  questions: ["How to integrate Atrea DUPLEX with aMotion controller into TapHome?","What does the Atrea aMotion TapHome template measure and control?","How to connect Atrea aMotion via Modbus TCP to TapHome?","How to change ventilation mode on Atrea aMotion from TapHome?","How to enable Modbus TCP on Atrea aMotion controller?","What is the difference between Atrea RD5 and aMotion for TapHome integration?"]
---

# Atrea aMotion

Communication: Modbus TCP

- [Atrea Official Website](https://www.atrea.eu/en/)

Atrea aMotion is the new-generation control system for Atrea DUPLEX heat recovery ventilation (MVHR) units, replacing the older RD5 controller. The aMotion system is available with aDot and aTouch user interface panels. TapHome connects directly to the aMotion controller via Modbus TCP over Ethernet on port 502 — no additional gateway is required.

The template provides full operating mode control (8 modes), thermostat with temperature setpoint, fan power adjustment (0–100%), bypass damper and zone control, circulation ratio setting, pressure level selection, two temperature sensors (outdoor and indoor), and comprehensive diagnostics monitoring 50+ alarm, warning and info registers.

## Network connection

The aMotion controller has a built-in Ethernet interface. Connect it to the same local network as TapHome Core using a standard Ethernet cable.

- **Protocol:** Modbus TCP
- **Port:** 502
- **Slave ID:** 1–255 (configurable via aTool)
- **Data encoding:** Int16, temperature values divided by 10, airflow values multiplied by 10

> [!WARNING]
> When reading or writing multiple registers in one batch, maintain at least a 5-second interval between requests. Shorter intervals may cause communication timeouts.

## Enabling Modbus communication

Modbus TCP must be explicitly enabled using the **aTool** service software before TapHome can communicate with the unit.

1. Open the **aTool** application and connect to the aMotion unit
2. Navigate to section **Komunikace** (Communication)
3. Enable **Modbus**
4. Configure the desired **Slave Address** (default: 1)

> [!WARNING]
> If Modbus is not enabled in aTool, the aMotion controller will not respond to any Modbus TCP requests on port 502.

> [!NOTE]
> The HTTP/XML API used by older Atrea RD5 integrations (e.g., pyatrea library) is **not compatible** with aMotion units. Direct Modbus TCP is the recommended and supported integration method.

## Configuration

When importing the template in TapHome, provide:

- **IP Address** — the aMotion controller's IP on the local network
- **Slave ID** — Modbus slave address (default: 1, configurable 1–255 via aTool)

> [!TIP]
> Assign a static IP address or DHCP reservation to the aMotion controller in the router settings to prevent the address from changing after a power cycle.

## Device capabilities

The template exposes the following devices:

### Operating mode and zone control

- **Mode Control** — multi-value switch for selecting the operating mode via registers H:1001 (write) / I:1001 (read). Available modes: Off, Auto, Ventilation, Circulation + Ventilation, Circulation, Night Cooling, Disbalance, Overpressure.
- **Zone Control** — multi-value switch for selecting the active zone via registers H:1003 (write) / I:1003 (read). Options: Zones 1+2 (both), Zone 1 only, Zone 2 only.
- **Pressure Level** — multi-value switch for pressure level setting via registers H:1007 (write) / I:1007 (read). Options: Off, Low, Normal.

### Thermostat and temperature monitoring

- **Thermostat** — room temperature control reading the current indoor temperature from I:1104 (T-IDA) and setting the desired temperature via H:1002. Temperature range -30.0 to 90.0 °C with 0.1 °C resolution.
- **Outdoor Air Temperature (T-ODA)** — reads outdoor air temperature from I:1101 (value / 10 = °C).
- **Indoor Air Temperature (T-IDA)** — reads indoor air temperature from I:1104 (value / 10 = °C).

### Fan and airflow control

- **Fan Power** — dimmer controlling fan power from 0% to 100% via register H:1004. Adjusts the ventilation intensity for both supply (M-SUP) and exhaust (M-ETA) fans simultaneously.
- **Circulation Ratio** — dimmer controlling the mixing proportion between recirculated and fresh air from 0% to 100% via register H:1008.
- **Bypass Damper Command** — multi-value switch for bypass damper position via registers H:1008 (write) / I:1009 (read). Options: Auto, Open, Closed.

### Module-level monitoring

The template includes 27 service attributes providing detailed real-time status information:

| Category | Monitored values |
|----------|-----------------|
| **Fan commands** | Supply fan M-SUP (%), exhaust fan M-ETA (%) |
| **Airflow** | Supply fan (m³/h), exhaust fan (m³/h), fresh air (m³/h), ventilation setpoint (m³/h), circulation setpoint (m³/h) |
| **Temperatures** | Supply air T-SUP (°C), extract air T-ETA (°C), exhaust air T-EHA (°C), average outdoor (°C) |
| **Actuator commands** | Circulation damper (%), preheater (%), heater A (%), heater B (%), cooler (%), bypass transition time (ms) |
| **Equipment status** | Fan status, dampers open/closed, preheater, heating, heater A/B, cooler A, pumps (heater A/B, cooler A) |

### Module-level diagnostics

The aMotion template monitors 50+ discrete registers (D:6003–D:6111) for errors, warnings, and informational messages, including:

- **Alarms:** Frost protection (1st/2nd), stop signal, unit overheating, unbalanced airflow, manometer faults, heater A/B faults, cooler A fault, internal/external bus faults, Ethernet communication fault, temperature sensor faults (T-EHA/T-ETA/T-ODA/T-IDA/T-SUP), confirmed stop signal, anti-freeze capillary, device not ready, airflow sensor faults (SUP/ETA/ODA)
- **Warnings:** Insufficient airflow/preheating, heat pump defrost, heater/cooler overload, heat exchanger freeze, airflow learning, UVC lamp change, trial operation end, clogged filters, cooling blocked
- **Info:** Heat exchanger defrost, HDO higher tariff, learning process, filter PF1/PF2/PF3 clogged, max heater A/B power, fault inputs IN1/IN2/IN3, anti-freeze DI1–DI4, airflow increase for heating, device inspection interval, filter replacement interval

### Additional capabilities

The aMotion units also expose Modbus registers for current season indicator, detailed operation mode (17 internal states from Off through Manual control), fan control method, maximum/minimum configurable airflow, airflow measurement source, circulation and bypass damper control methods, external temperature inputs from BMS (T-IDA and T-ODA), alarm/filter/UVC lamp reset commands, and scene trigger addresses. These can be added to the TapHome template in a future update.

## Troubleshooting

### No Modbus communication

1. Verify that Modbus is enabled in aTool — section **Komunikace** (Communication)
2. Confirm the aMotion controller's IP address — check the router's DHCP lease table or the unit's display
3. Ensure TapHome Core and the aMotion controller are on the same network/subnet
4. Check that no firewall is blocking port 502
5. Verify the Slave ID matches between TapHome and the unit configuration

### Temperature values appear incorrect

Temperature registers use Int16 encoding with the value divided by 10. For example, a register value of 215 represents 21.5 °C. Values above 32767 represent negative temperatures: (value - 65536) / 10. For example, value 65516 = (65516 - 65536) / 10 = -2.0 °C.

### Airflow values appear incorrect

Airflow registers use Int16 encoding with the value multiplied by 10. For example, a register value of 35 represents 350 m³/h.

### Communication timeouts

The manufacturer recommends a minimum 5-second interval between batch register reads. If TapHome reports frequent communication errors, ensure no other Modbus client (e.g., Home Assistant, BMS) is polling the same unit simultaneously with short intervals.

## Available devices

Atrea aMotion Module

Service Attributes

|                                     |
|-------------------------------------|
| Supply Fan Command M-SUP \[%]       |
| Exhaust Fan Command M-ETA \[%]      |
| Supply Fan Airflow M-SUP \[m³/h]    |
| Exhaust Fan Airflow M-ETA \[m³/h]   |
| Fresh Air Airflow \[m³/h]           |
| Bypass Damper Transition Time \[ms] |
| Circulation Damper Command \[%]     |
| Preheater Command \[%]              |
| Heater A Command \[%]               |
| Heater B Command \[%]               |
| Cooler Command \[%]                 |
| Cooler A Pump                       |
| Heater A Pump                       |
| Heater B Pump                       |
| Average Outdoor Temperature         |
| Cooler A Status                     |
| Heating Status                      |
| Heater A Status                     |
| Heater B Status                     |
| Preheater Status                    |
| Fan Status (SUP or ETA or both)     |
| Exhaust Air Temperature (T-EHA)     |
| Extract Air Temperature (T-ETA)     |
| Supply Air Temperature (T-SUP)      |
| Input and Output Dampers            |
| Circulation Airflow \[m³/h]         |
| Ventilation Airflow \[m³/h]         |

Circulation Ratio Dimmer

Mixing proportion between recirculated and fresh air (0–100 %)

Register: H:1008 (read/write) Int16 Unit: % numeric (0–100 = %)

Bypass Damper Command Multi-value Switch

Bypass damper position — Auto, Open, or Closed

Register: I:1009 (read), H:1008 (write) Int16 numeric

Values / States: Auto · Otevřeno · Zavřeno

Thermostat Thermostat

Room temperature control — setpoint and current indoor air temperature (T-IDA)

Register: I:1104 (read current), H:1002 (read/write desired) Int16 Unit: °C numeric (value / 10 = °C)

Zone Control Multi-value Switch

Active zone selection — Zones 1+2, Zone 1 only, or Zone 2 only

Register: I:1003 (read), H:1003 (write) Int16 numeric

Values / States: Zones 1&#43;2 · Zone 1 · Zone 2

Mode Control Multi-value Switch

Active operating mode — Off, Auto, Ventilation, Circ+Vent, Circulation, Night Cooling, Disbalance, or Overpressure

Register: I:1001 (read), H:1001 (write) Int16 numeric

Values / States: OFF · Auto · Ventilation · Circulation &#43; Ventilation · Circulation · Night Cooling · Disbalance · Overpressure

Outdoor Air Temperature (T-ODA) Temperature Sensor Read-only

Register: I:1101 Int16 Unit: °C numeric (value / 10 = °C)

Indoor Air Temperature (T-IDA) Temperature Sensor Read-only

Register: I:1104 Int16 Unit: °C numeric (value / 10 = °C)

Pressure Level Multi-value Switch

Pressure level setting — Off, Low, or Normal

Register: I:1007 (read), H:1007 (write) Int16 numeric

Values / States: OFF · Low · Normal

Fan Power Dimmer

Fan power control — adjusts ventilation intensity for both supply (M-SUP) and exhaust (M-ETA) fans

Register: H:1004 (read/write) Int16 Unit: % numeric (0–100 = %)

**Connection:** Modbus TCP • Slave ID: $\[SlaveId]

Possible improvements (17)

- I:1010 Current Season — Int16, read-only — current season indicator
- I:1119 Current Operation Mode — Int16, 0–16 (Off, Evaporation, Run-down, Normal, Filter test, ..., Manual control)
- I:1201 Fan Control Method — Int16, 0=Power, 1=Const pressure, 2=Const flow, 3=External — read-only
- I:1202 Maximum Configurable Airflow — Int16, ×10 m³/h, read-only
- I:1203 Minimum Configurable Airflow — Int16, ×10 m³/h, read-only
- I:1204 Airflow Measurement Source — Int16, 0=None, 1=Direct flow, 2=Diff pressure, 3=Voltage output — read-only
- I:1205 Circulation Damper Control Method — Int16, 0=None, 1=ON/OFF, 2=Eco, 3=Comfort, 4=Adjustable position — read-only
- I:1206 Bypass Damper Control Method — Int16, 0=None, 1=User-defined, 2=Automatic — read-only
- H:1005 Ventilation Airflow Setpoint — Int16, ×10 m³/h, R/W, 0–65000 m³/h
- H:1006 Circulation Airflow Setpoint — Int16, ×10 m³/h, R/W, 0–65000 m³/h
- H:1500 External T-IDA (from BMS) — Int16, ×0.1 °C, write-only — provide indoor temperature from external source
- H:1501 External T-ODA (from BMS) — Int16, ×0.1 °C, write-only — provide outdoor temperature from external source
- C:8001 Alarm Reset — Write 1 to acknowledge (reset) all inactive alarms
- C:8002 Filter Replacement Interval Reset — Write 1 to reset filter operation counter after filter change
- C:8003 UVC Lamp Replacement Interval Reset — Write 1 to reset UVC lamp operation counter after lamp change
- C:7000-7500 Scene Triggers — Reserved range for triggering pre-programmed scenes
- D:6024 Evaporation Status — Bool, 0=inactive, 1=active — not included in readscript but documented

## Sources

- Modbus TCP Index Table for aMotion Control
  
  [support.tecomat.cz](https://support.tecomat.cz/dotaz/atrea-jednotky-s-amotion) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/atrea-amotion/manufacturer/modbus_am_cz_2023_02.pdf)
- pyatrea — Python Library for Atrea Ventilation Units
  
  [github.com](https://github.com/JurajNyiri/pyatrea) 2026-03-20

## Related Documentation

- [Modbus Integration](https://taphome.com/en/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/en/docs/integration/modbus/)
- [Simple configuration using templates](https://taphome.com/en/docs/integration/modbus/templates/)
- [Modbus scripts and prefetch](https://taphome.com/en/docs/script/modbus-scripts/)
- [Modbus functions](https://taphome.com/en/docs/script/modbus/)
- [Modbus data types](https://taphome.com/en/docs/script/modbus-data-types/)