSR(H, 4, Int16)
Write switch state
MODBUSW(H, 4, Int16, St)
Circulation Pump Multi-value Switch Read-only
Register: A:30 UInt16 numeric
Values / States: AUTO · Ohrev · Chladenie

Circulation Pump

Read switch state
MODBUSR(H, 3, Int16)
Write switch state
MODBUSW(H, 3, Int16, Mu)
DHW Reheat On/Off Reed Contact Read and write

Triggers domestic hot water reheat cycle

Register: H:12 Int16

DHW Reheat On/Off

Read
MODBUSR(A, 30, Uint16)
Unit Error Switch Read-only

Heat pump error status — No Error, Fault, or Warning

Register: A:21 Int16 numeric
Values / States: Povolené · Blokované

Unit Error

Read switch state
MODBUSR(H, 12, Int16)
Write switch state
MODBUSW(H,12,int16, St)
Flow Rate Multi-value Switch Read-only
Register: A:49 Int16 Unit: l/min numeric
Values / States: Žiadna porucha · Porucha · Varovanie

Flow Rate

Read switch state
MODBUSR(A, 21, Int16)
Weather Dependent Mode Thermostat Read and write

Setpoint calculation mode — Fixed, Weather Dependent, with optional scheduling

Register: H:53 Int16 numeric

Weather Dependent Mode

Read temperature
var reg := MODBUSR(A, 41, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg / 100)
Read desired temperature
var reg := MODBUSR(H, 2, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg)
Write desired temperature
# Požadovaná výstupná teplota pri chladení, holding 2, celé °C, 5 až 22 °C.
# Absolútna hodnota platí len pri holding 53 = 0 (Pevne kurenie).
# V režime podľa počasia (holding 53 = 1 alebo 3) sa nastavuje posun v holding 55 (Equitermika - Posun chladenie).
# Zapisuje sa len zmena (MODBUSWNE), periodický zápis je vypnutý.
IF(ISNAN(Se), NaN, MODBUSWNE(H, 2, Int16, MAX(5, MIN(22, ROUND(Se)))))
Defrost/Startup Variable Read-only
Register: A:35 Int16 numeric

Defrost/Startup

Read
MODBUSR(A, 49, Int16) / 100
Liquid Refrigerant Temperature Multi-value Switch Read-only
Register: A:45 (implicit) Temperature Unit: °C numeric
Values / States: Pevne kurenie · Kurenie - Pocasie · Pevne + Plan · Pocasie + Plan

Liquid Refrigerant Temperature

Read switch state
MODBUSR(H, 53, Int16)
Write switch state
MODBUSW(H, 53, Int16, Mu)
DHW Setpoint Reed Contact Read and write

Domestic hot water reheat setpoint — adjustable range 30–65°C

Register: H:10 Int16 Unit: °C numeric

DHW Setpoint

Read
MODBUSR(A,35, Int16)
Leaving Water Temp pre PHE Temperature Sensor Read-only

Leaving water temperature before plate heat exchanger

Register: A:40 (implicit) Temperature Unit: °C numeric

Leaving Water Temp pre PHE

Read temperature
var reg := MODBUSR(A, 45, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg / 100)
Return Water Temperature Thermostat Read-only
Register: A:42 (implicit) Temperature Unit: °C numeric

Return Water Temperature

Read temperature
var reg := MODBUSR(A, 43, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg / 100)
Read desired temperature
var reg := MODBUSR(H, 10, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg)
Write desired temperature
MODBUSW(H, 10, Int16, Se)
Leaving Water Temp pre BUH Temperature Sensor Read-only

Leaving water temperature before backup heater

Register: A:41 (implicit) Temperature Unit: °C numeric

Leaving Water Temp pre BUH

Read temperature
var reg := MODBUSR(A, 42, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg / 100)
Quiet Mode Temperature Sensor Read and write
Register: H:9 Int16

Quiet Mode

Read temperature
var reg := MODBUSR(A, 40, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg / 100)
3-Way Valve Position Temperature Sensor Read-only

Valve routing — Space Heating or Domestic Hot Water

Register: A:37 UInt16 numeric

3-Way Valve Position

Read temperature
var reg := MODBUSR(A, 41, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg / 100)
Outside Air Temperature Switch Read-only
Register: A:44 (implicit) Temperature Unit: °C numeric
Values / States: ON · OFF

Outside Air Temperature

Read switch state
MODBUSR(H, 9, int16)
Write switch state
MODBUSW(H, 9, int16, St)
Trojcestný ventil Reed Contact

Trojcestný ventil

Read
MODBUSR(A, 37, Uint16)
Vonkajšia teplota Temperature Sensor

Vonkajšia teplota

Read temperature
var reg := MODBUSR(A, 44, Int16);
SWITCH(reg, 32765, NaN, 32766, NaN, 32767, NaN, reg / 100)
Connection: Modbus RTU • 9600 baud• 8N1 • Slave ID: $[SlaveId]
Possible improvements (10)
  • H:2 Leaving Water Main Cooling Setpoint — Cooling setpoint 5–22°C — only implemented in DCOM-RW template via service action on Operation Mode device
  • H:6 Room Thermostat Control Heating Setpoint — Room thermostat heating setpoint 12–30°C — only implemented in DCOM-RW template via service action
  • H:7 Room Thermostat Control Cooling Setpoint — Room thermostat cooling setpoint 15–35°C — only implemented in DCOM-RW template via service action
  • H:55 Weather Dependent LWT Cooling Offset — Weather dependent cooling leaving water setpoint offset -10–10°C — not exposed in any template
  • A:22 Unit Error Code — Error code (2 ASCII chars, text14 format) — partially covered by DCOM-RW module readscript ADDERROR
  • A:23 Unit Error Sub Code — Error sub-code 0–99 — partially covered by DCOM-RW module readscript
  • A:32 Booster Heater Run — 0=OFF, 1=ON — only available as module-level service attribute in DCOM-RW template, not as standalone device
  • A:36 Hot Start — 0=OFF, 1=ON — only available as module-level service attribute in DCOM-RW template
  • A:38 Operation Mode (actual) — 1=Heating, 2=Cooling — actual (vs. requested H:3). Only as module service attribute in DCOM-RW
  • A:50 Room Temperature — comp14, °C × 100 — room temperature reading. Not exposed in any template

Import parameters

Enter these values when you import the XML.

Asked in the appDefault
Slave Id1
IP address192.168.1.0

Sources

  • DCOM-LT/MB Reference and Installation Manual (English)
    www.daikin.eu 2026-03-18
    PDF
  • DCOM-LT/MB Register Map (Czech, from submodule)
    2026-03-18
    PDF
  • Daikin Altherma 3 DCOM-LT/MB Modbus Registers (GitHub Community)
    github.com 2026-03-18

Manufacturer documents are © their respective owners. They are provided as published by the manufacturer, for reference only.

Found a problem with this device template?

Tell us what's wrong, what's missing, or how the template should behave. We rely on your feedback to keep the catalog accurate.

Template · TapHome portal Daikin Altherma 3 Heat Pump Open this template in the Customer Portal to apply it to one of your homes, or to draft a refinement and submit it back to the catalog. Modbus RTU View in TapHome portal