﻿<?xml version="1.0" encoding="utf-8"?>
<Templates format="2" protocolVersion="54">
  <Template id="725f4f87-7888-4756-8cfa-ce1e8a798832" revision="1.0">
    <Name>Carlo Gavazzi EM340F</Name>
    <CcuModel>ModbusRtuCCU</CcuModel>
    <Producer>Carlo Gavazzi</Producer>
    <Model>EM340F</Model>
    <Category>7</Category>
    <Description></Description>
    <RevisionHistory>
      <Revision id="1.0">Initial version</Revision>
    </RevisionHistory>
    <SuggestedCCUParameters>
      <Baudrate>9600</Baudrate>
      <DataBits>8</DataBits>
      <Parity>None</Parity>
      <StopBits>One</StopBits>
    </SuggestedCCUParameters>
    <ImportParameters>
      <Parameter>
        <Name>${device_SlaveId}</Name>
        <Value>1</Value>
        <Id>SlaveId</Id>
      </Parameter>
      <Parameter>
        <Name>${ipAddress}</Name>
        <Value>192.168.0.1</Value>
        <Id>IpAddress</Id>
      </Parameter>
    </ImportParameters>
    <Module>
      <Name>Carlo Gavazzi EM340F</Name>
      <Id>-1</Id>
      <Model>ModbusModule</Model>
      <DeviceProperties>
        <SlaveId>$[SlaveId]</SlaveId>
        <IpAddress>$[IpAddress]</IpAddress>
      </DeviceProperties>
      <Devices>
        <Device>
          <Name>Total Production</Name>
          <Id>-2</Id>
          <Model>ModbusElectricityMeter</Model>
          <DeviceProperties>
            <InternalPollInterval>1500</InternalPollInterval>
            <ReadTotalConsumption>MODBUSR(H, 274, Int32) / 20000</ReadTotalConsumption>
            <ReadDemand>MODBUSR(H, 282, Int32) / 20000</ReadDemand>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Production kWh L1</Name>
          <Id>-3</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>1500</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 064, Int32) / 20000</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Production kWh L2</Name>
          <Id>-4</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>1500</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 066, Int32) / 20000</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Production kWh L3</Name>
          <Id>-5</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>1500</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 068, Int32) / 20000</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Total Consumption</Name>
          <Id>-6</Id>
          <Model>ModbusElectricityMeter</Model>
          <DeviceProperties>
            <InternalPollInterval>1500</InternalPollInterval>
            <ReadTotalConsumption>MODBUSR(H, 278, Int32) / 20000</ReadTotalConsumption>
            <ReadDemand>MODBUSR(H, 282, Int32) / 20000</ReadDemand>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Consumption kWh L1</Name>
          <Id>-7</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>1500</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 096, Int32) / 20000</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Consumption kWh L2</Name>
          <Id>-8</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>1500</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 098, Int32) / 20000</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
        <Device>
          <Name>Consumption kWh L3</Name>
          <Id>-9</Id>
          <Model>ModbusVariable</Model>
          <DeviceProperties>
            <InternalPollInterval>1500</InternalPollInterval>
            <IsReadOnly>False</IsReadOnly>
            <ReadState>MODBUSR(H, 100, Int32) / 20000</ReadState>
            <WriteState></WriteState>
          </DeviceProperties>
        </Device>
      </Devices>
    </Module>
  </Template>
</Templates>