﻿<?xml version="1.0" encoding="utf-8"?>
<Templates format="2" protocolVersion="54">
  <Template id="f15c16ca-2104-4d62-93fe-1e991adc366e" revision="1.0">
    <Name>Sfar MOD-1TE (PT100/PT500/PT1000)</Name>
    <CcuModel>ModbusRtuCCU</CcuModel>
    <Producer>Sfar</Producer>
    <Model>MOD-1TE</Model>
    <Category>10</Category>
    <Description></Description>
    <RevisionHistory>
      <Revision id="1.0">Initial version</Revision>
    </RevisionHistory>
    <SuggestedCCUParameters>
      <Baudrate>19200</Baudrate>
      <DataBits>8</DataBits>
      <Parity>None</Parity>
      <StopBits>One</StopBits>
    </SuggestedCCUParameters>
    <ImportParameters>
      <Parameter>
        <Name>InputSettingsRegister</Name>
        <Value>18</Value>
        <Id>InputSettingsRegister</Id>
      </Parameter>
      <Parameter>
        <Name>${device_SlaveId}</Name>
        <Value>1</Value>
        <Id>SlaveId</Id>
      </Parameter>
      <Parameter>
        <Name>${ipAddress}</Name>
        <Value>192.168.0.1</Value>
        <Id>IpAddress</Id>
      </Parameter>
    </ImportParameters>
    <Module>
      <Name>Sfar MOD-1TE (PT100/PT500/PT1000)</Name>
      <Id>-1</Id>
      <Model>ModbusModule</Model>
      <DeviceProperties>
        <SlaveId>$[SlaveId]</SlaveId>
        <IpAddress>$[IpAddress]</IpAddress>
      </DeviceProperties>
      <Devices>
        <Device>
          <Name>Modbus PT temperature sensor</Name>
          <Id>-2</Id>
          <Model>ModbusTemperatureSensor</Model>
          <DeviceProperties>
            <InitializeScript>MODBUSWNE(H, 61, Int16, $[InputSettingsRegister])</InitializeScript>
            <ReadTemperature>MODBUSR(A, 51, Int16)/10</ReadTemperature>
          </DeviceProperties>
        </Device>
      </Devices>
    </Module>
  </Template>
</Templates>