﻿<?xml version="1.0" encoding="utf-8"?>
<Templates format="2" protocolVersion="54">
  <Template id="c3149390-2df9-49b1-8d72-e040eaac3a6e" revision="1.0">
    <Name>IntesisBox Tank</Name>
    <CcuModel>ModbusRtuCCU</CcuModel>
    <Producer>Intesis</Producer>
    <Model></Model>
    <Category>4</Category>
    <Description></Description>
    <RevisionHistory>
      <Revision id="1.0">Initial version</Revision>
    </RevisionHistory>
    <SuggestedCCUParameters>
      <Baudrate>9600</Baudrate>
      <DataBits>8</DataBits>
      <Parity>None</Parity>
      <StopBits>One</StopBits>
    </SuggestedCCUParameters>
    <ImportParameters>
      <Parameter>
        <Name>${device_SlaveId}</Name>
        <Value>1</Value>
        <Id>SlaveId</Id>
      </Parameter>
      <Parameter>
        <Name>${ipAddress}</Name>
        <Value>192.168.0.1</Value>
        <Id>IpAddress</Id>
      </Parameter>
    </ImportParameters>
    <Module>
      <Name>IntesisBox Tank</Name>
      <Id>-1</Id>
      <Model>ModbusModule</Model>
      <DeviceProperties>
        <SlaveId>$[SlaveId]</SlaveId>
        <IpAddress>$[IpAddress]</IpAddress>
      </DeviceProperties>
      <Devices>
        <Device>
          <Name>System On/Off</Name>
          <Id>-2</Id>
          <Model>ModbusSwitch</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadSwitchState>MODBUSR(H, 30, Uint16)</ReadSwitchState>
            <WriteSwitchState>MODBUSWNE(H, 30, Uint16, St)</WriteSwitchState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Tank working mode</Name>
          <Id>-3</Id>
          <Model>ModbusMultiValueSwitch</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadSwitchState>MODBUSR(H, 31, Unt16)</ReadSwitchState>
            <WriteSwitchState>MODBUSWNE(H, 31, Uint16, Mu)</WriteSwitchState>
            <Value0IconId>39</Value0IconId>
            <Value0Name>Normal</Value0Name>
            <Value1IconId>16</Value1IconId>
            <Value1Name>Eco</Value1Name>
            <Value2IconId>37</Value2IconId>
            <Value2Name>Powerfull</Value2Name>
            <Value3Index>64</Value3Index>
            <Value4Index>65</Value4Index>
            <Value5Index>66</Value5Index>
            <Value6Index>67</Value6Index>
            <Value7Index>68</Value7Index>
            <Value8Index>69</Value8Index>
            <Value9Index>70</Value9Index>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Water temperature [°C]</Name>
          <Id>-4</Id>
          <Model>ModbusThermostat</Model>
          <DeviceProperties>
            <InternalPollInterval>1000</InternalPollInterval>
            <ReadCurrentTemperature>MODBUSR(H, 32, Uint16)</ReadCurrentTemperature>
            <ReadDesiredTemperature>MODBUSR(H, 33, Uint16)/10</ReadDesiredTemperature>
            <WriteDesiredTemperature>MODBUSWNE(H, 33, Int16, Se*10)</WriteDesiredTemperature>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Heat-up Interval [s]</Name>
          <Id>-5</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadState>MODBUSR(H, 34, Uint16)</ReadState>
            <WriteState>MODBUSWNE(H, 34, Uint16, Va)</WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Heat-up Interval [s]</Name>
          <Id>-6</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadState>MODBUSR(H, 34, Uint16)</ReadState>
            <WriteState>MODBUSWNE(H, 34, Uint16, Va)</WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Operation Interval [h]</Name>
          <Id>-7</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadState>MODBUSR(H, 35, Uint16)/2</ReadState>
            <WriteState>MODBUSWNE(H, 35, Uint16, Va*2)</WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Booster delay time [min]</Name>
          <Id>-8</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadState>MODBUSR(H, 36, Uint16)</ReadState>
            <WriteState>MODBUSWNE(H, 36, Uint16, Va)</WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Sterilization On</Name>
          <Id>-9</Id>
          <Model>ModbusSwitch</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadSwitchState>MODBUSR(H, 37, Uint16)</ReadSwitchState>
            <WriteSwitchState>MODBUSWNE(H, 37, Uint16, St*0xAA)</WriteSwitchState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Sterilization boiling temp [°C]</Name>
          <Id>-10</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadState>MODBUSR(H, 38, Uint16)</ReadState>
            <WriteState>MODBUSWNE(H, 38, Uint16, Va)</WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Sterilization Continuing Time [s]</Name>
          <Id>-11</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>15000</InternalPollInterval>
            <ReadState>MODBUSR(H, 39, Uint16)</ReadState>
            <WriteState>MODBUSWNE(H, 39, Uint16, Va)</WriteState>
          </DeviceProperties>
        </Device>
      </Devices>
    </Module>
  </Template>
</Templates>