﻿<?xml version="1.0" encoding="utf-8"?>
<Templates format="2" protocolVersion="54">
  <Template id="0341fda4-7f11-4a1a-a6f4-130bbca3f124" revision="1.0">
    <Name>Mitsubishi EHST20C</Name>
    <CcuModel>ModbusTcpCCU</CcuModel>
    <Producer>Mitsubishi</Producer>
    <Model>EHST20C</Model>
    <Category>2</Category>
    <Description></Description>
    <RevisionHistory>
      <Revision id="1.0">Initial version</Revision>
    </RevisionHistory>
    <ImportParameters>
      <Parameter>
        <Name>${device_SlaveId}</Name>
        <Value>1</Value>
        <Id>SlaveId</Id>
      </Parameter>
      <Parameter>
        <Name>${ipAddress}</Name>
        <Value>192.168.0.1</Value>
        <Id>IpAddress</Id>
      </Parameter>
    </ImportParameters>
    <Module>
      <Name>Mitsubishi EHST20C</Name>
      <Id>-1</Id>
      <Model>ModbusModule</Model>
      <DeviceProperties>
        <SlaveId>$[SlaveId]</SlaveId>
        <IpAddress>$[IpAddress]</IpAddress>
      </DeviceProperties>
      <Devices>
        <Device>
          <Name>System ON/OFF</Name>
          <Id>-2</Id>
          <Model>ModbusSwitch</Model>
          <DeviceProperties>
            <InternalPollInterval>2500</InternalPollInterval>
            <ReadSwitchState>MODBUSR(H, 25, Bool)</ReadSwitchState>
            <WriteSwitchState>MODBUSWNE(H, 25, Bool, St)</WriteSwitchState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Holiday</Name>
          <Id>-3</Id>
          <Model>ModbusSwitch</Model>
          <DeviceProperties>
            <InternalPollInterval>2500</InternalPollInterval>
            <ReadSwitchState>MODBUSR(H, 38, Bool)</ReadSwitchState>
            <WriteSwitchState>MODBUSWNE(H, 38, Bool, St)</WriteSwitchState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Status of Heating</Name>
          <Id>-4</Id>
          <Model>ModbusMultiValueSwitch</Model>
          <DeviceProperties>
            <InternalPollInterval>2500</InternalPollInterval>
            <Value0Index>0</Value0Index>
            <Value1Index>1</Value1Index>
            <Value2Index>2</Value2Index>
            <Value3Index>3</Value3Index>
            <Value4Index>68</Value4Index>
            <Value5Index>69</Value5Index>
            <Value6Index>70</Value6Index>
            <Value7Index>71</Value7Index>
            <Value8Index>72</Value8Index>
            <Value9Index>73</Value9Index>
            <Value0Name>No type</Value0Name>
            <Value1Name>Heating C1</Value1Name>
            <Value2Name>Heating C2</Value2Name>
            <Value3Name>Heating C3</Value3Name>
            <Value4Name>4</Value4Name>
            <Value5Name>5</Value5Name>
            <Value6Name>6</Value6Name>
            <Value7Name>7</Value7Name>
            <Value8Name>8</Value8Name>
            <Value9Name>9</Value9Name>
            <Value0IconId>5</Value0IconId>
            <Value1IconId>6</Value1IconId>
            <Value2IconId>7</Value2IconId>
            <Value3IconId>8</Value3IconId>
            <Value4IconId>9</Value4IconId>
            <Value5IconId>10</Value5IconId>
            <Value6IconId>11</Value6IconId>
            <Value7IconId>12</Value7IconId>
            <Value8IconId>13</Value8IconId>
            <Value9IconId>14</Value9IconId>
            <ReadSwitchState>MODBUSR(H, 72, Int16)</ReadSwitchState>
            <WriteSwitchState></WriteSwitchState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Room Temperature Zone 1</Name>
          <Id>-5</Id>
          <Model>ModbusTemperatureSensor</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadTemperature>MODBUSR(H, 94, Int16) / 100</ReadTemperature>
            <ReadHumidity></ReadHumidity>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Flow Temperature</Name>
          <Id>-6</Id>
          <Model>ModbusTemperatureSensor</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadTemperature>MODBUSR(H, 102, Int16) / 100</ReadTemperature>
            <ReadHumidity></ReadHumidity>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Return Temperature</Name>
          <Id>-7</Id>
          <Model>ModbusTemperatureSensor</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadTemperature>MODBUSR(H, 104, Int16) / 100</ReadTemperature>
            <ReadHumidity></ReadHumidity>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Energy Consumption measured Date - Day</Name>
          <Id>-8</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 281, Int16)</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Energy Consumption measured Date - Month</Name>
          <Id>-9</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 280, Int16)</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Energy Consumption measured Date - Year</Name>
          <Id>-10</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 279, Int16)</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Flow Rate</Name>
          <Id>-11</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 299, Int16)</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Last measured Total Energy Produced (kWh)</Name>
          <Id>-12</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 298, Int16)</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
      </Devices>
    </Module>
  </Template>
</Templates>