TapHome
Official · TapHome HVAC integration

Brink Renovent Excellent

Brink Renovent Excellent 300/400/450 residential heat recovery ventilation unit with Modbus RTU control via RS-485. Temperature monitoring, ventilation speed presets, bypass control, filter status and preheater diagnostics via TapHome.

BrinkModbus RTU8 devicesRevision 1.1 Last updated: November 19, 2026
Brink Renovent Excellent

Import into the TapHome appHardware › Modbus › Add from template

Download Template
On this page

Integration guide

The Brink Renovent Excellent is a residential heat recovery ventilation unit available in 300, 400 and 450 m3/h variants. The Excellent has no Modbus interface on its control board. It connects to TapHome over Modbus RTU (RS-485) through the external Brink Connect interface module, which converts the I²C bus of the unit to Modbus RTU.

The TapHome template controls the airflow with preset levels and a custom flow rate, switches the bypass mode, reads the outdoor and dwelling air temperatures, the filter status, the imbalance setting, the bypass valve state and the preheater power, and offers service actions for bypass, imbalance, filter reset and switching between Brink and Modbus control.

Hardware connection

Brink Connect module

Brink Connect works with Excellent units with the UWA control PCB running software S1.06.06 or later. It is supplied with a 1.5 m cable that plugs into the control PCB of the Excellent (wires C1–C4: brown, yellow, green, white).

Brink Connect terminals (screw terminals up to 1.5 mm²):

TerminalFunction
1+5 V supply
2GND
3I²C SDA (to the Excellent)
4I²C SCL (to the Excellent)
5RS485 A → A+/D+ on TapHome RS-485
6RS485 B → B-/D- on TapHome RS-485

The module is powered with +5 V DC ±10 % (0.2 W), has a housing for distribution boards (DIN 43880) and shows power with a green LED.

Important — Termination resistor

Brink Connect has an RS-485 termination resistor. Remove it if the module is not at the end of the bus. With several Brink Connect modules on one line, no more than 2 termination resistors may be installed.

Important — Safety

Disconnect the ventilation unit from mains power before connecting Brink Connect.

Communication parameters

  • Protocol: Modbus RTU, RS-485
  • Baud rate: 9600
  • Data bits: 8
  • Parity: Even
  • Stop bits: 1
  • Slave address: 11 (Brink Connect factory default), 1–247

The TapHome template suggests slave ID 1. Enter 11 when importing the template, or change the address of Brink Connect.

To change the slave address of Brink Connect, write the new address (1–247) to holding register H:999 (address 1000 in the Brink documentation). The new address is active immediately. Read it back at the new address to check it, then switch off the power of Brink Connect. With several Brink Connect modules on one bus, give each module a unique address first.

Configuration

Enabling Modbus control

Brink Connect can only read values until Modbus control is enabled. To control the airflow from TapHome, set register H:6012 to 4 (address 6013 in the Brink documentation). The template does this with the service action Zmena rezimu ovladania (modbus/brink) on the module: Modbus writes 4, Brink writes 0 and returns control to the settings of the Brink unit.

The desired airflow is written to H:6000 (address 6001 in the Brink documentation) in steps of 5 m3/h, within the range of the specific model.

After a power failure of the ventilation unit, Modbus control must be enabled again and the desired airflow written again.

Limitations

  • While the unit is controlled through Brink Connect, a control unit (Brink Air Control), a humidity sensor or a multiple switch cannot be used. If Brink Connect only reads values, Brink Air Control and the multiple switch can stay connected.
  • eBus CO2 sensors (Brink 532196) are supported, up to 4 sensors.
  • With cascaded units, connect Brink Connect to the Master unit.

Device capabilities

The device and attribute names in the template are in Slovak. The tables below give their meaning.

Devices

DeviceRegisterDescription
Výkon ventilatora rekuperácie (fan speed)H:6000 writeWrite-only preset levels, each named by its airflow: 50, 100, 125, 175, 200, 250 and 300 m3/h. The device action Požadované nastavenie rýchlosti prietoku writes any value from 50 to 300 m3/h.
Teplota nasavaneho vzuchu z exterieru (outdoor air)H:4008Outdoor air temperature, °C (tenths of a degree, signed)
Teplota odsavaneho vzduchu (dwelling air)H:4009Extract air temperature from the dwelling, °C
Filter statusH:4039OK / Znecisteny (filter fouled); service action Vynulovanie hlasenia writes 1 to the filter reset register H:6006
Nerovnováha povolená (imbalance permitted)H:4015 read, H:6003 writeOff = supply equals extract, On = imbalance permitted
Rezim Obtoku (bypass mode)H:4030 read, H:6005 writeAutomaticky (automatic), Zatvorene (closed), Otvorene (open)
Bypass (bypass valve)H:4029Read-only valve state: Inicializacia (initialising), Otvara sa (opening), Zatvara sa (closing), Otvorena (open), Zatvorena (closed)
Vykon predhrevu (preheater power)H:4037Preheater power, %

Module service attributes

AttributeRegisterNote
Stav predhrievačaH:4036Preheater status: 0 initialising, 1 not active, 2 active, 3 test mode
Výkon predhrievača [%]H:4037Preheater power, %
Stav filtraH:4039ok / polluted
Nerovnováha povolená [0 - vypnutá; 1 - povolená]H:40150 = supply equals extract, 1 = imbalance permitted
Posun nerovnováhy pri prívode [m3/h]H:4021Preset imbalance in m3/h, signed
Klapka obtoku [0 - Inicializacia; 1 - otvara sa; 2 - zatvara sa, 3 - otvorena, 4- zatvorena]H:4029Bypass valve state: 0 initialising, 1 opening, 2 closing, 3 open, 4 closed
Režim obtokuH:4030Bypass valve operation: 0 automatic, 1 closed, 2 open
Adresa Slave ModbusH:999Current slave address of Brink Connect
Aktualny prietok privadzaneho vzduchu [m3/h]H:4027Measured airflow (constant volume fan only)
Aktualny prietok odvadzaneho vzduchu [m3/h]H:4028Measured airflow (constant volume fan only)
snímač teploty ventilátora odsávania [C]H:4009Same as the dwelling air temperature
snímač teploty ventilátora prívodu [C]H:4008Outdoor air temperature, signed
Aktualny tlak privodu [Pa]H:4010Supply duct pressure
Aktualny tlak odvodu [Pa]H:4011Exhaust duct pressure

Pressures and measured airflows are available only on units with constant volume fans.

Module service actions

  • Nastavenie posunu nerovnováhy pri prívode — preset imbalance in m3/h, from -15 to +15 (H:6004)
  • Nastavenie režimu obtoku — Automatic, Closed, Open (H:6005)
  • Vynulovanie hlásenia filtra — filter reset, writes 1 to H:6006 like the device action
  • Zmena rezimu ovladania (modbus/brink) — Modbus (4) or Brink (0) control (H:6012)

Troubleshooting

No Modbus communication

  1. Check that Brink Connect is powered (green LED) and its cable is plugged into the control PCB of the Excellent.
  2. Check RS485 A (terminal 5) to A+/D+ and RS485 B (terminal 6) to B-/D- on TapHome.
  3. Check the slave address: Brink Connect is 11 from the factory, the template suggests 1.
  4. Check 9600 baud, 8 data bits, Even parity, 1 stop bit.
  5. Check the termination resistors — at most 2 on the line.
  6. Check that the control PCB runs software S1.06.06 or later.

Airflow does not change

  1. Enable Modbus control with Zmena rezimu ovladania (modbus/brink) → Modbus (H:6012 = 4).
  2. After a power failure of the unit, enable Modbus control and write the airflow again.
  3. Check that no Brink Air Control, humidity sensor or multiple switch is connected.

Temperature readings

Temperatures are in tenths of a degree — a reading of 215 means 21.5 °C.

Manufacturer documentation

Brink Modbus Interface (Brink Connect), art. no. 611885-G, pages 5–7: Installation manual (PDF)

Available devices 8

These devices appear in TapHome after import.

Brink Renovent Excellent Module
Service Attributes
Preheater StateFrost protection preheater status — Initialization, Inactive, Active, or Test mode
Preheater PowerPreheater output capacity as percentage (0–100%)
Filter Status
Imbalance Allowed
Imbalance Offset SupplySupply airflow offset percentage for imbalance correction
Bypass ModeCurrent bypass valve mode — Auto, Closed, or Open
Modbus Slave Address
Exhaust AirflowMeasured exhaust air volume flow rate in m3/h
Supply AirflowMeasured supply air volume flow rate in m3/h
Exhaust Temperature
Supply Temperature
Exhaust PressureExhaust air pressure in Pascal
Supply PressureSupply air pressure in Pascal
Aktualny tlak odvodu [Pa]
Service Actions
Set Imbalance Offset Supply
Set Bypass Mode
Reset Filter Warning
Set Control Mode

Renovent Excellent

Initialize
MODBUSW(H, 6012, Int16, 4);
Service Attributes
Stav predhrievača [0: Inicializácia/1:Neaktívny/2: Aktívny/3:Testovací režim]
modbusr(H,4036,int16);
Výkon predhrievača [%]
modbusr(H,4037,int16);
Stav filtra
var state := modbusr(H,4039,int16);
return(switch(todouble(state), 0, "ok", "polluted"))
Nerovnováha povolená [0 - vypnutá; 1 - povolená]
modbusr(H,4015,uint16)
Posun nerovnováhy pri prívode [m3/h]
modbusr(H,4021, int16)
Klapka obtoku [0 - Inicializacia; 1 - otvara sa; 2 - zatvara sa, 3 - otvorena, 4- zatvorena]
modbusr(H,4029,int16)
Režim obtoku [0 - auto; 1 - zatvoreny; 2 - otvoreny]
modbusr(H,4030,int16)
Adresa Slave Modbus
modbusr(H,999,int16)
Aktualny prietok privadzaneho vzduchu [m3/h]
MODBUSR(H, 4027, UInt16)
Aktualny prietok odvadzaneho vzduchu [m3/h]
MODBUSR(H, 4028, UInt16)
snímač teploty ventilátora odsávania [C]
MODBUSR(H, 4009, Int16) / 10
snímač teploty ventilátora prívodu [C]
MODBUSR(H, 4008, Int16) / 10
Aktualny tlak privodu [Pa]
MODBUSR(H, 4010, Int16)
Aktualny tlak odvodu [Pa]
MODBUSR(H, 4011, Int16)
Service Actions
Nastavenie posunu nerovnováhy pri prívode
Parameters: Posun nerovnovahy pri privode [m3/h] (-15–15 per)
modbusw(H,6004,int16,per);
Nastavenie režimu obtoku
Parameters: Parameter3

modbusw(H,6005,int16, isonv);
Vynulovanie hlásenia filtra
modbusw(H, 6006, int16,1)
Zmena rezimu ovladania (modbus/brink)
Parameters: Parameter2
if cont=4
MODBUSW(H,6012,int16,4);
else
MODBUSW(H,6012,int16,0);
end
Filter Status Multi-value Switch Read-only

Filter condition indicator — OK (clean) or Polluted (dirty), with service action to reset the filter warning

Register: H:4039 Int16 numeric
Values / States: OK · Znecisteny
Service Actions
Reset Filter Warning

Filter Status

Read switch state
modbusr(H,4039,int16);
Service Actions
Vynulovanie hlasenia
modbusw(H, 6006, int16,1)
Imbalance Allowed Switch Read and write

Enables or disables supply/exhaust airflow imbalance — when enabled, supply and exhaust fans can run at different speeds

Register: H:4015 → H:6003 Bool
Values / States: ON · OFF

Imbalance Allowed

Read switch state
MODBUSR(H, 4015, bool);
Write switch state
MODBUSW(H, 6003, bool, St);
Outdoor Supply Temperature Temperature Sensor Read-only

Outdoor air temperature measured at the supply fan inlet

Register: H:4008 Int16 Unit: °C numeric

Outdoor Supply Temperature

Read temperature
MODBUSR(H, 4008, Int16) / 10
Extract Air Temperature Temperature Sensor Read-only

Dwelling extract air temperature measured at the exhaust fan

Register: H:4009 Int16 Unit: °C numeric

Extract Air Temperature

Read temperature
MODBUSR(H, 4009, Int16) / 10
Ventilation Speed Multi-value Switch Read and write

Ventilation airflow preset selector — Away (50 m3/h), Night (125 m3/h), or Boost (250 m3/h), with service action for custom flow rate

Int16 Unit: m3/h numeric
Values / States: 50 · 100 · 125 · 175 · 200 · 250 · 300
Service Actions
Set Custom Flow Rate

Ventilation Speed

Write switch state
if Mu = 0
 MODBUSW(H, 6000, Int16, 50);
elseif Mu = 1
 MODBUSW(H, 6000, Int16, 100);
elseif Mu = 2
 MODBUSW(H, 6000, Int16, 125);
elseif Mu = 3
 MODBUSW(H, 6000, Int16, 175);
elseif Mu = 4
 MODBUSW(H, 6000, Int16, 200);
elseif Mu = 5
 MODBUSW(H, 6000, Int16, 250);
elseif Mu = 6
 MODBUSW(H, 6000, Int16, 300);
else
END
Service Actions
Požadované nastavenie rýchlosti prietoku
Parameters: Rychlost [50-300] (50–300 v)
MODBUSW(SH, 6000, Int16, v);
Bypass Multi-value Switch
Values / States: Inicializacia · Otvara sa · Zatvara sa · Otvorena · Zatvorena

Bypass

Read switch state
modbusr(H,4029,int16);
Rezim Obtoku Multi-value Switch
Values / States: Automaticky · Zatvorene · Otvorene

Rezim Obtoku

Read switch state
modbusr(H,4030,int16)
Write switch state
modbusw(H,6005,int16, Mu);
Vykon predhrevu Variable

Vykon predhrevu

Read
modbusr(H,4037,int16)
Connection: Modbus RTU • 9600 baud• 8E1 • Slave ID: $[SlaveId]
Possible improvements (21)
  • H:8000 Modbus Control Enable — 0=Modbus control off, 1=Switch control, 2=Flow rate control. Must be set before flow commands via H:8001/8002 take effect. Template uses H:6012 for control mode instead
  • H:8001 Switch Position — 0=Holiday, 1=Low, 2=Normal, 3=High. Alternative to direct flow preset writing. Requires H:8000=1
  • H:8002 Desired Flow Rate — Direct flow rate in m3/h. Requires H:8000=2. Alternative to H:6000 used by template
  • H:8003 Request Standby — 0=No action, 1=Set standby, 2=Set normal mode. Puts entire unit in standby
  • H:8010 Reset Filter Warning (remote) — Write 1 to reset. Alternative to H:6006 used by template. Read returns 1=executed, 0xFF=failed
  • H:8011 Appliance Reset — Write 1 to reset appliance. Read returns 1=executed, 0xFF=failed
  • H:4020 HRA Active Function — Current operating mode: 0=Standby, 4=Manual, 5=Holiday, 6=Night Ventilation, 7=Party, 8=Bypass Boost, 9=Normal Boost, 10=Auto CO2, 12=Auto Modbus, etc.
  • H:4022 Ventilation Mode — 0=Holiday, 1=Low, 2=Normal, 3=High, 4=Auto. Current ventilation mode — useful for readback
  • H:4050 Bypass Status — 0=Initialize, 1=Open, 2=Close, 3=Open, 4=Closed. Actual bypass valve position
  • H:4060 Preheater Status — 0=Initialize, 1=Inactive, 2=Active, 3=Test mode. Already partially exposed via module service attribute
  • H:4070 Frost Status — 16-state frost protection status: No Frost, Ice Detected, Heating, Fan Off, etc.
  • H:4081 NTC1 Temperature — Additional temperature sensor, tenths of degrees. Available on UWA2-B PCB
  • H:4082 NTC2 Temperature — Additional temperature sensor, tenths of degrees. Available on UWA2-B PCB
  • H:4083 RHT Sensor Humidity — Relative humidity in tenths of percent (0–100.0%). Requires RHT sensor mode enabled
  • H:4201 CO2 Sensor 1 Value — CO2 level in ppm. Up to 4 CO2 sensors supported (H:4201/4203/4205/4207)
  • H:6100 Bypass Mode (config) — 0=Automatic, 1=Bypass closed, 2=Bypass open. Template uses H:6005 for bypass write which is listed as 'Bypass mode' in official docs at H:6100
  • H:6120 Days Before Filter Warning — 1–365 days, default 90. Configures when filter warning triggers
  • H:4034 Supply Fan Speed — Supply fan speed in RPM
  • H:4044 Exhaust Fan Speed — Exhaust fan speed in RPM
  • H:4037 Supply Fan Humidity — Relative humidity at supply fan in tenths of percent (0–100.0%)
  • H:4047 Exhaust Fan Humidity — Relative humidity at exhaust fan in tenths of percent (0–100.0%)

Import parameters

Enter these values when you import the XML.

Asked in the appDefault
Slave Id1

Sources

  • Brink Modbus Interface 611885-G (Brink Connect) — installation manual
    a2t.dk 2026-11-18
  • openHAB Community — Brink Renovent Excellent 300 Modbus Integration

Found a problem with this device template?

Tell us what's wrong, what's missing, or how the template should behave. We rely on your feedback to keep the catalog accurate.

Template · TapHome portal Brink Renovent Excellent Open this template in the Customer Portal to apply it to one of your homes, or to draft a refinement and submit it back to the catalog. Modbus RTU View in TapHome portal