The Brink Renovent Excellent is a residential heat recovery ventilation unit available in 300, 400 and 450 m3/h variants. The Excellent has no Modbus interface on its control board. It connects to TapHome over Modbus RTU (RS-485) through the external Brink Connect interface module, which converts the I²C bus of the unit to Modbus RTU.
The TapHome template controls the airflow with preset levels and a custom flow rate, switches the bypass mode, reads the outdoor and dwelling air temperatures, the filter status, the imbalance setting, the bypass valve state and the preheater power, and offers service actions for bypass, imbalance, filter reset and switching between Brink and Modbus control.
Hardware connection
Brink Connect module
Brink Connect works with Excellent units with the UWA control PCB running software S1.06.06 or later. It is supplied with a 1.5 m cable that plugs into the control PCB of the Excellent (wires C1–C4: brown, yellow, green, white).
Brink Connect terminals (screw terminals up to 1.5 mm²):
| Terminal | Function |
|---|---|
| 1 | +5 V supply |
| 2 | GND |
| 3 | I²C SDA (to the Excellent) |
| 4 | I²C SCL (to the Excellent) |
| 5 | RS485 A → A+/D+ on TapHome RS-485 |
| 6 | RS485 B → B-/D- on TapHome RS-485 |
The module is powered with +5 V DC ±10 % (0.2 W), has a housing for distribution boards (DIN 43880) and shows power with a green LED.
Important — Termination resistor
Brink Connect has an RS-485 termination resistor. Remove it if the module is not at the end of the bus. With several Brink Connect modules on one line, no more than 2 termination resistors may be installed.
Important — Safety
Disconnect the ventilation unit from mains power before connecting Brink Connect.
Communication parameters
- Protocol: Modbus RTU, RS-485
- Baud rate: 9600
- Data bits: 8
- Parity: Even
- Stop bits: 1
- Slave address: 11 (Brink Connect factory default), 1–247
The TapHome template suggests slave ID 1. Enter 11 when importing the template, or change the address of Brink Connect.
To change the slave address of Brink Connect, write the new address (1–247) to holding register H:999 (address 1000 in the Brink documentation). The new address is active immediately. Read it back at the new address to check it, then switch off the power of Brink Connect. With several Brink Connect modules on one bus, give each module a unique address first.
Configuration
Enabling Modbus control
Brink Connect can only read values until Modbus control is enabled. To control the airflow from TapHome, set register H:6012 to 4 (address 6013 in the Brink documentation). The template does this with the service action Zmena rezimu ovladania (modbus/brink) on the module: Modbus writes 4, Brink writes 0 and returns control to the settings of the Brink unit.
The desired airflow is written to H:6000 (address 6001 in the Brink documentation) in steps of 5 m3/h, within the range of the specific model.
After a power failure of the ventilation unit, Modbus control must be enabled again and the desired airflow written again.
Limitations
- While the unit is controlled through Brink Connect, a control unit (Brink Air Control), a humidity sensor or a multiple switch cannot be used. If Brink Connect only reads values, Brink Air Control and the multiple switch can stay connected.
- eBus CO2 sensors (Brink 532196) are supported, up to 4 sensors.
- With cascaded units, connect Brink Connect to the Master unit.
Device capabilities
The device and attribute names in the template are in Slovak. The tables below give their meaning.
Devices
| Device | Register | Description |
|---|---|---|
| Výkon ventilatora rekuperácie (fan speed) | H:6000 write | Write-only preset levels, each named by its airflow: 50, 100, 125, 175, 200, 250 and 300 m3/h. The device action Požadované nastavenie rýchlosti prietoku writes any value from 50 to 300 m3/h. |
| Teplota nasavaneho vzuchu z exterieru (outdoor air) | H:4008 | Outdoor air temperature, °C (tenths of a degree, signed) |
| Teplota odsavaneho vzduchu (dwelling air) | H:4009 | Extract air temperature from the dwelling, °C |
| Filter status | H:4039 | OK / Znecisteny (filter fouled); service action Vynulovanie hlasenia writes 1 to the filter reset register H:6006 |
| Nerovnováha povolená (imbalance permitted) | H:4015 read, H:6003 write | Off = supply equals extract, On = imbalance permitted |
| Rezim Obtoku (bypass mode) | H:4030 read, H:6005 write | Automaticky (automatic), Zatvorene (closed), Otvorene (open) |
| Bypass (bypass valve) | H:4029 | Read-only valve state: Inicializacia (initialising), Otvara sa (opening), Zatvara sa (closing), Otvorena (open), Zatvorena (closed) |
| Vykon predhrevu (preheater power) | H:4037 | Preheater power, % |
Module service attributes
| Attribute | Register | Note |
|---|---|---|
| Stav predhrievača | H:4036 | Preheater status: 0 initialising, 1 not active, 2 active, 3 test mode |
| Výkon predhrievača [%] | H:4037 | Preheater power, % |
| Stav filtra | H:4039 | ok / polluted |
| Nerovnováha povolená [0 - vypnutá; 1 - povolená] | H:4015 | 0 = supply equals extract, 1 = imbalance permitted |
| Posun nerovnováhy pri prívode [m3/h] | H:4021 | Preset imbalance in m3/h, signed |
| Klapka obtoku [0 - Inicializacia; 1 - otvara sa; 2 - zatvara sa, 3 - otvorena, 4- zatvorena] | H:4029 | Bypass valve state: 0 initialising, 1 opening, 2 closing, 3 open, 4 closed |
| Režim obtoku | H:4030 | Bypass valve operation: 0 automatic, 1 closed, 2 open |
| Adresa Slave Modbus | H:999 | Current slave address of Brink Connect |
| Aktualny prietok privadzaneho vzduchu [m3/h] | H:4027 | Measured airflow (constant volume fan only) |
| Aktualny prietok odvadzaneho vzduchu [m3/h] | H:4028 | Measured airflow (constant volume fan only) |
| snímač teploty ventilátora odsávania [C] | H:4009 | Same as the dwelling air temperature |
| snímač teploty ventilátora prívodu [C] | H:4008 | Outdoor air temperature, signed |
| Aktualny tlak privodu [Pa] | H:4010 | Supply duct pressure |
| Aktualny tlak odvodu [Pa] | H:4011 | Exhaust duct pressure |
Pressures and measured airflows are available only on units with constant volume fans.
Module service actions
- Nastavenie posunu nerovnováhy pri prívode — preset imbalance in m3/h, from -15 to +15 (H:6004)
- Nastavenie režimu obtoku — Automatic, Closed, Open (H:6005)
- Vynulovanie hlásenia filtra — filter reset, writes 1 to H:6006 like the device action
- Zmena rezimu ovladania (modbus/brink) — Modbus (4) or Brink (0) control (H:6012)
Troubleshooting
No Modbus communication
- Check that Brink Connect is powered (green LED) and its cable is plugged into the control PCB of the Excellent.
- Check RS485 A (terminal 5) to A+/D+ and RS485 B (terminal 6) to B-/D- on TapHome.
- Check the slave address: Brink Connect is 11 from the factory, the template suggests 1.
- Check 9600 baud, 8 data bits, Even parity, 1 stop bit.
- Check the termination resistors — at most 2 on the line.
- Check that the control PCB runs software S1.06.06 or later.
Airflow does not change
- Enable Modbus control with Zmena rezimu ovladania (modbus/brink) → Modbus (H:6012 = 4).
- After a power failure of the unit, enable Modbus control and write the airflow again.
- Check that no Brink Air Control, humidity sensor or multiple switch is connected.
Temperature readings
Temperatures are in tenths of a degree — a reading of 215 means 21.5 °C.
Manufacturer documentation
Brink Modbus Interface (Brink Connect), art. no. 611885-G, pages 5–7: Installation manual (PDF)
Brink