  questions: ["Jak integrovat Flexit EcoNordic s TapHome?","Co ovlada sablona Flexit EcoNordic v TapHome?","Jak pripojit Flexit EcoNordic pres RS-485 k TapHome?","Jaky je rozdil mezi EcoNordic WH4 a W4 v TapHome?","Jak aktivovat krbove vetrani na Flexit EcoNordic pres TapHome?","Jak ovladat ohrev teple vody na Flexit EcoNordic?"]
---

# Flexit EcoNordic WH4 / W4

Komunikace: Modbus RTU

- [Oficialni stranka Flexit](https://www.flexit.no)

## Návod na integraci

Flexit EcoNordic je klimatizacni centrala kombinujici rovnotlake vetrani s rekuperaci tepla, ohrevem teple uzitkove vody a vodnim vytapenim (model WH4). S TapHome komunikuje pres Modbus RTU po RS-485 a umoznuje ovladani rezimu vetrani, teplotnich nastaveni, spravy teple vody a monitorovani provozu tepelneho cerpadla.

Podporovany jsou dva modely: **EcoNordic WH4** (vetrani + vytapeni + tepla voda) a **EcoNordic W4** (vetrani + tepla voda). WH4 navic obsahuje cidla a ovladani vytapeciho okruhu, ktera nejsou na W4 k dispozici.

## Hardwarove pripojeni

EcoNordic ma vestavene rozhrani Modbus RTU pristupne pres RS-485. Pripojte TapHome Core k portu RS-485 na EcoNordic pomoci krouceneho paru s GND.

> [!WARNING]
> V dostupne dokumentaci nebylo nalezeno schema zapojeni. Presne umisteni svorek RS-485 na jednotce najdete v instalacnim manualu EcoNordic nebo kontaktujte podporu Flexit. Od Flexitu je k dispozici volitelny **Modbus kabel (HP Res)** pro pripojeni externich kontroleru.

## Konfigurace

Nakonfigurujte pripojeni Modbus v TapHome s nasledujicimi parametry:

| Parametr | Hodnota |
|----------|---------|
| Baud rate | 9600 |
| Data bits | 8 |
| Parita | Even |
| Stop bits | 1 |
| Slave ID | 1 (vychozi) |

EcoNordic pouziva vlastni mapu Modbus registru v rozsahu adres 1-3037. Tato mapa se lisi od registrove mapy CI66 pouzivane starsimi modely Flexit Nordic S2-S4 / CL2-CL4 — adapter CI66 neni potreba.

> [!NOTE]
> EcoNordic lze ovladat take pres mobilni aplikaci **Flexit GO** (Android/iOS). TapHome a aplikace Flexit GO mohou fungovat soucasne — obe komunikuji s jednotkou nezavisle.

## Schopnosti zarizeni

### Ovladani rezimu vetrani

**Provozni rezim** (H:2013) je hlavni ovladani vetrani se ctyrmi rezimy:

- **Stop** — ventilatory vypnuty, zadne vetrani
- **Away** — snizene vetrani pro neobydlenou budovu
- **Home** — normalni denni provoz
- **High** — docasne zvysene vetrani

Dva specialni triggery poskytuji dalsi rezimy vetrani:

- **Rychle vetrani** (H:3006) — aktivuje docasne vysokorychlostni vetrani pro rychlou vymenu vzduchu (vareni, navstevy, vlhkost). Trvani je konfigurovatelne pres servisni akci (1-360 minut)
- **Krbove vetrani** (H:3007) — vytvari pozitivni tlak v interieru, aby se zabranilo vtahovani koure do mistnosti pri zapalovani krbu. Trvani je konfigurovatelne pres servisni akci (0-360 minut)

**Tlacitko Comfort** (H:2040) prepina komfortni rezim na jednotce, ktery docasne zvysuje vetrani a muze upravit teplotni nastaveni.

### Monitorovani teploty a nastaveni

Sablona poskytuje sest teplotnich cidel:

- **Teplota venkovniho vzduchu** (A:1) — teplota venkovniho vzduchu na nasavacim otvoru
- **Teplota privodniho vzduchu** (A:5) — cerstvy vzduch privedeny do budovy po rekuperaci a dohrevu
- **Teplota odtahoveho vzduchu** (A:9) — vzduch odtahovany z budovy pred rekuperaci
- **Teplota odpadniho vzduchu** (A:13) — vzduch odvedeny ven po rekuperaci
- **Teplota prutokov vytapeciho okruhu** (A:97) — teplota vody v privodnim potrubi vytapeciho okruhu (pouze WH4)
- **Teplota zpetneho toku vytapeciho okruhu** (A:101) — teplota vody ve zpetnem potrubi vytapeciho okruhu (pouze WH4)

Dva termostaty ovladaji nastaveni teploty privodniho vzduchu:

- **Teplota pri rezimu Home** (H:1155) — nastaveni pro rezim Home, rozsah 10-30°C
- **Teplota pri rezimu Away** (H:1163) — nastaveni pro rezim Away, rozsah 10-30°C

### Sprava teple vody

**Rezim teple vody** (H:3017) vybira strategii ohrevu teple uzitkove vody:

- **Comfort** — nabiji zasobnik pri priblizne 50 % zbyvajici teple vody, pri poklesu pod 15 % pouziva elektricky zalozni ohrivac
- **Economy** — nejuspornejsi rezim, nabiji az pri priblizne 15 % zbytku, bez elektrickeho zalozniho ohrivace

**Boost teple vody** (H:3019) spousti docasnou maximalmi vyrobu teple vody pomoci elektrickeho zalozniho ohrivace. Trvani je konfigurovatelne pres servisni akci (0-300 minut).

### Monitorovani tepelneho cerpadla a systemu

Modul nabizi devet servisnich atributu pro monitorovani stavu systemu:

- **Stav tepelneho cerpadla** (A:3028) — aktualni provoz tepelneho cerpadla: Pohotovost, Odvzdusnovani, Start, Normalni provoz, Zastaveni, Odmrazovani, Pohotovost pri chybe, Manualni a Nuceny provoz
- **Stav teple uzitkove vody** (A:3005) — stav vyroby teple vody: Comfort, Economy, Nepouziva se, Docasny boost, Nucene nabijeni, Zpozdeni Economy nebo Prevence legionely
- **Stav rekuperacniho vetrani** (A:3034) — odrazuje aktualni stav vetrani vcetne rezimu, ktere nejsou primo nastavitelne pres Provozni rezim (napr. Digestor a Krb)
- **Provozni rezim tepelneho cerpadla** (H:2061) — podrobny 17-stavovy enum ukazujici co tepelne cerpadlo aktualne dela (nabijeni zasobniku, prostorove vytapeni, ohrev vetrani, prevence legionely a kombinovane rezimy)
- **Dohrievaci teleso tepelneho cerpadla** (A:3029) — zda je dohrievaci teleso aktivni
- **Ochrana tepelneho cerpadla proti mrazu** (A:3031) — zda je ochrana proti mrazu aktivni
- **Stav ohrivace odkapavaci vany** (A:3036) — zda je ohrivac odkapavaci vany aktivni
- **Varovani pred vodnim kamenem** (A:3037) — upozorneni pri detekci usazenin vodniho kamene
- **Pozice klapky tepelneho cerpadla** (H:29) — pozice klapky v procentech

Dalsi servisni atributy jsou dostupne na jednotlivych zarizenich: rychlost odtahoveho ventilatoru, prikazy klapek, rychlost rotacniho vymeniku tepla, nastavena teplota prutokov tepelneho cerpadla, termicky vykon, rychlost obehovho cerpadla vytapeciho okruhu a pozice spotrebniho ventilu zasobniku.

### Sprava alarmu

Modul ReadScript monitoruje dva alarmove kanaly — **Alarm A** a **Alarm B**. Kdyz je alarm aktivni (stav = 2), TapHome ho hlasi jako chybu s hodnotou alarmu a stavem potvrzeni (Potvrzeny/Nepotvrzeny/Uzamceny).

Tri servisni akce jsou k dispozici pro spravu alarmu:

- **Potvrdit Alarm A** — potvrzeni nepotvrzeneho alarmu
- **Potvrdit Alarm B** — potvrzeni nepotvrzeneho alarmu
- **Odstranit vsechny neaktivni alarmy** — vymaze vsechny neaktivni/potvrzene alarmy ze systemu

### Dalsi schopnosti

EcoNordic take podporuje casovace filtru, vypocet ucinnosti rekuperace, monitorovani rychlosti privodniho ventilatoru a nastaveni vytapecich krivek (WH4). Stav rekuperacniho vetrani zobrazuje dalsi rezimy (Digestor, Krb, Docasne vysoke) nad ramec toho, co primo nabizi ovladani Provozniho rezimu. Tyto schopnosti mohou byt pridany v budouci aktualizaci sablony.

> [!TIP]
> EcoNordic funguje az do **-25°C venkovni teploty** s CO2 tepelnym cerpadlem. Rotacni vymenik tepla poskytuje az 90% teplotni ucinnost rekuperace. Monitorujte rozdil mezi teplotou privodniho a odtahoveho vzduchu pro posouzeni vykonnosti rekuperace.

## Reseni problemu

### Zadna komunikace Modbus

1. Overte pripojeni RS-485 kabelu mezi TapHome a jednotkou EcoNordic
2. Zkontrolujte komunikacni parametry: **9600 baud, 8-E-1** (parita Even, nikoli None)
3. Zkontrolujte, zda Slave ID v TapHome odpovida konfiguraci jednotky (vychozi: 1)
4. Ujistete se, ze EcoNordic je zapnuty a funkcni

### Cidla vytapeciho okruhu nezobrazuji data (WH4)

Cidla teploty prutokov a zpetneho toku vytapeciho okruhu jsou dostupna pouze na modelu **WH4**. Pokud pouzivate W4 (pouze vetrani + tepla voda), tato cidla nebudou hlasit hodnoty.

### Alarmy hlasene v TapHome

1. Zkontrolujte podrobnosti alarmu v servisnich atributech TapHome — zobrazuje se hodnota a stav alarmu
2. Pouzijte servisni akci **Potvrdit alarm** pro potvrzeni aktivniho alarmu
3. Pro interpretaci kodu alarmu se podivejte do aplikace Flexit GO nebo uzivatelskeho manualu
4. Bezne priciny: ucpane filtry, zastaveny rotor, aktivovana ochrana proti prehrati, problemy s vodnim systemem

## Dostupná zařízení 14

Tato zařízení se po importu zobrazí v TapHome.

Flexit EcoNordic Modul

Servisní atributy

|                                        |                                                                                                                                                      |
|----------------------------------------|------------------------------------------------------------------------------------------------------------------------------------------------------|
| Stav tepelneho cerpadla                | Provozni stav tepelneho cerpadla — Pohotovost, Odvzdusnovani, Start, Normalni provoz, Stop, Odmrazovani, Chyba, Manualni, Nuceny ventilator/cerpadlo |
| Stav teple uzitkove vody               | Aktualni stav vyroby teple vody — Comfort, Economy, Nepouziva se, Boost, Nucene nabijeni, Prevence legionely                                         |
| Stav rekuperacniho vetrani             | Aktualni stav vetrani — Vyp., Away, Home, High, Digestor, Krb, Docasne vysoke                                                                        |
| Provozni rezim tepelneho cerpadla      | Rezim tepelneho cerpadla — ukazuje co tepelne cerpadlo aktualne dela (nabijeni zasobniku, prostorove vytapeni, ohrev vetrani, prevence legionely)    |
| Dohrievaci teleso tepelneho cerpadla   |                                                                                                                                                      |
| Ochrana tepelneho cerpadla proti mrazu |                                                                                                                                                      |
| Stav ohrivace odkapavaci vany          |                                                                                                                                                      |
| Varovani pred vodnim kamenem           |                                                                                                                                                      |
| Pozice klapky tepelneho cerpadla       |                                                                                                                                                      |

Servisní akce

|                                    |
|------------------------------------|
| Odstranit vsechny neaktivni alarmy |
| Potvrdit Alarm A                   |
| Potvrdit Alarm B                   |

Čtení (modul)

```taphome
IF MODBUSR(A,3001, Uint16) = 2
ADDERROR(MODBUSR(A, 1021, float), "Alarm A: " + 
SWITCH(MODBUSR(A,3002, Uint16),
1, "Acknowledged, unlocked ",
2, "Unacknowledged",
3, "Locked",
"Unknown" ));
END

IF MODBUSR(A,3003, Uint16) = 2
ADDERROR(MODBUSR(A, 1023, float), "Alarm B: " + 
SWITCH(MODBUSR(A,3004, Uint16),
1, "Acknowledged, unlocked ",
2, "Unacknowledged",
3, "Locked",
"Unknown" ));
END
```

Servisní atributy

Heat Pump Status

```taphome
SWITCH(MODBUSR(A, 3028, Uint16), 
1, "Standby", 
2, "Air Purge process",
3, "Startup process",
4, "Normal operation",
5, "Stop process", 
6, "Defrost operation",
7, "Standby when error",
8, "Manual operation",
9, "Forced fan operation",
10, "Forced pump operation",
11, "State 10",
12, "State 11",
13, "State 12",
14, "State 13",
15, "State 14",
16, "State 15",
"Unknown"
)
```

Domestic hot water state

```taphome
SWITCH(MODBUSR(A, 3005, Uint16),
1, "Comfort",
2, "Economy", 
3, "Not in Use",
4, "Temporary Boost",
5, "Forced Charge",
6, "Economy delay",
7, "Legionella prevention",
"Unknown"
);
```

Heat recovery ventilation state

```taphome
SWITCH(MODBUSR(A, 3034, Uint16),
1, "Off", 
2 , "Away" , 
3 , "Home" , 
4 , "High", 
5 , "Fume hood", 
 6 , "Fireplace", 
 7 , "Temporary high",
 "Unknown");
```

Plant operating mode for heat pump

```taphome
SWITCH(MODBUSR(H, 2061, Uint16), 
1 , "Off" , 
2 , "Vent.heating from tank" , 
3 , "Load tank" ,
4 , "Load tank & vent.heating" ,
5 , "Space heating from tank" , 
6 , "Space heat.& vent.heat.from tank",
7 , "Load tank & space heat" , 
8 , "Load tank & space heat.& vent" , 
9 , "HP not available" , 
10 , "Swi-off delay flow through heat",
11 , "Legionella prev.vent.heat" , 
12 , "Legionella prev.space heat" , 
13 , "Space heat.with HP" ,
14 , "Space heat.& vent.with HP" , 
15 , "Load tank & space heat.with HP" , 
16 , "Load tank & vent.& space with HP", 
17 , "Legionella prev.tank",
"Unknown")
```

Heat Pump Reheating Coil

```taphome
Switch (MODBUSR(A, 3029, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat Pump Frost Protection

```taphome
Switch (MODBUSR(A, 3031, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Drain Pan Heater State

```taphome
Switch (MODBUSR(A, 3036, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat pump warning limescale

```taphome
Switch (MODBUSR(A, 3037, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat Pump Connection Dumper position

```taphome
MODBUSR(H, 29, Float, 2) + " %"
```

Servisní akce

Remove All Inactive Alarms

```taphome
MODBUSW(H, 3004, Uint16, 3);
```

Acknowledge Alarm A

```taphome
MODBUSW(H, 3002, Uint16, 2)
```

Acknowledge Alarm B

```taphome
MODBUSW(H, 3003, Uint16, 2)
```

Tlacitko Comfort Přepínač Čtení i zápis

Registr: H:2040 Bool

Hodnoty / Stavy: Active · Inactive

Čtení stavu přepínače

```taphome
MODBUSR(H, 2040, Bool)
```

Zápis stavu přepínače

```taphome
MODBUSW(H, 2040, Bool, St)
```

Teplota odpadniho vzduchu Teplotní senzor Pouze ke čtení

Teplota vzduchu odvedeneho ven po rekuperaci

Registr: A:13 Float Jednotka: °C numeric

Servisní atributy

|                                                    |
|----------------------------------------------------|
| Rychlost odtahoveho ventilatoru                    |
| Prikaz klapky odpadniho vzduchu                    |
| Prikaz klapky odpadniho vzduchu tepelneho cerpadla |

Čtení teploty

```taphome
MODBUSR(A, 13, Float, 2)
```

Servisní atributy

Exhaust Air Fan Speed

```taphome
 ROUND(MODBUSR(H, 9, Float, 2)) + " %"
```

Exhaust Air Damper Command

```taphome
Switch (MODBUSR(H, 2010, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Heat pump exhaust air damper command

```

```

Teplota odtahoveho vzduchu Teplotní senzor Pouze ke čtení

Teplota vzduchu odtahovaneho z budovy pred rekuperaci

Registr: A:9 Float Jednotka: °C numeric

Servisní atributy

|                                                    |
|----------------------------------------------------|
| Prikaz klapky odpadniho vzduchu tepelneho cerpadla |

Čtení teploty

```taphome
MODBUSR(A, 9, Float , 2)
```

Servisní atributy

Heat pump exhaust air damper command

```taphome
Switch (MODBUSR(H, 2064, Uint16), 1, "Active", 0, "Inactive", "Unknown");
```

Teplota prutokov vytapeciho okruhu Teplotní senzor Pouze ke čtení

Teplota vody v privodnim potrubi vytapeciho okruhu — pouze model WH4

Registr: A:97 Float Jednotka: °C numeric

Servisní atributy

|                                               |
|-----------------------------------------------|
| Rychlost rotacniho vymeniku tepla             |
| Nastavena teplota prutokov tepelneho cerpadla |
| Termicky vykon tepelneho cerpadla             |

Čtení teploty

```taphome
MODBUSR(A, 97, Float, 2)
```

Servisní atributy

Rotary heat exchanger speed

```taphome
 ROUND(MODBUSR(H, 1, Float, 2)) + " %"
```

Heat pump setpoint flow temperature

```taphome
MODBUSR(H, 73, Float, 2) + " °C"
```

Heat Pump Thermic Power Output

```taphome
MODBUSR(H, 65, Float, 2) + " kW"
```

Teplota zpetneho toku vytapeciho okruhu Teplotní senzor Pouze ke čtení

Teplota vody ve zpetnem potrubi vytapeciho okruhu — pouze model WH4

Registr: A:101 Float Jednotka: °C numeric

Čtení teploty

```taphome
MODBUSR(A, 101, Float, 2)
```

Boost teple vody Vícestavový přepínač Čtení i zápis

Docasna maximalni vyroba teple vody — Pripraveno, Start, Stop

Registr: H:3019 UInt16 numeric

Hodnoty / Stavy: Ready · Start · Stop

Servisní akce

|               |
|---------------|
| Trvani boostu |

Čtení stavu přepínače

```taphome
MODBUSR(H, 3019, UInt16)
```

Zápis stavu přepínače

```taphome
MODBUSWNE(H, 3019, UInt16, Mu)
```

Servisní atributy

Duration of boost

```taphome
MODBUSR(H, 1513, Uint32) + " min";
```

Servisní akce

Duration of boost

Parametry: Duration \[0-300 min] (0–300 dur)

```taphome
MODBUSW(H, 1513, Uint32, dur);
```

Rezim teple vody Vícestavový přepínač Čtení i zápis

Strategie ohrevu teple uzitkove vody — Comfort (nabiji pri 50 %) nebo Economy (nabiji pri 15 %)

Registr: H:3017 UInt16 numeric

Hodnoty / Stavy: Comfort · Economy

Čtení stavu přepínače

```taphome
MODBUSR(H, 3017, UInt16)
```

Zápis stavu přepínače

```taphome
MODBUSW(H, 3017, UInt16, Mu)
```

Servisní atributy

Heating circuit pump speed

```taphome
MODBUSR(H, 61, Float, 2) + " %"
```

Storage tank consumer valve position

```taphome
 ROUND(MODBUSR(H, 57, Float, 2)) + " %"
```

Provozni rezim Vícestavový přepínač Čtení i zápis

Provozni rezim vetrani — Stop, Away, Home, High

Registr: H:2013 UInt16 numeric

Hodnoty / Stavy: Stop · Away · Home · High

Čtení stavu přepínače

```taphome
MODBUSR(H, 2013, Uint16)
```

Zápis stavu přepínače

```taphome
MODBUSW(H, 2013, Uint16, Mu)
```

Teplota venkovniho vzduchu Teplotní senzor Pouze ke čtení

Registr: A:1 Float Jednotka: °C numeric

Čtení teploty

```taphome
MODBUSR(A, 1, Float)
```

Teplota privodniho vzduchu Teplotní senzor Pouze ke čtení

Teplota cerstveho vzduchu privedeneho do budovy po rekuperaci a dohrevu

Registr: A:5 Float Jednotka: °C numeric

Čtení teploty

```taphome
MODBUSR(A, 5, Float, 2)
```

Teplota pri rezimu Away Termostat Čtení i zápis

Nastaveni teploty privodniho vzduchu pro rezim Away (10-30°C)

Registr: H:1163 Float Jednotka: °C numeric

Čtení požadované teploty

```taphome
MODBUSR(H, 1163, Float, 2)
```

Zápis požadované teploty

```taphome
MODBUSW(H, 1163, Float, Se)
```

Teplota pri rezimu Home Termostat Čtení i zápis

Nastaveni teploty privodniho vzduchu pro rezim Home (10-30°C)

Registr: H:1155 Float Jednotka: °C numeric

Čtení požadované teploty

```taphome
MODBUSR(H, 1155, Float, 2)
```

Zápis požadované teploty

```taphome
MODBUSW(H, 1155, Float, Se)
```

Krbove vetrani Vícestavový přepínač Čtení i zápis

Aktivuje pretlakovy rezim pro zabraneni vstupu koure pri zapalovani krbu — Pripraveno, Spustit

Registr: H:3007 UInt16 numeric

Hodnoty / Stavy: Ready · Trigger

Servisní akce

|                            |
|----------------------------|
| Doba behu krboveho vetrani |

Čtení stavu přepínače

```taphome
MODBUSR(H, 3007,UInt16)
```

Zápis stavu přepínače

```taphome
MODBUSWNE(H, 3007, UInt16, Mu)
```

Servisní atributy

Fireplace Ventilation Runtime

```taphome
MODBUSR(H, 1105, Uint32) + " min"
```

Servisní akce

Fireplace Ventilation Runtime

Parametry: duration \[0 - 360 min] (0–360 dur)

```taphome
MODBUSW(H, 1105, Uint32, dur)
```

Rychle vetrani Vícestavový přepínač Čtení i zápis

Docasne vysokorychlostni vetrani pro rychlou vymenu vzduchu — Pripraveno, Spustit

Registr: H:3006 UInt16 numeric

Hodnoty / Stavy: Ready · Trigger

Servisní akce

|                            |
|----------------------------|
| Doba behu rychleho vetrani |

Čtení stavu přepínače

```taphome
MODBUSR(H, 3006, UInt16)
```

Zápis stavu přepínače

```taphome
MODBUSWNE(H, 3006, UInt16, Mu)
```

Servisní atributy

Rapid ventilation runtime

```taphome
MODBUSR(H, 1103, Uint32) + " min"
```

Servisní akce

Rapid Ventilation Runtime

Parametry: Duration \[1-360 min] (1–360 dur)

```taphome
MODBUSW(H, 1103, Uint32, dur)
```

**Připojení:** Modbus RTU • 9600 baud• 8E1 • Slave ID: $\[SlaveId]

Možná vylepšení (7)

- pyflexit CI66 Register Map (Nordic S2–S4, CL2–CL4) — Complete CI66 adapter register map (addresses 0–48) for Nordic models — NOT applicable to EcoNordic which uses proprietary registers
- H:2013 value 5+ Fume Hood and Calendar Modes — Heat Recovery Ventilation State shows values 5=Fume hood, 6=Fireplace, 7=Temporary high — but Operating Mode (H:2013) only exposes Stop/Away/Home/High (1–4). Fume hood may require separate trigger register
- unknown Filter Timer / Filter Alarm — CI66 has filter operating hours (reg 8), filter alarm (reg 27), filter alarm period (reg 46). EcoNordic likely has equivalent registers but they are not in the XML template
- unknown Heat Recovery Efficiency — CI66 exposes heat recovery percentage (0–100%). EcoNordic may have equivalent register — can be calculated from supply/extract/outside temperatures
- unknown Supply Air Fan Speed — Exhaust fan speed is exposed (H:9) but supply fan speed is missing from the template. EcoNordic likely has this register
- unknown Heating Circuit Setpoint Temperature — WH4 heating set value and parallel shift for the heat curve — not exposed in the template
- doc 2882 (404) Full EcoNordic Modbus Register Map — Official Flexit Modbus EcoNordic Basic XLSX register map returned 404 — may contain additional registers not in the XML template

## Parametry importu

Tyto hodnoty zadáte při importu XML.

| Ptá se v aplikaci | Výchozí       |
|-------------------|---------------|
| Slave ID          | `1`           |
| IP adresa         | `192.168.1.0` |

## Zdroje

- pyflexit — Flexit Modbus Python Library (register map)
  
  [github.com](https://github.com/Sabesto/pyflexit) 2026-03-20
- Home Assistant Flexit Integration
  
  [www.home-assistant.io](https://www.home-assistant.io/integrations/flexit/) 2026-03-20
- EcoNordic WH4/W4 User Manual (116927EN-07)
  
  [assets.ctfassets.net](http://assets.ctfassets.net/wzjhf3pmxyuk/1woGygq1Dvw0xDHElh4Sss/ce551d1f9cc20887831301048b1c2dce/EcoNordic_WH4_-_W4_Vartotojo_instrukcija_EN.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/flexit-econordic/manufacturer/econordic-user-manual.pdf)
- EcoNordic WH4 Product Data Sheet (117290EN-01)
  
  [nit.lt](https://nit.lt/wp-content/uploads/2019/02/flexit-EcoNordic-WH4-eng.pdf) 2026-03-20
  
  [PDF](https://taphome.com/compatibility/devices/flexit-econordic/manufacturer/econordic-assembly-manual.pdf)

Dokumenty výrobců jsou © jejich příslušných vlastníků. Poskytujeme je tak, jak je výrobce zveřejnil, pouze pro informaci.

## Související dokumentace

- [Modbus Integration](https://taphome.com/cs/compatibility/modbus-guide/)
- [Modbus](https://taphome.com/cs/docs/integration/modbus/)
- [Jednoduché nastavení pomocí šablon](https://taphome.com/cs/docs/integration/modbus/templates/)
- [Skripty Modbus a prefetch](https://taphome.com/cs/docs/script/modbus-scripts/)
- [Funkce Modbus](https://taphome.com/cs/docs/script/modbus/)
- [Datové typy Modbus](https://taphome.com/cs/docs/script/modbus-data-types/)