  questions: ["Wie integriere ich Flexit EcoNordic mit TapHome?","Was steuert die Flexit-EcoNordic-Vorlage in TapHome?","Wie verbinde ich Flexit EcoNordic über RS-485 mit TapHome?","Was ist der Unterschied zwischen EcoNordic WH4 und W4 in TapHome?","Wie aktiviere ich die Kaminlüftung am Flexit EcoNordic über TapHome?","Wie steuere ich die Warmwasserbereitung am Flexit EcoNordic?"]
---

# Flexit EcoNordic WH4 / W4

Kommunikation: Modbus RTU

- [Offizielle Flexit-Website](https://www.flexit.no)

## Integrationsanleitung

Die Flexit EcoNordic ist eine Klimazentrale, die kontrollierte Wohnraumlüftung mit Wärmerückgewinnung, Warmwasserbereitung und wasserführende Heizung (Modell WH4) kombiniert. Sie kommuniziert mit TapHome über Modbus RTU via RS-485 und ermöglicht die Steuerung von Lüftungsmodi, Temperatursollwerten, Warmwassermanagement und die Überwachung des Wärmepumpenbetriebs.

Zwei Modelle werden unterstützt: **EcoNordic WH4** (Lüftung + Heizung + Warmwasser) und **EcoNordic W4** (Lüftung + Warmwasser). Das WH4 verfügt zusätzlich über Heizkreissensoren und -steuerungen, die beim W4 nicht vorhanden sind.

## Hardwareanschluss

Die EcoNordic verfügt über eine integrierte Modbus-RTU-Schnittstelle, zugänglich über RS-485. Verbinden Sie TapHome Core mit dem RS-485-Port der EcoNordic über ein verdrilltes Adernpaar mit GND.

> [!WARNING]
> In der verfügbaren Dokumentation wurde kein Anschlussschema gefunden. Die genaue Position der RS-485-Klemmen am Gerät finden Sie im Installationshandbuch der EcoNordic oder kontaktieren Sie den Flexit-Support. Das optionale **Modbus-Kabel (HP Res)** ist als Zubehör von Flexit zum Anschluss externer Controller erhältlich.

## Konfiguration

Konfigurieren Sie die Modbus-Verbindung in TapHome mit diesen Parametern:

| Parameter | Wert |
|-----------|------|
| Baudrate | 9600 |
| Datenbits | 8 |
| Parität | Even |
| Stoppbits | 1 |
| Slave-ID | 1 (Standard) |

Die EcoNordic verwendet eine proprietäre Modbus-Registerkarte im Adressbereich 1-3037. Diese unterscheidet sich von der CI66-Registerkarte älterer Flexit Nordic S2-S4 / CL2-CL4 Modelle — ein CI66-Adapter wird nicht benötigt.

> [!NOTE]
> Die EcoNordic kann auch über die mobile App **Flexit GO** (Android/iOS) gesteuert werden. TapHome und die Flexit GO App können parallel betrieben werden — beide kommunizieren unabhängig mit dem Gerät.

## Gerätefunktionen

### Steuerung des Lüftungsmodus

**Betriebsmodus** (H:2013) ist die primäre Lüftungssteuerung mit vier Modi:

- **Stop** — Ventilatoren aus, keine Lüftung
- **Away** — reduzierte Lüftung für unbewohntes Gebäude
- **Home** — normaler Tagesbetrieb
- **High** — vorübergehend erhöhte Lüftung

Zwei spezielle Trigger bieten zusätzliche Lüftungsmodi:

- **Schnelllüftung** (H:3006) — aktiviert vorübergehende Hochgeschwindigkeitslüftung für schnellen Luftaustausch (Kochen, Besucher, Feuchtigkeit). Die Dauer ist über eine Serviceaktion konfigurierbar (1-360 Minuten)
- **Kaminlüftung** (H:3007) — erzeugt einen Überdruck im Gebäude, um das Eindringen von Rauch in den Raum beim Anzünden eines Kamins zu verhindern. Die Dauer ist über eine Serviceaktion konfigurierbar (0-360 Minuten)

Die **Comfort-Taste** (H:2040) schaltet den Komfortmodus am Gerät um, der vorübergehend die Lüftung erhöht und Temperatursollwerte anpassen kann.

### Temperaturüberwachung und Sollwerte

Die Vorlage bietet sechs Temperatursensoren:

- **Außenlufttemperatur** (A:1) — Außenlufttemperatur am Ansaugpunkt
- **Zulufttemperatur** (A:5) — Frischluft, die nach Wärmerückgewinnung und Nachheizung dem Gebäude zugeführt wird
- **Ablufttemperatur** (A:9) — Luft, die vor der Wärmerückgewinnung aus dem Gebäude abgesaugt wird
- **Fortlufttemperatur** (A:13) — Luft, die nach der Wärmerückgewinnung ins Freie abgeführt wird
- **Heizkreis-Vorlauftemperatur** (A:97) — Wassertemperatur in der Vorlaufleitung des Heizkreises (nur WH4)
- **Heizkreis-Rücklauftemperatur** (A:101) — Wassertemperatur in der Rücklaufleitung des Heizkreises (nur WH4)

Zwei Thermostate steuern die Zuluft-Temperatursollwerte:

- **Temperatur bei Home** (H:1155) — Sollwert für den Home-Modus, Bereich 10-30°C
- **Temperatur bei Away** (H:1163) — Sollwert für den Away-Modus, Bereich 10-30°C

### Warmwassermanagement

**Warmwassermodus** (H:3017) wählt die Strategie zur Warmwasserbereitung:

- **Comfort** — lädt den Speicher bei ca. 50 % verbleibendem Warmwasser, nutzt elektrische Zusatzheizung unter 15 %
- **Economy** — sparsamster Modus, lädt erst bei ca. 15 % Restmenge, ohne elektrische Zusatzheizung

**Warmwasser-Boost** (H:3019) löst eine vorübergehende maximale Warmwasserproduktion mit der elektrischen Zusatzheizung aus. Die Dauer ist über eine Serviceaktion konfigurierbar (0-300 Minuten).

### Wärmepumpen- und Systemüberwachung

Das Modul bietet neun Serviceattribute zur Überwachung des Systemzustands:

- **Wärmepumpenstatus** (A:3028) — aktueller Wärmepumpenbetrieb: Bereitschaft, Entlüftung, Start, Normalbetrieb, Stopp, Abtauung, Fehlerbereitschaft, Manuell und Zwangsbetrieb
- **Warmwasserstatus** (A:3005) — Status der Warmwasserbereitung: Comfort, Economy, Nicht in Betrieb, Temporärer Boost, Zwangsladung, Economy-Verzögerung oder Legionellenprävention
- **Status der Wärmerückgewinnungslüftung** (A:3034) — zeigt den aktuellen Lüftungszustand einschließlich Modi, die nicht direkt über den Betriebsmodus einstellbar sind (z.B. Dunstabzug und Kamin)
- **Anlagenbetriebsmodus der Wärmepumpe** (H:2061) — detailliertes 17-Zustände-Enum, das zeigt, was die Wärmepumpe aktuell tut (Speicherladung, Raumheizung, Lüftungsheizung, Legionellenprävention und kombinierte Modi)
- **Nachheizregister der Wärmepumpe** (A:3029) — ob das Nachheizregister aktiv ist
- **Frostschutz der Wärmepumpe** (A:3031) — ob der Frostschutz aktiv ist
- **Status der Kondensatwannenheizung** (A:3036) — ob die Kondensatwannenheizung aktiv ist
- **Kalkwarnung der Wärmepumpe** (A:3037) — Warnung bei erkannter Kalkablagerung
- **Klappenposition der Wärmepumpe** (H:29) — Klappenposition in Prozent

Weitere Serviceattribute sind auf einzelnen Geräten verfügbar: Abluftventilator-Drehzahl, Klappenbefehle, Rotationswärmetauscher-Drehzahl, Wärmepumpen-Vorlauftemperatur-Sollwert, thermische Leistung, Heizkreispumpen-Drehzahl und Speicher-Verbraucherventilposition.

### Alarmverwaltung

Das ReadScript des Moduls überwacht zwei Alarmkanäle — **Alarm A** und **Alarm B**. Wenn ein Alarm aktiv ist (Status = 2), meldet TapHome ihn als Fehler mit dem Alarmwert und dem Quittierungsstatus (Quittiert/Nicht quittiert/Gesperrt).

Drei Serviceaktionen stehen für die Alarmverwaltung zur Verfügung:

- **Alarm A quittieren** — quittiert einen nicht quittierten Alarm
- **Alarm B quittieren** — quittiert einen nicht quittierten Alarm
- **Alle inaktiven Alarme entfernen** — löscht alle inaktiven/quittierten Alarme aus dem System

### Weitere Funktionen

Die EcoNordic unterstützt außerdem Filterzeitgeber, Berechnung der Wärmerückgewinnungseffizienz, Überwachung der Zuluftventilator-Drehzahl und Heizkurvenanpassungen (WH4). Der Status der Wärmerückgewinnungslüftung zeigt zusätzliche Modi (Dunstabzug, Kamin, Temporär hoch) über das hinaus, was die Betriebsmodus-Steuerung direkt bietet. Diese Funktionen können in einem zukünftigen Vorlagen-Update hinzugefügt werden.

> [!TIP]
> Die EcoNordic arbeitet bis zu **-25°C Außentemperatur** mit ihrer CO2-Wärmepumpe. Der Rotationswärmetauscher bietet bis zu 90 % Temperatureffizienz bei der Wärmerückgewinnung. Überwachen Sie die Differenz zwischen Zuluft- und Ablufttemperatur, um die Leistung der Wärmerückgewinnung zu beurteilen.

## Fehlerbehebung

### Keine Modbus-Kommunikation

1. Überprüfen Sie die RS-485-Kabelverbindungen zwischen TapHome und dem EcoNordic-Gerät
2. Bestätigen Sie die Kommunikationsparameter: **9600 Baud, 8-E-1** (Even-Parität, nicht None)
3. Überprüfen Sie, ob die Slave-ID in TapHome mit der Gerätekonfiguration übereinstimmt (Standard: 1)
4. Stellen Sie sicher, dass die EcoNordic eingeschaltet und betriebsbereit ist

### Heizkreissensoren zeigen keine Daten (WH4)

Die Heizkreis-Vorlauf- und Rücklauftemperatursensoren sind nur beim Modell **WH4** verfügbar. Bei Verwendung eines W4 (nur Lüftung + Warmwasser) liefern diese Sensoren keine Werte.

### Alarme in TapHome gemeldet

1. Prüfen Sie die Alarmdetails in den TapHome-Serviceattributen — Alarmwert und -status werden angezeigt
2. Verwenden Sie die Serviceaktion **Alarm quittieren**, um einen aktiven Alarm zu quittieren
3. Zur Interpretation der Alarmcodes verwenden Sie die Flexit GO App oder das Benutzerhandbuch
4. Häufige Ursachen: verstopfte Filter, Rotor gestoppt, ausgelöster Überhitzungsschutz, Probleme mit dem Wassersystem

## Verfügbare Geräte 14

Diese Geräte erscheinen nach dem Import in TapHome.

Flexit EcoNordic Modul

Serviceattribute

|                                      |                                                                                                                                          |
|--------------------------------------|------------------------------------------------------------------------------------------------------------------------------------------|
| Waermepumpenstatus                   | Waermepumpen-Betriebszustand — Bereitschaft, Entlueftung, Start, Normalbetrieb, Stop, Abtauung, Fehler, Manuell, Zwangs-Ventilator/Pumpe |
| Warmwasserstatus                     | Aktueller Warmwasserproduktionsstatus — Comfort, Economy, Nicht in Betrieb, Boost, Zwangsladung, Legionellenpraevention                  |
| Status Waermerueckgewinnungslueftung | Aktueller Lueftungszustand — Aus, Away, Home, High, Dunstabzug, Kamin, Temporaer hoch                                                    |
| Anlagenbetriebsmodus Waermepumpe     | Anlagenmodus Waermepumpe — zeigt was die Waermepumpe aktuell tut (Speicherladung, Raumheizung, Lueftungsheizung, Legionellenpraevention) |
| Nachheizregister Waermepumpe         |                                                                                                                                          |
| Frostschutz Waermepumpe              |                                                                                                                                          |
| Status Kondensatwannenheizung        |                                                                                                                                          |
| Kalkwarnung Waermepumpe              |                                                                                                                                          |
| Klappenposition Waermepumpe          |                                                                                                                                          |

Serviceaktionen

|                                 |
|---------------------------------|
| Alle inaktiven Alarme entfernen |
| Alarm A quittieren              |
| Alarm B quittieren              |

Lesen (Modul)

```taphome
IF MODBUSR(A,3001, Uint16) = 2
ADDERROR(MODBUSR(A, 1021, float), "Alarm A: " + 
SWITCH(MODBUSR(A,3002, Uint16),
1, "Acknowledged, unlocked ",
2, "Unacknowledged",
3, "Locked",
"Unknown" ));
END

IF MODBUSR(A,3003, Uint16) = 2
ADDERROR(MODBUSR(A, 1023, float), "Alarm B: " + 
SWITCH(MODBUSR(A,3004, Uint16),
1, "Acknowledged, unlocked ",
2, "Unacknowledged",
3, "Locked",
"Unknown" ));
END
```

Serviceattribute

Heat Pump Status

```taphome
SWITCH(MODBUSR(A, 3028, Uint16), 
1, "Standby", 
2, "Air Purge process",
3, "Startup process",
4, "Normal operation",
5, "Stop process", 
6, "Defrost operation",
7, "Standby when error",
8, "Manual operation",
9, "Forced fan operation",
10, "Forced pump operation",
11, "State 10",
12, "State 11",
13, "State 12",
14, "State 13",
15, "State 14",
16, "State 15",
"Unknown"
)
```

Domestic hot water state

```taphome
SWITCH(MODBUSR(A, 3005, Uint16),
1, "Comfort",
2, "Economy", 
3, "Not in Use",
4, "Temporary Boost",
5, "Forced Charge",
6, "Economy delay",
7, "Legionella prevention",
"Unknown"
);
```

Heat recovery ventilation state

```taphome
SWITCH(MODBUSR(A, 3034, Uint16),
1, "Off", 
2 , "Away" , 
3 , "Home" , 
4 , "High", 
5 , "Fume hood", 
 6 , "Fireplace", 
 7 , "Temporary high",
 "Unknown");
```

Plant operating mode for heat pump

```taphome
SWITCH(MODBUSR(H, 2061, Uint16), 
1 , "Off" , 
2 , "Vent.heating from tank" , 
3 , "Load tank" ,
4 , "Load tank & vent.heating" ,
5 , "Space heating from tank" , 
6 , "Space heat.& vent.heat.from tank",
7 , "Load tank & space heat" , 
8 , "Load tank & space heat.& vent" , 
9 , "HP not available" , 
10 , "Swi-off delay flow through heat",
11 , "Legionella prev.vent.heat" , 
12 , "Legionella prev.space heat" , 
13 , "Space heat.with HP" ,
14 , "Space heat.& vent.with HP" , 
15 , "Load tank & space heat.with HP" , 
16 , "Load tank & vent.& space with HP", 
17 , "Legionella prev.tank",
"Unknown")
```

Heat Pump Reheating Coil

```taphome
Switch (MODBUSR(A, 3029, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat Pump Frost Protection

```taphome
Switch (MODBUSR(A, 3031, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Drain Pan Heater State

```taphome
Switch (MODBUSR(A, 3036, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat pump warning limescale

```taphome
Switch (MODBUSR(A, 3037, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat Pump Connection Dumper position

```taphome
MODBUSR(H, 29, Float, 2) + " %"
```

Serviceaktionen

Remove All Inactive Alarms

```taphome
MODBUSW(H, 3004, Uint16, 3);
```

Acknowledge Alarm A

```taphome
MODBUSW(H, 3002, Uint16, 2)
```

Acknowledge Alarm B

```taphome
MODBUSW(H, 3003, Uint16, 2)
```

Comfort-Taste Schalter Lesen und Schreiben

Register: H:2040 Bool

Werte / Zustände: Active · Inactive

Schaltzustand lesen

```taphome
MODBUSR(H, 2040, Bool)
```

Schaltzustand schreiben

```taphome
MODBUSW(H, 2040, Bool, St)
```

Fortlufttemperatur Temperatursensor Nur lesen

Temperatur der nach der Waermerueckgewinnung ins Freie abgefuehrten Luft

Register: A:13 Float Einheit: °C numeric

Serviceattribute

|                                    |
|------------------------------------|
| Abluftventilator-Drehzahl          |
| Fortluft-Klappenbefehl             |
| Waermepumpe Fortluft-Klappenbefehl |

Temperatur lesen

```taphome
MODBUSR(A, 13, Float, 2)
```

Serviceattribute

Exhaust Air Fan Speed

```taphome
 ROUND(MODBUSR(H, 9, Float, 2)) + " %"
```

Exhaust Air Damper Command

```taphome
Switch (MODBUSR(H, 2010, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat pump exhaust air damper command

```

```

Ablufttemperatur Temperatursensor Nur lesen

Temperatur der vor der Waermerueckgewinnung aus dem Gebaeude abgesaugten Luft

Register: A:9 Float Einheit: °C numeric

Serviceattribute

|                                    |
|------------------------------------|
| Waermepumpe Fortluft-Klappenbefehl |

Temperatur lesen

```taphome
MODBUSR(A, 9, Float , 2)
```

Serviceattribute

Heat pump exhaust air damper command

```taphome
Switch (MODBUSR(H, 2064, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heizkreis-Vorlauftemperatur Temperatursensor Nur lesen

Wassertemperatur in der Vorlaufleitung des Heizkreises — nur Modell WH4

Register: A:97 Float Einheit: °C numeric

Serviceattribute

|                                         |
|-----------------------------------------|
| Rotationswaermetauscher-Drehzahl        |
| Waermepumpen-Vorlauftemperatur-Sollwert |
| Thermische Leistung der Waermepumpe     |

Temperatur lesen

```taphome
MODBUSR(A, 97, Float, 2)
```

Serviceattribute

Rotary heat exchanger speed

```taphome
 ROUND(MODBUSR(H, 1, Float, 2)) + " %"
```

Heat pump setpoint flow temperature

```taphome
MODBUSR(H, 73, Float, 2) + " °C"
```

Heat Pump Thermic Power Output

```taphome
MODBUSR(H, 65, Float, 2) + " kW"
```

Heizkreis-Ruecklauftemperatur Temperatursensor Nur lesen

Wassertemperatur in der Ruecklaufleitung des Heizkreises — nur Modell WH4

Register: A:101 Float Einheit: °C numeric

Temperatur lesen

```taphome
MODBUSR(A, 101, Float, 2)
```

Warmwasser-Boost Mehrwertschalter Lesen und Schreiben

Voruebergehende maximale Warmwasserproduktion — Bereit, Start, Stop

Register: H:3019 UInt16 numeric

Werte / Zustände: Ready · Start · Stop

Serviceaktionen

|                 |
|-----------------|
| Dauer des Boost |

Schaltzustand lesen

```taphome
MODBUSR(H, 3019, UInt16)
```

Schaltzustand schreiben

```taphome
MODBUSWNE(H, 3019, UInt16, Mu)
```

Serviceattribute

Duration of boost

```taphome
MODBUSR(H, 1513, Uint32) + " min";
```

Serviceaktionen

Duration of boost

Parameter: Duration \[0-300 min] (0–300 dur)

```taphome
MODBUSW(H, 1513, Uint32, dur);
```

Warmwassermodus Mehrwertschalter Lesen und Schreiben

Warmwasserstrategie — Comfort (laedt bei 50 %) oder Economy (laedt bei 15 %)

Register: H:3017 UInt16 numeric

Werte / Zustände: Comfort · Economy

Schaltzustand lesen

```taphome
MODBUSR(H, 3017, UInt16)
```

Schaltzustand schreiben

```taphome
MODBUSW(H, 3017, UInt16, Mu)
```

Serviceattribute

Heating circuit pump speed

```taphome
MODBUSR(H, 61, Float, 2) + " %"
```

Storage tank consumer valve position

```taphome
 ROUND(MODBUSR(H, 57, Float, 2)) + " %"
```

Betriebsmodus Mehrwertschalter Lesen und Schreiben

Lueftungsbetriebsmodus — Stop, Away, Home, High

Register: H:2013 UInt16 numeric

Werte / Zustände: Stop · Away · Home · High

Schaltzustand lesen

```taphome
MODBUSR(H, 2013, Uint16)
```

Schaltzustand schreiben

```taphome
MODBUSW(H, 2013, Uint16, Mu)
```

Aussenlufttemperatur Temperatursensor Nur lesen

Register: A:1 Float Einheit: °C numeric

Temperatur lesen

```taphome
MODBUSR(A, 1, Float)
```

Zulufttemperatur Temperatursensor Nur lesen

Temperatur der Frischluft nach Waermerueckgewinnung und Nachheizung

Register: A:5 Float Einheit: °C numeric

Temperatur lesen

```taphome
MODBUSR(A, 5, Float, 2)
```

Temperatur bei Away Thermostat Lesen und Schreiben

Zuluft-Temperatursollwert fuer den Away-Modus (10-30°C)

Register: H:1163 Float Einheit: °C numeric

Solltemperatur lesen

```taphome
MODBUSR(H, 1163, Float, 2)
```

Solltemperatur schreiben

```taphome
MODBUSW(H, 1163, Float, Se)
```

Temperatur bei Home Thermostat Lesen und Schreiben

Zuluft-Temperatursollwert fuer den Home-Modus (10-30°C)

Register: H:1155 Float Einheit: °C numeric

Solltemperatur lesen

```taphome
MODBUSR(H, 1155, Float, 2)
```

Solltemperatur schreiben

```taphome
MODBUSW(H, 1155, Float, Se)
```

Kaminlueftung Mehrwertschalter Lesen und Schreiben

Aktiviert den Ueberdruckmodus, um Raucheintritt beim Anzuenden eines Kamins zu verhindern — Bereit, Ausloesen

Register: H:3007 UInt16 numeric

Werte / Zustände: Ready · Trigger

Serviceaktionen

|                        |
|------------------------|
| Kaminlueftung-Laufzeit |

Schaltzustand lesen

```taphome
MODBUSR(H, 3007,UInt16)
```

Schaltzustand schreiben

```taphome
MODBUSWNE(H, 3007, UInt16, Mu)
```

Serviceattribute

Fireplace Ventilation Runtime

```taphome
MODBUSR(H, 1105, Uint32) + " min"
```

Serviceaktionen

Fireplace Ventilation Runtime

Parameter: duration \[0 - 360 min] (0–360 dur)

```taphome
MODBUSW(H, 1105, Uint32, dur)
```

Schnelllueftung Mehrwertschalter Lesen und Schreiben

Voruebergehende Hochgeschwindigkeitslueftung fuer schnellen Luftaustausch — Bereit, Ausloesen

Register: H:3006 UInt16 numeric

Werte / Zustände: Ready · Trigger

Serviceaktionen

|                          |
|--------------------------|
| Schnelllueftung-Laufzeit |

Schaltzustand lesen

```taphome
MODBUSR(H, 3006, UInt16)
```

Schaltzustand schreiben

```taphome
MODBUSWNE(H, 3006, UInt16, Mu)
```

Serviceattribute

Rapid ventilation runtime

```taphome
MODBUSR(H, 1103, Uint32) + " min"
```

Serviceaktionen

Rapid Ventilation Runtime

Parameter: Duration \[1-360 min] (1–360 dur)

```taphome
MODBUSW(H, 1103, Uint32, dur)
```

**Verbindung:** Modbus RTU • 9600 baud• 8E1 • Slave ID: $\[SlaveId]

Mögliche Verbesserungen (7)

- pyflexit CI66 Register Map (Nordic S2–S4, CL2–CL4) — Complete CI66 adapter register map (addresses 0–48) for Nordic models — NOT applicable to EcoNordic which uses proprietary registers
- H:2013 value 5+ Fume Hood and Calendar Modes — Heat Recovery Ventilation State shows values 5=Fume hood, 6=Fireplace, 7=Temporary high — but Operating Mode (H:2013) only exposes Stop/Away/Home/High (1–4). Fume hood may require separate trigger register
- unknown Filter Timer / Filter Alarm — CI66 has filter operating hours (reg 8), filter alarm (reg 27), filter alarm period (reg 46). EcoNordic likely has equivalent registers but they are not in the XML template
- unknown Heat Recovery Efficiency — CI66 exposes heat recovery percentage (0–100%). EcoNordic may have equivalent register — can be calculated from supply/extract/outside temperatures
- unknown Supply Air Fan Speed — Exhaust fan speed is exposed (H:9) but supply fan speed is missing from the template. EcoNordic likely has this register
- unknown Heating Circuit Setpoint Temperature — WH4 heating set value and parallel shift for the heat curve — not exposed in the template
- doc 2882 (404) Full EcoNordic Modbus Register Map — Official Flexit Modbus EcoNordic Basic XLSX register map returned 404 — may contain additional registers not in the XML template

## Importparameter

Diese Werte geben Sie beim Import des XML ein.

| In der App abgefragt | Standard      |
|----------------------|---------------|
| Slave-ID             | `1`           |
| IP-Adresse           | `192.168.1.0` |

## Quellen

- pyflexit — Flexit Modbus Python Library (register map)
  
  [github.com](https://github.com/Sabesto/pyflexit) 2026-03-20
- Home Assistant Flexit Integration
  
  [www.home-assistant.io](https://www.home-assistant.io/integrations/flexit/) 2026-03-20
- EcoNordic WH4/W4 User Manual (116927EN-07)
  
  [assets.ctfassets.net](http://assets.ctfassets.net/wzjhf3pmxyuk/1woGygq1Dvw0xDHElh4Sss/ce551d1f9cc20887831301048b1c2dce/EcoNordic_WH4_-_W4_Vartotojo_instrukcija_EN.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/flexit-econordic/manufacturer/econordic-user-manual.pdf)
- EcoNordic WH4 Product Data Sheet (117290EN-01)
  
  [nit.lt](https://nit.lt/wp-content/uploads/2019/02/flexit-EcoNordic-WH4-eng.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/flexit-econordic/manufacturer/econordic-assembly-manual.pdf)

Herstellerdokumente sind © ihrer jeweiligen Eigentümer. Sie werden so bereitgestellt, wie der Hersteller sie veröffentlicht hat, nur zur Information.

## Verwandte Dokumentation

- [Modbus Integration](https://taphome.com/de/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/de/docs/integration/modbus/)
- [Einfache Konfiguration mit Vorlagen](https://taphome.com/de/docs/integration/modbus/templates/)
- [Modbus-Skripte und Prefetch](https://taphome.com/de/docs/script/modbus-scripts/)
- [Modbus-Funktionen](https://taphome.com/de/docs/script/modbus/)
- [Modbus-Datentypen](https://taphome.com/de/docs/script/modbus-data-types/)